CERTAIN MISC PETTY REPAIRS OF DAY TO DAY COMPLAINTS TO VARIOUS ACCNS, REPAIR/ MAINT TO DAMAGED ROOF/ CHAJJA, LEAKAGE SEEPAGE TREATMENT, PLUMBING, ATTENDING DAY TO DAY COMPLAINTS OF INTERNAL SUPPLY IN MD & OTM ACCN AT AFTC, CQAE (WE) & AFS JALAHALLI; 1 Use and waste of form work fair finished surfaces to sides and soffits of floor or roof beams, lintels, cantilevers etc all as specified and directed. 2 M&L for Steel reinforcement TMT bars 10mm dia and over cut to length and bent to shape required including cranking, bending spirally for hoping for columns, hooking end and binding with mild steel wire (annealed) not less than 0.9mm dia or securing with clips incl removal of old reinforcement all as specified and directed. 3 M&L for Steel reinforcement TMT bars 6mm dia to 8mm dia cut to length and bent to shape required including cranking, bending spirally for hoping for columns, hooking end and binding with mild steel wire (annealed) not less than 0.9mm dia or securing with clips incl removal of old reinforcement all as specified and directed. 4 M&L for Reinforced Cement Concrete (Nominal Mix) 1:1½:3 Type A1 (using 20 mm gradedstone aggregate) as in Slab/beam/columns supported on walls, beams and column in floors, balconies etc complete including demolition of old reinforced cement concrete and finishing the surface with one coat of white wash all as specified and directed. 5 Repair to cracks and damaged existing surface of RCC roof slab/RCC facia/RCC chajja upto double storey (Approx height 7.50 Mtr from the natural ground level) by structural strengthing using injection pressure grouting with Sikadur 52, low viscous epoxygroutof Make M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s Thermex Limited, M/s STP Limited, (as approved by GE), complete all as manufacturers and all as specified and directed by GE as under:- 6 Providing and drilling 10mm dia holes using pneumatic drill as per site condition but not exceeding 50cm c/c in zig-zag patten for 75mm depth and fixing high pressure bear up Metal/Aluminium body indection packer along the holes and packing with Sika rep Micro Crete 4, rapid setting cement based plugging mortar of Make M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s Thermex limited,M/s STP Limited, (as approved by GE) 7 Mixing base and hardner of Sikadur 52, low viscous solvent free epoxy injection grout of Make M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals,M/s Thermex limited,M/s STP Limited, (as approved by GE)using slow speed electricity operated mixing paddle (200-300RPM) and injecting the same using electrically operated high pressure (upto 1000 Kgf/SqCM) pump until refusal to adjacent complete as per manufacturers specification. 8 Cutting and flushing the nozzoles and excess materials with a sharp scraper to take away sharp protrusions and to get a smooth and flat finish 9 Note :- The work under (item No. 5 to item No. 8 of BOQ) shall be carried out through authorized and qualified applicators of the any following manufacturer only. M/s Sika India Pvt Ltd, M/s Fosroc Chemicals, M/s STP Limited, M/s Thermax Limited 10 A performance guarantee certificate for two years shall be submitted by the contractor to the GE on completion of work as specified 11 The unit rate quoted is deemed to included for Removing of accumulated earth of any width and depth upto 15 cm cleaning/cutting the grass with hand operated petrol/kerosene driven grass cutting machine and removing the grass waste around 3 m from plinth protectionto outside MD land Note: Periodicityof cutting of grass shall be before commencement of work and after completion of repairs. 12 M&L for Dismantling/ taking down old existing unserviceable cement plaster, loose/ unsound weaken cement concrete of any description and in any position from existing external / internal surface of RCC roof/ slab/ beams/ columns/ RCC facia for an average depth of 25mm (Approx height 7.5m from natural ground level) with power driven pneumatic flat/pointed chisel and removing the honeycombed area including all the corners and making a neat profile of the cavities, roughen the smooth surface , scrapping out/removing corrosion all loose/scale/rust etc form the visible reinforcement by applying rust remover such as Rust Off 100 of make M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s STP Limited, M/s ThermaxLimited( as approved by GE) and cleaning the steel reinforcement properly, complete all as per manufactures instructionand all as specified and directed by Engineer-in-Charge. 13 Note for item No. 12 :-(a) Providing cement based angle fillet for 75mm X 75mm admixer with Sikacim, integralwaterproofing liquid M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s Choksey Chemicals Pvt., M/s BOSTIk India pvt limited, M/s STP Limited, (as approved by GE) @ 0.2% by weight of cement or as per manufacturer’sinstructions over a coat of acrylic emulsion bonding agent, such as Sika Latex in 1:1:3 ratio of Make M/s Sika India Pvt Ltd, or equivalent in M/S Fosrox chemicals, M/s STP Limited, M/s Thermex Ltd (as approved by GE) having specific gravity of 1.02 or as per manufacturer’s instructions with necessary surface preparation such as creating mechanical key like rougheing the surface by scrabbing, grit blasting and cleaning the existing surface using high pressure water jet machine having pressure upto 500 barpressure to remove the dirt, dust, loose particles , wax, efforencene and other contaminations from the surface of RCC columns/ beams/ slabs/ facia/ any brick/ stone surfaces etc complete all as manufactures instructions and all as specified and directed by Engineer-in-Charge. 14 (b) Providing and applying FRIAZINC R, corrosion inhabiliting Active Zinc rich primer of make M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s STP Limited, M/s Thermex Ltd (as approved by GE) along the exposed reinforcement surface property and allowed to dry. 15 (c)Providing and applying Hibond, Epoxy based Thixotropic bonding adhesive of Make from M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s Choksey Chemicals Pvt., M/s BOSTIk India pvt limited, M/s STP Limited, ( as approved by GE) over the prepared concrete surface to get a good bonding between existing concrete surface and providing Sika Rep Microcrete 4 Fiber reinforced cementitious repair micro concrete of make M/s Sika India Pvt Ltd, or equivalent in M/s Fosroc Chemicals, M/s STP Limited, M/s Thermex Ltd ( as approved by GE) over Epoxy based bonding agent applied area before 6 Hrs etc including providing necessary proportions , bracing and runners to relieve the member from the load coming on it including scaffolding leak proof shuttering with working platform as required and as per design and pattern complete including preparing the surface to match with the existing surface,complete all as specified and directed. 16 (d) Note : The work under (Item No. 12 to Item No. 15 of BOQ) shall be carried out through authorized and qualified applicators from any of the following manufacturer only. M/s Sika India Pvt Ltd, M/s Fosroc Chemicals, M/s STP Limited, M/s ThermaxLimited 17 (i)A performance guarantee certificate for two years shall be submitted by the contractor to the GE on completion of work as specified. 18 (ii) The unit rate quoted for item No. 12 to 15 of BOQ is deemed to be included for Removing of accumulated earth of any width and depth upto 15 cm cleaning/cutting the grass with hand operated petrol/kerosene driven grass cutting machine and removing the grass waste around 3 m from plinth protectionto outside MD land Note: Periodicityof cutting of grass shall be before commencement of work and after completion of repairs. 19 Taking down chowkhat or frame (wooden/steel) exceeding 1.50 Sqm not exceeding4.0 Sqm each with shutter (with out taking off shutters from the frame) all as specified and as directed. 20 Taking down shutters of any description exc 1.0 Sq.m andn.exc 2.0 Sq.m each complete all as specified and directed. 21 M&L Second class hard wood plain, solid, straight Chowkats and frames, wrought, framed, rebated on the solid, rounded or chamfered, put together with glue pinned at jointscomplete all as specified and directed. 22 S&F 2nd class hard wood 35mm thick Factory made plain framed panelled shutter any number of panelswith lock rail and panel of 9mm BWP commercial ply or 12mm veneered partical board with commercial veneering on both faces. The size of rail and stile as per IS 1003 (Part-I), kiln seasoned and chemically pressure treated complete all as specified and directed. 23 S&F Factory made 35mm thick Glazed and skeleton shutters/windows, open rebated and prepared to receive glass, gauze, etc. divided into squares, with plain, chamfered or rounded, mitred and rebated sash bars, any numbers, edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc.; sizes of members of shutters as specified in SSR Part I, Section 8, clause 8.24 (a);all as specified and directed. 24 Preparation of new wood orwoodensurface of any description not otherwise described over 10cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified and directed 25 Supply and fixing 100mm long Butt hinges medium weight cold rolledstainless steel, and fixed complete all as specified and as directed. 26 Supply and fixing 200 mm long aluminium anodized barrel tower bolt extruded section complete all as specified and as directed. 27 S&F aluminium handles cast type anodised 200 mm long complete all as specified and as directed. 28 S&F 250mm aluminium alloy, anodised, sliding door bolts with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extrudud sections or cast aluminium alloy and fixed complete all as specified and as directed. 29 S&F Stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.4mm complete all as specified and directed. 30 Petty repair to wooden door,skelton door,flush door, wooden window, wooden ventilator, cupboard door, wardrobe door,PVC door with shutter (size upto 3 Sqm) including roller, windows, etc with minor repair and easying and adjustment/alignmentto openable with assessories and including taking down and refixing complete all as specified and directed. 31 Petty repair to aluminium section/glass doors, windows, ventilators, partitions and making good the same size upto 5 Sqm(i.e. including change of Handles, hinges, star lock, rubber beadings, bottom bearing, clips etc) including taking down and refixing complete all as specified and directed. 32 Supply and fixing in repairs 200 mm long aluminium anodized barrel tower bolt extruded section complete all as specified and as directed. 33 Supply and fixing 100mm long Butt hinges medium weight cold rolledstainless steel, fixed in repair to wooden frame/welded to metal frame complete all as specified and as directed. 34 S&F in repairs floor door stopper of aluminium alloy body and tongue anodized with hard drawn steel spring fixed in floor overall 140mm complete including taking down existing oneall as specified and as directed. 35 Supply and fixing in repairs aluminium handles cast type anodised 200 mm long complete all as specified and as directed. 36 Supply and Fixing in repairs 250mm Aluminium alloy, anodised, sliding door bolts with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extrudud sections or cast- aluminium alloy and fixed complete all as specified and as directed. 37 S&F Aluminium body door closer hydraulically regulated,designation No.3, universal type, suitable for door shutters of 851 to1000 mm in width and of weight between 61 to 80 kg and fixed including taking down existing one complete all as directed. 38 S&F in repair powder coated aluminium curtain rod fancy type (colour as approved) of 20mm boreincludingbrackets, stops, rollers, etc. andfixed to wall with steel screws complete all as specified and as directed . 39 Taking down and refixing MS window shutters n. exe 1.5 sqm through cutting of existing any type of hinges, handle and tower bolt and fixing new box type hinges, MS handle and MS tower bolt the same window by necessary welding.The quoted rates shall be included the following aspect:-(a) Cutting of existing piano hinges, handle and tower bolt from window frame and shutter.(b) Fixing of removed shutter in the same frame on MS box type hinges 100mm, MS handle 100mm and MS tower bolt 100mm by welding.(c) Easing and adjusting the shutter before re-fixing if required.(d) Finishing the window frame and shutter with two coat of synthetic enamel paint.(e) Necessary scaffolding material to be included as the building height is more than 10mtr.Note :Box type hinges, handle and tower bolt shall be measured separately as supply only and labour element is deemed to be included in this item. 40 Supply only MS Box type hinges 50mm. 41 Supply only MS Handle 100mm. 42 Supply only MS tower bolt 75mm 43 Supply and fixing in repair steel window peg stay all as specified and directed. 44 S&F in repair looking mirror of size 600mm x 450mm on commerical ply wood 6mm thick with PVC/ wooden moulding beading fixed to wooden plugs with chromium plated brass, screws and cup, washers, aluminium frame and fixed complete all as specified and directed. 45 M&L for Preparation of old decoratedplastered or unplastered surfaceof wall, brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent , trading, oil, greasy spots and applying one coat ofoil bound distemper complete all as specified and as directed. 46 Material and labourfor Preparation of old decoratedplastered or unplastered surfaceof wall, chajja,ceiling, balcony, facia etc., brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent, trading, oil, greasy spots and applyingone coat of whitewashcomplete all as specified and directed. 47 M&L for Preparation of old painted wooden surface of any description and applying one coat of synthetic enamel paint, not otherwise described over 10 cm width or girth, complete all as specified and directed. 48 M&L for Preparation of old painted surfaces of steel and applying one coat of synthetic enamel paintover 10 cm width or girth, not other wise describedcomplete all as specified and as directed. 49 Treating the sunken floor slab comporising of the following specifications all as specified & directed:- 50 (a) Demolition of cement concrete of any description in sunken portion of toilet and removing debris outside MD land. 51 (b) Cleaning the sunken/ lowered portion of RCC slab surfaces (including vertical total depth plus skirting height) of floors by wire brush, chisel out any mortar sticking to the surface and brooming completely and providing 40mm thick (avg) PCC 1:2:4 type B-1 using 20mm graded aggregate as in padding concrete to achieve proper slope including cutting holes in bricks or RCC wall for provision ofspout (WPC measured and paid separately) 52 (c) Rendering of uneven surfaces with 10mm thick CM 1:4 mixed with required water proofing compound as per manufacturer instruction. Fill it with water and check dampness and seepage. Where dampness/ seepage is noticed, nozzles shall be fixed and grouting carried out. (WPC shall be measured and paid separately). 53 (d)All junctions points of side wall spout where CI/ GI pipes are passing through shall be sealed with epoxy putty. 54 (e)After drying putty, wash the slab and sides of sunken portion with water and make it clear and clean. 55 (f) Applying two coats of polymer modified cementious water proof coating as per manufacture instruction to bottom and vertical sides up to finished floor level+100mm height. The thickness of two layer shall be 1mm. When the second layer is still sticky, coarse sand spray shall be carried for the vertical and bottom surface of the sunken portion all as specified and directed. 56 (g)Plaster the bottom and sides up to bottom of the skirting with minimum 20mm thick CM 1:4 mixed with integral water proofing compound as per manufacturers specification including rounding of corners and junctions sloping towards spout. (WPC shall be measured & paid separately). 57 (h)Material and labourfor PCC 1:5:10 type E2, using 40mm thick aggregate n exc 150mmthick as in filling of sunken floor portion complete all as specified & directed. 58 (j) Material and labourfor PCC 1:2:4 type B1 using 20mm graded aggregate, 50mm tnick as in floor etc complete all as specified & directed. 59 Note :- (a)Testing of water proof area (ponding test) shall be done by filling water for at least 72 hours and tested for leakage, seepage to the entire satisfaction of GE. 60 (b) Test shall be done in presence of Engineer-in-Charge. 61 (c)The treatment shall be carried out by authorised applicator of chemicals. 62 (d)Cost of testing is included in the unit quoted rate above. 63 Material and labourfor Water proofing treatment to the sunken portion applying two coat of two component (1 part Polymer and second part cementations powder) cementations, polymer modified elastomeric, water proofing coating composed of cement, properly selected and graded aggregates, additive and acrylic emulsion polymer as a binder apply first coat of (mix and application as per manufacturer’s instructions) all over floor surface. Prepared surface and apply to vertical surface up to 15cm from tiling level, allow to dry 4 to 6 hours. Prepare for apply 2nd coat perpendicular to first coat and allow to dry 4 to 6 hours. All joints to Trap/WC/Soil pipe shall be properly sealed with sealing compound/polymer modified mortar using Dr Fixit Pidicrete UBP or equivalent in M/s Pidilite orM/s Sika Chemical, Slope of slab shall be towards and including GI pipe 50mm dia of suitable length Spout pipe. Providing 15mm protective screed with cement mortar in 1.3 with WPC (Make : Dr Fixit LW + or equivalent in M/s Pidilite orM/s Sika Chemical) within 2 to 3 days of second coat complete all as specified as per manufacturer instructions. Make : Dr Fixit Pidfin 2K or equivalent in M/s Pidilite orM/s Sika Chemical complete all specified and directed by Engineer-in-Charge. 64 Note :- The work shall be carried out by authorised and qualified applicators of the above mentioned manufacturer. 65 Dismantling of floor, hearth or wall tiling incl cement mortar bedding (but not backing) and removing rubbish off from premises & M&L forceramic coloured tiles of size 350mmx250mm/ 300mm X 450mmx7 to 8 mm thick, on vertical surfaces, set and jointed in neat cement slurry and pointed in coloured / white cement to match the tiles inc rendering 10mm thick in CM 1:4 on fair faces of brick work or concrete surfaces as in backing coat to receive wall tiles etc complete all as specified and directed. 66 Dismantling of floor, hearth or wall tiling incl cement mortar bedding (but not backing) and removing rubbish off from premises & M&L for joint free non skid coloured ceramic tiles 7 to 8 mm thick area of each tile not exc 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointedin white or coloured cement to match incl 15 mm thick screed bed in cement mortar 1:4 for layingfloor finishes complete all as specified and directed. 67 S & F in repair vitreous china squatting pan Orissa pattern size 580 x 440mm white with integral foot rests incl connecting to P or S trap and to flush pipe anti syphonage pipe etc compete including provn of lime concerte bedding and making good to floor complete all as specified and as directed. 68 S & F PVC (SWR) pipes single socketed in any length with rubber ring joints fixed to walls/trenchesbore of pipe 75 mm with PVC clamps and saddles including taking down existing pipes and Dismantling of old unserviceable cast iron/RCC/PVC drain pipes jointed in cement mortar and taking out from trenches or walls of any bore including fittings complete all as specified and as directed 69 S & F PVC (SWR) pipes single socketed in any length with rubber ring joints fixed to walls/trenchesbore of pipe 110 mm with PVC clamps and saddles including taking down existing pipes and Dismantling of old unserviceablecast iron/RCC/PVC drain pipes jointed in cement mortar and taking out from trenches or walls of any bore including fittings complete all as specified and as directed 70 S & F in repairs PVC (SWR) bends of any radius with access door bore of pipe 75 mm complete all as specified and as directed. 71 S & F in repairs PVC (SWR) bends of any radius with access door bore of pipe 110 mm complete all as specified and as directed. 72 S & F in repairs 125/ 110 mm bore PVC (SWR) floortrap plain with grating incl jointing with solvent cement complete all as specified and as directed. 73 S&F PVC bends 110mm boreincluding taking down existing old one complete all as specified and as directed. 74 S&F PVC bends 75mm boreincluding taking down existing old one complete all as specified and as directed. 75 S&F in repairs PVC (SWR) floor trap 75mm dia of outlet pipe, plain with grating including jointing with solvent cement complete all as specified and as directed. 76 S&F in repair stack clamps made out of 50 mm x 5 mm flat iron and 110 mm dia round iron stays, including bolts and nuts and securing ends of stays to wall or rooffor 110 mm bore complete all as specified and directed. 77 S&F in repair stack clamps made out of 50 mm x 5 mm flat iron and 75 mm dia round iron stays, including bolts and nuts and securing ends of stays to wall or rooffor 75 mm bore complete all as specified and directed. 78 M&L Repair of leakage/seepage from the Nahani trap/ floor trap of kitchen/ bathroom/ washbasin of the upper Qtr, in any position at any height, complete including change of floor trap, PVC horizontal pipe embeded in floor in bathroom or kitchen making good to the damaged portion of flooring, laying and matching of tiles in the existing flooring, complete all as specified and directed. 79 M&L Repair of leakage/seepage from the wall/ door bend /door tee/Y junction/ T Junction of soil pipe / waste pipe/ vent pipe of kitchen/ bathroom/WC of the upper Qtr or at the ground floor Qtr including change of any damaged soil waste pipes or fittings of any shape, specification and size, making good to the damaged portion of wall with brick work in cement mortar 1:6 or cement concrete 1:2:4 and plastering to wall in CM 1:4 and finished the surfaces matching to existing wall complete to avoid the leakage/ seepage at the site of work as directed and as specified. 80 Note for item No 78 & 79:- (a)Find out main cause of leakage and take necessary steps to resolve / rectify.(b)Replace existing tiles in case leakage through NT/FT.(c)The rate also include for provision of new NT/FT.(d)The unit rate is also deemed to be included for reqd bonding chemicals to arrest the leakage/seepage as directed by the manufacturers specification. Make : M/s Sika Chemical, M/s Pidilite, M/s Dr Fixit 81 Petty repair to internal/external water inlet GI/CPVC pipe line of any size coming from over head tank to the quarter including socket,elbow,nipple ,with repair to water blockage , pipe line leakage, cleaning internally , removing of air/dust blockageincluding concealed water tubing etc n exc 3m length of any height using scaffolding as required and making the water supply functional complete all as specified and directed. 82 Supply and fixing 15mm bore galvanized steel water tubing, medium grade with all fittings and fixed complete to walls and ceiling or laid in floors including taking up or down old steel tubing and connection complete all as specified and directed.. 83 Supply and fixing 20 mm bore galvanized steel water tubing, medium grade with all fittings and fixed complete to walls and ceiling or laid in floors including taking up or down old steel tubing and connection complete all as specified and directed. 84 S&F in repairs Stop Valve standard of PTMT any colour high pressure screwed for iron pipe and fixed.(Minimum weight 15mm-90gms) and directed. 85 S & Fin repair bib tap standard of PTMT any colour screwed for iron pipe and fixed,15 mm bore (minimum weight 90gms) complete all as specified and as directed. 86 S & F in repairs PVC low level flushing cistern 10 Lit capacity including necessary brackets incl connecting flush pipe etcand making good the disturbed surfaces complete all as specified and as directed. 87 Taking down & re fixing high or low level flushing cistren 10 ltrs capacity & connections to pipes & fixing of chain & pull or lever after cleaning inside of all dirt, scale formation, replacement of rubber washers, syphon set, flush handle, float valve,stopping of leakage etc complete all as specified and as directed. 88 S&F Rotational moulded polyethylene water storage tank of500 Ltrs capacity cylindericalvertical with closed top including 3 Nos GI check nuts and tank nipple of 25mm bore for inlet and outlet, 25mm bore ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball hoisted and fixed in position all as specified in SSR part -I including taking down old unserviceable tank complete all as specified and directed. 89 S & F in repairs bib taps short/long body cast copper alloy chromium plated fancy type screwed down screwed foriron pipe or for brass ferrule and fixed for 15 mm bore complete all as specified and as directed. 90 S & F in repairs pillar tap with capstan heads chromium plated fency type screwed down high pressure with or withoutletter Hot or Cold with long screwed shanks and flynuts screwed for galvanised iron pipe and fixed complete for 15 mm bore complete all as specified and as directed. 91 S&F Health faucet (ABS Body) mild steel chromium plated suitable for 15 mm dia pipe with 1.25 meter long flexible tube and ABS wall hook including taking down existing one complete all as specified and as directed. 92 Supply and fixing in repairs plastic water closet seat, white, closed pattern with flat bottom, and cover and mild steel chromium plated or aluminised hinging device all as specified and directed. 93 S&F in repairs grating doom 125mm dia with waste hole of Chromium plated (Min wt 40 gms) complete all as specified and as directed. 94 S&F in repairs Overhead Shower rose ø125mm (Brass Chrome Plated)complete all as specified and as directed. 95 S & F in repairs 15 mm dia stop valves of cast copper alloy fancy type chromium plated screwed down high pressure with crutch or butterfly handle screwed both ends for iron pipe complete all as specified and as directed. 96 S&F in repairs pillar tap standard of PTMT any colour high pressure screwed for iron pipe and fixed.(Minimum weight 15mm-110gms) complete all as specified and directed. 97 S&F 150 mm dia round/square grating of CP with or without hole includingJointed to PVC pipe completeall as specified. 98 S&F in repairs 40mm bore unplasticised PVC pipe of pressure rating 10 kgf/Sqcm fixed complete to walls, ceiling or laid in floors complete all as specified and directed. 99 M&L Vitrified Ceramic tiles 10 mm thick, lightshade (square/ rectangular) polished, area of each tile not exceeding 0.36 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match, laid over andincluding screed bed or bedding layer, 15 mm thick in Cement Mortar 1:6complete including dismantling of existing old flooring tiles and disposal to outside MD land complete all as specified and directed. 100 M&L Vitrified Ceramic tiles 10 mm thick, lightshade (square/ rectangular) polished, area of each tile not exceeding 0.36 sqm, in vertcal surfaces such as skirting/ dado etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match, laid over andincluding screed bed or bedding layer ,15 mm thick in Cement Mortar 1:6complete including dismantling of existing old tiles and disposalto outside MD land all as specified and as directed. 101 Material and labourfor 25 mm thick PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in flooring surface as in level course etc including demolition of existing old cement concrete, including disposal of demolition material upto 500mtr from MD land complete all as specified and directed. 102 Supply and fixingAnodized aluminium size 605 x 605 mm snap grid frame work for false ceiling as per manufacturer instructions, with suitable size GI wire Hangers (up to 1200mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long and6mm thick Non asbestos fibre cement building boards, fixed to sheet suitably placed in false ceiling grid made of Aluminium as per specification and drawing and including dismantling old unservicable ceiling board & frame of any type and description, complete all as specified and directed. 103 M&L for removing old existing rubbish/battered/useless mixture of the binding materials such as cement / Lime and fine aggregate (<4.5mm retained on IS Sieve), loose/unsound weaken mixture of binding materials such as cement / Lime and coarse Aggregate (>4.5mm retained on IS Sieve), fine Aggregate of any description and in any position from existing external/internal surfaces of RCC components or any surface having average profundity of 15mm (Approx height 10m from natural ground level) by hand tool that has a long metal blade with a sharp edge at the end, chisel and hammer or using robust pneumatic chisel hand tools and removal beyond MoD land including cutting of all edges, making square shoulders of the aperture, coarsen the smooth surfaces, curettage /removing of all deterioted/decayed loose surface complete all as specified and directed by Engr-in-charge. 104 M&L for cleaning and removing all corrosion scales , rust , etc using emery / wire brush and finally cleaning using rust remover & cleaning agent that is one part alkaline based material, with corrosion inhibitors and dispersing agents and supplied as a clear brown solution. The specific gravity shall be 1.2 – 1.22 @ 25°C. The pH value shall be between 9.5 to 10 and the coverage shall be 5 – 6 m2/ L as per manufacturer instructions complete all asspecified and directed by Engineer-in-charge. 105 M&L for repair to cracks and damaged existing surfaces by Hydrogen Free Expanding And Plasticising Additive . It plasticizes the mix, allowing for substantial reduction in water without affecting the fluidity, thus improving the strength and impermeability, the admixture/ additive in cement to provide non‐shrink properties Cementitious Cable Encapsulation .(a). Fixing of pvc nozzles in zig-zag fashion not more than 50cm c/c on RCC surfaces on all directions as required after drilling holes in concrete, fixing pvc nozzles with fast setting mortar and covering with renderoc plug. The size of holes shall be 20mm dia and 75mm in depthcomplete all as specified and directed by Engineer-in-Charge. 106 M&L for Shear thinning agents in RCC/ walls/ ceiling/ columns/ beams/floor/bricks cracks after opening up in “V” groove manner covering the area of 300mm from central line of crack with the depth of 8 mm complete with three components compound graded filler, E-Resins and Shear thinning agents with adjustable consistency by varying the filler component epoxy resin based complete all as specified and directed by Engineer in Charge. 107 M&L for applying 2 coats of primer slurry prior to the application of the repair mortar having multiple corrosion inhibiting synergies and which is a blend of pc graded fillers corrosion inhibiting additive and re-dispersible polymers in powder form mixed with water for application by brush to coat the reinforcement/steel within 10mm of the finish surface and where chlorides are present so as to achieve adhesion bond strength of 1 MPa to steel. Pot life of 0.5 hr @ 30°C. It shall be workable for not more than 15 minutes at same temperature. The mixed density shall be not more than 2.05. The water/powder ratio shall be 0.3 by weight complete all as specified and directed by Engineer-in-charge. 108 M&Lfor providing and fixing welded MS wire mesh weighing not less than 1Kg/Sqm of size 50mmX50mm of 2.6mm dia on the prepared surface & surface should be cleaned andbe removed from dirt, fungus and all foreign material complete all as specified and directed by Engineer in Charge. 109 M&L for providing and spraying polyamine cured epoxy coatingincorporating a special alkali reactive emulsion breaking system compoundover the plastered surface. This impervious film prevents excessive water evaporation which in turn permits more efficient cement hydration, thus reducing shrinkage and increasing durability. It shall have a specific gravity of 1.02 and the minimum application temperature shall be 10°C and the strength of concrete complies with the internationally recognised ASTM C309-90 standards typically within the range of 200 to 285 ml/sqm, SG - 1.02 including all tools and tackles complete all as specified and directed by Engr-in- charge. 110 M&L for applying Polyster Resin based Anchoring material in concrete before fixing nozzle it should typically attains a compressive strength in excess of 20N/mm @ 3 hours and and ultimate compressive strength of 70N/mm in 7 days (50mm x 50mm x 50mm)when tested as per BS 6319 Part 2 : 1983as per manufacturer instructions complete all asspecified and directed by Engineer-in-charge. 111 M&L for applying 2 coats oftwo component amine cured epoxy mastic coating usingLight brush blasting using nonmetallic abrasive leaving a clean, rough and even pattern.it should bebased on a 100% epoxy formulation and contains no solvents or water diluents. Apply two coats with brush or squeeze to the existing surface, working well into the substrate.it should achieve Compressive Strength of >70 MPa after 14days, having pot life, minutes at 27⁰C, 100 g >40 mass as per manufacturer instructions complete all asspecified and directed by Engineer-in-charge. 112 M&L for applying 20mm shear thinning fibre reinforced polymer modified , impermeable to aggressive elements, dual shrinkage compensated, cementitious repair mortarwith alkali resistant synthetic fibres for exceptional resistance cracking complies ASTM C 109 with flexural strength ASTM C 348 @ 7 days meeting 7N/sqmm, tensile strength @ 7days (ASTM C 307)> 3 N/sqmm, compressive strength of 35MPa at 7 day and 45MPa at 28 days, at the outer or inner RCC which provides excellent bond to concrete, Improves tensile and flexural properties of mortar, Versatile having specific gravity of 1.02cement sand can be used for finishing purposecomplete all as specified and directed by Engr-in-charge. 113 M&L for applying 3 coats of corrosion inhibiting, polymer matrix with excellent mechanical properties such as adhesion and elongation as waterproofing barrier coating. It should be non toxic and non-re-emulsifying. Should conform to JIS Z 1535 and IS-3085 and DIN-1048.having Hardness - Shore D scale of 20,wet density of 1.66 g/cc, flexibility at low temperatures, tensile strength > 0.4 MPa, Elongation > 20%, adhesion to substrate greater than 1.5 N/mm², waterproofing to withstand 330 KPa positive pressure and 160 KPa negative pressure, Mixing should be done by electric rotary mixers. The substrate should be free of laitance, loose concrete, dust, oil etc. if applied on screed or any other cementitious surface the surface should be properly cured prior to application complete all asspecified and directed by Engineer-in-charge 114 M&L forapplying two coat of mixture of two monomer unsaturated liquid hydrocarbon , gaseous hydrocarbon and polymesrized them to get the high polymerdispersion emulsion successfully bonded to mortar, to improve adhesion to concrete, better durability, reducedshrinkage and increased flexibility and resistant toemulsification in damp condition modified Ensuring no porosityin new/old surface, temperatures between +5°C and +35°C, Resist to penetration of CO24.600 micron , compressive strength (11.5 N/mm2) at 3days strength - 11.5 (N/sqmm ) and at 28 days - 25.30N/sqmmas per manufacturer instructions complete all asspecified and directed by Engineer-in-charge. 115 M&L for Sprinkling sand particles of saturant making mechanical key, over which applying Single component, fiber reinforced cementitious repair mortar which is reinforced with specially designed bean shaped, alkali resistant synthetic fibers for exceptional resistance to cracking for a thickness of 10 mm. water ratio of which shall be 0.16, 28 days compressive strength shall be 30 MPa,mixed density shall be 2.18 kg/ltr, flexural strength shall be 6 MPa for 7 days and tensile strength for 7 days shall be more than 2MPa.Its adhesion bond strength shall be greater than 2 MPa with creep strain reduction of 8%.Single component, fiber reinforced cementitious repair mortar.cement and sand can be used for finishing purpose. The modulus of elasticity of this product shall be 23-26 KN/mm² complete all asspecified and directed 116 Note for item No. 103 to 115 :-The work for items Srl No 103 to 115 shall be executed directly by manufacturer or through their authorized and qualified applicators,of any following manufacturer only. M/s Fosroc chemicals, M/s Thermax Limited, M/s Tiki Tar Danosa India Ltd 117 The contractor must submit MOU with manufacturer/authorized applicator at the time of sample approval. 118 The contractor shall submit performance guarantee certificate for structural repair/leakage/seepage for a period of 10 years from the certified date of completion. 119 The unit quoted rate shall be inclusive of material, all labours, tools and plants including scaffolding required for working upto 15 mtr height from natural ground level. 120 The defect liability period for the structural repair work shall be 05 (five) years from the certified date of completion of work. 121 A security deposit of value equal to 2.5% of the rate quoted against each item shall be retained from Final bill payment due to the contractor for the defect liability period. 122 The unit quoted rate is deemed to include taking up or down of water pipe, tanks, wires etc found on roof or other working areas and re-fix same at the original position after completion of work. 123 Adoption of necessary safety arrangement like safety belts, ropes, helmet, netting etc are required for safety of working labour at height exceeding 3 to 15 mtr shall be mandatory & deemed to be included in the unit quoted rate 124 Removing plant/Uprooting of vegetation growth including roots on wall/roof/parapet near pipes etc and applying acid treatment afterremoving roots for preventing regrowth and making good disturbed surfaces/area in superficial area exc 150sq.cm but n.exc 400 sq.cm and averaging depth not exceeding 10 cm by using PCC 1:2:4 type B-0 (using 12.5 mm graded stone aggregate) or 10mm thick plastering in cement mortar 1:3 as required and finishing the surfaces to match with the existing surface complete all as specified and directed. 125 Material and labourfor Preparation of old decoratedplastered or unplastered surfaceof wall, brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent , trading, oil, greasy spots and applying one coat of cement based paint complete all as specified and as directed. 126 M&L for Preparation of old decorated surfaces of wallsby using pressure washer, remove all dirt & dust ,applying one coat of wall care putty and then applying two coats of premium oil bound distemper over one coat of primer as per manufauture instruction of required shade complete all as specified and directed. 127 M&L for Preparation of old decorated wall surfaces including cleaning with water, rubbing offungus complete removal,applying two coat of weather proof paint APEXexterior wall paint including necessary preparation to give uniform and smooth finish all as specified and directed. 128 M&L for preparation of old surface of floor, any description over 10cm width or girth not otherwise described and applying two coats of durable 100% acrylic latex- based textured synthetic paint as in basket ball court / badminton court and similar works using roller/ bruss with standard specification etc complete all as specified and directed by Engr-in-Charge. 129 M&L Plain cement concrete (1:3:6) type C1 (20 mm graded stone aggregate), 75mm thick, as in plinth protection courses, top surface of concrete finished even and smooth without using extra cement,including expansion joint 10mm thick filled with mastic filling comprising of 01 part of heated blown bitumen and 3 parts of dry sandincluding demolition of existing cement concrete and disposal of demolished material upto MD land complete all as specified and directed. 130 Dismantling floor, floor hearth or wall tiling including cement mortar bedding (but not backing) and rubbish off the premises and Material and labour for digitalGlazed/ rustic finish ceramic coloured tiles 350x250mm/ 450 x 300 mm x 7/8 mm thick set and jointed in neat cement slurry and pointed in white or coloured cement to match with tiles on vertical surface such as skirting/ dadoincluding 10mm thick 1:3 backingcoat complete all as specified and directed. 131 Taking down chowkhat or frame (wooden/steel/aluminium) not exceeding1.5 Sqm each with shutter (with out taking off shutters from the frame) all as specified and as directed. 132 S&F Solid PVC Door Frame of size 50mm x 47mm made out of 5mm plain colour PVC sheet reinforced with MS Square tube complete all as specified and directed. 133 S&F Factory made Solid PVC Door Shutter 30mm thick (style) consisting of frame made out of MS tubes for top & bottom rails.MS frame shall be covered with heat moulded plain colour PVCCchannel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail.Panelling of plain colour PVC sheet to be fitted in the MS frame welded/sealed to the stiles & rails with suitablePVCsheetbeadingand jointed together with solvent cement complete all as specified and directed. 134 S&F Butt hinges 75 mm long medium weight cold rolled stainless steel complete all as specified and as directed. 135 Supply and fixing 150 mm long aluminium anodized barrel tower bolt extruded section complete all as specified and as directed. 136 Supply and fixing aluminium handles cast type anodized 150 mm long complete all as specified and as directed. 137 S&F in repairs Stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.4mm complete all as specified and directed. 138 M&L Hacking out old broken glass (any thickness, size, quality or description) from wooden frames/steel frames glazed with putty or fixed with beads and material and labour for4mm thick plain sheet glass ordinary quality and glazed with oil putty or fixed with fillets 2nd class hard wood of sectional area not exc 3 Sqcm and glass not exc 0.5 Sqm in each pane complete all as specified and directed. 139 M&L Hacking out old broken glass (any thickness, size, quality or description) from wooden frames/steel frames glazed with putty or fixed with beads and material and labour for4mm thick plain sheet glass ordinary quality and glazed with oil putty or fixed with fillets 2nd class hard wood of sectional area not exc 3 Sqcm and glass exc 0.5 sqm in each pane complete all as specified and directed. 140 Petty repair to door shutters for easy closing/opening(size upto 3 Sqm) including minor repair and easing, adjustment/aligmentto openable with accessories and including taking down and refixing, tightening of hinges or changing the position of hinges,welding of hinges door to frame adjustment of tower bolts, sliding bolts with new screws etc,complete all as specified and directed. 141 Supply and Fixing 30 mm thick factory made flush shutter solid core construction with block board core and plywood face panels, comercial type on both faces complete all as specified and directed. 142 S&F in repairs 300mm, ordinary Mild steel rat tail rod pattern springs including roller and roller plate complete all as specified and directed. 143 S&F 5mm thick rubber beading strips of entrance doors having width exc 3cm and not exc 5cm to arrest entry of insects including taking down existing one complete all as specified and as directed 144 Supply and fixing in repairs aluminum handles cast type anodised 200 mm long complete all as specified and as directed. 145 Supply and fixing in repairs aluminum handles cast type anodised 150 mm long complete all as specified and as directed. 146 Supply and fixing in repairs 150 mm long aluminum anodized barrel tower bolt extruded section complete all as specified and as directed. 147 Supply and fixing 100mm long Butt hinges medium weight cold rolledstainless steel, fixed in repair to wooden frame/welded to metal frame complete all as specified and as directed. 148 Supply and fixing in repairs butt hinges 75 mm long medium weight cold rolled stainless steel complete all as specified and as directed. 149 Supply in repair 40 mm dia cupboard knobs brass polished, complete all as specified and directed. 150 Applying silicon sealent on joints of wall, cill, jambs, roof etc complete all as specified as directed 151 S&F Solid PVC Door Frame of size 50mm x 47mm made out of 5mm wood grain printed PVC sheet used instead of plain colour pvc sheet and edges will be painted to match with printed sheet complete all as specified and directed. 152 Providing and injecting chemical for post constructional Anti TermiteTreatment at points of contact of wood work by chemical emulsion (in oil or kerosene based solution) @ 0.5 litre/hole by drilling 6mm dia holes at a downward angle of 45 degree at 150mm centre to centre and sealing the same all as specified and directed. 153 M&L for 25mm dia mild steel powder coated drapery rod cut to length required without joint in between and including Mild steel powder coated fancy type brackets etc and fixed at openings including taking down existing old one complete as directed. 154 Taking down andre-fixing the same existing aluminium door/window/partitions (each shutter arean. exc 5sqm) after carrying out ceratin repairs as required, removing the existing beading and fixing new (i.e. included change of Handles, hinges, star lock, rubber beadings, bottom bearing, clips etc) rubber beading of suitable size with adhesive, overhauling of floor springs including repairing/cleaning/ greasing etc and make the same fully functional all as specified and directed. 155 S&F in repair powder coatedaluminium framewith all fixing arrangementsfor doors, sliding windows andventilators/ partitions etcwith one or more rebates including joining cleat for fixing etc aluminium section of powder coating not less than 50 micron including taking down old one of any description completeall as specified and directed. 156 S&F in repair Powder coated anodised aluminium windows, and ventilator shutters, sliding type without sash bars, aluminium sections weighing 0.55 Kg/m inculding necessary joining cleats glazing clips, rubber packing, anoised aluminium fittings suitable lock with roller complete all as specified and directed. 157 S&F 4 mm thick sheet glass ordinary quality and glazing complete in square n exc 0.50Sqm in each pane complete all as specified and directed. 158 Supply and Fix in repair for 10-12mm thick Prelaminated particle board, interior grade, prelaminated one side with decorative choice lamination & other side balancing white lamination, fixed with screws to timber frame work including taking down old one of any description complete all as specified and directed. 159 S&F in Factory Made Solid PVC Moulded Door Shutter, 28 to 30mm thick (stiles), with 2, 4, or 6 raised panel design with 2mm thick Moulded PVC Sheet on the front face& 2mm plain colour PVC sheet on back face, supplying & fixing in frame at site as per specification & drawing complete all as specified and directed. 160 S&F in repair solar control interior/ exterior window /door frosted glass film 50 micron reflective type (gareware sun control or equivalent) applied to old glass surfaces using adesive/ solvent with approved procedures to prevent the formation of air cleaningbubbles , wrinkkes , bilsters and other defectsetc complete all as specified and directed. 161 Supply & Fixing of UPVC glazed 3 track-2 panel sliding windows with mesh made out of multi chambered uPVC sections with TPE gaskets having isolated drainage and reinforced with Galvanized iron profiles throught out the window. The outer frame having an overall size of 108 x 48 mm with reinforcement of 1.2mm thickness and sash with overall size of 38 x 61 mm with reinforcement of 1.2 mm thickness mesh sash of overall size 38 x 58mm Fiber mesh reinforced with 1.2 mm of GI. Glazing bead for fixing of glass shall be of size 16mm x 19mm and TPV gasket. Windows will be provided with 5mm thick plain float glass, With Astrapia hardware or equivalent & Single point locking system of flush lock. Wall thickness of frame & sash shall be 2-2.2mm complete all as specified and directed. 162 Complete removal of existing water proofing treatment of any description and in any position including PCC padding any thickness and cleaning, wire brushing, watering & removal of debris outside MOD land.NOTE :-Unit rate quoted shall also include for removal of PVC water storage tank wherever existing carefully and refixing at the same or other position after completion of roof repair work 163 M&L Cutting out cracks to V-section in existing roofs or terracing, cleaning out and filling solidly with a hot mixture of bitumen and clean dry sand 1:1 (by weight) complete all as specified and directed. 164 Roughening surfaces of old concrete floors by picking, sweeping clean and washing down with waters to remove dusts etc. complete all as specified and directed. 165 M&L for Brushing neat cement slurry with 3kg/sqm all as specified and directed. 166 M&L PCC 1:2:4 type B-0 using 12.5 mm graded crushed stone aggregate as in concrete padding laid to required slope incl finishing the concrete surface fair and even without using extra cement complete all as specified and as directed. 167 M & L for 10 mm thick screed bed or bedding layer of mortar in cement mortar (1:4) for laying roof finish as padding finished with liquid WPC as per manufacturer instructions, complete all as specified and directed NOTE :- Integral WPC shall be measured and paid separately. 168 Apply oil bound bitumen primer @ 0.40 Litre / Sqm manufactured by the same agency as that of APP with density of 0.87 to 0.89 Kg / Litre at 25 degree Celsius on the prepared dry roof surface complete all as specified and as directed. 169 M&L APP polymeric membrane min weight 3.0kg/sqm and minimum 3mm thick reinforced with polyster non woven fabric(wt not less than 150 gms/sqm laid on primed surfaces by torch application method complete all as specified and directed. 170 M&L for preparation of new surfaces of any description not otherwise described over 10cm width or girth and applying two coats of solar reflective aluminium paint @ 0.10 kg/sqm of membrane surfaces complete all as specified and directed. 171 Raking out joints / pointing to squared rubble masonry coursed or uncoursed built in cement mortar or cement lime mortar complete all as specified and directed. 172 Keyed pointing on squared rubble masonry coursed or uncoursed (Bangalore Pattern) in cement mortar 1:4 complete all as specified and directed. 173 Supplying and laying of 25mm outer dia CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete all as specified and including taking out old steel/plastic/cpvc water tubing and connections complete as directed. 174 Supplying and fixing in repairs of 25mm outer dia Female Brass Threaded Adaptor (FTA/ FBTA CPVC complete all as specified and directed. 175 Supplying and fixing in repairs 25mm outer dia CPVC brass elbow all as specified and directed. 176 S&F Rotational moulded polyethylene water storage tank of1000 Ltrs capacity cylindericalvertical with closed top including 3 Nos GI check nuts and tank nipple of 25mm bore for inlet and outlet, 25mm bore ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball hoisted and fixed in position all as specified in SSR part -I including taking down of old unserviceable tank complete all as specified and directed. 177 Supply and fixing in repairs 20mm dia gun metal gate valve with iron wheel screwed both ends for iron pipe complete all as specified and directed. 178 S&F in repairs of swivel Shower with arm of PTMT any colour and 195mm long bend of 45 degree with flange for fixing with 15mm pipe (Minimum weight 15mm-90gms) complete all as specified and directed. 179 S&F in repairs Vitreous China urinals, half stall Urinal type (back or corner wall type), complete including providing and fixing plugs, Urinal spreader, CP push cock, bedding urinal against wall in cement mortar 1:2, securing urinal to plugs with and including 60mm long brass screws, pointing around urinal back in cement; fixing automatic flushing cistern with brackets, flush pipe, grating and Union for discharge pipe, complete all as specified and directed. 180 S&F in repair vitreous China urinals, bowl type (back or corner wall type), complete including providing and fixing plugs, Urinal spreader, CP push cock, bedding urinal against wall in cement mortar 1:2, securing urinal to plugs with and including 60mm long brass screws, pointing around urinal back in cement; fixing automatic flushing cistern with brackets, flush pipe, grating and Union for discharge pipe complete all as specified and directed. 181 S&F in repairs of Push tap any colour high pressure of PTMT screwed for iron pipe and fixed, (Minimum weight 15mm-47gms)and complete all as specified and as directed. 182 S&F in repairs 40 mm Waste coupling fittings, brass, chromium plated for glazed ware sinks, basins, etc. with long screwed shanks and fly-nuts, flange end bedded in red lead cement and other end fixed one complete all as specified and as directed. 183 S&F 32 mm Waste Coupling fittings, brass, chromium plated for glazed ware sinks, basins, etc. with long screwed shanks and fly-nuts, flange end bedded in red lead cement and other end fixed including taking down existing old one complete all as specified and as directed. 184 S&F in repairs of chromium plated tubular towel rail 20 mm dia brass D type 60 cm long between flanges complete all as specified and as directed. 185 S&F in repair Toilet paper holder box type of vitreous china fixed to walls with chromium plated (CP) brass screwsand complete all as specified and as directed. 186 S&F PVC connections 15mm size with PTMT nuts of length 450 mm including taking down existing old one complete all as specified and directed. 187 Supplying and laying of 20mm outer dia CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete all as specified and taking out old steel/plastic/cpvc water tubing and connections complete all as specified and directed. 188 Supplying and fixing in repairs of 20mm outer dia Female Brass Threaded Adaptor (FTA/ FBTA CPVC complete all as specified and directed. 189 Supplying and fixing in repairs 20mm outer dia CPVC brass elbowall as specified and directed. 190 Petty repair to toilet floor, bathroom, kitchen, etc seepageincluding sunken portion treatment with apply water proofing compound including repair and arrest the leakage to floor trap,nahani trap , grating and applying white cement etcmaking good to the damaged portion of flooring, laying and matching of existing flooring, complete all as specified and directed. 191 S&F CP sink cock with swinging casted round shape spout screwed down screwedfor iron pipe in repairs 15mm bore including taking down existing one complete all as specified and as directed. 192 S&F in repair Chromium platedsoap dishincluding fixing arrangement complete all as specified and directed . 193 S&F Towel Ring roundn exc 20cm dia stainless steel material fixed to wall with brackets including taking down existing one all as specified and as directed. 194 S&F PVC body cabinet box mirror of size 350mm X 450mm X 100mmPTMT alloy of approved pattern and design including taking down existing one complete as directed. 195 S&F in repairs Glass self assembly of 12mm thick andn exc 60cm length, 15cm wide with stainless steel brackets, stainless steel railing in bathroom and fixed to wall with brackets complete all as specified and as directed 196 S&F 300mm arc size, 5mm thick corner glass shelf with stainless steel brackets, stainless steel railing in bathroom and fixed to wall with brackets including removing the existing fitting as per manufacturers instructions and as required at site complete all as specified and as directed 197 S&F in repairs Wash basin vitreous china (flat back or angle back type) size 580x400mm including taps wastechain and plug and porceline stopper but brackets including cutting for and pinning inends of brackets or erecting stand with waste pipe, complete all as specified and directed. 198 S & F in repair waste coupling 32 mm dia of PTMT (half or full threaded) minimum weight 45 gram complete all as specified and as directed. 199 S &Fin repairs PVC connection pipe 15 mm dia, 600 mm long with check nut and bolt with washer complete all as specified and as directed. 200 S&F in repairs PVC waste pipe 32/40mm bore for WHB, Urinal & Sink complete all as specified and as directed. 201 S & F in repairs vitreous china wash down water closet (Pedestral pattern) EWC white incl plastic water closet seat cover and mild steel chromium plated or aluminium hinging device and connecting to P or S trap incl connecting flush pipe with flushing rim complete all as specified and as directed. 202 M&L Petty repairs to leaking water in bib taps, pillar cock, stop cock, angle valve, concealed stop valve, bottle trap of any description by changing thePVC washers/ Sheet washers,spindle brass,jumper brass or any other minor accessories items etc (incl taking down and refixing) complete all as specified and directed 203 S&F in repairs CP 2 way bib cock with wall flange fancy type chromium plated screwed down screwedfor iron pipe for 15mm bore complete all as specified and as directed. 204 S&F CP Concealed stop cock, Regular body with adjustable wall flange screwed down screwedfor iron pipe15mm bore including taken down existing one complete all as specified and as directed. 205 M&L forRepair to ends of chajjas/ parapets by removing old concrete,loose material &cleaning of the reinforcement and finishing the surface with rich cement mortar 1:3 , finished fair & even and making good with existing finishes complete all as specified and as directed.Note: Rate quoted by the tenderer shall be deemed to inclusive of double steel scaffolding. 206 Taking down cement plaster on brick or stone walls, or concreteetc., including raking out joints, hacking for key, scrubbing down with water, etc., including removal of rubbish off the premises and leaving the work clear of any plastering and Material and labour for Rendering 15 mm thick in two layers onbrick or stone or concrete surfaces,first coat 10mm thick in cement mortar1:4 and 2nd coat 5mm thick in cement mortar1:4 finished even and smooth without using extra cement completeall as specified and directed.Note :-(a) The unit rate quotedis deemed to include for removal of accumulated earth of any width and depth upto 15 cm cleaning/cutting the grass with hand operated petrol/kerosene driven grass cutting machine and removing the grass waste around 3 m from plinth protectionto outside MD land. 207 M&L preparation of newly plastered surfaces and applying three coats of white washing on walls surfaces complete all as specified and directed. 208 M&L Machine cut kota stone slab 20-25 mm thick as in flooring, laid over and incl 20 mm thick screed bed in CM 1:3 set and jointed in neat cement slurry and pointed with cement and pigment to match the shade of the slab incl rubbing and polishing including demolition of existing cement concrete and disposal of demolished material upto MD land complete all as specified and directed. 209 M&L applying two coat of cement based paint over a coat of primer, including preparation of newly plastered wall surfaces of any description, complete all as specified and as directed. 210 S&F in Solid PVC Wall Lining / panellingconsisting of5mm thick wooden colour PVC sheet inclusive of solvent cement and fixing at site on PVC frame as per specifications and drawing including taking down old one complete all as specified and directed. 211 S&F in 5mm thick PVC sheet fillet of width35mm for wall paneling inclusive of fixing on to wall to make PVC Frame as per specification and drawing including taking down old one complete all as specified and directed. 212 S&F in repair manually operated polyester fabric vertical venetian blinds of approved colour and pattern of any size and thickness of 0.45mm (+/-0.05mm) including high strength aluminium alloy channel fixing with two Nos clamp including all connected fittings and fixtures for windows,ventilators etc complete all as specified and directed. 213 Supply and fixing in repairs 7 feet 4 pipespulley operated cloths drying system consisting of aluminium pipe of outer dia 22mm, inner dia 19.80mm,made up of detrin with rope guide mounted on channel pair of length 24 feet (distance between two pipes is adjustable) locking system to hide rope knot, channel to be mounted or fixed with self taping screws provided in kit. Rope will be HDPE double core of 4mm dia fixing to ceiling as specified and directed by Engr-in-Charge and minimum weight of one pipe shall not be less than 0.20kg/, minimum weight of rope shall not be less than 7700Gms/unit. Make : Easydry or equivalent. 214 Grinding of existing mozaic/kota stone/tiles in wall/flooring including mirror polishing, cleaning of tiles/granite and joints filling and apply white cement,including grouting of floor trap surroundings with white cement complete all as specified and directed. 215 S & F in repair 18/19 mm thick ,water proof plywood , fixed to Cupboard work in any position with nails including removal of old boards of any description complete all as specified and as directed. 216 S&F PVC beading for cupboard work, colour and pattern as approved including taking down existing one complete all as specified and as directed 217 S&F Decorative laminates of 0.90 mm thick type matt finish, colour and pattern as approved. including taking down existing one complete all as specified and as directed. 218 S&F Stainless steel spring hinges of size and approved pattern and make suitable for base/wall unit of cupboard including taking down the existing one complete all as specified and directed. 219 S&F Stainless steel handles of size 100 mm of approved pattern and make suitable for Base/Wall unit of modular kitchen including taking down the existing one complete all as specified and directed. 220 S&F Continuous (piano) hinges, stainless steel bright finish or electrogalvanised of 40mm width of flaps (when open) complete including taking down old all as specified and as directed. 221 S&F in repairsstainless steel wire Bottle pull out basket (storagebasket) pull out type, of suitable size 100mm height of grade 304 with necessary fixing clips etc complete all as specified and directed. 222 S&F in repairs stainless steel wire Thali basket (storagebasket ) pull out type,of suitable size 150mm height of grade 304 with necessary fixing clips etc complete all as specified and directed. 223 S&F in repairs stainless steel wire saucer basket (storagebasket) pull out type, of suitable size 200mm height of grade 304 with necessary fixing clips etc complete all as specified and directed. 224 S&F Stainless steel telescopic slider of 500 mm of approved pattern and make suitable fordrawer in base unit of modular kitchen including taking down the existing old one complete all as specified and directed. 225 S&F Stainless steel handles of size 150 mm of approved pattern and make suitable for Base/Wall unit of modular kitchen Including taking down the existing old one complete. 226 S&F Magnetic catches with 8mm dia steel ball and brass body and striking plate including taking down old complete all as specified and directed. 227 M&L for 18-20mm thick granite (of any type) work (table rubbed and polished) in steps, jambs, pillars, window cills,cooking platforms, shelves in cupboard,handwash places and like including necessary cutting and grooving to wallsand making good by pointing in cement mortar (1:2) using admixture of pigment to match with shade of graniteover andincluding cement screedbed Cement Mortar (1:6) 15 mm thickcolourof granite as approved incl removal of old flooring of any description all as specified and directed.NOTE : (i)Dismantling of stone slab and tiles laid, bedded and pointed in any mortar of any discription of thickness in floor(ii)The unit rate is deemed to be included for rounding to edges of stone slabs. 228 Petty repairs to refixing the existing Wash hand basin and Sinks made of stainless steel 1mm thick kitchen flat back including fixing cantilever CI/Angle iron brackets embedded in concrete block including connecting waste coupling 32mm bore, including bedding, waste fitting, waste pipe in cement mortar on to dwarf wall and connecting union to pipe, filling gap in white cement and all necessary fittings to fixed in repair(including taking down and refixing the same position) complete all as specified and directed. 229 S&F sinks made of stainless steel 1mm thick kitchen or laboratory with plugs, washers and wastes; including bedding in cement mortarto dwarf wall or including fixing cantilever brackets and connecting union to pipe, overall size 495mm x 420mm bowl size 410mm x 330mm x 160mm fixed in repairsall as specified and directed. Make : M/s Diamond / Nirali / Amco / TATA or equivalent 230 S&F Plate rack of size 65 cm x 96 cm heavy duty made of stainless steel fixed in repairs complete all as specified and directed. 231 Petty repair to wall mixer,basin mixer,sink mixer etc including replacement of spindle brass, Jumper brass, rubber washer, head included taking down and refixing etc all as directed. 232 S&F in repair Brass Chromium plated wall mixer for mixing hot & cold water screwed down for 15mm bore iron pipecomplete all as specified and directed . 233 S&F Sinks with drainage board made of stainless steel 1mm thick kitchen or laboratory with plugs,washers and wastes; including bedding in cement mortar to dwarf wall orincluding fixing cantilever brackets and connecting union to pipe overall size 915mm x 460mm bowl size 410mm x 330mm x 160mm fixed in repairsall as specified and directed. 234 Material & Labour for providing and fixing stainless steel (Grade 304) railing made of hollow tubes, channels, plates etc., including welding, grinding,buffing, polishing and making curvature (where ever required) and fitting the same with necessary stainless steel nuts and bolts complete, including fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of floor or the side of waist slab with suitable arrangementincluding taking down/ dismantling of old one complete all as specified and directed. 235 M & L for 0.50mm thick Pre painted Galvalume aluminium zinc coating GI based corrugated steel sheet of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws incl dismantling of old corrugated AC/fibre/GI sheet of any pattern in roof including ridge complete all as specified and directed. 236 Dismantling wrought iron or mild steel work of any description and in any position complete all as specified and directed. 237 S&Fin framed work as in doors or gates of angle,tubes or other section with gusset plates, rails, braces,guard bar etc., complete, to be prepared for hanging or sliding with and includinghinges or steel hanging door fittings (exclusive of steel sheeting or other covering) and hanging; also fastening and fixing Fe 410 -W (Gde- E- 250) quality-A complete all as specified. 238 M&L for welding in repairs not exceeding 10 Cm length & thickness of metal to be welded not exceeding 6mm complete all as spcified and directed. 239 S&F welded steel wire fabric cut to length, bent to shape required and tying with and including annealed mild steel not less than 0.9mm dia or fixing with galvanised steel staples supplied and fixed complete to wood or steel membersnot exceeding 4kg/sqm including taking down old one complete all as specified and directed. 240 M&L pereparation for new steel surfaces and iron work of any description over 10cm width or girth not otherwise described and applying two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and directed. 241 Forming Construction joints 30 mm deep x 10 mm wide filled with sealing compound grade A complete all as specified and directed. 242 M&Lin repairs Pre-cast PCC 1:3:6 type C1 (20 mm graded agg) cement concrete block masonry with solid blocks exc. 10cm in width and set in cement mortar 1:6 including demolition of old brick work / stone masonry/PCC block built in cement mortar of any description as specified and directed. 243 M&L rendering 15 mm thick in CM 1:6 on brick surfaces finished even and smooth with out using extra cement all as specified and directed. 244 S&F in double action floor spring hydraulically regulated made up of minimum 1.25 mm thick aluminium alloy sheet foundation box, main body with stainless steel covert governing pivot made of brass, other parts made of mild steel heavy duty including taking down existing wire cloth all as specified and directed. 245 S&F in repairs 0.56 mm thick Plain, Aluminium sheeting, Alloy 31000 H4 in ridges, hips, valley gutter, drip and straight flashing (length and girth as fixed), complete all as specified and as directed. 246 Supply only integral water proofing compound of approved make all as specified and directed. 247 Cutting holes in stone wall exc half brick and n.exc one brick in cement mortar for inserting hold fasts/lugs and making good dismantled portion in cement mortar 1:3 or 1:2:4 type B-1 concrete using 20mm graded aggregate as required complete all as specified and as directed. 248 Renewingcement concrete tiles/interlocking tilesin patches, area n exc 5 Sq.m. including removing and cleaning old tiles, preparing beds and laying or setting, jointing and pointing new or old tilescomplete all as directed.Note : The rate included for cutting out broken tiles, removing and cleaning loose tiles, preparing bed removing rubbish, removing and replacing old with new tiles to match, complete with all cuttings etc, that may be required. New tiles requiredis deemed to be included in quoted rate all as directed. The unit rate is also including necessary beding in cement mortor/Sand filling complete all as specified and directed. 249 Repair, maintenance and making the continuity of supply after rectifying the defects of the electrical items such as light point, fan point, call bell point, socket point 5A/15A, switches, sockets, regulator, lamp holder, brackets, bell, buzzer, push button, batten, ceiling rose, pendent, any type of MCBs, DBs any type of light fixtures, any type of lamp, ceiling fan, exhuast fan, geyser, capacitor, replacement of fuse wires and all elcectrical accessories in day to day/door to door maintenance including reconnection with S&Fsmall pieces of elctrical cable of size upto 10 Sqmm single core and length not exceeding 0.50m, complete all as specified and as directed.Note:(i)Any major items required to be repaired/replaced will be measured and paid under relevant items as supply only.(ii)Cost of labour for replacement/ attending five complaints in same building number will be treated as one job 250 Note for item No 249:- (a)The above job shall be carried out by a trained electrician having ITI in electrical, documentary proof of the education of tradesman shall be producedto Engr-in-Charge before commencement of work. 251 (b) All bldg light complaints including service connection, sub main & internal electric for entire OTM and Md accn at CQAE shall be attended 252 (c) Record of complaints/complaint slip showing qtr No, bldgs No, nature of job supported with users signature shall be prepared as per format as directed by Engr-in-charge & will be deposited to concerned JE E/M within 24 hrs. 253 (d)All sort of petty T&P items such as PVC insulation tape, ladder, galvanised screws, nuts, bolts, washers etc. required to accomplish the job shall be provided by the contractor without any extra cost to deptt. 254 (j)In case of any delay in attending the complaint more than 12 hrs after handing over routine/urgent complaints, the contractor shall be liable to pay the penalty as described in penalty clause given here as under. 255 (k)The penalty shall be applicable to the contractor if the delay is noticed by the Engr-in-Cahrge more than twelve hrs after handing over works of urgent/ routine nature to the contractor. The Engr-in-Chargeshall handover the slip containing specification of work to the contractor by lodging the time and signature of contractor shall be obtained on slip.The contractor shall attend the complaint immediately and shall report to Engr-in-Charge with in 12 hrs. The contractor will keep his tradesmen in stand by for attending any routine / urgent works from the executive.If the nature of job is such that the work cannot be completed within period of 12hrs then the facts shall be brought to the notice of the GE/Engr-in-Chargeand the period for the working to the complaint shall be decided by the GE/EIC. If the delay is more then twelve hrs period and the GE is not satisfied with the reason for delay then penalty at the rate of Rs 50/- per job shall be deducted from the dues of the contractor. Please note that this penalty is exclusively other than the condition 67 of IAFW - 2249 and shall be treated as interim condition of the contract and shall be enforce above as and when delay in individual job is noticed and no claim whatsoever on this account shall be entertained by the Deptt. 256 (l) The decision of the Accepting Officer in this regard shall be final and binding. 257 Supply only switch piano flush type 5 Amps240 volts single pole one way, complete all as specified and directed. Make : Anchor, Havells, L&T, Indoasian 258 Supply only switch piano flush type 5 Amps240 volts single pole two way, complete all as specified and directed. Make :Anchor, Havells, L&T, Indoasian 259 Supply only switch piano flush type 15 Amps240 volts single pole one way, complete all as specified and directed. Make : Anchor, Havells, L&T, Indoasian 260 Supply only shuttered socket outlet 3 pin 5 Amps, flush type, complete all as specified and directed Make :Anchor, Havells, L&T, Indoasian 261 Supply only shuttered socket outlet 2 in 1, 5 pin, 5 and 15 Amps, complete all as specified and directed Make :Anchor, Havells, L&T, Indoasian 262 Supply only switch socket combination out let 3 pin 5 Amps, flush type, complete all as specified and directed. Make :Anchor/Havells/L&T/ Indoasian 263 Supply only switch socket combination out let 2 in 1, 6 pin 5 and 15 Amps, flush type, complete all as specified and directed.Make :Anchor/Havells/L&T/ Indoasian 264 Supply only Ceiling rose 3 plates flush type 6 Amps,250 volts ACISI marked, complete all as specified and directed 265 Supply only 7 watt LED lamp, complete all as specified and directed. Make : Philips/ Bajaj/ Crompton 266 Supply only lamp holder, insulated body, cord grip pattern SP 230 volt, complete all as specified and as directed. 267 Supply onlyPVC insulated FRLS PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, 4 Sqmmof single core, complete all as spcified and directed. Make : Havells/ Polycab/ Plaza. 268 Supply only metal clad switch socket single pole and neutral enclosure withtwo pin and earth plug and socket complete with one single pole MCB 20A concealed in walls. Make : Legrand/ L&T/ Indo Asian 269 Supply only plug top 3 pin 15 AmpsAC 230 volts, complete all as specified and directed. Make : Havells/ Cona/ Plaza 270 Supply only electronic LED driver 10/12 W suitable for round ceiling light indoor fitting of make Philips/ crompton/ Bajaj, complete all as specified and directed . 271 Supply only rigid, non-metalic, PVC conduit pipe, ISI marked, 32 mm bore, including bends, saddles, accessories, complete all as specified and as directed. Make : Avon plast/ supreme/ Diplast 272 Supply onlysinglepole MCB 6 to 32 Amps, 240 v, 50 Hz ACsuitable for ‘C’ curve, 10 KA breaking capacity conforming to IS 8828 of 1996, completeall as specified and directed.Make : Legrand/ L&T/ Indo Asian 273 Supply only electronicfan regulator 230 volts, step type socket type, hum free 100/240 watt , complete all as specified and directedMake :Havells / Anchor/ crabtree/Indoasian 274 Supply only 2.5 mfd condensor for ceiling fan, complete all as specified and directed. Make : Epcos/ Asian/ Tyton 275 Supply only rigid, non-metalic, PVC conduit pipe, ISI marked, 25 mm bore, including bends, saddles, accessories, complete all as specified and as directed. Make : Avon plast/ Supreme/ Diplast 276 Supply only 4 mfd condensor for exhaust fan, complete all as specified and directed. Make : Epcos/ Asian/ Tyton 277 Supply only electronic LED driver 36/40 W suitable for 2 x 2 ceiling light indoor fitting of make Philips/ crompton/ Bajaj, complete all as specified and directed . 278 Supply and Fixingbakelite sheet not less than 3 mm thick ofsize up to 1 Sqft as per site requirement, including refixing of old/ fixing of new Switch/socket/regulator etccomplete all as specified anddirected. 279 Supply only electronicfan regulator modular type 230 volts, step type socket type, hum free 100/240 watt, complete all as specified and directed.Make :Havells / Anchor/ Crabtree. 280 Supply only TPN, MCB 20 to 32 Amp, 240 v, 50 Hz ACsuitable for ‘C’ curve, 10 KA breaking capacitycomplete conforming to IS 8828 of 1996, all as specified Make : Legrand/ L&T/ Indo Asian 281 Supply only bell push, piono type 5/6 Amp, complete all as specified and directed.Make : Anchor/ Cona/ Havells/ Indoasian 282 Supply only PVC gang box suitable for 05 Amp SS , complete all as specified and directed . Make. Cona/L&T/Anchor 283 Supply only PVC Casing & Cappingof 15 mm (width), complete all as specified and directed. 284 Supply onlymodular PVC box 2 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian 285 Supply only plug top 3 pin 5 AmpsAC 230 volts, complete all as specified and directed. Make : Havells/ Cona/ Plaza 286 Supply only electric bell, AC 230 volt, single pole Ding Dong type complete all as specified and directed. Make :Anchor/Havells/L&T/ Indoasian 287 Supply onlyTPN, MCB 40 to 63 Amp, 240 v, 50 Hz ACsuitable for ‘C’ curve, 10 KA breaking capacitycomplete conforming to IS 8828 of 1996, all as specified Make : Legrand/ L&T/ Indo Asian 288 Supply only PVC gang box suitable for 15Amp SS , complete all as specified and directed . Make. Cona/L&T/Anchor 289 Supply onlyPVC insulated and FRLS PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, 2.5 Sqmm single core,complete all as spcified and directed. Make : Havells/ Polycab/ Plaza 290 Supply only PVC Casing & Capping of 25 mm (width), complete all as specified and directed. 291 Supply onlyPVC insulated and FRLS PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, 1.5 Sqmm of single core, complete all as spcified and directed. Make : Havells/ Polycab/ Plaza. 292 Supply onlymodular switch1 way 6 Amp.1 module , complete all as specified and directed.. Make : Legrand/ Crab tree/ Anchor/ Indoasian 293 Supply onlymodular Socket, 6A - 2/3 pin combined 2 module, complete all as specified and directed.. Make : Legrand/ Crab tree/ Anchor/ Indoasian 294 Supply onlymodular switch1 way 16 Amp.1 module, complete all as specified and directed.. Make : Legrand/ Crab tree/ Anchor/ Indoasian 295 Supply only modular Socket, 16A - 3/5 pin combined 2 module, complete all as specified and directed.. Make : Legrand/ Crab tree/ Anchor/Indoasian 296 Supply onlymodular white cover plate with frame,3 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian 297 Supply only modular white cover plate with frame,4 module, complete all as specified and directed.. Make : Legrand /Crabtree/ Anchor/Indoasian 298 Supply onlymodular white cover plate with frame,6 module, complete all as specified and directed.. Make : Legrand /Crabtree/ Anchor/Indoasian 299 Supply onlymodular white cover plate with frame,08 module, complete all as specified and directed.. Make : Legrand /Crabtree/ Anchor/Indoasian 300 Supply onlymodular white cover plate with frame,12 module, complete all as specified and directed.. Make : Legrand/ Crabtree/ Anchor/Indoasian 301 Supply onlymodular PVC box 4 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian 302 Supply only switch socket combination outlet 3 in 1/ 3 pin 3 and 5 Amps flush type with box, complete all as specified and directed. 303 Supply only switch socket combination outlet 5 in 1/ 5 pin 5 and 15 Amps flush type with box, complete all as specified and directed. 304 Supply onlymodular PVC box 3module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor 305 Supply only PVC Casing & Capping of 20 mm (width), complete all as specified and directed. 306 Supply onlyPVC insulated and FRLS PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, 6 Sqmm Single core, complete all as spcified and directed. Make : Havells/ Polycab/ Plaza. 307 Supply only SPN MCB 40 Amp, 240 v, 50 Hz ACsuitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828 of 1996, all as specified and directed. Make : Legrand/ L&T/ Indo Asian 308 Supply only insulation tape 25 mm width 10m long (ISI Marked), complete all as specified and directed. 309 M&L for sub main wiring with PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 6 Sqmm drawn through in and incl suitable size surface PVC Conduit/ existing concealed conduit and all accessories fixed to wall/floors along with 6 Sqmm surface PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing sub main wiring of any size.Note: (a)2 runs of 6 Sqmm cable along with one run of 6 Sqmm cable for earth conductor shall be measured as one lengthMake:- Havells/ Polycab/ Plaza. 310 S&F in replacement factory madepowder coated distribution board SPN 12 way double door,includingbus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DBall as specified and conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian 311 S&F in replacement distribution board MCCB four pole, 100 Amp ultimate breaking capacity 16 KAconforming to IEC -61439-1, complete all as specified and directed. Make : Legrand/ L&T/ Indo Asian 312 S&F in repairs 35/36 W (WW) LED recessed type 2x2 luminaire with classic design & glare free soft illumination. housing with white high reflection powder coated (RAL9016) CRCA sheet. Glare free, Opal diffuser for symmetrical light distribution fixed in separate CRCA sheet frame held in with housing by screws for easy maintenance. High efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle of 100° to ensure better uniformity. Powered by an independent Isolated, SELF Output electronic LED driver (SMPS based constant current supply) efficiency of 85% with built-in Surge protection 3Kv. System Lumen Output of 3000 lumens.Make : Philips/ Bajaj/CG/Havells. 313 S&F in repairof new PVC conduit medium grade of size 25mm on wall /roofwith help of screw and GI shaddle including fixing of existingserviceable copper /aluminium conductorand all fitting fixture such as Tee, Elbow and lapping, completeall as specified and as directed. Make : Supreme/Diplast/Avon plast 314 S&F in repair of new PVC conduit medium grade of size 20 mm on wall /roofwith help of screw and GI shaddle including fixing of existingserviceable copper /alluminium conductorand all fitting fixture such as Tee, Elbow and lapping,completeall as specified and as directed. Make : Supreme/Diplast/Avon plast 315 S&F in repairs LED bed side light /wall light/study lightenvironmentel friendly energy effcient of capacity3 W warm whiteetc,inbuilt drivercomplete with all accessories internally pre-wired swing type and including connecting up towith twin core twisted flexible copper conductor cable with suitable size complete all as directed . Make : Bajaj/ Philips / Wipro/CG 316 Supply & Fixing in replacement of electronic LED driver 2/3 W suitable for bed side light fitting as per site requirement complete all as specified and directed . 317 Taking down aluminium/copper point wiring & including hard wood battens, surface conduit and board/ blocks etc or through conduits for light, socket or power point, fan point complete and making good the disturbed plaster surfaces of wall, floor, ceilingand painting 2 coat of white wash/distamber to match the existing surface, complete all as specified and directed. 318 M & L for Point wiring with PVC insulated FRLS 1.5 sq mm multi stranded copper conductor cable 1100 Volts grade drawn through and including surface PVC conduit/existing concealed conduit/PVC casing-caping ets as per site requirement onwalls / roofs / floors / ceiling etc and including provision of 1.5 sqmm copper cable as earth continuity conductor and connected to common earth dolly with all fitting and fixing accessories including sunk in cast iron / pressed steel terminal boxes (duly painted with two coats of anti corrosive paint out side and two coats of aluminium paint inside ) with 3.0 mm thick hylum brand laminated white bakelite sheet cover for mounting switches, sockets, fans regulators etccomplete for the following :-Make of wire: Polycab/Plaza/HavellsNote: (a) Switches, sockets outlets, Light fittngs, fans, bells & regulators shall be measured and paid for separetely). 319 All as per item No. 318here in before but forOne light point/fan point controlled by one way 5 Amp switch. 320 All as per item No. 318here in before but forOne light point controlled by two way 5 Amp switch. 321 All as per item No. 318here in before but for one bell point controlled by one way bel push. 322 All as per item No. 318here in before but forOne 3 pin socket out let 5 Ampon the same board 323 All as per item No. 318here in before but for one switch socket outlet 3 pin 5 Amps on independent board 324 All as per item No. 318here in before but for Wiring with 2.5 Sqmm copper multistranded unsheathed cable and2.5 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently etc complete all as specified and directed. 325 All as per item No. 69here in before but for Wiring with 4 Sqmm copper multistranded unsheathed cable and4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently etc complete all as specified and directed. 326 Supply and Fix switch piano flush type 5 Amps240 volts single pole one way, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian 327 Supply and Fix switch piano flush type 5 Amps240 volts single pole two way, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian 328 Supply and Fix switch piano flush type 5 Amps240 volts bell push, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian 329 Supply and Fix shuttered socket outlet 3 pin 5 Amps, flush type, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian 330 Supply and Fix shuttered switch socket outlet 3 pin 5 Amps, flush type, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian 331 Supply and Fix shuttered socket outlet 2 in 1, 3 pin, 5 and15 Amps, complete all as specified and directed.Make : Anchor/Havells/L&T/Indoasian 332 S & F2.5 mfd condensor for ceiling fan, complete all as specified and directed. Make : Epcos/ Asian/ Tyton 333 S & F ceiling rose surface bakelight two to three terminal complete all as specified and directedMake : Anchor/Havells/L&T 334 S & Felectric bell, AC 230 volt, single pole Ding Dong type complete all as specified and directed. Make :Anchor/Havells/L&T 335 S & Ffan regulator 120W,for ceiling fan complete all as specified and directed Make : Anchor/Havells/L&T 336 Supply and Fixing in repairs of 4 feet surface mounted batten type luminaire , lumen output of 2000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm. The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02, Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ. The luminaire shall have flicker content<5% and shall have high and low cut off with auto restart feature.Driver Safety requirement stds: IS 15885-2-13. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 KV. The luminaire shall have Class-1 Electrical insulation, Class-B serviceability .The luminaire and driver shall be BIS approved, complete all as specified and directed.Make : Philips/ Bajaj / CG/Havells. 337 Supply & fix in repair decorative surfacemountedultra slim Square/Roundprofile 18 W LED(WW/WH) lighting fixture Square shape with extruded polycarbonate, environmental friendly, energy efficient ready to use pack of18 Watt and includingcosidering material & labour forfixing ceiling hight upto 7.5 Mtr, complete all as per site requirementand directedMake : Philips/ Bajaj / CG/Havells. 338 M&L for sub main wiring with PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 6 Sqmm drawn through in and incl suitable size PVC casing capping and all accessories fixed to wall/floors along with 6 Sqmm PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing old sub main wiring of any size.Note: (a)2 runs of 6 Sqmm cable along with one run of 6 Sqmm cable for earth conductor shall be measured as one lengthMake:- Havells/ Polycab/ Plaza. 339 S&F in replacementfactory madepowder coated distribution board VTPN, 4 way double doorMCCB DB includingbus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DBcomplete all as directedMake : Indoasian/ Havells/ Legrand. 340 S&F in replacement on distribution board MCCB four pole, 63 Amp ultimate breaking capacity 16 KA conforming to IEC -61439-1, complete all as specified and directed.Make : Havells/ L&T/ Indoasian 341 S&F as in repair PVC casing capping medium grade of size 32 mm on wall /roofwith help of screw including serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping,completeall as specified and as directed. Make: Polycab/ Modi/ Presto Plast 342 M&L for cutting of hole through brick wall with the help of Core cutting machineincluding providing, fixing and removing shoring,cleaning,internal plastering and removing surplus hard core,rubbish not exceeding 50 mtrs including fixing of exhaust fan of size 250-450 mm all as specified and as directed. 343 M&L forin repair louver made of galvanised steel sheet suitable for 300 mm size exhaust fan, fixed on wall including necessary fixing arrengement up to height 11 mtrcomplete all as specified and directed.Note : All safety measures shall be the responsibility of the contractor. 344 Supply and fixingExhaust fan 300 mm sweep 230/ 240 volt AC single phase PVC body 1400 RPM including necessary nut, bolts / screws including taking down existing one writing MES No. with synthetic enamel paint all specified and directed.Make : Havells/Bajaj/ Orient/USHA.Note:-Old Unserviceable Exhaust fan shall be deposited to MES store yard without any extra cost to the deptt. 345 M&L in repairfor stainless steel wire cloth 0.63 mm dia of wire and average width of aperture 1:40 mm for covering of exhaust fan hole in wall of size 450 mm X450 mm with PVC/woodenbeading fixed on wall including necessary fixing arrangement up to height 11 mtrcomplete all as specified and directed.Note : All safety measures shall be the responsibility of the contractor 346 Supply and fixing in repair building security/ LED street light fitting 36 Watt, 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal, management in multiple optics complete, with IP 65/66 protection complete all as specified and directed. Make: Philips/Bajaj/CG 347 Supply and fix GI pipe 32 mm dia, medium grade for mounting bracket, bent to shape 1.5 meter length and fixing arrangement with two Nos ofclamps set, nut, bolts, washers, andincl taking down old unserviceable GI pipe complete all as specified and directed 348 Supply and fix 1100 Volts grade heavy duty flat weather proof twin core cable of size 4 Sqmm with multistrand aluminium conductor including taking down of old one complete all as directed and specified . Make: Plaza/Polycab/ Finolex 349 Supply and Fixing in repairs of wall focus track light18 wattWW an operating voltage range from 140V-270Vcomplete all as specified and directed.Make : Philips /Luker/ Havells/Bajaj. 350 Supply and Fixing in repairs of channel 2 Mtr lengthforfocus track light complete all as specified and directed. 351 Refixingexisting serviceable LED light fitting fixture any capacity and of any type complete with all accessories internally pre-wired and including connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size after cleaning all dust etc. completeall as specified and as directed . 352 M&L for Sub main wiring with PVC insulated unsheathedFRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 4 Sqmm drawn through in and incl suitable sizesurface PVC Conduit/ existing concealed conduit and all accessories fixed to wall/floors along with 4 Sqmm PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing sub main wiring of any size.Note: (a)2 runs of 4 Sqmm cable along with onerun of 4 Sqmm cable for earth conductor shall be measured as one length.Make:- Havells/ Polycab/ Plaza. 353 S&F in replacementfactory madepowder coated distribution board TPN, 4 way double doorMCBDB includingbus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DBcomplete all as directedMake : Indoasian/ Havells/ Legrand. 354 S&F in replacement factory madepowder coated distribution board SPN 8 way double door,includingbus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DBall as specified and conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian 355 S & F MCB in repair and replacement ofSPN 240 volts 16 to 40 Amps complete including taking down unserviceable fitting complete all as specified and as directed .Make : Legrand/ L&T/ Indo Asian 356 Supply and fixing in replacement of unserviceableceiling fan 1200mm sweep, energy efficient BLDCISI mark withstar rating 230 Volts AC 50 Hz, single phase including provision of fixing arrangement, nut and bolt andflexible 3 core of size 1.5 sqmm not less than 0.5 m long complete including taking down existing one, writing MES No with synthetic enamel paint all as specified and as directed. Make : Havells/Bajaj/ Orient.Note:-(a)Old Unserviceable ceiling fan shall be deposited to MES store yard. 357 S&F as in repair PVC casing capping medium grade of size 25 mm on wall /roofwith help of screw including serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping,completeall as specified and as directed. Make: Polycab/ Modi/ Presto Plast 358 S&F in repairs 35/36 W( WH) LED recessed type 2x2 luminaire with classic design & glare free soft illumination. housing with white high reflection powder coated (RAL9016) CRCA sheet. Glare free, Opal diffuser for symmetrical light distribution fixed in separate CRCA sheet frame held in with housing by screws for easy maintenance. High efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle of 100° to ensure better uniformity. Powered by an independent Isolated, SELF Output electronic LED driver (SMPS based constant current supply) efficiency of 85% with built-in Surge protection 3Kv. System Lumen Output of 3000 lumens.Make : Philips/ Bajaj/CG/Havells. 359 Excavation in trenches not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level and laying of pipelines etcinsoft/loose soil, complete all as specified and directed. 360 Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed. 361 Removing surplus excavated material (soil) not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and directed. 362 Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed.Note :- (i)Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment. 363 Material and labour for well burnt bricks ‘B’ class as mechanicalprotection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and directed. 364 Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earthwork, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :-The tenderer shall take into consideration for following points while quoting rate for this item andthe unit rate is deemed to be inclusive for :-(i) Earth work and excavation in any type of soil(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick ,complete all as specified and as directed.(iii) Removing excavated material out side MD land.(iv)Laying of any type/any bore of pipe in trenches including taking down existing unserviceable pipe. Supply of pipe shall be measured and paid separately(v)150 mm thickPCC 1:2:4 type B1 using 20mm graded stone aggregate as inroad to make good existing disturbed surfaces. 365 Supply only of GI pipe light grade for cable protection of size 50 mm bore with fittings, complete all as specified and directed. 366 Material and labour in repair for4 core 16 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laid inlaying in trenches/cable ducts, fixed to wall/pole etc complete all as specified and directed.Make :- Havells/Polycab/ RPG Asian 367 Material and labour in repair for 3 ½ core 25 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laid in trenches/cable ducts, fixed to wall/pole etc, complete all as specified and directed. Make : Havells, Polycab, RPG Asian 368 Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tape etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box, complete all as specified and as directed for thecable sizefrom 16Sqmmto 25 Sqmm 3.5 core of underground LT armoured cables.Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall deemed to be included in the unit rate quoted. 369 Supply, installation, testing and commissioning LTFeeder pillar box double door CPRI Testedof Size 400X250X350mmsuitable for 3 phase 415 Volts of suitable size out door made out 3.15mm thick CRCA sheet of outdoor of panel with angle iron frame of size 32x32x5mm cubical type complete with aluminium bus bar 100 Amp and including PCC foundation as per site requairment to accomodated to the following.INCOMING(a)MCB TPN32 Amp 10 KA - 01 No. (b)LEDindicating lampR-Y-B - 03 Nos. OUTGOING(a) Weather Proof panelPlug and shocket angled type IP 67three Phase 3P+N +E, 20 Amp - 01 No(b) Weather Proof plug and shocket angled type IP 67 Single Phase 2P+E , 20 Amp- 01 No.(a)MCB TPN20 Amp 10 KA - 01 No. (a)MCB SPN20 Amp 10 KA - 01 No. 370 Supply and Fixin repair and replacement ofsurface mounted Square/Roundfor LED 18W Watt downlights made of extruded Aluminium housing and high power LED light source withDriver clear diffuser with separate electronic driver with complete accessories all as specified and directed .Make : Philips/ Bajaj/ CG/Havells. 371 M&L for cutting of hole through stone wall with the help of Core cutting machineincluding providing, fixing and removing shoring,cleaning,internal plastering and removing surplus hard core,rubbish not exceeding 50 mtrs including fixing of exhaust fan of size 250-450 mm all as specified and as directed. 372 Supply and fixingExhaust fan250 mm sweep 230/ 240 volt AC single phase PVC body1400 RPM including necessary nut, bolts / screws including taking down existing one writing MES No with synthetic enamel paint all specified and directed.Make : Havells/Bajaj/ Orient/USHA.Note:-Old Unserviceable Exhaust fan shall be deposited to MES store yard. 373 S&F as in repair energy efficient wallmounted LED luminaire5 WX2wooden finish(WW), The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02. Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ supply single phase including connecting with PVC insulated three core flexible copper conductor of suitable size from ceiling rose to fitting and fixing to ceiling complete all as directed. Make : Philips /Luker/ Havells/Bajaj. 374 Supply and fix 1100 Volts grade heavy duty flat weather proof twin core cable of size 6 Sqmm with multistrand aluminium conductor including taking down of old one complete all as directed and specified . Make: Plaza/Polycab/ Finolex 375 Supply & Fixing in replacement of electronic LED driver 18/20 W suitable for round ceiling light indoor fitting of make Philips/ crompton/ Bajaj, complete all as specified and directed . 376 S & Fin replacement 9 watt LED lamp, complete all as specified and directed. Make : Philips/ Bajaj/ Crompton 377 M & L for Point wiring with PVC insulated FRLS 1.5 sq mm multi stranded copper conductor cable 1100 Volts grade drawn into and including concealedrigid non mettalic PVC conduit/casing caping medium grade not less than 19/20 mm ( ISI marked ) with all fitting and fixing accessories including sunk in pressed steel chromium plated terminal boxes, concealed in wall/surface/roofs/floor/ceiling etc as per site requirement and making & maching the existing surface ) white bakelite sheet cover for mounting switches, Sockets, Fan regulators etc or modular cover plate with frame including sunken boxes suitableto fix modular cover plate with frame , concealed in wall or 1.5 sq mm multi stranded copper conductor cable as continuous earth wire drawn with wiring and connected to common earth dolly complete all as specified and directed for the following :- Make of wire: Polycab/Plaza/HavellsNote:Blanking plate,Modular cover plate ,Switches, sockets outlets, Light fittngs, fans, bells & regulators shall be measured and paid for separetely). 378 All as per item No. 377 here in before but for one light point/fan/bell point controlled by one wayswitch. 379 All as per item No. 377here in before but for one light point controlled by twowayswitch. 380 All as per item No. 377here in before but for one bell point controlled by one bell push. 381 All as per item No. 377 here in before but for one 3 pin socket out 5 Ampon the same board 382 All as per item No. 377 here in before but for one switch socket outlet 3 pin 5 Amps on independent board 383 All as per Sl No 377 above but Wiring with 2.5 Sqmm copper multistranded unsheathed cable and 2.5 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently etc complete all as specified and directed. 384 All as per Sl No 377 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently etc complete all as specified and directed. 385 Supply and Fixmodular switch1 way 6 Amp.1 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor/Indoasian 386 Supply and Fixmodular switch2 way 6 Amp.1 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor /Indoasian 387 Supply and Fixmodular switchbell push .1 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor /Indoasian 388 Supply and Fixmodular Socket, 6A - 2/3 pin combined 2 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor/Indoasian 389 Supply and Fixmodular switch1 way 16 Amp.1 module, complete all as specified and directed. Make :Legrand/ Crabtree/ Anchor /Indoasian 390 Supply and Fix modular Socket, 16A - 2/3 pin combined 2 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian 391 Supply and fix White cover plate with frame,2/3 module 392 Supply and fix White cover plate with frame,4 module 393 Supply and fix White cover plate with frame,8 module 394 Supply and fix White cover plate with frame,6 module 395 Supply and fix White cover plate with frame,12 module 396 S & F Modular fan regulator 120W, 2 Module for ceiling fan complete all as specified and directedMake : Legrand/ Crabtree/ Anchor 397 Supply and Fixingof 4 feet surface mounted emergency battern type luminaire , lumen output of 2000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm.complete all as specified and directed.Make : Philips/ Bajaj /CG/Havells. 398 M&L for Sub main wiring with PVC insulated unsheathedFRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 4 Sqmm drawn through in and incl suitable size PVC casing capping and all accessories fixed to wall/floors along with 4 Sqmm PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing sub main wiring of any size.Note: (a)2 runs of 4 Sqmm cable along with onerun of 4 Sqmm cable for earth conductor shall be measured as one length.Make:- Havells/ Polycab/ Plaza. 399 S&F in replacement factory madepowder coated distribution board SPN 6 way double door,includingbus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DBall as specified and conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian 400 S & F in repair and replacement of MCB single pole 240 volts 6 to 40 Amps complete including taking down unserviceable fitting complete all as specified and as directed .Make : Legrand/ L&T/ Indo Asian 401 Supply and Fixing in repairs of 2 feet surface mounted batten type luminaire , lumen output of 1000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm. The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02, Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ. The luminaire shall have flicker content<5% and shall have high and low cut off with auto restart feature.Driver Safety requirement stds: IS 15885-2-13. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 KV. The luminaire shall have Class-1 Electrical insulation, Class-B serviceability .The luminaire and driver shall be BIS approved, complete all as specified and directed.Make : Philips/ Bajaj / CG/Havells. 402 Supply and Fixing in repairs of LED Outdoor under water light 12 X3 , IP68, suitable for swimming pools/façade etc. RGBincluding control panel and necessary cable from control panel to light approx 5 mtrcomplete all as specified and directed. Make : cat No : SZLFUM012x3W-RGB of Shakti /Philips/ Bajaj/ CG/Havells 403 S&F in replacement factory madepowder coated distribution board SPN 4 way double door,includingbus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DBall as specified and conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian 404 S & F MCB in repair and replacement ofSPN 240 volts 63 Amps complete including taking down unserviceable fitting complete all as specified and as directed .Make : Legrand/ L&T/ Indo Asian 405 S&F in repairs 35/36 W (WW) LED Surface type2x2 luminaire with classic design & glare free soft illumination. housing with white high reflection powder coated (RAL9016) CRCA sheet. Glare free, Opal diffuser for symmetrical light distribution fixed in separate CRCA sheet frame held in with housing by screws for easy maintenance. High efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle of 100° to ensure better uniformity. Powered by an independent Isolated, SELF Output electronic LED driver (SMPS based constant current supply) efficiency of 85% with built-in Surge protection 3Kv. System Lumen Output of 3000 lumens.Make : Philips/ Bajaj/CG/Havells. 406 Material and labour forBoring of holes under road, pavement hard standing by trenchless technology using ultra sound technique and necessary machine including supply of HDPE pipes upto 50 mm dia suitable for 0.4 Mpa working pressure, complete all as specified and directed. 407 Material and labour in repair for 3 ½ core 35 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed layid in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian 408 Material and labour in repair formaking straight through joint with suitablejointing kit consisting of water proof adhesivesfor UG cable of size 3.50 core 25 Sqmm to 35 Sqmm, complete all as specified and directed. 409 Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tape etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box, complete all as specified and as directed for thecable sizefrom 25Sqmmto 35 Sqmm 3.5 core of underground LT armoured cables.Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall deemed to be included in the unit rate quoted. 410 Supply, installation, testing and commissioning indoor panel box CPRI Testedof Size 800x600X450 mmsuitable for 3 phase 415 Volts IP 54 of suitable size out door made out 2.00 mm thick CRCA sheet of indoor panel with angle iron frame of suitable sizecubical type with one side cable Alleycomplete with suitable size bus bar and including wall mounting clamp as per site requirement to accomodated to the following.INCOMING(a)MCCB 4 pole 250 Amp 25 KA - 01 No. (b)LEDindicating lampR-Y-B - 03 Nos.(c)Digital Ammeter with selecter switch andsuitable capacity of CTs- 01 No (d) Digital Voltmeterwithselecter switch - 01 No(d) Space for provn of 3 Phase KWH Main meter-01 No OUTGOING(a)MCCB 4 pole 100 Amp 16 KA - 03 Nos. (b)MCCB 4 pole 63 Amp 16 KA - 01 No. 411 Supply, installation, testing & commissioning of maintenance free chemicalearthing system comprising of 17mm dia copper bondedrod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducingliquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed..Make : Model HTSP 317 of safeTrode or equivalent in Snaga/ Cubes 6 Global 412 The quoted rate shall also deemed to be included the following :- (i)Prior toinstallation of maintenance free chemicalearthing, soil resistivity test to be carried out at the location where earthingwork to be donein presence of Engr-in- Charge/JE (E/M),user and the report has tosubmitto Garrison Engineer with recommendation of manufacturer, if required additional interconnection ofearthing (not more than 08 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testingandsubmission of report with recommendationdeemed to be included in the quoted rate. 413 (ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors. 414 (iii) Rateofearth energizer compound of 25 Kg of 02 bags and earthresistance reducingliquid 10 litre per cane for each pit deemed to be included in the quoted rate. 415 (iv)Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor along with the sample approval 416 (v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete. 417 (vi) Copper strip of size 20 x 3 mm shallbe fixed on proper post insulator at the instrument end (copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately). 418 (vii)Testing of earth shall be carriedout in presence ofdepartmental and user representativeand report shall be submitted to Garrison Engineer duly signed by all concerned. 419 (viii)Earth resistance tester will be provided by the contractor.Tester should be calibrated from authorised company/ lab. 420 (ix)Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned.After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained. 421 (x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion. 422 (xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock. 423 (xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained. 424 (xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period. 425 (xiv) The electrode shallcarry manufacturers name . 426 (xv) The connection clamp shall be permanentlly welded to the copper boundedrodto avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination. 427 (xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm. 428 (xvii)Earth work such as auguring andmaking good the surrounding area shall carried out in any type of soil. 429 (xviii)The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material. 430 (xix) Sign boardof mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxideZinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge. 431 Material and labour for Earth pit cover madeof heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit complete including taking down old one complete all as specified and directed.Make : Model SEPC 250 of SAFE TRODE or equivalent in Snaga/ Cubes 6 Global 432 S&F in repair copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing old unserviceable copper strip etc, complete all as specified anddirected. Note : - All Joints should be joined by Exothermic Welding or Brazing. 433 Supply, installation, testing and commissioning LTFeeder pillar box CPRI Testedof Size 800x600X450 mmsuitable for 3 phase 415 Volts of suitable size out door made out 3.15mm thick CRCA sheet of outdoor of panel with angle iron frame of size 50x50x6mm cubical type complete with aluminium bus bar 600 Amp and including PCC foundation as per site requairment to accomodated to the following.INCOMING(a)MCCB 4 pole 315 Amp 36 KA - 01 No. (b)LEDindicating lampR-Y-B - 03 Nos.(c)Multifunction Meter (V,I,PF) with suitable capacity of CTs- 01 NoOUTGOING(a)Through Bus Bar 434 Note :- An amount of Rs 2,14,139.00 on account of credit schedule for schedule A part II shall be deducted from the total amount of BOQ to arrive at the contract sum.