| 1 | II |
| 2 | 132 kV EQUIPMENT |
| 3 | Circuit breaker (3 phase) |
| 4 | 1250 A, 31.5 kA SF 6 CB with support structure, marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short circuit test reports shall be furnished.) (Spring- Spring ) |
| 5 | ISOLATORS (3 phase), withsolid core insulators, marshaling boxes, terminal connectors(Motor Operated) with moving contact of HDEC copper only. |
| 6 | 1250A, 31.5 kA with one earth switch (Double break Isolator) |
| 7 | 1250A, 31.5 kA without earth switch (Double break Isolator) |
| 8 | 1250A, 31.5 kA without earth switch (Double break Isolator) (Tandem arrangement) |
| 9 | Portable discharge rods ( 1 phase) |
| 10 | Current Transformers5 core (1 phase) |
| 11 | 1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2S class,31.5 kA with 120% extended current rating with marshalling boxes, terminal connectors etc. |
| 12 | 8800 pF CVTs (1 phase) with marshalling boxes,terminal connectors etc . |
| 13 | 120 kV Surge arresters SH class-IV ( 1 phase) withmarshalling boxes, terminal connectors etc. |
| 14 | ERECTION HARDWARE (132 kV) |
| 15 | Insulator strings antifog type & hardware, spacers, conductor (S), Bus bar material, galvanised cable trays/Cable rack, bay MB, Clamps, Connectors including, Junction box,PVC pipes for equipment and lighting, all accessories etc. for the following (main bus shall be of quad Moose conductor and transfer bus shall be strung with double Moose conductor) |
| 16 | Line Bay |
| 17 | 132 kV Solid Core, Bus post Insulators for erection hardware |
| 18 | 415 V ACDB (no of feeders shall be asper therequirement of the project) |
| 19 | 250V DCDB (no of feeders shall be asper therequirement of the project) |
| 20 | 48 V DCDB Ext |
| 21 | 132 kV (Duplex Panels) |
| 22 | Control, Relay & Protection Panel for |
| 23 | 132 KV Line control & relay panels with Numerical type of distance protection and Numerical E/F-O/C relays complying IEC 61850 (Edition-2) Protocol with optical fiber ports sufficient DI/DO ports for scheme with additional 6 DI and 6 DO Ports for spare with auto reclose etc. |
| 24 | 132 KV Numerical type line differential protection relay complete with all material and relays comlying to IEC 61850 Protocol with Optical fiber ports sufficient DI/DO fo scheme with additional 6 DI/DO spares. |
| 25 | 132 kV TBC (with A/R) with numerical distance protection relays and earth fault / overcurrent relays complying to IEC 61850 Protocal with optical fiber ports sufficient DI/DO for scheme with additional 6 DI/DO for spare. All indicating meters/ multifunctions meters shall be communicable tpewith 0.5 class accuracy. |
| 26 | Other supervision/aux relay |
| 27 | Master trip relay VAJHM-53 |
| 28 | Trip Circuit Supervision relay |
| 29 | LBB relay |
| 30 | 3 PH 4 Wire ABT Energy Meter |
| 31 | 250 V Battery Bank 500 AH |
| 32 | 250 V Charger |
| 33 | Lighting Panel (Indoor) Type ACP-1 as per Tech.Specification |
| 34 | Sub Station Automation (SCADA System) |
| 35 | Integration with existing Sub- Station automation system comprising of necessary equipments, optical fibre cable, jointing kits& materials wth networking and interfacing, complete in all respect including any miscellaneous items. |
| 36 | Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc. |
| 37 | Power cables (XLPE) 1.1 kV |
| 38 | 3.5C X 150 mm2 |
| 39 | Power cables (PVC) 1.1 kV |
| 40 | 4C X 16 mm2 |
| 41 | Control cable (PVC) 1.1 kV |
| 42 | 2C X 2.5 mm2 |
| 43 | 5C X 2.5 mm2 |
| 44 | 7C X 2.5 mm2 |
| 45 | 10C X 2.5 mm2 |
| 46 | 14C X 2.5 mm2 |
| 47 | 19C X 2.5 mm2 |
| 48 | Materials for earthing mat with all materials and accessories as well as spikes as per requirement of design as per IEEE standards for complete earthing of grid Sub-Station with the followings. (The quantity is tentative and final quantity will depend on actual design):- |
| 49 | 40 mm MS rod for main earth mat including treated chemical type earthpits. |
| 50 | 75x12 mm G.I Flats risers for equipments, columns and structures |
| 51 | 50x6 mm G.I flats for risers for all other equipments etc. |
| 52 | Materials for Earthing pits with supply of all earthingmaterials including base plate. |
| 53 | Sub- Station galvanized Steel structure and expanded metal fencing around the S/Y area with fastner as for( LM also) for 132 KV(The quantity is tentative and final quantity will depend on actual design):- |
| 54 | Lattice structure with fasteners etc.(HT) |
| 55 | Lattice structure with fasteners etc.(MS) |
| 56 | Earth Pit (Treated) |
| 57 | Mandatory spares |
| 58 | 132 kV CB |
| 59 | 132 kV Isolator |
| 60 | 132 kV CT, 1200A, 120% extended current rating |
| 61 | 132 kV CVT, 8800 pF |
| 62 | 120 kV surge arrester |
| 63 | Lighting fixture Type- FB: as per Tech. Specification(BICDO 40W LED) |
| 64 | Lighting fixture Type- PF: as per Tech. Specification(BRTFG 72W LED) |
| 65 | Galvanised Cable Racks as per design requirement. |
| 66 | 11 KV Disc Insulator120/90 KN |