Tender For Replacement And Upgradation Of Existing Ups And Associated Mv Panel At Kcb, Admin And Hospital Building Inside Iitm Premises
Tender Value
72.87 Lakhs
Estimated cost
Bid Submission
02 Sep 2025
0 days left
EMD
1.45 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
madras → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Replacement And Upgradation Of Existing Ups And Associated Mv Panel At Kcb, Admin And Hospital Building Inside Iitm Premises
BOQ
| Sl. No. | Item Description |
| 1 | SITC of100KVA(3Ph-3Ph) 12V/576VDC, Online Double Conversion UPS under Parallel Redundant System including MS rack for housing the batteries along with necessary interconnection cables. Warranty: 2 Years for UPS. |
| 2 | SITC of 12V/150Ah/48 Nos of SMF BatteriesBattery Make: EXIDE SMF VRLAWarranty: 2 Years for SMF Batteries. |
| 3 | SITC of40KVA(3Ph-3Ph) 12V/408VDC, Online Double Conversion UPS under Parallel Reduntant System including MS rack for housing the batteries along with necessary interconnection cables. Warranty: 2 Years for UPS. |
| 4 | SITC of of 12V/100AH / 34 Nos SMF BatteriesWarranty: 2 Years for SMF Batteries |
| 5 | SITC of6KVA(1Ph-1Ph) 12V/192VDC, Online Double Conversion UPS including MS rack for housing the batteries along with necessary interconnection cables. Warranty: 2 Years for UPS |
| 6 | SITCof 12V/28AH /16 Nos SMF BatteriesWarranty: 2 Years for SMF Batteries |
| 7 | Supply and laying of single core 95sqmm copper PVC FRLS Single Core Flexible Industrial power cable, 1100 V in a suitable size PVC Coated Steel Wire Reinforced flexible Hose Pipe. |
| 8 | Supply and making end termination with suitable copper lugs for 95sqmm copper PVC FRLS Single Core Flexible Industrial power cable |
| 9 | Supplying and fixing of the 4 pole,250A MCCB\"s in the existing MV panel with necessary incoming and outgoing connections without enclosure and including extended bars /wires if required/ terminal spreaders. |
| 10 | Supply and fixing of Sheet Metal MCCB Enclosure, Powder Coated.suitable for fixing 250A 4P MCCB |
| 11 | SITC of 63A TPN tap off box / plug in box 1.6mm thick sheet steel enclosure duly painted with powder coated on existing Over head busbar system complete with TPN disconnector, connections, earthing as required. |
| 12 | Earthing with copperearth plate 600x600x3mmthick including 2 Runs of 25 x 3 mm copper flat between the bottom of the plate and theclamp fixed on the top of the GI pipe , funnel etcand providing masonary enclosure with cover plate having locking arrangement and watering GI pipe of 2.7m long etc with charcoal/coke/salt and salt as required. |
| 13 | MV PANEL |
| 14 | Supply , Erection,Testing and commissioningof suitable size floor mounting cubical type followingLT Main Panel board suitable for 415V 3ph 4 wire 50Hz AC supply system fabricated in a compartmentalizeddesign from CRCA sheet steel of 2mm thick for frame works and cover with 3mm thick removable gland plate ,cleaning and finishing with 7 tank process for powder coating with siemens grey having extensible type TPN copper alloy busbar of suitable capacity as per the incomer ACB /MCCB/SDF ratingswith DMC/SMC busbar suppotrs with short circuit withstand capacity of 31MVA / 1Second , bottom base channel of 75mmX 50mm X 5mm. |
| 15 | BUS BARS |
| 16 | Bus bars will be electrolytic copper , air insulated , R,Y,B, N(Black) PVC sleeved capable of carrying full load currentfor all the 3 phases and neutral continiously. The bus chamber should have proper air ventilators. |
| 17 | EARTHING |
| 18 | 2 separate run of 25 x 3 mm copper earth bus painted in green colour should be provided all along the panel and connected to the main grid. Interconnectios should be taken to metering chamber, MCCB\"s, ACB\"s, FSU\"s etc sothat all current carrying components are effectively earthed. |
| 19 | ADDITIONALSCOPE OF WORK |
| 20 | The scope of work includes minor civil works like breaking of concrete floors ,masonary works ,and suitable MS \"П\" type channels for the proposed panel as per the instruction from the Engineer in Charge. . The cable should be re terminated ater completion of all the erection works.Necessary Panel drawings , QAP and GTP have to beapproved by the Engineer incharge before fabrication. |
| 21 | Incomer |
| 22 | 400A FP, MCCB 36kA with electronic based trip units- ,front operated handle and with ON/OFF/TRIP indications-2 Noswith inter lock |
| 23 | Buscoupler |
| 24 | 400A FP MCCB 36kA with electronic based trip units- ,front operated handle and with ON/OFF/TRIP indications-1 No with inter lock |
| 25 | Outgoing |
| 26 | 250A TPN MCCB 36kA- 4 Nos with electronocs based trip units,100A TPN MCCB 25kA- 2 Nos, 63A TPN MCCB 25kA- 2 Nos with thermal magnetic based trip units ,front operated handle. |
| 27 | 400A copper bus bars for 3phases and neutral |
| 28 | 3 phase indication lamps with toggle switch-1set, microprocessor based digitalmulti function meter with communication port andthe facility for active and reactive power measurements -2set with required CTs and control fuses etc.Necessary Spreaders / extended copper bus bars of suitable rating with required holes should be provided for the cable and bus bar terminations. |
AI Tender Summary
Tender Timeline
Aug 21, 2025
11:30 IST
Tender Published
Tender notice published.
CompletedSep 02, 2025
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedSep 03, 2025
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender