| 1 | Name of Work: Upgradation of Existing 1x5 MVA Electrical Substation into 2x5 MVA for Betwa Vihar Awasiya Yojna, Village Booda, At Jhansi.Note :-(1)-GST Excluded on the aforesaid work. |
| 2 | Earth Mat & Earthing Items Excavation of trench of size 600x750mm, 600x750x750 =360mt.SOR 2022 New Item |
| 3 | Chemical earthing of transformer neutral and body.MR |
| 4 | Supply and laying of 50 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. MR |
| 5 | SITC of 1 HP submersible pump. PSR |
| 6 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. DSR-2022 5.20 |
| 7 | GANTRY STRUCTURE Terminal Gantry charge. RESSPO 2024-25 ANNEX-15 |
| 8 | Main Busbar gantry complete sructure.RESSPO 2024-25 ANNEX-15 |
| 9 | 33kv line isolator. RESSPO 2024-25 ANNEX-15 |
| 10 | 33kv bus isolator RESSPO 2024-25 ANNEX-15 |
| 11 | Structure for above(Complete) RESSPO 2024-25 ANNEX-15 |
| 12 | 33kv post insulator. RESSPO 2024-25 ANNEX-15 |
| 13 | Structure for above(Complete) RESSPO 2024-25 ANNEX-15 |
| 14 | 33kv Lighting arresters RESSPO 2024-25 ANNEX-15 |
| 15 | Structure for above(Complete) RESSPO 2024-25 ANNEX-15 |
| 16 | Over Head Fittings Supply & erection of 33 KV pin insulators with larg steel head G.I. pin on main terminal gantry. DSR-202213.23 |
| 17 | Disc Insulator ( B&S Type ) -70KN 33KVS.I.R UPPCL2025-26/46 |
| 18 | Disc Fitting 70 KN ( B&S Type ) S.I.R UPPCL 2025-26/50 |
| 19 | S/E of ACSR Panther Conductor. complete in all respect. S.I.R UPPCL 2025-26/63 |
| 20 | Supply & Fixing of P.G. clamps suitable for panther to panther conductor for jumpering. S.I.R UPPCL 2025-26/15 |
| 21 | 33 kv Fuse set S.I.R UPPCL 2025-26/97 |
| 22 | Structure for above(Complete) RESSPO 2024-25 ANNEX-15 |
| 23 | Supply of transfarmers, VCB\"s & control panels Supply of (UPPCL Approved) 5000 V.A. 33/11 KV 3 Phase Delta/Star, 50 Hzs step Down, Outdoor type, with off load Tap changing Switch with First Filling of Transformer oil (No load Loss max 5 KW & Load Loss max 31 KW) complete with all fittings and inclusive of transformer oil for first filling as per ISS:335 at site. (make- Crompton/Siemens) S.I.R UPPCL 2025-26/112 |
| 24 | 90 lbs rail pieces for transfarmer (44.64kg/M) RESSPO 2024-25 ANNEX-15 |
| 25 | Plinth for transfarmer RESSPO 2024-25 ANNEX-15 |
| 26 | 33 KV/VCB with double T/F control panel and CT 200/100/1A with structure(i) 33 KV VCB(ii) control panel I/C for 33KV double T/F(iii) CT 200/100/1-1A(iv) steel structure RESSPO 2024-25 ANNEX-15 |
| 27 | Plinth & Foundation of VCB. RESSPO 2024-25 ANNEX-15 |
| 28 | Supply of 33 KV Current Transformer 200/100/1-1-1A S.I.R UPPCL2025-26/99 |
| 29 | Structure for above(Complete) RESSPO 2024-25 ANNEX-15 |
| 30 | Supply of 33 KV Potential Transformer (PT), outdoor, Epoxy cast, Impregnated minimum oil filled, Single phase PTR 33 KV/3/110v.S.I.R UPPCL 2025-26/101 |
| 31 | Structure for above(Complete) RESSPO 2024-25 ANNEX-15 |
| 32 | 600/300/5A,350MVA, I/C. RESSPO 2024-25 ANNEX-15 |
| 33 | Outgoing 200/100/5A RESSPO 2024-25 ANNEX-15 |
| 34 | Bus Coupler 350MVA RESSPO 2024-25 ANNEX-15 |
| 35 | Installation & Errection Lifting, Loading Carriage, Unloading of the 5000 K.V.A. 33/11 KV Power Transformer from Manufacturing Unit up to Site and keeping it on the Plinth at Site. MR |
| 36 | Installation Testing & Commissioning of the 5000 K.V.A. 33/11 KV Power Transformer at Site.MR |
| 37 | Installation, Testing & Commissioning of 33 KV VCB/SF-6 Circuit Breaker including material cost of control cables & Laying cost of control cables including loading, unloading, local carriage & errection of the same & making all necessary conection etc. as per direction of Engineer-in-charge.etc. complete in all respect.MR |
| 38 | Installation, Testing & Commissioning of Control Panel SF-6 Circuit Breaker (including material cost of ontrol cables & Laying cost of control cables) comprising of loading, unloading, local carriage & errection of the same & making all necessary conection etc. as per direction of Engineer-in-charge.etc. complete in all respect.MR |
| 39 | Installation, Testing & Commissioning of 11 KV VCB (Incoming/ Outgoing) including material cost of control cables & Laying cost of control cables including loading, unloading, local carriage & errection of the same & making all necessary conection etc. as per direction of Engineer-in-charge.etc. complete in all respect. MR |
| 40 | Installation, Testing & Commissioning of 11 КV VСВ Bus Coupler including material cost of control cables & Laying cost of control cables including loading, unloading, local carriage & errection of the same & making all necessary conection etc. as per direction of Engineer-in-charge.etc. complete in all respect. MR |
| 41 | Supply/Installation of 24 volt Battery and charger with Cabinet. RESSPO 2024-25 ANNEX-15 |
| 42 | Cables & Jointing Kits 185 sqmm 3 Core S.I.R UPPCL 2025-26/12 |
| 43 | 33KV XLPE Cable AL.3x300 sqmm. S.I.R UPPCL2025-26/18 |
| 44 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. DSR-20228.1Above 120 sq. mm and upto 400 sq. mm8.1.2 |
| 45 | Supplying and making outdoor cable end termination with heat shrinkablı jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:DSR-202210.5Upto 240 sq. mm10.5.3 |
| 46 | Upto 300 sq. mm 10.5.4 |
| 47 | Supplying and making Indoor cable end termination with heat shrinkablı jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: DSR-202210.4 Upto 240 sq. mm10.4.3 |
| 48 | Upto 300 sq. mm 10.4.4 |
| 49 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.SOR-2018 504185 Sqmm(M) |
| 50 | 300 Sqmm (o) |
| 51 | S/E of Double Pole comprising of 2 nos. SP-55 pole, 3 No. 100x50mm MS 2.24 M long Channel, painting, 1 no. 75x40 mm MS channel 2.24 M long. D- clamp, packing piece etc all complete as per direction of E/Ic |
| 52 | Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/.20 mm dia X 1.8 metres long stay rod, anchor plate of size 15cm * 45cm * 7.5mm thick, thimble, stay clamps, turn buckle (20mm * 600mm) 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1) cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. DSR-202213.1 |
| 53 | Supply ofControl Cable for controlling the equipment & signal processing.RESSPO 2024-25 ANNEX-15 4x2.5 sqmm(a) |
| 54 | 2x2.5 sqmm (b) |
| 55 | Wire mesh fencing (Barbed wire) with gate.(switchyard) RESSPO 2024-25 ANNEX-15 |
| 56 | supply of stone ballast 40mm size for laying switchyard . S.I.R UPPCL2025-26/9 |
| 57 | Painting of Sub-Station structure copmlete. RESSPO 2024-25 ANNEX-15 |
| 58 | Sundry Store at Sub-Station MR |
| 59 | Dismantling brick work or stone work in lime or cement mortar and including stacking of materials as directed by Engineer-in-charge with in a distance of 60 mt. (200 feet). SOR (2022) 692 |
| 60 | Dismantling reinforcement cement concrete or reinforcement brick work, including stacking of materials as directed by Engineer-in-charge with in a distance of 60 mt. (200 feet). SOR (2022)694 |
| 61 | Excavation in foundation in ordinary soil(loam clay or sand) requiring the use of spacial T&P such as pick axas, sabbals etc. including lift upto 1.5 meter (5 fts.) and lead upto 30 m (100 fts) & including filling, watering and ramming of excavated earth into the tranches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the Engineer-in-charge upto a distance of 30 m (100 fts) from the foundation trenches. SOR (2022) (252) |
| 62 | Providing and laying in cement concrete 1:4:8(1 cement : 4 soarce sand : 8 graded stone aggregate 40 mm nominal size) and curing complete, including cost of form-work, in foundation and floors. S.O.R.-(275) (2022) |
| 63 | Earth filling in plinth including supply of necessary quantity of earth from the distance not exceeding 12km from the site of work & including watering, dressing etc. Rate include cost of all material, labour and T&P etc. reqduird for proper completion of the work. S.O.R.-(255) (2022) |
| 64 | R.C.C work with cement approved coarse sand and 2 cm. (3/4\") gauge approved stone ballast in the proportion of 1:1.5:3 in R.C.C.at foundation and footing with 4cm. excluding supply of reinforcement and its binding but including its fixing and binding the same with 24 B.W.G.G.Ibinding wire and including necessary centering and shuttering etc and also including supply of all materials, labour & T&Petc required for proper completion of the work. Binding wire cost being including in the item .(SOR2022- 287(1)) |
| 65 | R.C.C work with cement approved coarse sand and 2 cm. (3/4\") gauge approved stone ballast in the proportion of 1:1.5:3 inR.C.C T beam and slab roofs and R.C.C. Column excluding supply of reinforcement and its binding but including its fixing and binding the same with 24 B.W.G.G.Ibinding wire and including necessary centering and shuttering etc and also including supply of all materials, labour & T&Petc required for proper completion of the work. (SOR2022- 288(1)) |
| 66 | R.C.C. work with cement approved coarse sand and 2 cm .(3/4\") guage approved stone ballast in the proportion of 1:1.5:3 in slab excluding supply of reinforcement and its binding but including its fixing and binding the same with 24 B.W.G.G.Ibinding wire and including necessary centering and shuttering etc. and also including supply of all materials, labour &T&P etc. required for Prpoper completion of the work. Binding wire cost being included in the item SOR-(2022) 284(1) |
| 67 | Mild steel or iron in plain work such as reinforced concrete or reinforced brick work (when not included in an over all rates) wrought to required shape as necessary including bending for proper completion of the work and including supply of all steel and wastage & overlapping & hooks. S.O.R.- (2022) 504 |
| 68 | First class brick work in 1:6 cement and fine sand of 1.25 FM. mortar in foundation and plinth including supply of all materials, labour and T & Petc. required for proper completion of the work. S.O.R.- (2022) 303 |
| 69 | First class brick work in 1:6 cement and fine sand of 1.25 FM. mortar in superstructure. Including necessary cutting and moulding of bricks as requiered and also including honey comb brick work, thickness of wall not to be less than 1.5 brick thick. Add extra labour to above item no. 301 to 304. Ref No. 309 Cement mortar 1:6 (1 cement: 6 fine sand)S.O.R. (2022)- 303 TO 304+ 310 |
| 70 | 12 mm Cement plaster in single coat on fair side of single or half brick wall for interior plastering upto floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80 mm. In girth and finished even and smooth. No extra for mixing any additive. SOR (2022) 17.58 |
| 71 | 15 mm Cement plaster in single coat on fair side of single or half brick wall for interior plastering upto floor two level including internal rounded angleschamfers, and /or rounded angles not Exceeding 80 mm.In Girth and finished even smooth . Chapter-13 (ii) 1 Cement : 4 Fine sand S.O.R.2022-(17.59) |
| 72 | Providing and applying plaster of paris putty of 2mm thickness over plastered surface toprepare the surface even and smooth complete . SOR (2022)-(13.26) Page No. 63 |
| 73 | Wall painting with acryline emulsion paint, having VOC (Volatile Organic Compound) content less than 50 grams/litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. (Two Coats).D.S.R.( 13.82.) (2023) |
| 74 | Providing & Laying of 8 to 10 mm thick ivory or light shade Vitrified tiles of 600 mm X 600 mm size in flooring or skirting laid with 1:3 cement mortar (1) cement: 3 coarse sand) finishing with cement slurry & with pigment grouting & polishing complete i/c supply of all materials, labour T& P required for proper completion of work.S.O.R. (2022) PAGE NO. 61 New Item No-2S.O.R. (2022) PAGE NO. 61 New Item No-2 |
| 75 | Providing and laying of Ferrow cement concrete in 1:24 cement approved coarse sand and 20 mm gauge approved stone ballast and mixing water proofing compound @ 1.0 kg/bag of cement in thickness of 5 cm average including making ridges and valley for proper drainage of roof water including embedding of expended metal zali of 6 gauge iron wire including cutting and fixing properly over slab and including 6 mm thick cement plaster in 1:2 cement and coarse sand finished with floating coat of neat cement also including supply of all materials, labour and T&P etc required for proper completion of work and as per direction of Engineer-in-charge. SOR (2022) New item No-2 Page no. 54 |
| 76 | Providing and fixing Pristine White U PVC Window. Company must have own production facilities (extrusion & fabrication) & control the entire cycle from Extrusion to Installation to Post Sales Service. Profile frame of high impact modified grade uPVC, which shall be manufactured from Tropicalized Blend with TiO2 and required additives. Profile must be colorfast and conform to standard EN12608.Slider Window: Supply & fixing three track three panel slider windows with Fibre Mesh (2 Glass & 1 Mesh Panel), Outer frame of windows should be 118 X 50mm and Sash of 45 X 74mm with roller, wall thickness of profile 1.8±0.3mm & Windows design must be as per approved drawing only. Glass should be of make: Saint-Gobain/ ASAHI/ equivalent with 5mm Single Clear Toughened Glass as per given specification with weather seal EPDM/TPE gasket. As per Market Rate.(Company-Fenesta) As per Market Rate.(Company-Fenesta) |
| 77 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws.D.S.R.-2023 (9.20.1) |
| 78 | Providing and fixing ISI marked oxidised M.S. hinges, bolts, locks, handles spring and or other fittingswith necessary screws etc. complete : S.O.R.-474(2022) |
| 79 | Supply & Fixing Door Lock (18\") including supply of all materials, labour and T&P etc. required for proper, comletion of work. As per market rate. As per market rate. |
| 80 | Mild steel or iron work in havy sizes such as trusses: builts up gates, door frames, record racks roof work. glites etc. wrought to required form including drilling holes; rivetting or welding where necessary, and also including supply of steel, bolts, nuts etc.& their fixing required for proper completion of the work. SOR (2022)503 |
| 81 | Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge.16.78 DSR(2023) With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30 16.78.1 DSR(2023) |
| 82 | Providing and laying of 80mm Interlocking concrete block pavement laid in stone dust base and fill joint with fine sand. Joint filled after labling and dressing base including supply of all material, labour, T&P etc required for proper completion of the work. SOR (2022) New Item no. 3 (Page No. 61) |
| 83 | Providing, laying and making kerb channel 30 cm wide and 50 mm thick with cement concrete 1:3:6 (1 cement: 3 coarse sand:6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth etc. complete and as per direction of Engineerin- charge. 16.63 DSR (2023) |
| 84 | Painting or Varnishing on iron works in small areas or new wood work with one coat of ready mixed priming paint & one coat of approved superior quality ready mixed paint of clear synthetic varnish including supply of all materials, labour and T&P etc. required for proper completion of the work. Paint to be used should confirm to the I.S.I.No. 103 1950 SOR 2022) 641 |
| 85 | BOQ Internal Electrical Work |
| 86 | BOQ Internal Pumbing Work |