Tender Document For Sub-Station and Transmission Line [PACKAGE-C8(1B)]-TECHNICALSPECIFICATION FOR 12kV, 800A, 18.4kA, MULTI PANEL (Incoming, Bus Coupler with Adaptor Panel and Outgoing) SHUNT TRIP, INDOOR TYPE SCADA COMPATIBLE SWITCHGEAR WITH MOTOR OPERATED SPRING CLOSING VACUUM CIRCUIT BREAKER- 1 ELECTRICAL PART : 2 WBSETCL Assessed Quantities: 3 245KV 40KA for 3sec Gas Insulated Switchgear - i)2500 A rated Double Bus Barwith BUS earthing arrangement ii) 3 phase / single phase encapsulated iii) Minimum 2000 A rated Circuit Breaker for line and Transformers & 2500A for Bus coupler Bay iv) CT with current ratio 1600-800-400/1A (5 core) for feeder & transformer & 2000-1600/1A (3 core) for bus coupler as per CT specification v) Each feeder comprises of Circuit Breaker, Disconnectors, CTs, Bus bar, density monitors, gas partition etc. vi) suitable for EHV cable entry withdouble terminationarrangementif single Run cable is used other will be kept as spare. vii) Standalone Local Control Cubicle (LCC) with all required accessoriesand Gas monitoring system and the requiredPD sensors to cover the total GIS portion. -The complete system shall be as per technical specification and requirement comprising of - 4 Complete LineBayswith accommodation of3 nos GIS Line VTeach having 3 cores(2 nos core for Protection and 1 no core for metering and other parameters as per technical specification 5 LA for Line bay ( one number per phase - to be installed within GIS) 6 CompleteTransformer Bays 7 Buscoupler Bay 8 2 sets of 3 phase Bus PT each having 3 cores (2 core Protection and 1 core Metering), each for Main Bus-I & Main Bus-II with disconnectors & earth switch. As per Tech Spec 9 Disconnector with earthing arrangement and gas tight barriers atOne side of Main Bus I & IIfor future extension.one side 10 Portable UHF PD monitoring System - The analyser shall have 6 channel input withinherent PD location accuracy of 0.5m., colour display unit and user friendly interface for detailed analysis.The system includes allaccessoriesto monitorPD, UHF cables,required software and other accessories to complete as per Technical Specification. 11 Dew Point Meter as per Technical Specification 12 145KV 31.5KA for 3sec Gas Insulated Switchgear i)2000 A rated Double Bus Barwith BUS earthing arrangement ii) 3 phase / single phase encapsulated iii) Minimum 2000 A rated Circuit Breaker iv) Each feeder comprises of Circuit Breaker, Disconnectors, CTs, Bus bar, density monitors, gas partition etc.v) CT with current ratio 1000-800-400/1A (5 core) for feeder & transformer & 2000-1600/1A (3 core) for bus coupler as per CT specification vi) suitable for EHV cable entry withdouble terminationarrangementif single Run cable is used other will be kept as spare. vii) Standalone Local Control Cubicle (LCC) with all required accessoriesand Gas monitoring system and the requiredPD sensors to cover the total GIS portion. -The complete system shall be as per technical specification and requirement comprising of - 13 Complete LineBayswith accommodation of3 nos GIS Line VTeach having 3 cores(2 nos core for Protection and 1 no core for metering and other parameters as per technical specification 14 Complete Transformer Bays for LV side of 160 MVA 220/132 KV Transformer & HV side of 50 MVA 132/33 KV Transformers 15 Bus coupler Bay 16 Disconnector with earthing arrangement and gas tight barriers atOne side of Main Bus I & IIfor future extension.one side 17 2 sets of 3 phase Bus PT each having 3 cores (2 core Protection and 1 core Metering), each for Main Bus-I & Main Bus-II with disconnectors & earth switch. As per Tech Spec 18 36 KV, 31.5KA for 3sec Indoor, floor mounted drawoutSwitchgear Assembly (2500A Bus rating with Copper Bus Bar) with VCB suitable for EHV cable entry withtripple termination arrangement and bus earthing arrangement from both side, Line earthing arrangement and dead line status and corresponding electrical and mechanicalinterlocking arrangementas per technical specification and requirement comprising of - 19 Outgoing Feeder Bays, 1250A Circuit Breaker ratingas per Techspec. 20 LV side of50MVA 132/33KV Transformer Bays (2000 A Breaker Capacity) CT Ratio 2000-1000/1A 3 coreas per Tech spec 21 HV side of6.3 MVA 33/11KV Transformer Bays(1250 A Breaker Capacity ) as per Tech Spec 22 Station service transformer bay (1250A Circuit Breaker rating) 23 Bus section Bay (2500 A Breaker Capacity) 24 (i)2(two) set of 3 phase Bus PT - 5 limb, (One set each for Main Bus-I & Main Bus-II) with isolation arrangement.as per Tech Spec. (ii) Other required equipment & accessories like Bus Earthing arrangement etc. to complete the system . 25 12 KV, 1600 A, 25 KA, 30 V DC, SCADA compatible, VCB Switchgear includingProtection Relays, ,control & annunciation equipment and other accessories complete as per technical specification (uploaded for Nandanpuronly) Cable and bus earthing shall be electrically and mechanically interlocked with associated breaker as per interlock requirement. but rating should be as per BOQrequirement comprising of - 26 Outgoing Line Bays (CT Ratio 400-200/1) 2 coreVCB rating 1250A 27 Incoming Transformer Bays(CT Ratio 600-400/1A) 4 core VCB rating 1250A 28 Bus section Bay VCB rating 1600A 29 (i) 3(Three) set of 3 phase Bus PTwith isolation arrangement must be mounted above incomer switchgearpanel. (ii) Other required equipment and accessories like Bus earthing arrangement etc to complete the system 30 Electric Overhead Travelling Crane (E.O.T.) 31 Electric Overhead Travelling Crane (E.O.T.)- For 220 KV GIS Building 5.0 Metric Ton capacity or maximum weight of GIS shipping unit whichever is higher -complete with all accessories as per technical specification and requirement. 32 Transformers : 33 160 MVA, 220/132/33 KV, 3 Phase ,Auto Transformer suitablefor NIFPSwith Bushing CTs and NCTS andRTCC panel alonwith BCUand other accessories as per technical specification ofAuto Transformer. 220KV & 132KV bushingshall be of RIP/RIS type. 34 Nitrogen injection type Fire Prevention and ExtinguishingSystem including reservoir tank andall required accessories for 160 MVA, 220/132/33 KV, 3 Phase Power Transformer 35 50 MVA, 132/33 KV, 3 Phase, 2 winding Power Transformerwith Bushing CTs and NCTsincluding RTCC panel alongwith BCU and alongwith all accessoriesin line with technical specification of Power Transformer.132 KVbushingshall be of RIP/RIS type. 36 6.3 MVA, 33/11 KV, 3 Phase, 2 winding Power Transformer with Bushing CTs and NCTs in line with technical specification of Power Transformer . As per Tech spec 37 STATION SERVICE TRANSFORMER: 315 KVA, 33/0.415 KV, 3Ph, 2-Windingas per technical specification andrequirement 38 EARTHINGTRANSFORMER: 33KV, 3 Ph ,fault current rating of874 Amp for 30 secas per Technical Specification and requirement 39 Isolators : As per Technical specification 40 220 KV, 1600A, 40 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH (excluding insulators) for HV side of 160 MVA Transformers(water proof mechanism housing with auxiliary switch) 41 Solid Core Insulator for each set of above Isolators 42 220 KV, 1600A, 40 KA for 3sec, HCB, motor operated 3-phase Assembly WITH EARTHING SWITCH (excluding insulators) for Line bay(water proof mechanism housing with auxiliary switch) 43 Solid Core Insulator for each set of above Isolators 44 132KV, 1250 A,31.5 KA for 3sec, HCB, 3Ph Assembly isolator with Earth Switch for line feeder, motor control - excluding solid core insulators as per Tech. Specification (water proof mechanism housing with auxiliary switch) 45 Solid coreInsulator for each set of above Isolators 46 132KV, 1250A,31.5 KA for 3sec, HCB, 3Ph Assembly isolator with out Earth Switch for Transformers, motor control - excluding solid core insulators as per Tech. Specification (water proof mechanism housing with auxiliary switch) 47 Solid coreInsulator for each set of above Isolators 48 33KV, 1250A,31.5 KA for 3sec, CRDB, 3Ph Assemblywithout earthswitch as per Tech. Specification - forHV side of 33/11KV Transformer & Earthing Transformer(excludingInsulators ) 49 Solid coreInsulator for each set of above Isolators 50 33KV, 2000 A,31.5 KA for 3sec, CRDB, 3Ph Assemblywithout earthswitch as per Tech. Specification - for LV side of 132/33 KV Transformer,(excludingInsulators ) 51 Solid coreInsulator for each set of above Isolators 52 33KV, 1250A,31.5 KA for 3sec, CRDB, 3Ph Assembly with Horn-gap fuse units to be mounted on same structure of isolator ( for Station service Transformers ) as per Tech. Specification(excluding insulator) 53 Solid Core Insulator for each set of above Isolators 54 LIGHTNINGARRESTORAs per Technical specification 55 198 KV, single phase, 10 KA, Heavy Duty, Station Class, Gapless (for 2 nos. 160 MVA Transformersas per technical specification and as per requirement. (Polymer type) 56 198 KV class polymer type LA at Composite Tower 57 120 KV, Single phase, 10 KA, Heavy Duty, Station Class, Gapless for 2 nos 160MVA Transformers,2 nos 50MVA Transformerand line bays (Polymer type) 58 42 KV, Single phase, 10 KA, Heavy Duty, Station Class, Gapless (for 2 nos 50MVA transformer, 3 Nos 6.3 MVA 33/11 KV Transformer &2 nos.315KVA station serviceTransformer) ((Polymer type) 59 12 KV, 3 phase 10KA,Station class GapelessLA (LV side of 3nos. 6.3MVA Transformers) (Polymer type) 60 220 V Battery & Charger( As per technical Specification ) 61 VRLA Battery SET - 800AH 220 Voltas per Tech Spec. 62 Battery Health monitoring system forabovementioned 220V batteries as per Technical Specification. 63 Battery Charger - 220Volt. suitable for above Battery set in line with Technical Specification(Float Charger capacity - 80A and Float cum Boost Charger capacity - 150A) - Charger shall be equipped with disconnecting arrangement forLoad and Battery - Charger shall be capable of charging the battery both in Constant Current and Constant Voltage mode with appropriate selector switch - Fuse fail indication arrangements are to be provided for all fuse units. All the indications like fuse fail, blocking diode fail, rect. fail, battery earth fault, charger fail etc are to be provided locally, as well as necessary potential free contacts to send at remote end also. 64 VRLA BATTERY SET -75 AH 30 VoltCapacity will be as per design or75 AH whichever is higher as per uploadedtech spec 65 Battery Charger - 30Volt. Foalt cum Boost Charger Float charger capacity 35A or as per design whichever is higher as per Tech Spec ( uploaded) - Charger shall be equipped with disconnecting arrangement forLoad and Battery - Charger shall be capable of charging the battery both in Constant Current and Constant Voltage mode with appropriate selector switch - Fuse fail indication arrangements are to be provided for all fuse units. All the indications like fuse fail, blocking diode fail, rect. fail, battery earth fault, charger fail etc are to be provided locally, as well as necessary potential free contacts to send at remote end also.(as per uploaded spec.) as per uploaded spec 66 PROTECTION PANEL ( SIMPLEX REAR Open Door type ) inclusive of all relays, Annunciator (Minimum 24 windows or more as per scheme requirement, with RS485 port for Modbus Communication, Auxiliary AC and DC Supply as well as Dedicated AC Fail and DC Fail windows) at each panel and other accessories as per specificaction and requirement. (Protection Panels will be installed in Relay Room.) 67 Protection panel with BCU and Breaker Control Switch for 220 KV Line Feeder. Each feeder panel will have 2 nos. Distance Protection Relays of different manufacturer having different model, algorithm, hardware with Group Selection Switch and all other accessories complete as per Tech. Spec. 68 Protection Panel with BCU and Breaker Control Switch for 220 KV side of 220/132/33 KV Transformer complete as per Tech. Spec. (Transformer Differential Relay, Circulating Curent Protection Relay in addition to all other Transformer HV Protection relays are to be considered in HV side Panel). 69 Protection Panel with BCU (having 2 set voltage coils for measuring 3-phase bus voltages from both Bus PTs) and Breaker Control Switch for 220 KV Bus Coupler complete as per Tech. Spec. 70 220 KV Busbar Differential Panel with low impedance type Centralized Busbar Protection Relay having in-built LBB protection, End Fault protection, CT Open detection feature etc. complete as per Tech. Spec. (Panel to be complete with all relays, components and wiring i.r.o. at least 3 nos. future Line bays and 1 no. future Transformer HV bay in addition to present bays) 71 Protection panel with BCU and Breaker Control Switch for 132 KV Line Feeder. Each feeder panel will have 2 nos. Distance Protection Relays of different manufacturer having different model, algorithm, hardware with Group Selection Switch and all other accessories complete as per Tech. Spec. 72 Protection Panel with BCU and Breaker Control Switch for 132 KV side of 220/132/33 KV Transformer complete as per Tech. Spec. 73 Protection Panel with BCU and Breaker Control Switch for 132 KV side of 132/33 KV Transformer complete as per Tech. Spec. (Transformer Differential Relay, HV REF Protection Relay in addition to other Transformer HV Protection relays are to be considered in HV side Panel) 74 Protection Panel with BCU (having 2 set voltage coils for measuring 3-phase bus voltages from both Bus PTs) and Breaker Control Switch for 132 KV Bus Coupler complete as per Tech. Spec. 75 132 KV Busbar Differential Panel with low impedance type Centralized Busbar Protection Relay having in-built LBB protection, End Fault protection, CT Open Detection feature etc. complete as per Tech. Spec. (Panel to be complete with all relays, components and wiring i.r.o. at least 3 nos. future Line bays and 1 no. future Transformer HV bay in addition to present bays) 76 Protection Panel with BCU and Breaker Control Switch for 33 KV Line Feeder as per Tech. Spec. 77 Protection Panel with BCU and Breaker Control Switch for 33 KV side of 33/0.415 KV Station Service Transformer (S.S.T.) as per Tech. Spec. Panel schematics will be similar to Line Feeder Panel, along with addtitional S.S.T. Supervision Relays. 78 Protection Panel with BCU and Breaker Control Switch for 33 KV side of 132/33 KV Transformer as per Tech. Spec. 79 Protection Panel with BCU and Breaker Control Switch for 33 KV side of 33/11 KV Transformer (considering HV REF Protection Relay, HV Over-current Relay and all other accessories alongwith space and provision for future Transformer Differential Relay) as per Tech. Spec. and actual requirement. 80 Protection Panel with BCU (having 2 set voltage coils for measuring 3-phase bus voltages from both side Bus PTs) and Breaker Control Switch for 33 KV Bus Section bay as per Tech. Spec. 81 Meter Panel without meter( As per drawing uploaded) 82 XLPE Copper Cableas per Technical Specification 83 220 KV 630 Sq. mm single Core Copper Cable AL sheath forLine from Composite Tower To GIS- Single phase connection with double run cable for each phase- The actual length will be decided after finalisation of LUP drawing. 84 220 KV 630 Sq. mm single Core Copper Cable AL Sheath for HV side of 160 MVA TransformersSingle phase connection with single run cable for each phase- The actual length will be decided after finalisation of LUP drawing. 85 220 KV 400 Sq. mm Single Core Cu cable AL sheath(as per technical specification and as per requirement) forLine bays- Single phase connection with single run cable for each phase - The actual length will be decided after finalisation of LUP drawing. 86 132 KV 630 Sq. mmsingle core Cu cable AL sheath (as per technical specification and as per requirement) for connection of 132 KV side of 2 nos 160 MVA, 220/132/33 KV Transformers - Single phase connection with doublerun cable for each phase - The actual length will be decided after finalisation of LUP drawing. 87 132 KV 400 Sq. mm Single Core Cu cable AL sheath(as per technical specification and as per requirement) for connection of 132 KV side of 2 nos 50MVA, 132/33 KV Transformers and Line bays- Single phase connection with single run cable for each phase - The actual length will be decided after finalisation of LUP drawing. 88 33 KV 630 Sq.mmSingle Corecopper cable for LV side of 50MVA Transformer - Single phase connection with double run cable for each phase - The actual length will be decided after finalisation of LUP drawing. 89 33 KV 240 Sq.mmThree Core copper cable for three 33/11KV 6.3MVA Transformer , two 315KVA Transformer - Three Phase Connection with single run cable - The actual length will be decided after finalisation of LUP drawing. 90 11 KV 400 Sq.mm 3 coreCopper for 33/11KV 6.3MVA Transformer - Three Phase Connection with singlerun cable - The actual length will be decided after finalisation of LUP drawing. 91 Outdoor End Termination Kit/ cable sealing end and other required accessories for above XLPE cables as per requirement and specification : 92 For 220KV 630 Sq.mmsingle core copper cable for Line 93 For 220KV 630 Sq.mmsingle core copper cable forTransformer 94 For 220KV 400 Sq.mmsingle core copper cable for Line 95 132 KV 630 Sq.mm single Core Copper Cable for LV side of 160 MVA Transformer (single phase connection with doublerun cable for each phase ) 96 132 KV 400 Sq.mm single Core Copper Cable forHV side of 50 MVA Transformer & Line feeder(single phase connection with single run cable for each phase ) 97 33 KV 630 Sq.mmSingle Corecopper cable for LV side of 50MVA Transformer (single phase connection with two run cable for each phase) 98 33 KV 240 Sq.mm size Three Core for three 6.3MVA 33/11KV Transformer, two 315 KVA Auxiliary Transformer,( Three phase connection with single run cable ) 99 11 KV 400 Sq.mm size Three Core for three 6.3MVA 33/11KV Transformer(Three Phase Connection Single run cable) 100 Indoor End Termination Kit for above XLPEcable : Dry Plug-In type GIS Indoor Termination kitwith all its accessories complete. This includes cable connecting contact plates and cable terminal box at GIS termination of type-A, Fig -3 as per IEC 60859 with support structure and insulator as per approved drawing, technical specification /requirement as per the following cables. For 33 : Dry Heat Shrink type as per approved drawing, technical specification /requirement as per the following cables. 101 For 220KV 630 Sq.mmsingle core copper cable for Line 102 For 220KV 630 Sq.mmsingle core copper cable forTransformer 103 For 220KV 400 Sq.mmsingle core copper cable for Line 104 132 KV 630 Sq.mm single Core Copper Cable for LV side of 160 MVA Transformer (single phase connection with doublerun cable for each phase ) 105 132 KV 400 Sq.mm single Core Copper Cable forHV side of 50 MVA Transformer & Line feeder(single phase connection with single run cable for each phase ) 106 33 KV 630 Sq.mmSingle Corecopper cable for LV side of 50MVA Transformer (single phase connection with two run cable for each phase) 107 33 KV 240 Sq.mm size Three Core for three 6.3MVA 33/11KV Transformer, two 315 KVA Auxiliary Transformer,( Three phase connection with single run cable ) 108 11 KV 400 Sq.mm size Three Core for three 6.3MVA 33/11KV Transformer(Three Phase Connection Single run cable) 109 Generator 110 DG set 100KVA with all accessoriesas per Technical specification 111 Communication Equipment (As per technical specification, BOQ and mentioned Annexure) 112 Fibre Optic Terminal equipment ( with minimum five redundantdirections with MSP protection)/Optical Line Terminal Equipment (SDH-STM 4) for the Sub Station Reduntant Power Supply card and Control card etc. complete to meet Tech. Spec. Requirement in all respect ( should be compatible with FO equipment at BAPL,SLDC & Backup SLDC for data and voice communication and carrier aided protection). 113 E1 Interface cards( Minimum 16 interfaces/card) 114 Ethernet Interfaces10/100 Mbps with Layer-2 switching ( Minimum 8 interfaces/card) 115 Equipment Cabinets 116 Main Distribution Frame (100 pairs) 117 Pre-connectorised optical fibre patch cords as per requirement 118 E-1 Port Interfacing Cable 119 EPAX (with cabinet)To be suitable both for FO Equipment and PLCC equipment with 2 digit, 3 digit & 4 digit Station numbering facility and programmable features such as using analog telephone & Laptop with (4 x 8 nos.) Local Subscribers 120 Digital Teleprotection Coupler suitable for integration with SDH terminal equipment to communicate on G 703 (E1, 2 Mbps) with minimum eight commands as per Technical Specification requirement. 121 Telephone Receiver (2-wire) for connection with EPAX,to be installed at different rooms of GIS cum Control& office building, C-type quarter, Colony buildings, Security room at main gate and other areas as per direction of Site-In-Charge. 122 Telephone cable (armoured) for all2-wire telephones & other requirements as per specification and as per requirement 123 STP Data Cable(CAT 6) with flexible GI conduit pipe for data transfer and for connecting IP phones (placed at Control room, communication room, Sub-Station In-charges room etc.) with FO Panel 124 Two no. licensed software for configuration of SDH and DPC to be handed over in two pendrive to Communication wing 125 48V, 300AH VRLA type Battery 126 48V, 60A Battery Charger 127 48V DCDB as per technical specification 128 Integration withexisting Fiber Optic System at connecting Sub-Stationon optical channel (STM-4), in consultation with the OEM, whose equipment is installed at other end. i) for voice & data communication ii)for carrier aided protection purpose -with supply of equipment and material(SFP,Patchcord, etc) as required. Intigration of new SDH, with existing SDH at connecting substation must not affect repoting of existing SDH at NMS, for which necessay action needs to be taken. 129 SAS system (as perindicative Scheme diagram, Technical Specification and requirement) -Monitoring & Control of the Sub Station from a far end Operting Station in addition to local unit 130 Rack mounted Main Server (Intel XeonSilver 4215processor or higher) with KVM console with display & all accessories ( server is to be mounted at SERVER PANEL-1, for connection FO port to be considered). 131 Rack mountedStandbyServer (Intel Xeon Silver 4215 processor or higher) with KVM console with display & all accessories ( server is to be mounted at SERVER PANEL-2, for connection FO port to be considered). 132 Local HMI (client Terminal) with 32 Monitor (LED) 133 Remote HMI PC with monitor (32LED) and necessary software for remote control and monitoring via local substation Gateway ,shall support IEC60870-5-104and IEC 61850 protocol. Remote HMI shall 100% replication of local substation HMI in all respect . 134 MainGateway (Intel Xeon Silver 4215 processor or higher)-Bay level data shall report to GATEWAY & SERVER independently. support simultaneous communication with 4 independent Master stations over IEC 104 protocol. 135 Standby Gateway (Intel Xeon Silver 4215 processor or higher)- Bay level data shall report to GATEWAY & SERVER independently. support simultaneous communication with 4 independent Master stations over IEC 104 protocol 136 Disturbance Recorder Cum Engineering Workstation PC (Industrial Grade) withMonitors (24 size- LED) 137 1 no PC with monitor (24 size LED) and necessary software for remote end to fetch DR data from relays and to configure all relays . 138 Rack mounted complete GPS unit, to be mounted in server panels . 139 Laser Colour Printer (suitable for at least A3 size) 140 Dot Matrix Printer 141 PRP Compliant, managed 20 FO port Ethernet Switch, industrial grade. 142 SAS application software with required license (suitable for 8000 signals, with life time validity) and other relevant operating & system software for running the scheme successfully. 143 Redundant Inverter of 5KVA or higher capacity in HOT-STANDBY Mode, on220V station battery , to feed SERVER, GATEWAY, HMI, Engineers WorkStation,Monitors, Ethernet Switches, KVM Switches,Printers, MODEM/ROUTER, etc. 144 Cabling System -Multimode / Single Mode Dual Window armoured fibre optic approach cable as required with HDPE duct, Flexible GI Conduit, all other power & control cables, Jacks, connectors and any other hardware to meet functional / performance requirement. 145 LIU having minimum 12 ports. 146 Red Box having minimum 4 RJ45 & 2 FO ports. 147 Remote Monitoring & control (wherever required) of Station Auxilliary System like Fire Fighting System, Air Conditioning System, Battery System, Lighting System, ACDB, 220V & 48V DCDB,replica of annunciator with buzzer & reset arrangement,& fire fighting annunciatoretc. complete as per technical specification requirement. For auxilliary system, AUX BCU to be mounted in separate panel. 148 Premium quality Integrated Control console deskwith chairs and other furnituresfor HMI Workstations, DR PC, telephones, storing of log sheets & manuals etc. suitable for three operators 149 Data Integration with SLDC and Back up SLDC End Including programme as per technical specification and also as per site requirement by directly communication with agency engaged for AMC of SCADA at SLDC and Back up SLDC End. 150 Router cum firewall shall be provided at local end for remote data transmission . 151 Network panel and other material / equipment / accessories required for successful completion ofthe job . 152 Automated notification in the form of SMS - i) SMS is required to be sent to 5 (five) mobile numbers at a time. ii) When required, any number can be deleted or altered. For that easy interface is to be provided. A log (with user-id and time) for the same is also required to be maintained. iii) The type of disturbaces or trippings for which SMS to be sent must be cofigurable. iv) All required hardwares and softwares to establish the system is under scope of the bidder. v) ISP connection in the name of WBSETCL and any formalities (if required) is to be done by the Bidder.SIM will be provided by WBSETCL. vi) After handing over the system, any recurring charges for SIM will be borne by WBSETCL. 153 Vendor Assessed Quantities: 154 ACDISTRIBUTION BOARD(comprising of Main ACDB, Sub-ACDBMLDB,DB) complete as per technical specificationand as per requirement. In addition to incomers from 2 nosStation Transformer, and Diesel Generator, suitable incomer for Solar Roof Top plant (40 kWp capacity) is to be considered as per requirement for GIS building and 11 KV room . 155 DCDISTRIBUTION BOARD (220 V DC)complete as per technical specificationand as per requirement 156 30V DCDB (with single source) for 11 KV System as per uploaded Tech spec 157 Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedulefor entire work including cable laying fromACDB & DCDB ,paneland any other equipment and also any equipments supplied by WBSETCL including Supply and installation of all required cables as per transformer & RTCC scheme drawing . Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement 158 19 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 159 16 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 160 12 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 161 8 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 162 4 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 163 5 core, PVC, Armoured4 Sq. mm Copper as per Technical Specification.(For all CT, PT & CVT connection. For CT individual colour coded cables are to be used for individual core). 164 4 core, PVC, Armoured4 Sq. mm Copper as per Technical Specification. 165 5 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 166 3 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 167 2 core, PVC, Armoured2.5 Sq. mm Copper as per Technical Specification. 168 POWERCABLE-Multi Core, PVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification and as per requirement as per approved drawing and cable schedulefor entire work including cable laying fromACDB & DCDB ,paneland any other equipment and also any equipments supplied by WBSETCL including Supply and installation of all required cables as per transformer & RTCC scheme drawing (Allcablesshall be of Copper only.)Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement 169 1C X 500 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 170 3.5C X 185 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 171 4C X 16 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 172 4C X 25 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 173 4C X 50 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 174 4C X 35 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 175 2C X 50 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 176 1C X 50 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 177 2C X 4 sq. mmPVC, Armoured, 1.1 KV POWERCABLE (Copper) as per Technical Specification 178 ACSR CONDUCTORwith accessoriesas per Technical Specification and as per requirement 179 ACSR Moose 180 ACSR Panther 181 Earth /Shield wirefor LM down comer 182 ALUMINIUM TUBULAR PIPE (Schedule 80) as per Technical Specification and as per requirement 183 3 IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement 184 2.5 IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement 185 1.5 IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement 186 CLAMPS,CONNECTORS,BUNDLE SPACER, Hardware fittings & accessoriesincluding equipment connectors(SUITABLE FOR SCH. 80) and as per approved ACSR conductor as per Technical Specification and as per requirement 187 220KV System 188 132KV System 189 33 KV System 190 11KV System 191 0.4KV System 192 Solid Core POSTINSULATOR& Anti fog type Disc insulatorwithhardware fittings and accessories as per Technical Specification andrequirement 193 220KV System 194 132KV System 195 33 KV System 196 11KV System 197 ILLUMINATION SYSTEM 198 ILLUMINATION SYSTEM COMPLETE (Both Indoor & outdoor)GIS building control building switchyard periphery C type building B type buildingPump House, Security Goomty / Barrack, DG Room,other area installation including light pole with foundation worketc as per technical specificationandrequirement. Allluminaire used shall be of LED type (irrespective of the type mention in specification) and all fans shall be of energy efficient BLDC type. 199 Dehumidifier as per specification 200 Dehumidifier with suitable capacity & size for 33 KV Switchgear Roomas per approved drawing 201 Direct Stroke Lightning Protection for GIS building(considering Roof Top Solar Plant), Control builting, FFPH, as per relevant IEC. 202 Furnitures and Gadgets for Conference Room - Premium quality furnitures of reputed brand like Godrej or equivalent are to be considered. However, before procurment of furnitures and gadgets, written approval from WBSETCL site-in-charge is to be taken. 203 Conference table suitable for 30 person 204 Executive High Back chairs 205 Digital Audio / visual projector - 4K resolution, 2 nos USB 2.0 and 2 nos HDMI 2.0 ports (Preferred make - Sony, Epson, JVC, Panasonic) 206 64 or higher Interactive smart whiteboard of reknowned make 207 Meeting room Audio system (microphones - 30 nos., wall mounted speakers, amplifiers, other required hardwares & softwares) - (Make Harman, Sennheiser or equivalent) 208 Decorative dimmable LED lights (average 500 lux level) 209 High quality window blinds matching with room interior 210 AIR CONDITIONING SYSTEM COMPLETE as per Technical Specification and as per requirement (All machines must be of same make.) 211 RelayRoom and SAS Room & communication Room- Ductable Air Conditioning System is to be considered. -All machines must be ofsame make . Considering continuous operation ,machines must be of Industrial gradeand refrigerent must be of R32 or better environmental standards .as per spec 212 5star rated Split type Non-Ductable AC for Battery & Chargerroom, In-Charge Room, Conference room DB Room etcAll machines must be ofsame make . Considering continuous operation, machines must be of Industrial grade / 5 star rated split and refrigerent must be of R32 or better environmental standards as per spec 213 FIRE FIGHTING & FIRE PROTECTION SYSTEM - As per Tech spec 214 Fire hydrant system in ring formation along the periphery of switchyard covering entire portion (Entire 132 KV Switchyard &220 KV switchyard), GIS building, Control Building etc as required. 215 Portable fire extinguisher & bucket at key locations of switchyard ,control room, GIS building, office area ,residential and other building and near each Power Transformer as per Technical spec . and as per requirement. 216 Fire Alarm System (Concealed cabling is preferred ) - i) Smoke & heat detection system covering all the rooms of GIS cum Control room building ii) adequatebeam detector with redundancyfor GIS room - as per technical specification & requirement 217 CCTV Survelliance system (as perTech specification ) - The system shall be capable to integrate with central control centre. The actual quantity shall be finalised depending on the approved design . 218 Fixed Bullet camera (short range) with all accessories -as per technical specification. 219 Fixed Bullet camera (long range) with all accessories -as per technical specification. 220 Fixed Dome camera with all accessories-as per technical specification. 221 PTZ camera with all accessories-as per technical specification. 222 IP Based Outdoor Thermal Camera with all accessories as per technical specification 223 VMS management server with 30 days recording facility for minimum 40 cameras (with MS Windows professional operating system) -as per technical specification. 224 Video surveillance software and license for 40 cameras or more (which shall be valid for lifetime) -as per technical specification. 225 40 4K Display, 24 x 7 operation; as per technical specifications 226 2 KVA online UPS with 30 minute backup-as per technical specification. 227 24 Port PoE 1G Network Switch with 4 nos SFP Ports along with 1G SM SFP Modules; as per technical specifications 228 Required number of Industrial Grade 4 Port 1G Network Switch with 2 Nos. SFP Ports along with 1G SM SFP Modules; as per technical specifications 229 Media Converter, PTZ keyboard with joystick, cabinet, junction box, POE injector, LIU, power supply, Indoor floor mount rack, outdoor rack, clamp, connector and hardware for camera fixing etc. -as per technical specification. 230 All types of armoured fibre optic cables, CAT 6 cables, armoured copper cables, HDMI cable, HDPE conduits, PVC straight pipe and accessories etc. required to complete the system-as per technical specification. 231 Computer Table, rolling Chair, additional mounting pole and Other tit-bit materials not specified above but required for successful completion of CCTV surveillance systemas per site requirement. 232 NEXT GENERATION FIREWALL/ CYBERSECURITY GATEWAY and all required hardwares & software for integration with remote Control Command & Centre AS PER TECHNICAL SPECIFICATIONS. 233 One additional viewing unitsat In-Charge Room with all required hardware and software 234 SUBSTATION EARTHING SYSTEM : As per Technical specification 235 32mm dia or higherMS rod for main earthmat grid,corner mesh and periphry for outdoor switchyard . The actual quantity shall be finalised depending on the approved design (Only design quantity with lap length without any wastage for main mat, periphry& corner mesh will be considered for payment.) The Earthmat design is to be done considering earth resistivity of 30 Ohm-m oractual measured value whichever is higher. 236 32mm dia or higherMS rod for riser below and aboveground auxiliary Mat fencing and gate earthing bending length and overlapping length as per requirement & as per approved drawing 237 GS flat for riser above ground / cable trench & other areas.Rod/pipe electrode , test link and other materials etc. - as per requirement, technical specificationand approved design/layout including earthpit. 238 Earthing for GIS enclosure and GIS building as per manufacturers recommendation including civil work. 239 Earth Link Box, SVL, Earth Strip, earth continuity cable for single bondwherever required for Earthing of allXLPE Cablecomplete at cable conductor junction point etc as per technical requirement / as per approved drawings. 240 Earth Strip and other accessories including lugs for link box etc wherever required for Earthing of allXLPE Cablecompletei as per technical requirement / as per approved drawings. 241 3 ph Earth Link Box with SVLas per technical requirement / as per approved drawings. 242 3 ph Earth Link Box with outSVL as per technical requirement / as per approved drawings. 243 1 ph Earth Link Box with SVL as per technical requirement / as per approved drawings. 244 1 ph Earth Link Box with outSVL as per technical requirement / as per approved drawings. 245 6.6 KV/3.8 KV Copper Bonding Cableas per technical requirement / as per approved drawings. 246 1.1KV Grade 240 sqmm CopperEarth continuity Cableas per technical requirement / as per approved drawings. 247 GRID CONNECTED ROOF TOP SOLAR POWER SYSTEM (As per Technical Specification) 248 5kWpSolar Roof Top plant (at the roof of GIS & Control building) having high quality mono. crystalline type solar PV module from reputed brand (as mentioned under WBSETCL Makers list), Mounting structures (Fixed Type) with Civil pedestals including civil work as per requirement. 249 i) High quality inverter from reputed brand as mentioned under WBSETCL Makers list) suitable for 40kWp solar roof top plant. ii ) All other required accessories- Data logger with CPU, LCD monitor, UPS,Metering,Junction box & distribution boxes, Type-II Surge protective device, string monitoring uints, pyrano.meter with sensors, all Cables, hardware, earthing & lightning protection materials, required furnitures & cabinets, conduits etc. to complete the system of 40kWp grid connected plant 250 Essential spares necessary for operation, routine maintenance and testing of equipment supplied for 3 years to be covered under Annual Maintenance Contract. 251 MISCELLANEOUS ITEMS -As per Technical specification 252 i) Glow signboard for name of the substation- minimum size 50 sq ft, ii) schematic SLD on glow signboard iii) Danger plate, phase plate, bay nameplate etc iv) Statutory caution boards made of mild steel of 250 mm x 200 mm and at least 2 mm thick and vitreous enamelled, white on both sides and with inscription in signal red colour on front side as required. v) Shock treatment chart in local and English language duly mounted on wooden frame with glass as required vi) Safety Slogans - to be put up in Offices and Sub-station premises (Site-in-charge may select the slogans from WBSETCL Safety Manual, Version 2.0, Page 18)vii) WBSETCLLOGO & Sub-Station Nameat main gate of Sub-Station entry with good quality durable materials 253 Ferrules & lugs, GI conduit, Cu flexible wires for panel earthing etc. 254 .Angle, Channel and other hardwares for installation of panels, DBs etc. 255 Supply of itemsfabrication marker, tags,Protection cover tiles, PVC warning tape, route marker, jointing marker, clamps connector etc as per specification & approved drawing 256 Trefoil clamp suitable for approved XLPE cable 257 Bay marshalling kiosk, dummypanel, junction box, , Lighting & other Distribution Boards etc. As per requirement& as per Technical specification 258 Bay marshalling kiosk, 259 Dummypanel, 260 Junction box, (CT,PT,CVT as per requirement 261 Distribution Boards as per requirement 262 Cable Tray (Ladder type & perforated type etc ) as per requirement for indoor cable trench and and as per requirement within GIS building 263 Industrial type Exhaust Fans and mechanised louvers of required quantity for 220KV & 132KV GIS Hall, 33 KV indoor switchgear& 11 KV Switchgear Room as per requirement & as per Tech Spec 264 HDPE Pipes 265 200 mm Dia 266 150 mm Dia 267 One storage type RO + UV + UF water purifier for office building 268 Spares:- Spare relays including test jack are to be delivered after duly tested at CTD WBSETCL on chargeble basis. All materias will be as per scheme of this project ) 269 Distance Protection relay (as approved at 220 KV Line bay for Main-1 potection) 270 Distance Protection relay (as approved at 220 KV Line bay for Main-2 potection) 271 Distance Protection relay (as approved at 132 KV Line bay for Main-1 potection) 272 Distance Protection relay (as approved at 132 KV Line bay for Main-2 potection) 273 Transformer differential Relay(same as approved for 220 KV Transformer bay) 274 Transformer differential Relay(same as approved for 132 KV Transformer bay) 275 BCU (same as approved for 220KV bays ) 276 BCU (same as approved for 132KV bays ) 277 BCU (same as approved for 33KV bays ) 278 BCU (same as approved for auxilliary system) 279 PRP Compliant, managed Ethernet Switch, industrial grade. (same as approved for SCADA Systeml) 280 Over Current& Earth fault Relay 281 Bus Bar Differential Relay (One Central Unit and one Peripheral Unit) 282 Trip Relay 283 VT selection Relay 284 Spares: Spare are to be delivered at nearest store in consultation with in charge All materias will be as per scheme of this project. 285 220KV GIS Circuit Breaker complete mechanism 286 220KV GIS Disconnector complete mechanism 287 220KV GIS High speed earth switch complete mechanism 288 132KV GIS Circuit Breaker complete mechanism 289 132KV GIS Disconnector complete mechanism 290 132KV GIS High speed earth switch complete mechanism 291 33KV CT - same as supplied for Line bay 292 33KV CT - same as supplied for 50 MVA Transformer bay 293 Safety Equipment 294 Full Body Safety Harness with Twin rope lanyard, length < 3 meter with waist belt and accessories as per IS - 3521 295 First aid box complete with all items (as perAnnexure in line with WBSETCL Safety Manual, Version 2.0) - to be placed at Control Room & Maintenance Room 296 Discharge cum earthing rod - Highly insulated FRP telescopic type with all accessories suitable for 245 KV system or higher,CPRI type tested as per IEC - 1230:1993 & IEC - 1235 with tested epoxy earthing rod for 10 KV /ft for 1 min as per IEC- 855 297 Safety Helmet - Made of Polyethylene/ glass fibre reinforced with head band, cradle, strap fittings with withstanding temp of 50oC as per IS – 2925 (Suitable stand / Racks are to be provided to store the helmets. Helmets are to be colour coded for visitors, technical staff and others) 298 Gum Boot made of Rubber (Suitable stand / Racks are to be provided for storage.) 299 Renowned make High Voltage Detector - Suitable for 11 KV to 245 KV , 50 HZ system with sensing level 1 mtr. for 132/220/ 400 KV system complete with HV probe, 5.0 mtr telescopic insulation stick with visual LED and Buzzer indication as per IS - 13771/ IS - 2071 300 Safety shoes - Double density PU sole, leather with hard Toe cap, Non-woven Eva lining, anti static /electric shock proof Insole (with minimum electrical resistance and high voltage of 18 KV), conforming to IS – 15298 301 Hand Gloves - Made of soft quality rubber, seamless latex, shock proof, for electrical purpose suitable upto33 KV -system as per IS - 4770 302 Electric Arc Protection Suit - FR suit compatible to wearwith hood, jacket, face shield, trouser etc complaint with NEFA- 70 E standard as per IEC - 61482-1-1-2007/9 303 Insulating mat - High density insulating matsasper IS - 15652 with ac(rms) kv 3.3, sizes of rolls 5000 mm X 1000 mm (to cover entire operating length of 33KV switchgear, DB room & Panel room) 304 Safety Ladder - Single step self supporting type with complete Fiber glass, 3 inch wide, antiskid fibre steps, non - slip fibre glass shoes with thick rubber pad, Height 8 ft 305 Safety Torch / Search Light - Body:- Fibre glass, PCB - glass epoxy to meet all weather condition, Circuitry - IC Control, Charge -220 Volt AC, Light Source - 12 V Halogen Bulb, 55 watt, Power source - 12 volt, 7 AH sealed battery, Extra jack tobe provided for direct lightning by 12 volt DC, Continuous run - 2 hr High beam Rechargeable Hand Held Search light 306 Lifting Rope - Hemp Rope / Sisal Rope / Manila Rope - One inch dia., 30mtr long 307 Passenger Elevator (6 person capacity, ) - For GIS & Control buildingcomplete in all respect as per technical specification and as per requirement. 308 Industrial grade Vacuum Cleaner of reputed make 309 Civil Part: 310 Supply, fabrication, galvanisaton of variousswitchyard & equipment structures,LM-Lattice type ( 35Mtr or 50 Mtr-based on DSLP Calculation), XLPE cable supporting structure completeas per approved electrical layoutdrawings and technical specification (Electrical & civil) and as per requirement complete. (including Nuts & Bolts and foundation bolts) 311 Switchyard Structures including Nuts & Bolts 312 Foundation Bolts for switchyard structures including nuts, washers and anchor plates (Foundation Bolts shall be galvanisedupto threaded length from top) 313 Supply, fabrication of various structures (MS FLAT, MS Plate, Insert plate, Angles, Transformer Rail, Channels, ISMB, Chequred plate, MS grating for GIS Building, Transformer, Cable trench , drain etc. as per approved drawings, technical specification (Electrical & civil) andrequirement complete.