Tender For Repair And Maint Of Stand By Dg Sets, Control Panels, Switch Amf Panels And Other Connected Worksat Tbrl Range Ramgarh Area; 1 Material and labour for conducting ‘B’ check of DG sets of 25 KVA to 62.5 KVA capacities to carry out maintenance/servicing as given below complete all as specified and directed. (i) Change of diesel filter/oil filter, air filter, replacement of engine oil etc.(ii) Check and clean engine, alternator battery, instrument panel, elect panel, Timer, Contactors ,Meters and others etc.(iii) Tightening of all nuts & bolts of DG set and its accessories.(iv)Check for any diesel leakage from any point and rectify if observed.(vii)Check electrical connections of engine .The wiring shall be maintained properly and engine starting system from engine instrument panel is to be kept in order. (viii)Check and tighten the AVM pads nuts and bolts, change AVM pads if found damaged. AVM to be provided by contractor.(xiii) Oiling, Greasing and checking for proper & smooth functioning and testing on load completeNote 1. :- Price for minor spare parts like nut bolts, grease, copper conductor cable for control wiring, AVM pads will be included in the quoted rates against each capacity.2. Price for major spare parts diesel filter, oil filter, air filter, engine oil and coolant required for replacement shall be measured and paid for separately under respective item of schedule. 2 All as per serial item no 1 above but for 82.5 KVA to 125 KVA DG set-ditto- 3 All as per serial item no 1 above but for 180 KVA to 250 KVA DG set -ditto- 4 All as per serial item no 1 above but for 320 KVA to 400 KVA DG set-ditto- 5 All as per serial item no 1 above but for 600 KVA to 810 KVA DG set -ditto- 6 Supply only new fuel oil filter elements with O ring for 25 KVA to 62.5 KVADG Set complete all as specified and directed. 7 All as per serial item no 6 above but for 82.5 KVA to 125 KVA DG set -ditto- 8 All as per serial item no 6 above but for 180 KVA to 250 KVA DG set -ditto- 9 All as per serial item no 6 above but for 320 KVA to 400 KVA DG set-ditto- 10 All as per serial item no 6 above but for 600 KVA to 810 KVA DG set-ditto- 11 Supply only new lubricant oil filter cartridge element with O ringfor25 to 62.5KVADG set complete all as specified and directed. 12 All as per serial item no 11 above but for 82.5 KVA to 125 KVA DG set-ditto- 13 All as per serial item no 11 above but for 180 KVA to 250 KVA DG set -ditto- 14 All as per serial item no 11 above but for 320 KVA to 400 KVA DG set -ditto- 15 All as per serial item no 11 above but for 600 KVA to 810 KVA DG set-ditto- 16 Supply only new air filter (both outer & inner) element with O ringfor25 KVAto 62.5 KVA DG set complete all as specified and directed. 17 All as per serial item no 16 above but for 82.5 KVA to 125 KVA DG set-ditto- 18 All as per serial item no 16 above but for 180 KVA to 250 KVA DG set -ditto- 19 All as per serial item no 16 above but for 320 KVA to 400 KVA DG set -ditto- 20 All as per serial item no 16 above but for 600 KVA to 810 KVA DG set -ditto- 21 Supply only of Engine oil (15W40 or eq.) grade for DG set complete all as specified and directed. 22 Supply only coolant of specific grade forDG set complete all as specified and directed. 23 Supply only for filling of distilled water for battery complete all as specified and directed. 24 Taking down and dismantling all the components from engine assembly of 25 KVA to 62.5, diesel engine, segregating serviceable and semi/unserviceable parts, decarbonisation, cleaning all interior & exterior parts after disconnecting theout-going connection of diesel engine from the panel board, repair /replacement of defective spares and re assembling the DG set after completion of work and make it serviceable complete all as specified and directed. Note: (i) Spare parts/ components measured and paid for separately under relevant items. (ii) Cost of transportation of defective components from site of work to workshop (if any) shall deemed to be included in the unit quoted rate 25 All as per serial item no 24 above but for 82.5 KVA to 250 KVA DG set-ditto- 26 All as per serial item no 24 above but for 320 KVA to 400 KVA DG set-ditto- 27 Repair/re-conditioning of cylinder head (as dismantled under serial item No. 24 above) including machine work of 25 KVA to 62.5 KVA DG set complete all as directed. 28 Repair/re-conditioning of cylinder head (as dismantled under serial item No. 25 above) including machine work of 82.5 KVA to 250 KVA DG set complete all as directed. 29 Repair/re-conditioning of cylinder head (as dismantled under serial item No. 26 above) including machine work of 320 KVA to 400 KVA complete all as directed. 30 Repair/re-conditioning of cooling pump with its all assembly, pipes and clamping ring, engine mounted (as dismantled under serial item No. 24 to 26 above) including machine work of any capacity complete all directed. 31 Repair/overhauling turbo-charger (as dismantled under serial item No. 24 to 26 above) including repair/replacement of unserviceable spares of any capacity complete all as specified and directed. 32 Repair/calibration and testing of injectors (as dismantled under serial item no. 24 to 26 above) of any capacity complete all as directed. 33 Overhauling and testing of governor assembly (as dismantled under serial item No. 24 to 26 above) of any capacity Including machine work complete all as specified and directed. 34 Material and labour for repair of fuel injection pump/pt pump including dismanting the fuel injection/ pt pump, segregating serviceable and semi/unserviceable parts, replace all unserviceable parts and cleaning serviceable parts, drying, lubricating, re-assembling the FIP/PT pump with cleaned serviceable parts along with new parts as required , calibration, testing complete on computerised testing equipment all as directed. 35 Supply only piston suitable for DG engine 25 KVA to 62.5 KVA complete all as specified and directed. 36 Supply only cylinder liner suitable for DG engine 25 to 62.5 KVA complete all as specified and directed 37 Supply only piston ring set suitable for DG engine 25 to 62.5 KVAcomplete all as specified and directed. 38 Supply only piston pin suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 39 Supply only piston circlips suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 40 Supply only O seal ring, first groove suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 41 Supply only O seal ring, 2nd & 3rd groove suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 42 Supply only main bearing upper & lower suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 43 Supply only oil seal ring suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 44 Supply only radiator cap suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 45 Supply only thrust bearing suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 46 Supply only inlet/exhaust valvesuitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 47 Supply only inlet/exhaust valve seat ring suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 48 Supply only valve guide suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 49 Supply only valve collet suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 50 Supply only valve stem cap suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 51 Supply only valve seal suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 52 Supply only washer for cylinder head cover suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 53 Supply only seal ring (rocker arm) suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 54 Supply only water drain cock sub assembly suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 55 Supply only front oil seal suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 56 Supply only rear oil seal suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 57 Supply only connecting rod bearing suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 58 Supply only connecting rod bush suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 59 Supply only oil sump washer suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 60 Supply only inlet pipe for feed pump suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 61 Supply only v-belt suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 62 Supply only copper washer suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 63 Supply only HCT switch suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 64 Supply only thermostat body suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 65 Supply only radiator water inlet hose suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 66 Supply only radiator water outlet hose suitable for DG engine 25 to 62.5 KVA complete all as specified and directed 67 Supply only thermostat element suitable for DG engine 25 to 62.5 KVA complete all as specified and directed. 68 Supply only pistonsuitable for DG engine 82.5 KVAto 250 KVA complete all as specified and directed 69 Supply only cylinder liner suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed 70 Supply only piston ring set suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 71 Supply only piston pin suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 72 Supply only piston circlips suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 73 Supply only o seal ring, first groove suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 74 Supply only o seal ring, 2nd & 3rd groove suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 75 Supply only main bearing upper & lower suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 76 Supply only oil seal ring suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 77 Supply only radiator cap suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 78 Supply only thrust bearing suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 79 Supply only inlet/exhaust valvesuitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 80 Supply only inlet/exhaust valve seat ring suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 81 Supply only valve guide suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 82 Supply only valve collet suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 83 Supply only valve stem cap suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 84 Supply only valve seal suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 85 Supply only washer for cylinder head cover suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 86 Supply only seal ring (rocker arm) suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 87 Supply only Water drain cock sub assembly suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 88 Supply only front oil seal suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 89 Supply only rear oil seal suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 90 Supply only connecting rod bearing suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 91 Supply only connecting rod bush suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 92 Supply only oil sump washer suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 93 Supply only inlet pipe for feed pump suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 94 Supply only v-belt suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 95 Supply only copper washer suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 96 Supply only HCT switch suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 97 Supply only thermostat body suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 98 Supply only radiator water inlet hose suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 99 Supply only radiator water outlet hose suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 100 Supply only thermostat element suitable for DG engine 82.5 KVA to 250 KVA complete all as specified and directed. 101 Supply only piston suitable for DG engine 320 KVAto 400 KVA complete all as specified and directed 102 Supply only cylinder liner suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed 103 Supply only piston ring set suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 104 Supply only piston pin suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 105 Supply only piston circlips suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 106 Supply only o seal ring, first groove suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 107 Supply only o seal ring, 2nd & 3rd groove suitable for DG engine 320 KVA to 400 KVA KVA complete all as specified and directed. 108 Supply only main bearing upper & lower suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 109 Supply only oil seal ring suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 110 Supply only radiator cap suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 111 Supply only thrust bearing suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 112 Supply only inlet/exhaust valvesuitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 113 Supply only inlet/exhaust valve seat ring suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 114 Supply only valve guide suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 115 Supply only valve collet suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 116 Supply only valve stem cap suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 117 Supply only valve seal suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 118 Supply only washer for cylinder head cover suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 119 Supply only seal ring (rocker arm) suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 120 Supply only water drain cock sub assembly suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 121 Supply only front oil seal suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 122 Supply only rear oil seal suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 123 Supply only connecting rod bearing suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 124 Supply only connecting rod bush suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 125 Supply only oil sump washer suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 126 Supply only inlet pipe for feed pump suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 127 Supply only v-belt suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 128 Supply only copper washer suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 129 Supply only HCT switch suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 130 Supply only thermostat Body suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 131 Supply only radiator water inlet hose suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 132 Supply only radiator water outlet hose suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 133 Supply only thermostat element suitable for DG engine 320 KVA to 400 KVA complete all as specified and directed. 134 Dismantling of self-starter 24V DC by disconnecting battery connection, taking out to civil workshop for carrying out following repair work and refixing including testing complete: - (i) Rewinding of armature & field coil. (ii) Replacement of carbon brush and solenoid switch (iii) Replacement of gear assembly all as specified and directed. 135 Dismantling of self-starter 12V DC by disconnecting battery connection, taking out to civil workshop for carrying out following repair work and refixing including testing complete: - (i) Rewinding of armature & field coil. (ii) Replacement of carbon brush and solenoid switch (iii) Replacement of gear assembly all as specified and directed. 136 Material and labour for repair of alternator 3 phase 440V of any capacity DG set, including dismantling the alternator from its mounting by unscrewing the nut & bolts. cleaning the whole assembly of alternator, replace the commutator, carbon brush, rectifier, slip rings, slip ring end bearing drive end bearing etc andre-assembling the all parts and mounted the alternator on its same place and do the connection as previous complete all as specified and directed . 137 Dismantling of defective dynamo from engine, supply and fixing new dynamo 24 volt DC, including replacement of worn out nuts bolts mounting clamp etc. complete all as specified and as directed. 138 Supply and replacement self-starter 12 volts DC suitable for DG Set 63/82.5/110 KVA complete all as specified and directed. 139 Supply and replacement self-starter 24 volts DC suitable for DG set 125/200/250/320/400 KVA complete all as specified and directed. 140 Opening the coupling of DG set of capacity 82.5 to 400 KVA the outer cover and taking out the fly wheel ring and shifting to workshop for repair in and including replacement of fly wheel ring by pressing machine and reinstalled the same after repair to make it fully functional complete all as specified and directed. 141 Supply and replacement of compact type battery charger unitsuitable for charging01 battery ,12 V 180 AH complete all as specified and directed with 2m copper leads -02 Nos & brass clamps complete all as specified and directed 142 Material and labour cleaning of diesel tank of DG set of any capacity including replacement of worn out pipe line and measuring scale and fixing in original position and make it leak proof with necessary clamps complete all as specified and directed. 143 Supply and fixing battery 12V, 150 AH with 25 nos electro plates including battery lead positive & negative battery terminal complete duly charged . Make exide (brand : exide express) or equivalent all as specified and directed. 144 Supply and fixing battery 12V, 160 AH pulse ultra lite, maintenance free including battery lead positive & negative battery terminal complete duly charged . make - cummins part No. AX1012845 or equivalent complete all as specified and directed. 145 Supply and fixing battery 12V, 180 AH with 25 Nos electro plates including battery lead positive & negative battery terminal complete duly charged . Make Exide (brand : exide express) or equivalent complete all as specified and directed 146 Supply and fixing in repair automatic voltage regulator suitable for 25 KVAto 82.5 KVAas per sample complete all as specified and directed. 147 Supply and fixing in repair automatic voltage regulator suitable for 100 KVAto 250 KVAas per sample complete all as specified and directed. 148 Supply and fixing in repair automatic voltage regulator suitable for 320 KVAto 810 KVAas per sample complete all as specified and directed. 149 Repair to existing unserviceable automatic main failure (AMF) panel of any capacity installed at various locations by carrying out the following repair work:(a) Disconnecting the incoming power supply and taking out and dismantling the electrical components from the AMF panel of any make and replacement of unserviceable/burn out/defective parts and cleaning/servicing entire interior and exterior serviceable parts and refixing the same in existing position including connections, testing and commissioning etc complete all as specified and directed.(Note: (i) Spare/parts shall be measured and paid for separately as supply only under respective items here-in-below. (ii)fixing charge for spare/part, control wiring (copper conductor cable FRLS) of any size, cleaning of panel, replacement of unserviceable lock and any type welding work used for repair the panel shall deemed to be inclusive under this item. 150 Supply only MCB, SP, 6-32 amps, C curve suitable for AMF panel 35-250 KVA complete all as specified and directed. 151 Supply only MCB, SPN, 6-32 amps, C curve complete all as specified and directed. 152 Supply only MCB, TPN, 6-32 amps, C curve complete all as specified and directed. 153 Supply only instrument operating relay, coil voltage 12 volts DC suitable for AMF panel complete all as specified and directed. 154 Supply only 3 pole power contactors type MNX-185 (185 amp) with suitable coil voltage or equivalent as per site requirement complete all as per Make : L & T or equivalent all as per specified and directed. 155 Supply only 4 pole power contactors type KCL64 225 (225 amp) with suitable coil voltage or equivalent as per site requirement complete all as per Make :Kirloskar or equivalent all as per specified and directed. 156 Supply only 3/4 pole power contactors MNX 400 (400 amp)with suitable coil voltage or equivalent as per site requirement complete all as per Make :L&T, GE, Havells, Kirloskar or equivalent all as per specified and directed. 157 Supply only selector switch suitable for AMF panel of any capacity complete all as specified and directed. 158 Supply only digital panel meter with built in transducer suitable for AMF panel of any capacity complete all as specified and directed. 159 Supply only oil pressure meter suitable for AMF panel of any capacity complete all as specified and directed. 160 Supply only lubricant oil temp meter suitable for AMF panel of any capacity complete all as specified and directed. 161 Supply onlyheat temp meter suitable for AMF panel of any capacity complete all as specified and directed. 162 Supply only battery charging meter suitable for AMF panel of any capacity complete all as specified and directed. 163 Supply only current transformer, copper wound suitable for any capacity complete all as specified and directed. 164 Supply only relay timer 0.6 S-60M*2 C/O suitable for AMF panel of any capacity complete all as specified and directed. 165 Supply only standard push button and selector actuators suitable for AMF panel of any capacity complete all as specified and directed. 166 Material and labour for replacement of AMF panel controller suitable of DG set of capacity 25 KVA to 125 KVA complete all as specified and directed. 167 Material and labour for replacement of AMF panel controller suitable of DG set of capacity 180 KVA to 380 KVA complete all as specified and directed. 168 Supply and fixing in replacement MCCB 125 amp 16 KA, 3 pole, adjustable type complete all as specified and directed. 169 Supply and fixing in replacement MCCB 160 amp 36KA,3 pole, adjustable type complete all as specified and directed.. 170 Supply and fixing in replacement MCCB 200 amp 36KA, 3 pole, adjustable type complete all as specified and directed.. 171 Supply and fixing in replacement MCCB 250 amp 36 KA, 4 pole, adjustable type complete all as specified and directed. 172 Supply and fixing in replacement MCCB 400 amp 36KA, 4 pole, adjustable type complete all as specified and directed. 173 Supply and fixing in replacement MCCB 630 amp 50KA, 4 pole, adjustable type complete all as specified and directed. 174 Supply and fixing ofon-load type changeover switch 400 amp, 415 volt, open enclosure type complete all as specified and as directed. Make: Havells/L&T/BCH/Schneider 175 Supply and fixing ofon-load type changeover switch 250 amp,415 volt, open enclosure type complete all as specified and as directed. Make: Havells/L&T/BCH/Schneider 176 Supply and fixing ofon-load type changeover switch 200 amp, 415 volt, open enclosure type complete all as specified and as directed. Make: Havells/L&T/BCH/Schneider 177 Supply and fixing ofon-load type changeover switch 100 amp, 415 volt, with SSenclosure type complete all as specified and as directed. Make: Havells/L&T/BCH/Schneider 178 Supply, installation, testing and commissioning cummins power command controller (PCC 3300) Part No. A054J968 for DG set as per existing or equivalent. complete all as specified and directed. 179 Supply, installation, testing and commissioning cummins PCB assembly for DG Set Part No. 0327-1507 as per existing or equivalent. complete all as specified and directed. 180 Supply, installation, testing and commissioning cummins Aux 105 PCB board for DG Set Part No. A028T766 as per existing or equivalent. complete all as specified and directed. 181 Supply, installation, testing and commissioning cummins electronic control panel, genset Dg controller part no. 4083935 as per existing or equivalent. complete all as specified and directed. 182 Supply, installation, testing and commissioningcummins power command HMI 211,24V DC for DG set as per existing or equivalent. complete all as specified and directed. 183 Supply, installation, testing and commissioning of factory made and tested AMF panel for 250 KVA DG set indoor type, platform mounted, suitable for 415 volts 3 phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 2.0 mm thick CRCA mild steel sheet and mild steel, mounting channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:- 184 (a)Under voltage relay 415V AC for main -1 No. (b) Under voltage relay 415 V AC for DG - 1 No.(c) AC Timer 230 Volt , 2 No. +2 NC - 1 No.(d) DC timer 12/24 V -1No.(e) Control MCB SP 6 Amp.230 V – 9 Nos.(f) Control MCB SP 16 Amp.230 V – 2 Nos.(g) Battery charger 12/24 DC with SMPS- 1 No. (h) LED indicating light for main & DG—6 Nos(j) LED indicating light for main and gen. On – 2 nos.(k) LED Indicating Light for battery Charger –1 No.(l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-100 A ) 96 mm X 96 mm with Selector switch - 1 Set.(n) CT Coil 350 / 5 A - 3 Nos.(o) DC Volt Meter 15/30 V - 1 No.(p) DC Amp Meter0-15 A - 1 No.(q) Trickle / Boost switch –2 Nos.(r) Auto / Manual Selector Switch ---1 No.(s) Start & Stop Push Button- 2 Nos.(t) 4 point alarm annunciator with inbuilt hooter ,test, accept& resetpush button, 12/24 V DC - 1 No(u) Power Contactor 350 A 3 Pole 415V AC for DG - 1 No.(v) Power Contactor 350 A 3 Pole 415V AC for Main - 1 No.(w) Incoming MCCB 350 A 36 KA 3 Pole Thermal Magnetic release adjustable type for Main & DG Supply - 2 Nos(x) AMF controller 24V DC - 01 No. (y) Aux Relay, coil voltage 24 DC ,14 pin - 06 No. (z) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set.(aa) PCC foundation as per manufacturers instruction. complete all as specified and directed. 185 Supply, installation, testing and commissioning of factory made and tested AMF panel for 82.5 KVA DG set outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class (IP-65) and made of out of not less than 3.15 mm thick CRCA mild steel sheet and mild steel, Mounting Channel work made out of 75 mm ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:- 186 (a)Under Voltage relay 415V AC for main -1 No.(b) Under voltage relay 415 V AC for DG - 1 No.(c) AC Timer 230 Volt , 2 No. +2 NC - 1 No.(d) DC Timer 12/24 V -1No.(e) Control MCB SP 6 Amp.230 V – 9 Nos.(f) Control MCB SP 16 Amp.230 V – 2 Nos.(g) Battery Charger 12/24 DC with SMPS- 1 No. (h) LED Indicating Light for Main & DG—6 Nos(j) LED Indicating Light for Main & Gen. ON – 2 Nos.(k) LED Indicating Light for battery Charger –1 No.(l) Digital Volt meter ( 0-500 V ) 96 mm X 96 mm with Selector switch - 1 Set. (m) Digital Amp meter ( 0-100 A ) 96 mm X 96 mm with Selector switch - 1 Set.(n) CT Coil 125 / 5 A - 3 Nos.(o) DC Volt Meter 15/30 V - 1 No.(p) DC Amp Meter0-15 A - 1 No.(q) Trickle / Boost switch –2 Nos.(r) Auto / Manual Selector Switch ---1 No.(s) Start & Stop Push Button- 2 Nos.(t) 4 point alarm annunciator with inbuilt hooter, test, accept & resetpush button, 12/24 V DC - 1 No.(u) Power Contactor 125 A 3 Pole 415V AC for DG - 1 No.(v) Power Contactor 125 A 3 Pole 415V AC for Main - 1 No.(w) Incoming MCCB 125 A 16 KA 3 Pole Thermal Magnetic release adjustable type for Main & DG Supply - 2 Nos(x) AMF controller 12/24V DC - 01 No. (y) Aux Relay, coilvoltage 12/24 DC ,14 pin - 06 No. (z) Interconnecting Aluminium Link from MCCB to Contactors with Incoming & Outgoing- 1 Set.(aa) PCC foundation as per manufacturers instruction. complete all as specified and directed.