| 1 | GENERAL SUMMARYNote:- Schedule\"A\" Part-I to III are prepriced by MES under Ser No. 2.00 to 4.00. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only |
| 2 | Lumpsum price worked out by the contractor for \"BUILDINGS / STRUCTURES\" as listed in Schedule \"A\" Part-I, on serial page No.20 |
| 3 | Lumpsum price worked out by the contractor for \"SEWAGE DISPOSAL\" as listed in Schedule \"A\" Part-II, on serial page No.22 |
| 4 | Lumpsum price worked out by the contractor for \"ELECTRIFICATION AND WATER SUPPLY\" as listed in Schedule \"A\" Part-III, on serial page No.23 |
| 5 | SCHEDULE \"A\" PART-IV (MISCELLANEOUS ITEMS- To be quoted by Contractor) |
| 6 | Material and labour for point wiring with 1100 Volts, FRLSH grade, 1.5 Sq.mm, Single core, PVC Insulated, unsheathed, multistranded copper conductor cable, confirming to IS - 694 drawn through and including medium grade PVC conduit, 20 mm dia including all accessories concealed in walls / roofs / floors / ceiling etc. and pressed GI modular box as per OEM for switch/ sockets and suitable size as required at site and suitable for modular brackets for fixing modular switches, fittings, regulators etc including 1100 Volts, FRLSH Grade, 1.5 Sq.mm, single sore, PVC insulated, unsheathed, multistranded copper conductor cable as earth continuity conductor with colour coding and connecting to earth dolly complete all as specified. for the following Note: (i) Cost of modular GI box and modular outer cover plate shall be included in the quoted rate. (ii) Blank plate wherever required is deemed to be included in the quoted rate. |
| 7 | (a) One light/fan point controlled by one, one-way switch |
| 8 | (a) One socket 05 Amps on same board |
| 9 | All as per item No. 6 described here - in - before but for 3/6 pin 5 Amps socket on independent board |
| 10 | All as per item No. 6 described here - in - before but for 3/6 pin 15 Amps socket on independent board with 2.5 Sqmm copper cable and provision of 2.5 Sqmm FRLSH PVC insulated stranded copper conductor cable for earth continuity conductor connected to common earth dolly connecting up to fittings complete. |
| 11 | Supply and fix ceiling fan 1200 mm sweep 220V, 5 star rated, BLDC fan without remote and regulator including suitable fixing arrangement complete all as specified and directed. |
| 12 | Supply and fix Exhaust fan Heavy duty 300 mm sweep, metal body 900 RPM, 230 Volts, 50 Hz with louvers, including cutting and making hole in wall for fixing complete all as specified and directed. |
| 13 | Material and labour for sub main wiring with two runs of single core 4.0 sqmm PVC insulated, unsheathedmultistranded copper conductor 1100 volts FRLS cable, with one run of 4.0 sqmmsingle core PVC insulated unsheathedmultistranded copper conductor 1100 volts FRLS cableas earth continuity conductor and one run ofsuitable size non metallic rigid PVC conduit and conduit accessories fixed on concealed on wall/roofincluding cutting chases etc complete all as specified and as directed.Note :(i) Two runs of main cable , one run of earth continuity conductor cable and one run of PVC conduit will be measured as one unit for payment purpose. |
| 14 | Supply, installation and testing of Split Air Conditioner of 2.0 TR capacity inverter type 5 star rated with indoor and outdoor units (copper condenser coil, copper cooling coil and evaporator, smart AC with hybrid jet inverter technology including copper pipe which has blue fin technology condenser coils and fins, including required length of copper tubing and cables for connecting indoor and outdoor units) complete with cordless remote control unit, with inverter rotary compressor with inbuilt air ioniser and dual PM 2.5 HD filter with anti viral technology for better indoor air quality complete including inlet and outlet copper pipe and all accessories required as per site requirment complete all as specified and directed by Engineer-in-Charge.Note: Rate quoted is deemed to be inclusive of the following:- (i) Drain Pipe UPVC with the insulation from indoor unit to outside and is to be fixed with necessary clamps.(ii) Sealing the hole from outside, after installation, with white cement and painting to match with existing finishes.(iii) Pressure testing, cooling performance check and product demonstration.(iv) 4 core cable of any required length for connecting indoor and outdoor unit.(v) During installation the copper pipe to be in vaccum condition.(vi) Installation to be done by authorised dealer only. |
| 15 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4 KVA complete all as specified and directed by Engineer-in-Charge. |
| 16 | Supply and fix LED white light batten 20 watt with extruded aluminium housing for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver Warm white box type with all accessories internally pre wired and including connecting up with twin / three core flexible copper conductor cable with suitable size from ceiling rose to fitting with PVC round block 02 nos for mounting complete all as specified and as directed. |
| 17 | Supply and fix LED mirror light fiiting surface mounted type 2 feet x 10W LED white light with all accessories internally pre wired and including connecting up with twin / three core flexible copper conductor cable with suitable size from ceiling rose to fittingwith PVC round block 02 nos for mounting etc, complete all as specified and as directed. |
| 18 | Supply and fixing recess mounting flat panel 36 Watt LED fitting 2x2 feet with flat panel to enhance the white powder coated CRCA housing complete with full window acrylic diffuser & electronic driver, high brightness LEDs etc complete with all accessories intenally prewired and necessary mounting arrangements, complete all as directed by Engineer-in-charge. |
| 19 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade for 25 sqmm 3.5 core size complete all as specified and as directed. Note: Earthwork , excavation, sand cushionuing and cable protection shall be measured and paid seperately. |
| 20 | Spreading and compacting of approved riddled earth in cable ducts / trenches for cable cushion on both top and bottom of cable, including ramming all as specified and directed by Engineer-in-Charge. (Note :- Punned thickness only will be measured) |
| 21 | Material and labour for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by usinggalvanized earth wire4mm diaconnected by means of bolts, nuts, check nuts and washer of galvanized iron or steel, provision of 15 mm dia GI pipe medium grade for protection of GI earth wire and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, MS funnel, wire gauge, 50 mm thick RCC 1:2:4, type B1earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance not exceeding 50 metre, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I |
| 22 | Signature of Contractor |