| 1 | SUB HEAD-I (Wiring) |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required |
| 3 | Group A |
| 4 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required |
| 5 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 6 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 7 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 8 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 9 | 4 X 1.5 sq. mm + 2 X 1.5 sq. mm earth wire |
| 10 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 13 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 14 | S/Fixing hexagonal fan box of size 150 mm dia made outof 16 SWG MS sheet including 12mm dia MS rod in the U shape with its vertical legs bent horizontally at thetop at least 19 cm on either side and bound to the top reinforcement of the roof at the time of casting i/c S/F 3 mm thick phenolic laminated sheet at the bottom complete as reqd. |
| 15 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 16 | SUB HEAD-II (Distribution System) |
| 17 | Supplying and fixing following way, horizontal type SPN , sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with metal door, tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/ Isolator) (Make-Havells -Metallica ) |
| 18 | 12 Way SPNDouble Door (CAT No-DHDNSHODAW12 ) |
| 19 | 16 Way SPNDouble Door (CAT No-DHDNSHODAW16 ) |
| 20 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, having provision ofmounting MCCB upto 125A as incomer complete with making interconnection etc as required. (but without outgoing MCBs and incomer MCCB ) (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) (Make:- ( Make L&T-DTVTL006DD or Similar Superior make) |
| 21 | 6 way (6+6+6), Double door |
| 22 | Supplying and fixing following rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 23 | 5 amps to 32 amps, 240 volts Single pole. |
| 24 | 40 amp SP MCB |
| 25 | Double Pole 6-32A |
| 26 | Double Pole 40A |
| 27 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 28 | 25 amps |
| 29 | 40 amps |
| 30 | S/F Following rating and breaking capacity Three Pole MCCBwith thermomagnetic release and terminal spreaders in the existing vertical DB i/c making interconnection with existing Bus Bar etc as required. |
| 31 | 125A 16KA |
| 32 | Supplying and fixing Cable End Box ( IP 43 ) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 33 | For 10 way, Double door SPN MCBDB |
| 34 | For 14 way, Double door SPN MCBDB |
| 35 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 36 | SH-III (Telephone, Television Wiring & Conduting Only) |
| 37 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. |
| 38 | 1 or 2 Module (75mmX75mm) |
| 39 | 3 Module (100mmX75mm) |
| 40 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 41 | 5/6 amps switch |
| 42 | 3 pin 5/6 amp socket outlet |
| 43 | Telephone Socket outlet. |
| 44 | TV Antenna socket outlet. |
| 45 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 46 | 20mm |
| 47 | 25mm |
| 48 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 49 | 2 Pair |
| 50 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 51 | 1 run of cable |
| 52 | SUB HEAD-IV (Earthing and Lightning Conductor) |
| 53 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 54 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 55 | Supplying and laying 25 mm X 5 mm G.I strip on surface or in recess etc as required. |