Servicing, Improving Ir Value And Rectification Of 11Kv Sub-Station Of Parsala Water Supply Scheme Under Bmd, Phe Dte.- 1 Attending the fault at Parsala, Bankura District with carrying different Testing, Servicing kit/machine like Insulating Resistance Checking machine (1 KV, 2.5 KV, 5 KV) 3 Phase Variac, Current Injection machine/ kit, Voltage injection machine/kit, Blower, Multimeter, Clamp meter, Different type of tools tackles, Various Testing Wires, MCBS, Wires & Cables, HT insulation Tapes, Gas can with nozzle, CRTWD-40, Lecta Cleaner, Adhesive non Adhesive PVC Tape and items for complete servicing and testing the Transformers, VCBS, AVR with connecting HT, LT cables 2 Charges for 11 KV VCB Racked out from 11 KV Panel, 11 KV VCB Mechanism dismantling, 11 KV VI Housing Rubbing, Cleaning by applying CRC, WD-40 and Heating treatment done for IR Improvement, after IR improving 11 KV VCB Racked In inside Panel and power charging by Expert Electrical Engineer 3 Charges for 11 KV HT Cable disconnection, 11 KV CT Primary & Secondary Side disconnection, 11 KV CT Dismantling, 11 KV CT Testing, 11 KV CT Rubbing, Cleaning by applying CRC, WD-40 and Heating treatment donefor IR Improvement, finally Re-fitting the 11 KV CT and reconnection of 11 KV HT Cable by Expert Electrical Engineer 4 Charges for 11 KV cable Disconnecting, cable sleeves cutting, cable end cleaning and Heating treatment has been done for improving IR value and re-connecting the 11 KV HT cable of AVR input & output power cable & 4 panel VCB outgoing cable 5 Charges for 11 KV CT Spouts Dismantling from Panel, Rubbing, Cleaning by applying CRC, WD-40 and Heating treatment done for IR Improvement and finally Re-fitting of Incomer & OG – 2 Panel 6 Charges for 11 KV Bus-Bar Spouts Dismantling from Panel, Rubbing, Cleaning by applying CRC, WD-40 and Heating treatment done for IR Improvement andRe-fitting 7 Supply,delivery and fitting fixingof 200-Watt Space Heater 8 Supply,delivery and fitting fixing of Thermostat 9 2.5 sq. mm. S/C, 1.1 kV grade Control cable supply for space heater and thermostat wiring 10 Supply,delivery and fitting fixingof 2 Nos. Space Heater along with 1 No. Thermostat connection wiring charges for Outgoing- 2VCB Panel 11 Add: 18% GST 12 Add: 1% Cess