| 1 | Taking down carefully copper/ Aluminum point wiring (light, fan socket or power) complete incl. (fitting such as switches, ceiling roses, pendants, regulators, sockets, boards, DB, MCB, light fittings etc), removing materials from site and making good disturbed surfaces of walls, floors etc, complete all as specified and directed |
| 2 | Material and labour for point wiring for one light / Fan / Ex Fan pointcontrolled by 1 one way switch with 1.5 Sqmm PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable 1100 Volts grade in and including PVC capping and casing (double lock, ISI Marked) of suitable size with all necessary fittings along with 1.5 sqmm continuous PVC insulated unsheathed stranded copper conductor (FRLS) cable for earth continuity wire, connected to earth dolly and to be terminated in and including MS rectangular Box with bakelite sheet cover / PVC rectangular switch board of suitable size for mounting switches, sockets, fan regulators etc or MS modular boxes / PVC modular box suitable for mounting modular switches, sockets etc including testing on completion complete all as specified and directed. |
| 3 | All as per item No 2 here-in-before but for one bell point controled by one bell push on the same board with other switches or independent all as specified and directed. |
| 4 | All as per item No 2 here-in before but for one 3 pin, 5 Amp socket point on the same board with other switch, complete all as specified and directed. |
| 5 | All as per Item No 2 here-in-before but for one switch socket outlet, 5 Amp on independent board all as specified and as directed. |
| 6 | All as per item No 2 here-in before but for one 3/5 pin, 15 Amp switch socket combination on independent board with 2.5 sqmm PVC insulated unsheathedmultistranded FRLS copper conductor, complete all as specified and directed |
| 7 | Material and Labour forsub main wiring with 2 run of single core 6.0 Sqmm FRLS (ISI Marked) PVC insulated unsheathed multistranded copper conductor cable drawn through and including PVC Conduit / casing capping of suitable size along with accessories etc including one run of 6.0 Sqmm FRLS (ISI Marked) PVC insulated unsheathed multistranded copper conductor as earth wire, including taking down old wiring, complete all as specified and directed. Note :- Two run of 6.0 Sqmm single core cable, one run of 6.0 Sqmm earth wireand one run of PVC conduit/ casing capping shall be measured as one run length. |
| 8 | Supply and fix in repair PVC casing and caping of size 32 x12 mm complete all as specified and directed. |
| 9 | Supply and fix Switch piano flush button single pole, one way 6 Amp, complete all as specified and directed |
| 10 | Supply and fix modular switch 1 way 6 Amps 1 Module complete all as specified and directed |
| 11 | Supply and fix modular switch 1 way 16 Amps 1 Module complete all as specified and directed |
| 12 | Supply and fix bell push, flush type, 6 Amps, complete all as specified and directed |
| 13 | Supply and fix modular bell push6 Amps 1 Module complete all as specified and directed. |
| 14 | Supply and fix socket outlet 5 pin, 6 Ampscomplete all as specified and directed |
| 15 | Supply and fix Switch Socket combination 2 in 1, 6A flush type5 pin, 230 volts complete all as specified and directed |
| 16 | Supply and fix Switch socket combination 2 in 1,3 pin, 6 amps and 16 amps flush type universal shuttered, complete all as specified and directed |
| 17 | Supply and fix modular socket2 in 1,5 pin 6 Amps, 2 modules complete all as specified and directed |
| 18 | Supply and fix modular socket2 in 1,3 pin 16 Amps, 2 modules complete all as specified and directed |
| 19 | Supply and fix call BellAC 230 Volts, single pole, complete all asspecified and directed |
| 20 | Supply and fix Ceiling rose, 2 pole / 3 pole, PVC/polycarbonate, insulated body (ISI Marked) complete all as specified and directed |
| 21 | Fixing only serviceable Ceiling rose, 2 pole / 3 pole, PVC / polycarbonate, insulated bodycomplete all as specified and directed |
| 22 | Supply and fix in repair lamp holder PVC / Polycarbonate type with back plate suitable for batten fittings (ISI Marked) complete all as specified and directed |
| 23 | Supply and fix Stepped type electronic fan regulator, AC 50 HZ, 230V,100 Watts, minimum 4 steps(ISI Marked), complete all as specified and directed |
| 24 | Supply and fix Modular Fan regulator,100 watts 2 modules complete all as specified and directed |
| 25 | Supply and fix white modular cover plate with frame 1 Module complete all as specified and directed |
| 26 | Supply and fix white modular cover plate with frame 3 Module complete all as specified and directed |
| 27 | Supply and fix white modular cover plate with frame 6 Module complete all as specified and directed |
| 28 | Supply and fix white modular cover plate with frame 8 Module complete all as specified and directed |
| 29 | Supply and fix in repair LED tube light fittings 1 x 09/10 Watt two feets long with polycarbonate housing & intigrated electronic driver and necessary electric connection complete all as specified and as directed |
| 30 | Supply and fix in repair LED tube light fittings 1 x 18/20 Watt four feets long with polycarbonate housing & intigrated electronic driver and necessary electric connection complete all as specified and as directed |
| 31 | Supply and fix in repair wallmountedbulk headLED light fitting 10 W, made up of poly carbonate housing with diffuser & intigrated electronic driver and necessary electric connection complet all as per specified and directed |
| 32 | Supply and fix in repair indoor commercial LED Luminaires Plano 2ftX2ft 36 watt ultra modern recess mounting luminaire with high performance LEDs suitable for mounting with grid ceilingand including connecting up with twin core twisted flexible copper conductor cable includingtaking down old light fittings complete all as specified and directed. |
| 33 | Supply and fix in repair of LED lampwith in built driver with metal heat sink double sided connection of capacity 1x 18 watts all as specified and directed. |
| 34 | Supply and fixing in repair switch socket combination5 Pin 6 Amp with PVC Box complete all as specified and directed. |
| 35 | Supply and fix in repair white modular cover plate with frame 3 Module complete all as specified and directed |
| 36 | Supply and fix in repair white modular cover plate with frame 8 Module complete all as specified and directed |
| 37 | Supply and fix in repair Switch piano flush button single pole, one way 5 Amp,complete all as specified and directed |
| 38 | Supply and fix in repair modular switch 1 way 6 A, 1 Module complete all as specified and directed |
| 39 | Supply and fix in repair call bellAC 230 Volts, single pole,complete all asspecified and directed |
| 40 | Supply and fix sheet metal enclosure MCB DB 8 waySPN double door suitable for 240 V, fixed on walls includingblanking plate as per requirement and taking down unserviceable DBs complete all as specified and directed |
| 41 | Supply and fix sheet metal enclosure MCB DB 6 waySPN double door suitable for 240 V, fixed on walls includingblanking plate as per requirement and taking down unserviceable DBs complete all as specified and directed |
| 42 | Supply and fix MCB SP 240 Volts, \"C\" series, breaking capacity 10 KA of rating 32 Amps complete all as specified and directed |
| 43 | Fixing only Minature circuit braker (MCBs) of any cap, 240 Volt (serviceable MCB SPN obtained from unserviceable DBs shall be reused) complete all as specified and directed |
| 44 | S&F MCB SP 240 Volts, \"C\" series, breaking capacity 10 KA of rating 6-32 Amps complete all as specified and directed |
| 45 | Fixing only Minature circuit braker (MCBs) of any cap, 240 Volt (serviceable MCB SP obtained from unserviceable DBs shall be reused) complete all as specified and directed |