Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | FIRE ALARM, WET RISER / HYDRANT & SPRINKLER SYSTEM |
| 2 | Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. |
| 3 | 200 mm Dia |
| 4 | 150 mm Dia |
| 5 | 100 mm Dia |
| 6 | 80 mm Dia |
| 7 | 25 mm Dia |
| 8 | Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) |
| 9 | 100 mm Dia |
| 10 | 80 mm Dia |
| 11 | 65 mm Dia |
| 12 | 50 mm Dia |
| 13 | 32 mm Dia |
| 14 | 25 mm Dia |
| 15 | Providing, Fixing,Testing & commissioning of 15 mm Dia quartzoid bulb type Sprinklers of rating 68 degree centigrade with required accessories. |
| 16 | Pendant sprinkler / sprinkler |
| 17 | Supplying, fixing, testing & commission of butterfly valve ofPN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects. |
| 18 | 200 mm dia |
| 19 | 150 mm dia |
| 20 | 100 mm dia |
| 21 | 80 mm dia |
| 22 | Providing, installation, testing and commission of non-return valve offollowing sizes PN-10 as per design standerd IS: 5312 or BS:1868 with companion flanges, bolts, nuts, washers etc. complete in all respects. |
| 23 | 150 mm dia |
| 24 | 100 mm dia |
| 25 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 26 | 30 m |
| 27 | SupplyingInstallationtesting& Commissioningof 25 mm Air Release valve gunmentalhavingrubberballandwith25 mm BSP threaded male inletincluding necessary accessories and connections complete in all respect. |
| 28 | SupplyingInstallationtesting& Commissioningof 25 mm Ball valve PN-1 gunmental as per IS:778 including necessary accessories and connections. |
| 29 | Providing & fixingofWeatherproofstandard fire hosecabinet boxmadeout of 18 gauge MSsheetincludingtwocoatsofpostoffice red paint over one coat of primer with 4 mm, thickglassdooronfrontpainted\"FIRE\"in red luminious paint, The size of thebox should be 750 mm X 600 mm X 250 mm size capable of accommodation a pair of hose with couplingand nozzel. The box should be floor mounted type with railway coach lock arrangementand leverfor openingthe door after breaking the glass complete. |
| 30 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63mm dia male and female couplings duly bound with Gl wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 31 | Stainless Steel |
| 32 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: |
| 33 | Stainless Steel (Grade 304) |
| 34 | (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) |
| 35 | 450 Ipm at 35 m Head |
| 36 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required.. |
| 37 | Providing & fixing of pressure gauge in ranging from 0 to 14 kg per sqmm ISI marked from approved manufacturers complete in all respects. |
| 38 | Supplying fixing ofCast iron body 63 mm dia male instantaneousintelcouplingwith housing cabinet (500X400X400for 2 way and 600X400 for 4 way) cap and chain for fire brigadecorrection conformingto IS:904and makingconnectionwith fire fightingpipe or undergroundwater tank completing the work in all respect as per the directions of the Engineer-in-charge. |
| 39 | Four Way connection |
| 40 | Providing/FixingofCubicaltypefloor mountedFire pump Controlpanel fabricated from16GM.S.sheetdulypowdercoated finish of aproved shade and comprising of:a) One 63 amp. TP+NL M.C.C.B. with rotary handle of beacking capacity 35 KA.b) One Volt meter (0-500V) with selector switch.c) One set including lamps |
| 41 | SupplyingLaying testing & Commissioningof 2 corex 1.5 sq.mmsingle standard copper conductor, PVCinsulatedarmored cable. |
| 42 | Supply and laying of alluminium conductor PVC insulated armoured served sheathed cables 1100 volts grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on side and on top on surface the cable run shall be fied on M.S. clamps etc. of suitable size or as directed by the Engineer-in-charge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 43 | 150 sqmm 3-1/2 core |
| 44 | 95 sqmm 3-1/2 core |
| 45 | 50 sqmm 3-1/2 core |
| 46 | 35 sqmm 3-1/2 core |
| 47 | 16 sqmm 4 core |
| 48 | Supply, Installation, Testing & commissioning of Single/Double sided Signage with 20 mtr. viewing distance with built in LED, High efficiency L80 LED with 50,000 hour life, Usage: Exit Signage cum Emergency light with Function Use either as an emergency luminaire or exit sign, with standalone Testing system, Housing of Polycarbonate, Glow wire test : 850°C, RAL9003, Type of mounting: Wall or ceiling, Operation Mode Non -Maintained or Maintained mode selectable, Connection voltage 230V +/- 5% [220V-240V], compliant with EN standards, with IEC CB test certificate LED, Built in Battery: Ni-Cd, Duration 3 hours, Viewing distance 2+A300m, Dimensions in mm: 270 x 119 x 49. |
| 49 | P&F of Fire man axe made of carbon steel handle insulated with rubber tested to 20,000 Volts. Manufactured as per Indian standard IS:926. |
| 50 | Providing and fixing pressure switch in M.S. pipe line including connection as required |
| 51 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fitting and base support for tank.[Sintex, Electroplast, Star, Lotus or equivalent having valid ISI license]. |
| 52 | Supply and fixing of Single way landing / Hydrant / Yard Hydrant valve 63 mm dia. Gun metal instantanous with female coupling with chain etc. complete. |
| 53 | Single Headed Gunmetal |
| 54 | Surfacedressingofroadwithpainting betweenusing 2.25 kg. of bitumenper sq.mt with 1.65 cum of stone chipping ,13.2 mm nominal size/100 sq.mt of road surface including corolidation. |
| 55 | Supply, Installation, Testing & Commissioning of Electric Driven Main Fire Pump Suitable for auto operation & consisting of following: complete in all respect as required. |
| 56 | Horizontal split Casing type, centrifugal, multistage, pump of cast iron body & bronze impeller with stainless steel shaft Mechanical seal at specified flow of 1620 lpm at 70 Meter head confirming to IS 1520. |
| 57 | Suitable HP squirrel cage induction motor,TEFC synchronous speed 1500 RPM 60 HP (with permissible slip) suitable for operation on 415 volts, 3 phase 50Hz.AC with IP 55 protectiion for enclosure, horizontal foot mounted type with class- \"F\" insulation, conferming to IS-325 |
| 58 | Common base frame fabricated out of M.S channel of suitable size flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. |
| 59 | Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications. |
| 60 | Supply, Installation, Testing & Commissioning of Diesel Engine Driven main fire pump suitable for auto operation & consisting of following: complete in all respect as required. |
| 61 | Horizontal split Casing type,centrifugal, multistage, pump of cast iron body & bronze impeller with stainless steel shaft, Mechanical seal at specified flow of 1620 lpm at 70 meter head confirming to IS 1520. |
| 62 | Suitable HP 1500 RPM, 4 stroke, cold starting type Diesel Engine with Heat Exchanger confirming to relevant BIS & IS Standards, complete with all required accessories/system, fuel oil filter ,lubricant oil pump with filter, 1 set Starting batteries of 180AH capicity each with suitable angle iron stand,engine starting panel havng all the controls meters, gauges, |
| 63 | techo meter,hour meter, starting switch with keys for manual starting, auto starting mechanism, 12/24 volt electric starting equipment, Deisel tank for 8 hrs continuous running for Diesel Engine having minimum capicity of 200 Ltrs. (Tank made out of 3mm thick M.S.Sheet with filling cap, drain cock, diesel indicator duly mounted on M.S.angle) exhaust pipe of minimum 10 mtr. length, duly insulated with 50 mm thick glass wool with 1.0 mm.thick alluminium sheet cladding, exuast reidential silencer,stop solenold for auto stop in the event of fault with audio indications, painting etc. as required. |
| 64 | M.S fabricated Common base frame,flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. |
| 65 | Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications. |
| 66 | Supplying, fixing, testing & commission of Electric Driven Pressurisation Pump (Jockey Pump) suitable for auto operation consisting of following complete in all respect as required. |
| 67 | Horizontal type, centrifugal & suction type, pump of cast iron body & bronze impeller with stainless steel shaft Mechanical seal, gland packing & flow of 180 lpm at 70 Mtr. Head confirming to IS:-1520. |
| 68 | Common base frame fabricated out of M.S channel of suitable able size flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. |
| 69 | Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications. |
| 70 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection classIP 42 as required : |
| 71 | INCOMING630A, 50kA 4 Pole MCCB, Ics=100% lcu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800AmpsOUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 72 | MAIN FIRE PUMP250 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 73 | JOCKEY PUMP125 A, 50kA TPN MCCB, Ics=100% lcu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 74 | DIESEL ENGINE CONTROLControl for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine |
| 75 | SYSTEM CONTROLLERDesigning, Supply, Installation,esting and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 76 | SITC Automatic priming arrangement for all fire pumps including necessary pipe, fitting, water level controller, 1 HP pump, auto starter gate valve NRV\"s etc complete. |
| 77 | Cost of minor repair / repainting or necessary works after installation of fire figting works. |
| 78 | FIRE ALARM SYSTEM & FIRE EXTINGUISHERS |
| 79 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 + 5 % V, 50 hz), |
| 80 | 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 81 | Ten Loop Panel |
| 82 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal (smoke cum heat) detector complete with mounting base complete as required. |
| 83 | Supplying, installation, testing & commissioning of intelligent addressable thermal (heat) detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 84 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 85 | SupplyingInstallationtesting& Commissioningof Intelligent Addressable Manual Call points- double action Break Glass cum pull station suitable for wall/column mounting. |
| 86 | SupplyingInstallationtesting& Commissioningof Intelligent Addressable Hooter cum multi carriar strobe.Unit as per specificationsand customizationof intensity selectionas15,30 , 75 or110cdof strobe unit is possibleby panel.Soundersum strobe willbedrivenbysupervised24 V DCinput and will give 80 db output at 3 m strobe unite willbesynchronized1Hzstrobeflashrate for better evacuation in complete facility. |
| 87 | SupplyingInstallationtesting& CommissioningIntelligent Addressablesingle AddressableControl Relay Module-Form \"C\" contacttype. |
| 88 | SupplyingLaying testing & Commissioningof 2 corex 1.5 sq.mmsingle standard copper conductor, PVCinsulatedarmored cable. |
| 89 | Supply & fixing of CO2 type fire extinguisher,4.5 kg. capacity (ISI Marked IS:2878 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 90 | Supply & fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS:15683 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 91 | Supply & fixing of fire Bucket 4+ with stand |
| 92 | Supply & fixing of Electrode Earthing Complete. |
| 93 | PUMP HOUSE, BORRING & U.G.T. |
| 94 | PUMP HOUSE |
| 95 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 96 | Providing and laying in cement concrete 1:4:8 (1 cement : 4 coarse sand :8 graded Stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 97 | Local Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 km. from the site of work & including watering, dressing etc. Rateinclude cost of all materials, labourand T&P etc. required for proper completion of the work. |
| 98 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 99 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 100 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer\"s standard dilution) |
| 101 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone grit im the proportion of 1:1.5:3 in lintels of doors and windows excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. strength of the concrete shall not beless than M-20. |
| 102 | Same as Item No. 4 but R.C.C. work in slab (M-20). |
| 103 | Same as Item No. 4 but R.C.C. work in beam (M-20). |
| 104 | Same as Item No. 4 but R.C.C. work in foundation (M-20). |
| 105 | Same as Item No. 4 but R.C.C. work in column (M-20). |
| 106 | Class M-150 brick work in 1:6 cement coarse sand (of 2.25 fineness modulus) mortar infoundation & plinth including supply of all materials, labour, tools and plants etc. required for proper completion of the work. |
| 107 | M-150 Brick work in super-structure (1:6 cement coarse sand above plinth level up to floor two level (up to two storeys) includingnecessarycutting and moulding of brick work asrequiredand also including honeycombed brick work in thickness of wall more than 12cms. |
| 108 | Same as in item above but in1:3 cement and coarse sand mortar in superstructure for wall thickness 12 cms & below brick work M-150. |
| 109 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 110 | Providing and laying \"brick coba\" 12mm thicklaid with M-150 class brick bat coba 7.50cm thick with gap of 15mm to eachother,over 20 mm thick base of cement mortar1:4cementand coarse sand mixed with water proofing compound spreading cement slurry mixed with acrelic cement concrete water proofing compound filled gaps of coba & top of coba mortar mixed with water proofing compound in 1:4 cementandcoarsesandmortar finised smooth & |
| 111 | top mashed false square 30 cm x 30 cm and side wall parapet shall be mono tythic plaster wall up to 30 cm higher and junction and corner shall be rounded by brickballastcement and coarse sandmasonany Cobawithtop finised plaster mixed with acetic water proofing compound@ 2%byweight & including s/o all material, labour, T& P etc complete for proper completion of work. |
| 112 | Mild steel or iron work of small sizes and sections such as holding down bolts, hold fast tierods,gratings etc. ( when not included in an over all rates) wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required completion of work fabrication of holes doors, chaukhats nosing. |
| 113 | Providing & fixing of hold fast for chaukhatsof doors and windows. |
| 114 | Providing & fixing of door / windows grill. |
| 115 | Z-Section steel windows |
| 116 | Angle iron door chaukhats 40*40*5 |
| 117 | ISMB 200 SECTION |
| 118 | Supply & fixing of flush doors commercial quality conforming to I.S. 2202 Part 1 (1983) including fixing and adjustment of hinges bolts locks handles springs fitting with necessary screws to be supplied departmentally. (a) 35mm thick |
| 119 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete : 250x16 mm |
| 120 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete : |
| 121 | (a) 250 mm x 10mm |
| 122 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete : 125 mm |
| 123 | P/F FE-500 STEEL work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 124 | Fixing of Door, windows / ventilators chaukhats in position. |
| 125 | (a) Door chaukhats |
| 126 | (b) Window chaukhats |
| 127 | 15 mm cement plaster on rough side of single or half brick wall of mix: 1:4 (1 cement: 4 coarse sand) |
| 128 | 12 mm cement plaster in single coat on fair side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 course sand of 2.25 F.M. |
| 129 | 12 mm cement plaster in single coat on rough side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 course sand |
| 130 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 131 | 18mm thick cement plaster in dado or skirting in 1:2 consisting of one part of cement and 2 parts of approved coarse sand laid in panels, finished with 3mm floating coat of neat cement or cement and marble dust in ratio of 5:1 including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 132 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors 40 mm wide and 4 mm thick. |
| 133 | Painting or varnishing work in small areas or new wood work with one coat upto one square metre of ready mixed priming paint and one coat of approed superior quality ready mixed paint or varnish including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. Paint to be used should fonfirm the ISI no. 103-1950 (M.S. works) |
| 134 | Same as above but wooden painting |
| 135 | Distempering (Two coat) with Dry distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. |
| 136 | Finishing wall with water proof cement paint of approved make and quality on new wood with two coat to give an even shade including supply of all materials, labour, tools and plant etc. required for proper completion of the work. (Three Coat) |
| 137 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with : 4.0 mm thick glass panes |
| 138 | Cost of Internal Electrification works |
| 139 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 140 | Group C |
| 141 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 142 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 143 | Lighting Fixtures (Lights/Fans) : |
| 144 | SITC of 20W LED batten with Microwave motion technology for providing an energy-efficient solution and with aluminum housing & integrated electronic driver complete in all respect. |
| 145 | Miscellaneous Items : |
| 146 | S/F of hexagonal fan box with hexagonal side of approx 80mm in length fabricated from 16SWGM.S. sheet incorporating 10mm dia, M.S. round barduly bent for supporting fan hanger dully painted withred oxide and screwing arrangement with wiring conduit laid in the R.C.C. roof before concreting along with supply of all materials, labour T & P etc., for proper completion of work. |
| 147 | TUBEWELL |
| 148 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level. |
| 149 | All Types of Soil |
| 150 | 350 mm dia |
| 151 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depth below ground level. |
| 152 | Rocky strata including Boulders |
| 153 | 350 mm dia |
| 154 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/plain ended casing pipes of required dia, conforming to IS: 4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in-charge. |
| 155 | 150 mm nominal size dia having minimum wall thickness 5.00 mm |
| 156 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge. |
| 157 | 200 mm nominal size dia |
| 158 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 159 | Around Pipe (3.14*0.15*0.15*120.00) |
| 160 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 161 | (3.14*3.50*3.50*0.30) |
| 162 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \"V\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tube well, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 163 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for bore well of: |
| 164 | 150 mm dia |
| 165 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tube well as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. |
| 166 | 150 mm dia |
| 167 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tube well as per IS:2800 (part I). |
| 168 | 150 mm dia |
| 169 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. |
| 170 | 80 mm dia nominal bore |
| 171 | Supplying and drawing following sizes of FRLS PVC insulatedcopper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 10 x 4 sq. mm |
| 172 | Supplyof Submersibule pump with control panel, support wire etc. complete 7.5 H.P. (KSB / EQ.) |
| 173 | 100 K.L. CAPACITY U.G. TANK |
| 174 | Excavation of foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 175 | From Lvl. 0.00 Mt. to 1.50 mt |
| 176 | From Lvl. 1.5 Mt. to 3.0 mt |
| 177 | From Lvl. 3.0 Mt. to 4.5 mt |
| 178 | Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded Stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 179 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone grit in Slabs excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. strength of the concrete shall not beless than M-25. |
| 180 | As in item abovebut inR.C.C.Raft foundation and footingwithapproved stone ballast. M-25 |
| 181 | As in item abovebut inColumn withapproved stone ballast. M-25 |
| 182 | P/F FE-500 STEEL work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 183 | 12 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 4 Coarse sand |
| 184 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (25 mm thick floor). |
| 185 | Providing and laying water proofing treatment in underground structure by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 186 | Providing M.S. foot rest including fixing with 20x20x10 cm. cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 gradded aggregate of nominal size 20mm ) as per standard design with 20x20mm sq bars. |
| 187 | 560 mm diameter C.I. cover (heavy duty) the weight of the cover to be not less than 108 kg |
| 188 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 189 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 190 | Suspended floors, roofs, landings, balconies and access platform. |
| 191 | ARRANGEMENT OF SIGNAGE IN HOSPITAL FOR SAFE EXIT |
| 192 | Providing & erecting direction & place identification& other fire related informations for emergency retro- reflectorised sign as per IRC-67 made of high intensity grade sheeting. The retro reflective sheeting type-IV shall be tested for 3 year outdoor weathering test in Indian conditions as per IRC 67:2012 & proof of the same in form of government report shall be uploaded while quoting tender vide clause 801.3 fixed over aluminium sheeting, 2mm thick with area exceeding 0.9 sqm. Supproted on a mild steel single angle iron post 75x75x6 mm, 2 nos firmly fixed to the ground by means of property designed foundation with M-15 grade cement concrete 45x45x60 cm below ground level as per approved drawing complete. |
| 193 | RESOURCES TRAINING FOR STAFF & TRAINING MODULES FOR RESCUE OPERATION |
| 194 | GST Extra As per Applicable |