Project Description

Tender For Combined Electrical Works At Various Location In Nitc; 1 Three Phase ECED 2 Wiring for circuit/ submain wiring alongwith4 x 10 sq mm + 2 x 6 sq mm earth wireFRLS PVC insulated copper conductor, single core cable in surface/ recessed pvc conduit as required. 3 Wiring for circuit/ submain wiring alongwith 4 x 16 sq mm + 2 x 6 sq mm earth wireof FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 Supplying and drawing 3 x 2.5 sq mm FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. 5 Supplying and fixing of 20 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required 6 Supplying and fixing of 25 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required 7 Supplying and fixing 15/16 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc.as required 8 Supplying and fixing6 pin 15/16 A modular socket ( 3 MD type ) on the existing modular plate & switch box including connections but excluding modular plate etc.as required 9 Supplying and fixing 4 module (125 mm X 75 mm) GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 10 Supplying and fixing 8 module (125 mm X 125 mm) GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 11 Providing and fixing 100 A , 4P MCCB, 16 KA breaking capacity and 4 pole MCCB with thermomagnetic release and terminal spreaders in existing MCCB DB , making conection as required. 12 Supplying and fixing 8 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar. interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 13 Supplying and fixing 3 phase 4 way (8+12) double door, suface/recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing MCCB as incomer and TP MCB as out going, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB) 14 Supplying and fixing 6 way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 15 Supplying and fixing of 4 ways (8+12) , Double door. surface/ recess mounting. vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 16 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 17 Supplying and fixing32 A rating Triple pole , 415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. 18 Supplying and fixing32 A rating 4 pole , 415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. 19 supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required 20 Supplying and fixing 40 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required. 21 Supplying and fixing 63 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required. 22 Supplying and fixing 40 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required. 23 Supplying and fixing 63A , Four pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 24 Supplying and fixing 63A , Triple pole, 415 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc.. 25 Supplying and fixing 40 A , Four pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 26 Supplying and fixing 40A , three pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 27 Supply of 4 x 50 Sq.mm PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988 28 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement, watering pipe of 2.7 metre long etc.with charcoal/coke and salt as required. 29 Supplying and laying 25mm x 3mm strip at 0.05 metre below ground as earth electrode, including connection/ terminating with SS nut,bolt,spring washer , double plate washer etc.as required ( jionting shall done by overlapping and with 2 set GI nut bolt and washer spaced 50mm) 30 Providing and fixing 25 mm X 6 mm G.Istrip on surface or in recess for connections etc. as required. 31 Supply 60kg of earthing compound (EXCEL compound or equivalent) etc. as required. 32 Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required. 33 Laying and fixing of Above 35 sq mm and upto 95 sq mm (clamped with 25 x 3 mm MS flat clamp) PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as required. 34 Supplying and making end termination with brass compression gland providing sutable size gland earthing and aluminium lugs for 4 x 50 sq mm PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 35 supplying and making end termination of suitable size for the submain wiring with Copper lugs for 4x10 + 2x6sqmm of PVC insulated copper conductor 36 supplying and making end termination of suitable size for the submain wiring with Copper lugs for 4x16+ 2x6sqmm of PVC insulated copper conductor 37 Material testing lab architecture 38 MCB 39 Supplying and fixing 40 to 63A rating, Three pole (Three phase ) 415 Volts, 10kA, C curve, miniature circuit breaker suitable for inductive load of triple pole in the existing MCB DB complete with connections, testing and commissioning etc as required. 40 Supplying and fixing 63A rating, Four pole, Three phase, 415 Volts, 10kA, C curve, miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc as required. 41 Wiringforcircuit/submainwiringalongwithearthwirewiththe followingsizesofFRLSPVCinsulatedcopper conductor,single corecableinsurface/recessedmediumclassPVCconduitas required. 42 4 X 16 sq. mm + 2 X 6 sq. mm earth wire 43 4 X 4 sq. mm + 2 X 4 sq. mm earth wire 44 End termination 45 Supplying and making end termination of suitable size for the submain wiringwith Copper lugs for 4x16 + 2x6sqmm of PVC insulated copper conductor 46 Supplying and fixing followingrating, four pole, (threephase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existingMCBDB complete with connections, testing and commissioning etc. as required. 47 63A 48 Supplyingand fixingof following ways surface/ recessmounting, vertical type, 415 V, TPN MOB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MOB TPDB is normally used where 3 phase outlets are required.) 49 8 way (8 + 24), Double door 50 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required. 51 Triple pole 52 Single pole 53 SupplyinganddrawingfollowingsizesofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 54 3 x 2.5 sq. mm 55 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 56 20 mm 57 Supplying and fixing FP sheet steel enclosure on surface/ recess alongwith 16/25/32 A 415 VCcurveFPMCBcomplete with connections, testing and commissioning etc. as required. 58 Supplying and fixing suitable size GI box withmodular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. 59 Supplying and fixing single pole blanking plate in the existing MOB DB complete etc. as required. 60 UG CABLE FOR NAME BOARD 61 Supplying of one number 2C x 6 Sq.mm size Aluminium conductor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required. 62 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 2 C x 6 sq.mm in the existing DWC HDPE pipe/ Metal pipe as required. 63 Supplying and laying of 63 mm dia (OD-63 mm & ID-51 mm nominal) DWC HDPE pipe ISI markedalong with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 64 Supply and layingof3 inch 80 NB GI pipe (medium class B)on ground with all accessories like socket, bend, couplerswith fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., and making good the damages of road with concrete mixture of 1 : 2 : 4 including watering & ramming etc. as required. 65 Supplying and fixing 6-32 A rating, 240/415 V, C curve miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB, complete with connections, testing and commissioning etc. as required. 66 Single pole 67 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 68 25A 69 Supplying and drawing 3 numbers 2.5 sq mm FRLS PVC insulated copper conductor single core cable (Red, Black & Green) in existing surface / recessed PVC conduit as required. 70 Supplying and fixing of 20mm size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 71 Supply and making end termination with brass compression gland and aluminium legs for 2 C x 6 sq.mm (19 mm) size of XLPE insulated PVC sheathed armoured aluminium cable as required.spacing not exeed 50 cm etc. as required. 72 Supply and laying of one number of 14 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required. 73 Supplying and fixing 4 pole MCB metal enclosure on surface / recess, complete with earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required. 74 Supplyingand fixing of weather proof outdoor junction box for outdoor installation of size 205mm x 255mm x112mm with knockouts for cable entry including dinbar, suitable connectors for connecting Al cable to copper cable of suitable size, provision for fixing two number of double pole MCB, weather proof gourmets,glands,clamps,screws of required length fastners connections for surface/ recess fixing onexisting tubular pole etc. as required(clip type)Hensel IP 69 KF 2525G made or Equivalent. 75 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Upto 35 sq. mm (clamped with 1mm thick saddle) size on wall surface/pipe as required. 76 Health Centre 77 Supplyinganddrawing3 x 2.5 sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 78 Supplyinganddrawing 3 x 4sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 79 Supplyinganddrawing 3 x 6sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 80 Wiring for circuit/ submain wiring alongwith earth wire with the 4 x16 sq.mm + 2 x 6 sq.mmof FRLS PVC insulated copper conductor, single core cable in surface/ recesssed medium class PVC conduit as required. 81 Supplying and fixing of 20 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 82 Supplying and fixing of 25 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 83 Supplying and fixing of 32 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 84 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular switch socket outlet and 15/16A modular switch ,connections etc. as required. 85 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Single pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 86 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Double pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 87 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Triple pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 88 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Triple pole and neutral intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 89 Supplying and fixing 4 pole MCB metal enclosure on surface / recess, complete with earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required. 90 Supplying and fixing 25A rating, double pole, (single phase and neutral), 240 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 91 Supplying and fixing 63A rating, Four pole, (Three phase and neutral), 415 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 92 Supplyingand fixingsingle pole blanking plate in the existing MCB SBcomplete etc.as required.) 93 Supplying of one number 3.5 C x 70 Sq.mm size Aluminium conductor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required. 94 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of above 35 sq. mm Upto 95 sq. mm (clamped with 1mm thick saddle) size on wall surface/pipe as required. 95 Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required. 96 Supply and making end termination with brass compression gland and aluminium legs for 3.5 C x 70sq.mm (32 mm) size of XLPE insulated PVC sheathed armoured aluminium cable as required.spacing not exeed 50 cm etc. as required. 97 Supplying and fixing 3 phase 8 way(4+24) , double door, vertical type three pole and neutral ,sheet steel,MCB distribution board,415 V on suface/recess mounting, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB etc) 98 Supplying and fixing 63 A rating, 415 V, 10kA, C curve miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. 99 Supplying and fixing 12 way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 100 Providing and fixing 125 A, 36 KA, FPMCCB rating and breaking capacity and pole MCCB with thermomagneticreleaseand terminal spreaders in existingcubicle panel board including drilling holes in cubicle panel,making connections ,etc.as required. 101 Supplying and fixing 63 A rating, 415 V, 10kA, C curve miniature circuit breaker suitable for inductive load of three pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. 102 Charges for removing the old wall mounted DBs, making good the damages of the wall/ floor including painting, dismantle the DB and other accessories without any damage and conveyance of the material to the godown etc, as required. 103 Supplying and making end termination of suitable size for the submain wiring with suitable lugs for 4 x 16 +2 x 6 sqmm of PVC insulated copper conductor. 104 Supplying and fixing 20/25 A modular DP switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 105 Supplying and fixing 3 pin 25 A modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 106 Supplying and fixing 1/2 module, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 107 Supplying and fixing 3 phase 6 way , double door, suface/recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing MCCB as incomer and TP MCB as out going, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB etc) 108 Charges for cleaning and spray painting the existing Panel board of 180 x 95 x 40 or nearest size withtwo coats of suitable colour (Grey) paint, over a coat of primer in installed position and marking the identification of switches with white paint etc, as required 109 Fabrication & fixing of 123 x 93 cm panel board Sheet made from 2 mm thick MS sheet,powder coated in suitable colour over a coat of primer, providing rubber beadings and suitable size hinches, Nuts & Bolts for fixing on the existing panel board etc. as required. 110 Fabrication & fixing of 94 x 42 cm panel board Sheet made from 2 mm thick MS sheet,powder coated in suitable colour over a coat of primer, providing rubber beadings and suitable size hinches, Nuts & Bolts for fixing on the existing panel board etc. as required.

BOQ

Name of Work: Combined Electrical works at various location in NITC
Sl. No. Item Description
1Three Phase ECED
2Wiring for circuit/ submain wiring alongwith4 x 10 sq mm + 2 x 6 sq mm earth wireFRLS PVC insulated copper conductor, single core cable in surface/ recessed pvc conduit as required.
3Wiring for circuit/ submain wiring alongwith 4 x 16 sq mm + 2 x 6 sq mm earth wireof FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
4Supplying and drawing 3 x 2.5 sq mm FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.
5Supplying and fixing of 20 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required
6Supplying and fixing of 25 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required
7Supplying and fixing 15/16 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc.as required
8Supplying and fixing6 pin 15/16 A modular socket ( 3 MD type ) on the existing modular plate & switch box including connections but excluding modular plate etc.as required
9Supplying and fixing 4 module (125 mm X 75 mm) GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
10Supplying and fixing 8 module (125 mm X 125 mm) GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
11Providing and fixing 100 A , 4P MCCB, 16 KA breaking capacity and 4 pole MCCB with thermomagnetic release and terminal spreaders in existing MCCB DB , making conection as required.
12Supplying and fixing 8 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar. interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
13Supplying and fixing 3 phase 4 way (8+12) double door, suface/recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing MCCB as incomer and TP MCB as out going, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB)
14Supplying and fixing 6 way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
15Supplying and fixing of 4 ways (8+12) , Double door. surface/ recess mounting. vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
16Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
17Supplying and fixing32 A rating Triple pole , 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc.
18Supplying and fixing32 A rating 4 pole , 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc.
19supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required
20Supplying and fixing 40 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required.
21Supplying and fixing 63 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required.
22Supplying and fixing 40 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required.
23Supplying and fixing 63A , Four pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required.
24Supplying and fixing 63A , Triple pole, 415 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc..
25Supplying and fixing 40 A , Four pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required.
26Supplying and fixing 40A , three pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required.
27Supply of 4 x 50 Sq.mm PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988
28Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement, watering pipe of 2.7 metre long etc.with charcoal/coke and salt as required.
29Supplying and laying 25mm x 3mm strip at 0.05 metre below ground as earth electrode, including connection/ terminating with SS nut,bolt,spring washer , double plate washer etc.as required ( jionting shall done by overlapping and with 2 set GI nut bolt and washer spaced 50mm)
30Providing and fixing 25 mm X 6 mm G.Istrip on surface or in recess for connections etc. as required.
31Supply 60kg of earthing compound (EXCEL compound or equivalent) etc. as required.
32Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required.
33Laying and fixing of Above 35 sq mm and upto 95 sq mm (clamped with 25 x 3 mm MS flat clamp) PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as required.
34Supplying and making end termination with brass compression gland providing sutable size gland earthing and aluminium lugs for 4 x 50 sq mm PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
35supplying and making end termination of suitable size for the submain wiring with Copper lugs for 4x10 + 2x6sqmm of PVC insulated copper conductor
36supplying and making end termination of suitable size for the submain wiring with Copper lugs for 4x16+ 2x6sqmm of PVC insulated copper conductor
37Material testing lab architecture
38MCB
39Supplying and fixing 40 to 63A rating, Three pole (Three phase ) 415 Volts, 10kA, \"C\" curve, miniature circuit breaker suitable for inductive load of triple pole in the existing MCB DB complete with connections, testing and commissioning etc as required.
40Supplying and fixing 63A rating, Four pole, Three phase, 415 Volts, 10kA, \"C\" curve, miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc as required.
41Wiringforcircuit/submainwiringalongwithearthwirewiththe followingsizesofFRLSPVCinsulatedcopper conductor,single corecableinsurface/recessedmediumclassPVCconduitas required.
424 X 16 sq. mm + 2 X 6 sq. mm earth wire
434 X 4 sq. mm + 2 X 4 sq. mm earth wire
44End termination
45Supplying and making end termination of suitable size for the submain wiringwith Copper lugs for 4x16 + 2x6sqmm of PVC insulated copper conductor
46Supplying and fixing followingrating, four pole, (threephase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existingMCBDB complete with connections, testing and commissioning etc. as required.
4763A
48Supplyingand fixingof following ways surface/ recessmounting, vertical type, 415 V, TPN MOB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MOB TPDB is normally used where 3 phase outlets are required.)
498 way (8 + 24), Double door
50Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required.
51Triple pole
52Single pole
53SupplyinganddrawingfollowingsizesofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required.
543 x 2.5 sq. mm
55Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
5620 mm
57Supplying and fixing FP sheet steel enclosure on surface/ recess alongwith 16/25/32 A 415 V\"C\"curveFPMCBcomplete with connections, testing and commissioning etc. as required.
58Supplying and fixing suitable size GI box withmodular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
59Supplying and fixing single pole blanking plate in the existing MOB DB complete etc. as required.
60UG CABLE FOR NAME BOARD
61Supplying of one number 2C x 6 Sq.mm size Aluminium conductor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required.
62Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 2 C x 6 sq.mm in the existing DWC HDPE pipe/ Metal pipe as required.
63Supplying and laying of 63 mm dia (OD-63 mm & ID-51 mm nominal) DWC HDPE pipe ISI markedalong with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
64Supply and layingof3 inch 80 NB GI pipe (medium class B)on ground with all accessories like socket, bend, couplerswith fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., and making good the damages of road with concrete mixture of 1 : 2 : 4 including watering & ramming etc. as required.
65Supplying and fixing 6-32 A rating, 240/415 V, \"C\" curve miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB, complete with connections, testing and commissioning etc. as required.
66Single pole
67Supplying and fixing following rating, double pole, (single phase and neutral), 240 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required.
6825A
69Supplying and drawing 3 numbers 2.5 sq mm FRLS PVC insulated copper conductor single core cable (Red, Black & Green) in existing surface / recessed PVC conduit as required.
70Supplying and fixing of 20mm size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
71Supply and making end termination with brass compression gland and aluminium legs for 2 C x 6 sq.mm (19 mm) size of XLPE insulated PVC sheathed armoured aluminium cable as required.spacing not exeed 50 cm etc. as required.
72Supply and laying of one number of 14 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required.
73Supplying and fixing 4 pole MCB metal enclosure on surface / recess, complete with earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required.
74Supplyingand fixing of weather proof outdoor junction box for outdoor installation of size 205mm x 255mm x112mm with knockouts for cable entry including dinbar, suitable connectors for connecting Al cable to copper cable of suitable size, provision for fixing two number of double pole MCB, weather proof gourmets,glands,clamps,screws of required length fastners connections for surface/ recess fixing onexisting tubular pole etc. as required(clip type)Hensel IP 69 KF 2525G made or Equivalent.
75Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Upto 35 sq. mm (clamped with 1mm thick saddle) size on wall surface/pipe as required.
76Health Centre
77Supplyinganddrawing3 x 2.5 sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required.
78Supplyinganddrawing 3 x 4sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required.
79Supplyinganddrawing 3 x 6sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required.
80Wiring for circuit/ submain wiring alongwith earth wire with the 4 x16 sq.mm + 2 x 6 sq.mmof FRLS PVC insulated copper conductor, single core cable in surface/ recesssed medium class PVC conduit as required.
81Supplying and fixing of 20 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
82Supplying and fixing of 25 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
83Supplying and fixing of 32 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
84Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular switch socket outlet and 15/16A modular switch ,connections etc. as required.
85Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of Single pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required.
86Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of Double pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required.
87Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of Triple pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required.
88Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of Triple pole and neutral intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required.
89Supplying and fixing 4 pole MCB metal enclosure on surface / recess, complete with earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required.
90Supplying and fixing 25A rating, double pole, (single phase and neutral), 240 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required.
91Supplying and fixing 63A rating, Four pole, (Three phase and neutral), 415 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required.
92Supplyingand fixingsingle pole blanking plate in the existing MCB SBcomplete etc.as required.)
93Supplying of one number 3.5 C x 70 Sq.mm size Aluminium conductor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required.
94Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of above 35 sq. mm Upto 95 sq. mm (clamped with 1mm thick saddle) size on wall surface/pipe as required.
95Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required.
96Supply and making end termination with brass compression gland and aluminium legs for 3.5 C x 70sq.mm (32 mm) size of XLPE insulated PVC sheathed armoured aluminium cable as required.spacing not exeed 50 cm etc. as required.
97Supplying and fixing 3 phase 8 way(4+24) , double door, vertical type three pole and neutral ,sheet steel,MCB distribution board,415 V on suface/recess mounting, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB etc)
98Supplying and fixing 63 A rating, 415 V, 10kA, \"C\" curve miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc. as required.
99Supplying and fixing 12 way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
100Providing and fixing 125 A, 36 KA, FPMCCB rating and breaking capacity and pole MCCB with thermomagneticreleaseand terminal spreaders in existingcubicle panel board including drilling holes in cubicle panel,making connections ,etc.as required.
101Supplying and fixing 63 A rating, 415 V, 10kA, \"C\" curve miniature circuit breaker suitable for inductive load of three pole in the existing MCB DB complete with connections, testing and commissioning etc. as required.
102Charges for removing the old wall mounted DB\"s, making good the damages of the wall/ floor including painting, dismantle the DB and other accessories without any damage and conveyance of the material to the godown etc, as required.
103Supplying and making end termination of suitable size for the submain wiring with suitable lugs for 4 x 16 +2 x 6 sqmm of PVC insulated copper conductor.
104Supplying and fixing 20/25 A modular DP switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
105Supplying and fixing 3 pin 25 A modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
106Supplying and fixing 1/2 module, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
107Supplying and fixing 3 phase 6 way , double door, suface/recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing MCCB as incomer and TP MCB as out going, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB etc)
108Charges for cleaning and spray painting the existing Panel board of 180 x 95 x 40 or nearest size withtwo coats of suitable colour (Grey) paint, over a coat of primer in installed position and marking the identification of switches with white paint etc, as required
109Fabrication & fixing of 123 x 93 cm panel board Sheet made from 2 mm thick MS sheet,powder coated in suitable colour over a coat of primer, providing rubber beadings and suitable size hinches, Nuts & Bolts for fixing on the existing panel board etc. as required.
110Fabrication & fixing of 94 x 42 cm panel board Sheet made from 2 mm thick MS sheet,powder coated in suitable colour over a coat of primer, providing rubber beadings and suitable size hinches, Nuts & Bolts for fixing on the existing panel board etc. as required.

AI Tender Summary

OUR REF NO 50743672
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 9.01 Lakhs
LAST DATE 09-09-2025
Authority
Authority Name National Institute Of Technology
Work Description Tender For Combined Electrical Works At Various Location In Nitc; 1 Three Phase ECED 2 Wiring for circuit/ submain wiring alongwith4 x 10 sq mm + 2 x 6 sq mm earth wireFRLS PVC insulated copper conductor, single core cable in surface/ recessed pvc conduit as required. 3 Wiring for circuit/ submain wiring alongwith 4 x 16 sq mm + 2 x 6 sq mm earth wireof FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 Supplying and drawing 3 x 2.5 sq mm FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. 5 Supplying and fixing of 20 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required 6 Supplying and fixing of 25 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required 7 Supplying and fixing 15/16 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc.as required 8 Supplying and fixing6 pin 15/16 A modular socket ( 3 MD type ) on the existing modular plate & switch box including connections but excluding modular plate etc.as required 9 Supplying and fixing 4 module (125 mm X 75 mm) GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 10 Supplying and fixing 8 module (125 mm X 125 mm) GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 11 Providing and fixing 100 A , 4P MCCB, 16 KA breaking capacity and 4 pole MCCB with thermomagnetic release and terminal spreaders in existing MCCB DB , making conection as required. 12 Supplying and fixing 8 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar. interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 13 Supplying and fixing 3 phase 4 way (8+12) double door, suface/recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing MCCB as incomer and TP MCB as out going, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB) 14 Supplying and fixing 6 way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 15 Supplying and fixing of 4 ways (8+12) , Double door. surface/ recess mounting. vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 16 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 17 Supplying and fixing32 A rating Triple pole , 415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. 18 Supplying and fixing32 A rating 4 pole , 415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. 19 supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required 20 Supplying and fixing 40 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required. 21 Supplying and fixing 63 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required. 22 Supplying and fixing 40 Arating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc, as required. 23 Supplying and fixing 63A , Four pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 24 Supplying and fixing 63A , Triple pole, 415 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc.. 25 Supplying and fixing 40 A , Four pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 26 Supplying and fixing 40A , three pole, 430 V, C curve Miniature circuit breaker (MCB)inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 27 Supply of 4 x 50 Sq.mm PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988 28 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement, watering pipe of 2.7 metre long etc.with charcoal/coke and salt as required. 29 Supplying and laying 25mm x 3mm strip at 0.05 metre below ground as earth electrode, including connection/ terminating with SS nut,bolt,spring washer , double plate washer etc.as required ( jionting shall done by overlapping and with 2 set GI nut bolt and washer spaced 50mm) 30 Providing and fixing 25 mm X 6 mm G.Istrip on surface or in recess for connections etc. as required. 31 Supply 60kg of earthing compound (EXCEL compound or equivalent) etc. as required. 32 Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required. 33 Laying and fixing of Above 35 sq mm and upto 95 sq mm (clamped with 25 x 3 mm MS flat clamp) PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as required. 34 Supplying and making end termination with brass compression gland providing sutable size gland earthing and aluminium lugs for 4 x 50 sq mm PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 35 supplying and making end termination of suitable size for the submain wiring with Copper lugs for 4x10 + 2x6sqmm of PVC insulated copper conductor 36 supplying and making end termination of suitable size for the submain wiring with Copper lugs for 4x16+ 2x6sqmm of PVC insulated copper conductor 37 Material testing lab architecture 38 MCB 39 Supplying and fixing 40 to 63A rating, Three pole (Three phase ) 415 Volts, 10kA, C curve, miniature circuit breaker suitable for inductive load of triple pole in the existing MCB DB complete with connections, testing and commissioning etc as required. 40 Supplying and fixing 63A rating, Four pole, Three phase, 415 Volts, 10kA, C curve, miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc as required. 41 Wiringforcircuit/submainwiringalongwithearthwirewiththe followingsizesofFRLSPVCinsulatedcopper conductor,single corecableinsurface/recessedmediumclassPVCconduitas required. 42 4 X 16 sq. mm + 2 X 6 sq. mm earth wire 43 4 X 4 sq. mm + 2 X 4 sq. mm earth wire 44 End termination 45 Supplying and making end termination of suitable size for the submain wiringwith Copper lugs for 4x16 + 2x6sqmm of PVC insulated copper conductor 46 Supplying and fixing followingrating, four pole, (threephase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existingMCBDB complete with connections, testing and commissioning etc. as required. 47 63A 48 Supplyingand fixingof following ways surface/ recessmounting, vertical type, 415 V, TPN MOB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MOB TPDB is normally used where 3 phase outlets are required.) 49 8 way (8 + 24), Double door 50 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required. 51 Triple pole 52 Single pole 53 SupplyinganddrawingfollowingsizesofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 54 3 x 2.5 sq. mm 55 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 56 20 mm 57 Supplying and fixing FP sheet steel enclosure on surface/ recess alongwith 16/25/32 A 415 VCcurveFPMCBcomplete with connections, testing and commissioning etc. as required. 58 Supplying and fixing suitable size GI box withmodular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. 59 Supplying and fixing single pole blanking plate in the existing MOB DB complete etc. as required. 60 UG CABLE FOR NAME BOARD 61 Supplying of one number 2C x 6 Sq.mm size Aluminium conductor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required. 62 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 2 C x 6 sq.mm in the existing DWC HDPE pipe/ Metal pipe as required. 63 Supplying and laying of 63 mm dia (OD-63 mm & ID-51 mm nominal) DWC HDPE pipe ISI markedalong with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 64 Supply and layingof3 inch 80 NB GI pipe (medium class B)on ground with all accessories like socket, bend, couplerswith fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., and making good the damages of road with concrete mixture of 1 : 2 : 4 including watering & ramming etc. as required. 65 Supplying and fixing 6-32 A rating, 240/415 V, C curve miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB, complete with connections, testing and commissioning etc. as required. 66 Single pole 67 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 68 25A 69 Supplying and drawing 3 numbers 2.5 sq mm FRLS PVC insulated copper conductor single core cable (Red, Black & Green) in existing surface / recessed PVC conduit as required. 70 Supplying and fixing of 20mm size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 71 Supply and making end termination with brass compression gland and aluminium legs for 2 C x 6 sq.mm (19 mm) size of XLPE insulated PVC sheathed armoured aluminium cable as required.spacing not exeed 50 cm etc. as required. 72 Supply and laying of one number of 14 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required. 73 Supplying and fixing 4 pole MCB metal enclosure on surface / recess, complete with earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required. 74 Supplyingand fixing of weather proof outdoor junction box for outdoor installation of size 205mm x 255mm x112mm with knockouts for cable entry including dinbar, suitable connectors for connecting Al cable to copper cable of suitable size, provision for fixing two number of double pole MCB, weather proof gourmets,glands,clamps,screws of required length fastners connections for surface/ recess fixing onexisting tubular pole etc. as required(clip type)Hensel IP 69 KF 2525G made or Equivalent. 75 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Upto 35 sq. mm (clamped with 1mm thick saddle) size on wall surface/pipe as required. 76 Health Centre 77 Supplyinganddrawing3 x 2.5 sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 78 Supplyinganddrawing 3 x 4sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 79 Supplyinganddrawing 3 x 6sq. mm ofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. 80 Wiring for circuit/ submain wiring alongwith earth wire with the 4 x16 sq.mm + 2 x 6 sq.mmof FRLS PVC insulated copper conductor, single core cable in surface/ recesssed medium class PVC conduit as required. 81 Supplying and fixing of 20 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 82 Supplying and fixing of 25 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 83 Supplying and fixing of 32 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 84 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular switch socket outlet and 15/16A modular switch ,connections etc. as required. 85 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Single pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 86 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Double pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 87 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Triple pole intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 88 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of Triple pole and neutral intheexisting MCBDBcompletewithconnections,testingand commissioning etc. as required. 89 Supplying and fixing 4 pole MCB metal enclosure on surface / recess, complete with earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required. 90 Supplying and fixing 25A rating, double pole, (single phase and neutral), 240 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 91 Supplying and fixing 63A rating, Four pole, (Three phase and neutral), 415 V,residual current circuit breaker (RCCB),having a sensitivity current 30mA inthe existingMCBDBcomplete with connections, testing and commissioning etc. as required. 92 Supplyingand fixingsingle pole blanking plate in the existing MCB SBcomplete etc.as required.) 93 Supplying of one number 3.5 C x 70 Sq.mm size Aluminium conductor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required. 94 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of above 35 sq. mm Upto 95 sq. mm (clamped with 1mm thick saddle) size on wall surface/pipe as required. 95 Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required. 96 Supply and making end termination with brass compression gland and aluminium legs for 3.5 C x 70sq.mm (32 mm) size of XLPE insulated PVC sheathed armoured aluminium cable as required.spacing not exeed 50 cm etc. as required. 97 Supplying and fixing 3 phase 8 way(4+24) , double door, vertical type three pole and neutral ,sheet steel,MCB distribution board,415 V on suface/recess mounting, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB etc) 98 Supplying and fixing 63 A rating, 415 V, 10kA, C curve miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. 99 Supplying and fixing 12 way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 100 Providing and fixing 125 A, 36 KA, FPMCCB rating and breaking capacity and pole MCCB with thermomagneticreleaseand terminal spreaders in existingcubicle panel board including drilling holes in cubicle panel,making connections ,etc.as required. 101 Supplying and fixing 63 A rating, 415 V, 10kA, C curve miniature circuit breaker suitable for inductive load of three pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. 102 Charges for removing the old wall mounted DBs, making good the damages of the wall/ floor including painting, dismantle the DB and other accessories without any damage and conveyance of the material to the godown etc, as required. 103 Supplying and making end termination of suitable size for the submain wiring with suitable lugs for 4 x 16 +2 x 6 sqmm of PVC insulated copper conductor. 104 Supplying and fixing 20/25 A modular DP switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 105 Supplying and fixing 3 pin 25 A modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 106 Supplying and fixing 1/2 module, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 107 Supplying and fixing 3 phase 6 way , double door, suface/recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing MCCB as incomer and TP MCB as out going, complete with 200 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB etc) 108 Charges for cleaning and spray painting the existing Panel board of 180 x 95 x 40 or nearest size withtwo coats of suitable colour (Grey) paint, over a coat of primer in installed position and marking the identification of switches with white paint etc, as required 109 Fabrication & fixing of 123 x 93 cm panel board Sheet made from 2 mm thick MS sheet,powder coated in suitable colour over a coat of primer, providing rubber beadings and suitable size hinches, Nuts & Bolts for fixing on the existing panel board etc. as required. 110 Fabrication & fixing of 94 x 42 cm panel board Sheet made from 2 mm thick MS sheet,powder coated in suitable colour over a coat of primer, providing rubber beadings and suitable size hinches, Nuts & Bolts for fixing on the existing panel board etc. as required.
Basic Detail
Tender No Engg/EMU/2025-26/Three phase-ECED/Health centreMaterial testing lab/UG cable for Name Board/
Bidding Type Tender
Location
City calicut
State Kerala
Key Dates
Publish Date 19 Aug 2025
Submission Date 09 Sep 2025
Open Date 11 Sep 2025
Finance
Tender Value 9.01 Lakhs
Tender Fee Ref. Documents
EMD 18100
Exemption Available
Document List
217cbd19-147a-452f-9658-f9a649474334.html
BOQ_918595.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 19, 2025
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 09, 2025
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Sep 11, 2025

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

217cbd19-147a-452f-9658-f9a649474334.html

xls

BOQ_918595.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender