| 1 | Arranging general servicing for the above 10/15 KVA E/A set at site including replacement of lubeoil, filters, complete as required as per OEM recommendations |
| 2 | Supplying and replacement of fallowing spare parts / consumables for the DG set as required. |
| 3 | Diesel pipe of 1mtr length |
| 4 | Hydraulic Fuel Pipes with Banjo-bolt connectors |
| 5 | DG set stop solenoid assembly |
| 6 | V Belts Cogged Type |
| 7 | e) S/F of ON/OFF Push button with wiring |
| 8 | De-coupling and removingof 10KVA Kirloskar Alternator of Canopy DG set andtransportationto the specializedworkshop at Vijayawada/Eluru i/cloading and unloading at Tundurru complete as required |
| 9 | Dismantling/ separationof rotor & stator from 10KVA Alternator (M/s Kirloskar Green), removing of burnt/ faultywinding, cleaning of stator/rotor core, re-winding of Alternator Windings ( both Stator & Rotor winding) of 1-ph, 10KVAAlternator (for 230V, 50Hz ,1-ph power supply output)with F/H class insulated copper/wire/strip, applying varnish, drying the same by keeping in oven etc as required. (Note: after deduction of salvage value of old copper) |
| 10 | Transportation of the repaired alternator from work shop @ Vijayawada/Eluru to Tundurru & Re-coupling of alternator to Engine,Re-alignment with dial gauge with high skilled Technician, reconnection of outgoing cables both earthlings and testing on load etc as required |
| 11 | Supply and fixing of SMPS battery charger suitable for charging lead acid battery with 230V 50HZ AC supply input and 12V DC output i/c short circuit protection, reverse battery terminal protection etc as required. |
| 12 | Supply, installation, testingof 12V, 100AHLead acid battery wth 24months peace to peace warranty low maintenance including initial charging complete etc as required. (Model: Exide-Genplus 110D31R) |
| 13 | Repairing and calibration of fuel injection pump assembly & nozzles of 10/15 KVA EA set including removing / refaxing transportation charges to work shop complete as required |
| 14 | Prdg. Repairs to self motorTVS model of 10/15KVA capacity DG set at work shop by replacing burnt field winding ,Armature,brushes,i/c dismantling of assembly& transportation ,Providing repairs and reinstallation after repair the same etc as required. |
| 15 | Replacement of stainless steel door hinges in place damage door hingessuitable for above DG set as required |
| 16 | Replacement of stainless steel dooraldrops Heavy Dutyin place damage lock suitable for locking arrangementabove DG set as required |
| 17 | Supply and fixing of Bitumen tar sheet on the top of the 15KVA capacity DG set canopy for rusted roof of the canopy and preventing water leakages etc as required. |
| 18 | Repair of burnt Exhaust Fan at work shop by replacing burntwinding ,capacitor i/c dismantling of assembly& transportation ,Providing repairs and reinstallation after repair the same etc as required. |
| 19 | Testing and commissioning of the 10/15 KVA above set with cable connections, earth connections, silencer fixing and engine/alternator parameters etc complete as required. |
| 20 | S/F of AVR in Alternator excitation circuit of Kirloskar make and model i/c necessary interconnections, testing on load etc as required |