| 1 | INSULATION WORKS |
| 2 | Storage Tanks:-HOT INSULATION Providing thermal insulation including supply of all insulating and anciliary material, weather protective covering, consumables and other necessary materials, testing of the material as required including transportation of the materials towork sites, applying insulation on surfaces as specified, including all preparatory works thereon, all binding, tying, lacing, stitching and/or otherwise securing, providing vapour barrier, finishing with plain/corrugated sheet cladding or as specified providing bolts, rivets, self tapping screws wherever specified, providing inspection windows etc., providing necessary scaffolding, all tools and tackles, equipment, apparatus etc., labour and supervision and completing the work in all respect at all heights as per drawings, specifications and instructions of Engineer-in-Charge. (Applicable Specification EIL 6-44-0002).(The mentioned thickness in Insulation Line List is based on standards, Sub contractor to validate the thickness standard calculations and design the same as per requirement. The validations & calculations should be submitted and approval needs to be obtained by M/s B and R/ HPCL.) |
| 3 | Tank No: -01,02,03 (Dia-10M x HT-15M)-03 Nos Tanks. For Shell of vertical storgae tank.Surface Material : CS ; Operating Temp. 170 Degto 300 Deg.Insulation Material : Rockwool : Insulation Thickness : 75MMAluminium cladding 0.71 mm (22 SWG) corrugated sheet & The profile of corrugated sheet shall be 32mm 5mm.It includes shell manway, nozzles, agitator, wind girder, curb angle and other attachement for shell. |
| 4 | Tank No: -01,02,03 (Dia-10M x HT-15M) For tank Roofs.Surface Material : CS ; Operating Temp. 170 Degto 300 Deg.Insulation Material : Rockwool; Insulation Thickness : 75MMAluminium cladding 1.22 mm (18 SWG) Flat sheet It includes Roof manway, nozzles, other attachement for roof. |
| 5 | For Electrical Heat Tracing Piping :Surface Material : CS ; Operating Temp. 170 Degto 300 Deg.Insulation for IE consists of inner layer of Rockwool and outer layer of PUF / PIC. The thicknesses have been specified as THK(I) and THK(O) for inner and outer layers respectively.suitable aluminium moisture barrier to be provided inbetween rockwool and PUF.Providing thermal insulation including supply of all insulating and anciliary material, Vapour barrier, weather protective covering, consumables and other necessary materials, testing of the material as required including transportation of the materials to work sites, applying insulation on surfaces as specified, including all preparatory works thereon, all binding, tying, lacing, stitching and/or otherwise securing, providing vapour barrier, finishing with plain sheet cladding or as specified providing bolts, rivets, self tapping screws wherever specified, providing inspection windows etc., and also providing necessary scaffolding to electrical heat tracing works , all tools and tackles, equipment, apparatus etc., labour and supervision and completing the work in all respect at all heights as per drawings, specifications and instructions of Engineer-in-Charge. (Applicable Specification EIL 6-44-0002).(The mentioned thickness in Insulation Line List is based on standards, Sub contractor to validate the thickness standard calculations and design the same as per requirement. The validations & calculations should be submitted and approval needs to be obtained by M/s B and R/ HPCL.) |
| 6 | Pipes NB 0.75 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 7 | Pipes NB 2 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 8 | Pipes NB 3 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 9 | Pipes NB 4 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 10 | Pipes NB 6 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 11 | Pipes NB 8 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 12 | Valve fixing NB 0.75 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 13 | Valve fixing NB 2 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 14 | Valve fixing NB 3 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 15 | Valve fixing NB 4 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 16 | Valve fixing NB 6 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 17 | Valve fixing NB 8 Inches;Thick(I) 75mm and Thick(O) 25mm |
| 18 | Piping Surface Material : CS & AS ; Operating Temp. 170 Degto 300 Deg.Insulation Material : Rockwool Hot Insulation: Insulation type IH: Providing thermal insulation including supply of all insulating and anciliary material, Vapour barrier, weather protective covering, consumables and other necessary materials, testing of the material as required including transportation of the materials to work sites, applying insulation on surfaces as specified, including all preparatory works thereon, all binding, tying, lacing, stitching and/or otherwise securing, providing vapour barrier, finishing with plain sheet cladding or as specified providing bolts, rivets, self tapping screws wherever specified, providing inspection windows etc., providing necessary scaffolding, all tools and tackles, equipment, apparatus etc., labour and supervision and completing the work in all respect at all heights as per drawings, specifications and instructions of Engineer-in-Charge. (Applicable Specification EIL 6-44-0002). (The mentioned thickness in Insulation Line List is based on standards, Sub contractor to validate the thickness standard calculations and design the same as per requirement. The validations & calculations should be submitted and approval needs to be obtained by M/s B and R/ HPCL.) |
| 19 | Pipes NB 0.75 Inches;Thick 25mm |
| 20 | Pipes NB 0.75 Inches;Thick 75mm |
| 21 | Pipes NB 1 Inches;Thick 25mm |
| 22 | Pipes NB 2 Inches;Thick 50mm |
| 23 | Pipes NB 4 Inches;Thick 75mm |
| 24 | Pipes NB 4 Inches;Thick 90mm |
| 25 | Pipes NB 6 Inches;Thick 40mm |
| 26 | Valve fixing NB 0.75 Inches;Thick 25mm |
| 27 | Valve fixing NB 0.75 Inches;Thick 75mm |
| 28 | Valve fixing NB 1 Inches;Thick 25mm |
| 29 | Valve fixing NB 2 Inches;Thick 50mm |
| 30 | Valve fixing NB 4 Inches;Thick 75mm |
| 31 | Valve fixing NB 4 Inches;Thick 90mm |
| 32 | Valve fixing NB 6 Inches;Thick 40mm |
| 33 | Heat Exchanger, Pump, Shear Mixer:HOT INSULATION Providing thermal insulation including supply of all insulating and anciliary material, weather protective covering, consumables and other necessary materials, testing of the material as required including transportation of the materials towork sites, applying insulation on surfaces as specified, including all preparatory works thereon, all binding, tying, lacing, stitching and/or otherwise securing, providing vapour barrier, finishing with plain sheet cladding or as specified providing bolts, rivets, self tapping screws wherever specified, providing inspection windows etc., providing necessary scaffolding, all tools and tackles, equipment, apparatus etc., labour and supervision and completing the work in all respect at all heights as per drawings, specifications and instructions of Engineer-in-Charge. (Applicable Specification EIL 6-44-0002).(The mentioned thickness in Insulation Line List is based on standards, Sub contractor to validate the thickness standard calculations and design the same as per requirement. The validations & calculations should be submitted and approval needs to be obtained by M/s B and R/ HPCL.) |
| 34 | Heat Exchanger Approx- Dia 2M x Lg 7MSurface Material : CS ; Operating Temp. 170 Degto 385 Deg.Insulation Material : RockwoolInsulation Thickness : 90MMAluminium cladding 0.71 mm (22 SWG) Flat sheet.It includes shell manway, nozzles, and other attachement for shell. |
| 35 | PumpsSurface Material : CS ; Operating Temp. 170 Degto 300 Deg.Insulation Material : Rockwool +PUF/PICInsulation Thickness :Thick(I) 75mm and Thick(O) 25mm |
| 36 | Shear MixerSurface Material : CS ; Operating Temp. 170 Degto 300 Deg.Insulation Material : Rockwool +PUF/PICInsulation Thickness :Thick(I) 75mm and Thick(O) 25mm |
| 37 | \"NOTE:-THE ABOVE RATE SHALL BE INCLUSIVE OF ALL TAXES & DUTIES, ROYALTIES, CESS, FEE, ENVIORMENTAL & POLLUTION, FITNESS & SAFETY CLEARANCE CHARGES (IF ANY), OR ANY OTHER INCIDENTAL CHARGES ETC BUT EXCLUDING GST.\" |