| 1 | Schedule \"A\" |
| 2 | S&F in repair MCCB 4 pole, 415 V,63 Amp with breaking capacity 16 KA complete all as specified anddirected. |
| 3 | S&F in repair MCCB 4 pole,415 V, 100 Amp with breaking capacity 16 KA complete all as specified anddirected. |
| 4 | S&F in repair MCCB 4 pole, 415 V,125 Amp with breaking capacity16 KA complete all as specified anddirected. |
| 5 | S&F in repair MCCB 4 pole,415 V,160 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 6 | S&F in repair MCCB 4 pole, 415 V,200 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 7 | S&F in repair MCCB 4 pole, 415 V,250 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 8 | S&F in repair MCCB 4 pole, 415 V,400 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 9 | S&F in repair MCCB 4 pole, 415 V,630 Amp with breaking capacity 36 KA complete all as specified anddirected. |
| 10 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, poles struts, laying of cables/pipes, etc., not exceeding 10 Sqm on plan and not exceeding 1.5m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 11 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm as in soils complete all as specified and as directed. |
| 12 | Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point as in soils complete all as specified and as directed. |
| 13 | Material and labour for cuttingof existing road/ hard standing etc of any description of surface and excavation in trenches 30cm wide and 60cm depth for laying of UG electric cableincluding making good the disturbed road/hard standing by providing PCC (1:3:6) type C1to match with existing surfacecomplete all as specified and directed.Note:- The rate includes returning, filling, watering and ramming in layers and making good the surface with PCC (1:3:6) as the existing after laying of electic cables |
| 14 | Supply and spread sand in trenches as sand cushioning to underground cable for protection with dry fine river sand and provide required cover after punning down 18CM will be measured and paid complete all as specified and directed.(Note: Thickness of sand cushion after punning down will be measured and paid.) |
| 15 | Supply and laying wellburntsub class‘B’ bricks(designated 75) locally available best quality, laid dryin trenches forprotection of underground cable complete all as specified and directed. |
| 16 | Supply and laying of 40 mm bore GI tube lightgrade as in cable protection pipe including all fittings and including taking down / taking out from trench of cable complete all as specified and directed. |
| 17 | Supply, laying, Jointing connecting in replacement of LTUG cable XLPEinsulated,PVC bedded galvanised steel strip or wirearmoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 16 sqmm 4 core laid in trenches/ on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed. |
| 18 | Supply, laying, Jointing connecting in replacement of LTUG cable XLPEinsulated,PVC bedded galvanised steel strip or wirearmoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25 sqmm 4 core laid in trenches/ on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed. |
| 19 | Supply, laying, Jointing connecting in replacement of LTUG cable XLPEinsulated,PVC bedded galvanised steel strip or wirearmoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 35 sqmm 4 core laid in trenches/ on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed. |
| 20 | Supply, laying, Jointing connecting in replacement of LTUG cable XLPEinsulated,PVC bedded galvanised steel strip or wirearmoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 50 sqmm 3.5 core laid in trenches/ on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed. |
| 21 | M&L for cleaning, scrapping re-painting of LT panel board with two coat of synthetic eanamel paint complete all as specified and directed. |
| 22 | M&L for repair of indoor/outdoor type feeder pillar box any type door hinge broken, MS work structure damage, locking handle, shutter not proper closed, rubber gasket, any type welding works required complete all as specified and directed. |
| 23 | Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanized iron 25x4 mm strip as earthing lead by means of galvanized iron or steel bolts nuts check nuts and washers and other end connected with earthing testing point including providing suitable testing points as directed including funnel, watering pipe of 20mm bore, light grade galvanized iron pipe, wire mesh charcoal of coal dust and common salt in alternative layer all around the earth electrode compacted thickness 15cm with concrete pit in PCC 1:3:6 type C1 50mm thick pre cast RCC 1:2:4 type B1 cover slab set in CM (1:4) re-enforcement with 8mm dia deformed bars @ 15cm C/C and suitable handle of 10mm dia MS round bars, including earth work in hard/dense soil as required complete all as shown in electrical plate No 3 of MES Schedule Part I and testing on completion all as specified and as directed. (Note: GI Earthing lead upto 7.5m in length is deemed to be included in the unit rate. The lead required beyond 7.5m shall be measured and paid for separately) |
| 24 | Supply & Fix in replacement digital 0 to 200 Amp meter complete all as specified and directed. |
| 25 | Supply & Fix in replacement digital 0 to 500 Volt meter complete all as specified and directed. |
| 26 | Supply & Fix in replacement CT coil 250/5 Amps complete all as specified and directed. |
| 27 | Supply & Fix in replacementphase indicator lamp (R,Y,B) complete all as specified and directed. |
| 28 | Supply & Fix in replacement slector switch complete all as specified and directed. |
| 29 | Supply & fix in repair onload change over switchfour pole of cap 100 Amp of frame 2 type, open execution complete all as specified and directed. |
| 30 | Supply & fix in repairload change over switchfour pole of cap 250 Amp of frame 3 type, open execution complete all as specified and directed. |
| 31 | M & L for vegitation of grass cutting all around surrounding and inside area LT panels , feeder pillars & transfromer at MES installations will be provided sufficient man power with tools by the contractor whereever is required as directed (a) Contractor will arrange the manpower for cleaning the sub stn as and when needed be deemed to be included in the rate quoted(b) Contractor will arrange own conveyance and communication system like moble etc to maintian/cleaning the MES installations at Leimakhong Mil Stn. |
| 32 | S&F in repair of aluminium lugs of size 16 sqmm fixed with MCCBs/busbar in LT Panels /feeder pillars panel incl nuts , bolts & washer complete all as specified and directed |
| 33 | S&Fin repair of aluminium lugs of size 25 sqmm fixed with MCCBs/busbar in LT Panels /feeder pillars panel incl nuts , bolts & washer complete all as specified and directed |
| 34 | S&Fin repair of aluminium lugs of size 35 sqmm fixed with MCCBs/busbar in LT Panels /feeder pillars incl nuts , bolts & washer complete all as specified and directed |
| 35 | S&Fin repair of aluminium lugs of size 50 sqmm fixed with MCCBs/busbar in LT Panels /feeder pillars panel incl nuts , bolts & washer complete all as specified and directed |
| 36 | S&Fin repair of aluminium lugs of size 70 sqmm fixed with MCCBs/busbar in LT Panels /feeder pillars panel incl nuts , bolts & washer complete all as specified and directed |