| 1 | 34W/44WEU/MR-02/2025-26: Provn of Qty-05 Chemical earthing pits to improve earth resistance value. |
| 2 | M&L for supply, installation and testing of maintenance free chemical earthing system consisting of 99.9% pure copper solid rod type, UL approved copper boned earth rod of 10 feet length, 17.2 mm dia.(as per drg ) made of high tensile low carbon steel rod, molecularly bonded with 99.9% electrolytic grade copper on outer surface (minimum copper bonding thickness-250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25KA fault current by CPRI with 50kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125mm dia, the compound should comply to IEC:62561-7 having passed leaching, corrosion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit lab with FRP earth pit cover of top size lockable Ltd. It includes GI protection pipe light grade of size 40mm dia with GI strip of size 32x6mm upto test point, complete all as specified and directed by Engineer in Charge. Note:- (a) Copper strip connecting between two earthing will be measured and paid separately to respective item. (b) Cost of earthwork and necessary PCC work for earthing pit is included in the above item. (c)Installation of earthing will be done by the company Engr a site. (d) Testing will be done by the company rep and 5years guarantee certificate will be submitted by the company and ISD for sum of 10% of guoted rate. (e) The test result of each set of earthing is less than 1 Ohm.All earthing test will be carried out in presence of MES rep manufacture rep and test result will be recorded in a register with sign of manufacturer & Engr-in-charge. (f) 5 Years guarantee certificate from company for maintaining earth result less than 1Ohm will be submitted by contractor. (g) 1425 RTC SS universal clamp of size 175x50x3mm.(h) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25kg.(j)Chemical earthing will be installed by manufacturer rep and purchase voucher of earthing will be produced before payment.Payment shall be made only after getting satisfactory result. |
| 3 | S&F of earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 32x6mm copper strip, complete all as specified and directed by Engineer in Charge. |
| 4 | Supply, laying, jointing of GI pipe of light grade of size 50mm dia including jointing material/ GI fittings in trenches, complete all as specified and directed by Engineer in Charge. |
| 5 | S&F test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and crewed including 3 Nos 8mm dia 25mm long hex. Head crew, complete all as specified and directed by Engineer in Charge. |
| 6 | 34W/44WEU/MW-01/2025-26: Provn of Qty-04 AC AT AFNET Section. |
| 7 | Supply and install Hi wall split AC units (2TR) indoor/outdoor complete with cordless remote control unit and with in built Heating and cooling arrangment and Digital inverter twin rotary type,5 star rating, complete all as specified and directed by Engineer in Charge. |
| 8 | S&F digital voltage stabilizer for automatic operation, copper wound, single phase naturally air cooled indoor type & designed for input variation between 130 V to 270 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA, with low and high voltage cut-off protection, protect equipment from potentially danger voltage, inbuilt in thermal temp burn out with latest IC technology and assesories, complete all as specified and directed by Engineer in Charge. |
| 9 | M&L sub main wiring with 2 runs of copper conductor PVC FRLS insulated unsheathed cable 1100 volt grade 4 sqmm drawn through PVC conduit medium grade ISI marked25mm dia as per IS specification fixed concealedin wall/ceiling including conduit and conduit accessories and incl provn of PVC insulated 4 Sqmm multistranded copper conductor as earth continuity conductor connected to earth dolly all as specified including dismantling old and making good to the disturbed surface by plastering and two coat of distemper, complete all as specified and directed by Engineer in Charge.Note:- Two runs of 4 sqmm cable along with one run of 4 Sqmm PVC insulated unsheathedcopper conductor as earth wire, conduitand conduit accessories will be measured as one length). |
| 10 | S&F metallic AC earth plug and socket withSheet metal enclosure with MCB SP 20A to 32A, complete all as specified and directed by Engineer in Charge. |
| 11 | S&F amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) SPN 32Amps and current carrying capacity in the MCB DB complete with connection testing and commissioning, complete all as specified and directed by Engineer in Charge. |
| 12 | 34W/44WEU/MR-01/2025-26: Provn of one Air Conditioner Point at all SMQs. |
| 13 | M&L submain wiring with 2 runs of copper conductor PVC FRLS insulated unsheathed cable 1100 volt grade 4 sqmm drawn through PVC conduit medium grade ISI marked25mm dia as per IS specification fixed concealedin wall/ceiling including conduit and conduit accessories and incl provn of PVC insulated 4 Sqmm multistranded copper conductor as earth continuity conductor connected to earth dolly all as specified including dismantling old and making good to the disturbed surface by plastering and two coat of distamper, complete all as specified and directed by Engineer in Charge. Note : Two runs of 4 sqmm cable alongwith one run of 4 Sqmm PVC insulated unsheathedcopper conductor as earth wire, conduitand conduit accessories will be measured as one length). |
| 14 | S&F metallic AC earth plug and socket withSheet metal enclosure with MCB SP 20A to 32A, complete all as specified and directed by Engineer in Charge. |
| 15 | S&F amp rating 240V, 10KA \"C\" curveminiature circuit breaker (MCB) SPN 32Amps and current carrying capacity in the MCB DB complete with connection testing and commisioning in existing MCB DB, complete all as specified and directed by Engineer in Charge. |
| 16 | NOTE: BOQ has bifurcated job wise, if bidder quoted different rate for same item at different jobs then lowest quoted rate shall be considered for acceptance for all jobs. |