| 1 | Supply, Installation, testing and commissioning (SITC) of LT Cubicle Hybrid Distribution Panel suitable for 440 Volt, 3 Phase & Neutral, 50Hz. Supply. Detail Specification and Scope as per enclosed Annexure-\"A\". |
| 2 | Supply, Installation, Testing and Commissioning (SITC) of 2000 Amp., 65KA, 3-Pole EDO ACB along with associated accessories like interconnecting busbars, metering, indication and protection system in the existing panel inside FGKsuitable for 440 Volt, 3 Phase & Neutral, 50Hz. supply system. Detail Specification and Scope as per enclosed Annexure-\"B\". |
| 3 | Fabricate, Supply, Installation, testing and commissioning of Heavy duty Switch Dis-connector Fuse (SDF)TPN rating 630 A. having specious Sheet Steel / CRCA enclosures.Detail Specification and Scope as per enclosed Annexure-\"C\". |
| 4 | M&L for Pipe Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected by using galvanised iron 25x4mm strip as earthing lead including all required accessories like- nuts, bolts and washer, adequate quantity of charcoal dust mixed with common salt to a packed thickness of 15 cm all around the electrode, PCC chamber and reinforced PCC, 20 mm bore GI pipe with funnel medium grade for watering and 20 mm dia GI pipe light grade for protection of earth lead from earth pit to the building/test point up to 7.5 mtr. |
| 5 | S & L of 25x4mm galvanised iron strip as earth continuity conductor (ECC) or main earthing lead from earth pits to LT Panel and fixing on wall/cable tray with insulator & GI fastners/nutbolts support at suitable intervals as diretedby WIC and EIC. |
| 6 | Material and Labour for making pathway for Cables by drilling holein wall, cutting the wallfloor, MS trench cover as per site requirement and writing the cable details with black clour background and white colour gothic letter on wall & panels as directed. Note: All the demolished and excavated material shall be disposed off with in 500 mtr. distance as directed and complete with making good of all the rough surfaces using cement concrete mortar. |
| 7 | Supply, Installation of Hot Dip G.I. or M.S. Powder Coated Perforrated cable trays minimum size: 450mm x 50 mm x 2mm with coupler plates and hardware as per site requiremnt for installation on wall at a suitable height as per site requrement and as directed. |
| 8 | Supply, Installation of Hot Dip G.I. or M.S. Powder Coated Perforrated cable trays minimum size: 300mm x 50 mm x 2mm with coupler plates and hardware as per site requiremnt for installation on floor and wall at a suitable height as per site requrement and as directed. |
| 9 | S & F of mild steel work (for trench covers boarders and cable tray support) with joist, angle, channel or tee sections, fixed independently including cutting, welding fixing etc. with one coat of red oxide primer and gray/black paint complete. Fe 410-W(Gde-E-250) quality A. |
| 10 | S & F of mild steelplates (plain or chequered), channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment. complete with cutting and welding. Fe 410-W(Gde-E-250) quality A. |
| 11 | Supply & Laying of XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 300 sq. Mm, 3&1/2 Core. Make: Polycab, Gloster, Finolex, Havells, KEI, BCH or substantial equivalent as directed by WIC & EIC. |
| 12 | Supply and laying of PVC insulated, armoured, heavy duty electric control cable of copper conductor Solid/multistrand, 1100 volts grade ,cross-sectional area 2.5 sq. mm, 4 core. and cable to be laid in cable trench and cable tray including termination at both end by using suitable size copper lugs,brass gland etc.for APFC automatic switching operation through feedback from load point. Make: Polycab, Gloster, Finolex, Havells, KEI, BCH or substantial equivalent as directed by WIC & EIC. |
| 13 | Supply and Fixing of Heavy duty brass gland and barrel type heavy duty Aluminum Lugswith MS Nut-bolts washers and making end terminations of 3&1/2 Core 240 or 300 Sq.mm. PVC/XLPE Insulated Aluminum conductor Armoured cable complete as directed. Make of Gland & Lug: Comex, Dowells, Jainson |
| 14 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; in soft/loose soil for laying of pipe/cable complete all as specified. (Note:The work will be executed inside the factory premises, so that the excavation work will be done manually. Any damage during excavation work will be brone and rectified by the contractor.) |
| 15 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; in hard/dense soil for laying of pipe/cable complete all as specified. (Note: The work will be executed inside Factory premises, so that the excavation work will be done manually. Any damage during excavation work will be brone and rectified by the contractor.) |
| 16 | Returning, filling in soft/loose soil and hard/dense soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed. |
| 17 | Demolition and dismantlingof Unraenforced Cement Concrete of any description and in any position not otherwise specifically provided for as directed. |
| 18 | M&L for Cement concrete (type C2 1:3:6, 40mm graded aggregate) in foundations, filling and mass concretefor making good of excavated cable route. |
| 19 | M&L for trenchless boring under the soft/loose or hard/dense soil, building/wall/road/culvert/drain etc. and lay the pipe/cable along with the trenchless bore to pass 04 Nos. the undergroundLT armoured cable of size 3&1/2C x 300 sq.mmthrough 04 Nos. GI Pipe or as specified. (Note: Any damage during excavation/ boring work will be brone and rectified by the contractor.) |
| 20 | M&L for supply and laying of GI Pipe light grade of 100 mm bore dia (Make: Jindal/Tata/SAIL) for passing of control cable as directed. |
| 21 | M&L for supply and spreading of ganga sandunder floors or in foundations or in trenches for cushoning of cable in layer 15 cm. thick including watering and consolidation. |
| 22 | Material and Labour for brick work i.elaid dry old size brick with sub- class ‘B’ bricks straight or curved on plan exc 6 m mean radius for protection of underground cable. |
| 23 | M&Lfor supply fixing of Cast Iron cable route marker size: 300 mm (L) x 150 mm (B) x 10 mm (T) or more including inscription duly engraved text/letter/number and MS Angle Mast minimum size:50x50x5mm and height 1Mtr.buried in ground/grouting with cement concrete 1:2:4: (1 Cement, 1 Coarse Sand and 4 graded stone aggregate 20mm nominal size) on site as directed. |
| 24 | M&L for supply/fixing of Cable tag, Size: 25mm x 15mm x 1 mm. including fixing arrangement made up of stainless steel or aluminum with required embossing as directed. |