| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 25-08-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 01-09-2025 |
| 2 | 13-08-2025 | ERRATA/ AMENDMENT TO THE BOQ/ TENDER DOCUMENTS | BOQ | 25-08-2025 |
| Sl. No. | Item Description |
| 1 | Taking down carefully any type of old unserviceable point wiring copper or aluminium conductor (light, fan, socket, bell or power) point complete with fittings such as switches ceiling roses, lamp holders, sockets, fan regulators, call bell, light fittings with PVC conduit surface / concealed or wooden battens including sunken cast iron / pressed steel terminal boxes etc and making good the disturbed surfaces of walls, roof, floors etc to match with the existing surfaces complete all as specified & directed. |
| 2 | Taking down carefully any type of old unserviceable submain wiring with PVC conduit surface / concealed or wooden battensetc and making good the disturbed surfaces to match with the existing surface complete all as specified & directed. |
| 3 | Taking down old unserviceable DBs/Main switches any type/size complete with all accessories and remove from site complete all as specified & directed. |
| 4 | M&L of Sub main wiring with two single core PVC Insulated cable two run of size 4 Sqmm multi-strand copper conductor FRLSH cable 1100 volts grade drawing in and including PVC conduit, medium grade not less than 20 mm dia with all conduit accessories and one run of 4.0 Sqmm multi-strand copper conductor FRLSH cable as continuous earth wire including making good disturbed surface to match existing complete all as specified & directed.Note : - Two run of 4 Sqmm & one run of 4.0 Sqmm cable shall be measured as one unit run. |
| 5 | M&L ofSub main wiring with two single core PVC Insulated cable two run of size 6.0 Sqmm multi-strand copper conductor FRLSH cable 1100 volts grade drawing in and including PVC conduit, medium grade not less than 25 mm dia with all conduit accessories and one run of 6.0 Sqmm multi-strand copper conductor FRLSH cable as continuous earth wire complete all as specified and directed.Note : - Two run of 6 Sqmm & one run of 6 Sqmm cable shall be measured as one unit run. |
| 6 | Material & Labour for point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLSH cable 1100 Volts grade drawn intoand concealed PVC conduits medium grade not less than 20mm( ISI marked) including all fitting and fixing accessories including 1.25 mm thick sunken pressed steel terminal boxes/Modular metal flush box duly painted with two coats of anti-corrosive paint outside and two coats of aluminium paint inside with and including 3mm thick hylam brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators fixed with CP screws with cup wahsers and PVC insulated 1.5 Sqmm multi-strand copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces complete all as specified & directed for One light Point controlled by one switch. |
| 7 | ~ditto~ all as item No. 6.00 as above but for oneFanPoint controlled by one switch. |
| 8 | ~ditto~ all as item No. 6.00 as abovebut for oneBell Point controlled by one switch. |
| 9 | ~ditto~ all as item No. 6.00 as abovebut for one socket point 5 Amp controlled by one switch on same board. |
| 10 | ~ditto~ all as item No. 6.00 as above but for onesocket point 5 Amp controlled by one switch on Independent board. |
| 11 | ~ditto~ all as item No. 6.00 as above but for onelight point controlled by two way switch. |
| 12 | ~ditto~ all as item No. 6.00 as abovebut with 1100 Volts grade copper stranded conductor FRLSH cable of size 2.5 Sqmm main & with 2.5 Sqmm earth multi-strand copper conductor cable as earth wire for 3 pin switch socket outlet 15 Amp on Independent board complete all as specified & directed. |
| 13 | M&L for drawingthe wire in with casing capingcomplete with point wiring withFRLSHPVC insulated, unsheathed stranded copper conductor of nominal area 1.5 Sqmm, 1100 volts grade, along with one single run of same size and type of copper wire as continuous earth wireto common earth dolly in andsunkenterminal boxes pressed MS/GI steel terminal boxes not less than 1.20 mm thick for mounting switch, socket etc including 3 mm thick Hylam brand sunmicalaminated sheet coveror inner outer plates for modular switches with brass screw and cup washers with all accessories and making good to disturbed surface with cement mortar ratio of 1:3 and matching surface with existing white/colour wash, oil bound or cement base paint etc to match with existing surface complete all as specified and directed for one light/ Fan / Bell Point controlled by one switch. |
| 14 | ~ditto~ all as item No. 13 as abovebut for one socket point 5 Amp controlled by one switch on same board. |
| 15 | ~ditto~ all as item No. 13 as above but for onesocket point 5 Amp controlled by one switch on Independent board. |
| 16 | ~ditto~ all as item No. 13 as above but for onelight point controlled by two way switch. |
| 17 | ~ditto~ all as item No. 13 as abovebut drawing in with casing capingpoint wiring using 2.5 Sqmm (Nominal area)triple layerFRLSHPVC insulated unsheathed copperconductor 1100 volts for one 3/6 pin socket outlet ,suitable for 6/16 amps on “independent board”.with 2.5 sqmm with one single run copper wire as continuous earth wireto common earth dolly complete all as specified & directed. |
| 18 | Material & Labour for point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLSH cable 1100 Volts grade drawn into the existing conduits including all fitting and fixing accessories including 1.25 mm thick sunken pressed steel terminal boxes duly painted with two coats of anti-corrosive paint outside and two coats of aluminium paint inside with and including 3mm thick hylam brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators fixed with CP screws with cup wahsers and PVC insulated 1.5 Sqmm multi-strand copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces complete all as specified & directed for one light Point controlled by one switch. |
| 19 | ~ditto~ all as item No. 18 as abovebut for oneFanPoint controlled by one switch. |
| 20 | ~ditto~ all as item No. 18 as above but for oneBell Point controlled by one switch. |
| 21 | ~ditto~ all as item No.18 as above but for one socket point 5 Amp controlled by one switch on same board. |
| 22 | ~ditto~ all as item No. 18 as above but for onesocket point 5 Amp controlled by one switch on Independent board. |
| 23 | ~ditto~ all as item No. 18 as above but for onelight point controlled by two way switch. |
| 24 | ~ditto~ all as item No. 18 as above but with 1100 Volts grade copper stranded conductor FRLSH cable of size 2.5 Sqmm main & with 2.5 Sqmm earth multi-strand copper conductor cable as earth wire for 3 pin switch socket outlet 15 Amp on Independent board complete all as specified & directed. |
| 25 | S&Fcall bell ding dong sound type suitable for AC 230 volt single pole complete all as specified & directed. |
| 26 | S&F switch bell push flush type suitable for 5 Amp 230 Volt of polycarbonate body complete all as specified & directed. |
| 27 | S&F switch piano flush type suitable for 5 Amp 230 Volt of polycarbonate body complete all as specified & directed. |
| 28 | S&F socket outlet 2 in 1, 5 Pin 5 Amp flush type of polycarbonate body complete all as specified & directed. |
| 29 | S&FSwitch socket combination 5 in 1, 5pin 5/6 Amps flush type universal of polycabonate body complete all as specified & directed. |
| 30 | S&FSwitch socket combination 5 in 1, 5pin 6/16 Amps flush type universal of polycabonate body complete all as specified & directed. |
| 31 | S&F lamp holder / batten or angle holder Insulated body incl 9 w LED bulbwith back plate suitable for batten fittings complete all as specified & directed |
| 32 | S&F Ceiling rose surface type 60x30 mm three terminals of polycarbonate body complete all as specified & directed. |
| 33 | S&F Ceiling Fan regulator electronic type 280 Watt capacity of polycarbonate body ISI marked complete all as specified & directed. |
| 34 | S&Fin replacement frame plate for modular switch 1 module includingscrews and washers etc model/make as per existingin site complete all as specified and as directed. |
| 35 | S&F in replacement of frame plate for modular switch 2 module includingscrews and washers etc model/make as per existingin site complete all as specified and as directed. |
| 36 | S&F in replacement of frame plate for modular switch 3 module includingscrews and washers etc model/make as per existingin site complete all as specified and as directed. |
| 37 | S&F in replacement of frame plate for modular switch 4 module includingscrews and washers etc model/make as per existingin site complete all as specified and as directed. |
| 38 | S&F in replacement of frame plate for modular switch 6 module includingscrews and washers etc model/make as per existingin site complete all as specified and as directed. |
| 39 | S&F in replacement of frame plate for modular switch 8 module includingscrews and washers etc model/make as per existingin site complete all as specified and as directed. |
| 40 | S&F in replacementMS Housing box 1/2 module suitable formodular switch as per existingswitch boxand making good to the disturb surfacecomplete all as specified and as directed. |
| 41 | S&F in replacementMS Housing box 3 module suitable formodular switch as per existingswitch boxand making good to the disturb surfacecomplete all as specified and as directed. |
| 42 | S&F in replacementMS Housing box 4/5 module suitable formodular switch as per existingswitch boxand making good to the disturb surfacecomplete all as specified and as directed. |
| 43 | S&F in replacementMS Housing box 6/8 module suitable formodular switch as per existingswitch boxand making good to the disturb surfacecomplete all as specified and as directed. |
| 44 | S&F in replacement of modular switch6-10Amps one module230 volts AC as per existing model/make complete all as specified and as directed |
| 45 | S&F in replacement of modular switch16 Amps one module230 volts AC as per existing model/make complete all as specified and as directed |
| 46 | S&F in replacement of modular socket, 6A -2/3 pin combined 2 module,230 volts AC as per existing model/make complete all as specified and as directed. |
| 47 | S&F in replacement of modular socket, 6/16A -2/3 pin combined 2 module,230 volts AC as per existing model/make complete all as specified and as directed . |
| 48 | S&F in replacement modular fan regulator, 2 Module 4 step 180w heavy duty 230 volts as per existing model/make complete all as specified and as directed. |
| 49 | S&F in replacement of 3mm thick hylam sheet of any sizeincluding brass screws and washers etc as per required at site complete all as specified and as directed. |
| 50 | S&F in replacement modular bell push switch piano, flush type, 6 Amps complete all as specified and as directed. |
| 51 | S&F in replacementswitch piano type switch two way AC 230 volts6 Ampsas per on existing switch board complete all as specified & directed. |
| 52 | Supply and fix rigid non metallic, medium grade, PVC conduit, concealed type of size25 mm with all accessories such as couplers, lock nuts, saddles, pipe hook, tees, bends, etc., including cutting chases for conduits and making good the disturbed surface with PCC as per site requirement complete all as specified & directed. |
| 53 | Supply and fix rigid non metallic, medium grade, PVC conduit, concealed type of size 32 mm with all accessories such as couplers, lock nuts, saddles, pipe hook, tees, bends, etc., including cutting chases for conduits and making good the disturbed surface with PCC as per site requirement complete all as specified & directed. |
| 54 | S&F in replacement of single corewire 4 Sqmm multi-strand PVC insulated copper conductor FRLS cable(red,yellow,blue & black) including connections of cable with MCBs or bus bars complete all as specified and directed.Make :- Anchor/Havells/ polycab/ plaza |
| 55 | S&F in replacement of single corewire 2.5 Sqmm multi-strand PVC insulated copper conductor FRLS cable (red,yellow,blue & black)including connections of cable with MCBs or bus bars complete all as specified and directed.Make :- Anchor/Havells/ polycab/ plaza |
| 56 | S&F in replacement of single corewire 1.5 Sqmm multi-strand PVC insulated copper conductor FRLS cable(red,yellow,blue & black) including connections of cable with MCBs or bus bars complete all as specified and directed.Make :- Anchor/Havells/ polycab/ plaza |
| 57 | Supply & Fixing in repair sheet metal enclosure MCB DB double door [Acrylic], single pole and neutral, 240 volts, 8 way with 200 Amp, 10 KA breaking capacity rated bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.Make: Legrand cat no :5076 21 or eq in SEIMENS |
| 58 | Supply & Fixing in repair sheet metal enclosure MCB DB double door [Acrylic], single pole and neutral, 240 volts,4 way with 200 Amp, 10 KA breaking capacity rated bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.Make: Legrand or eq in SEIMENS/GE |
| 59 | S&F in replacement sheet metal enclosure MCB DB double door [Acrylic], Triple pole and neutral,440 volts, 4 way with 200 Amp, 10 KA breaking capacity rated copper bus bar with blanking plate wherever required and IP-43 degree protection complete all as specified & directed.Make:Legrand Cat no :5077 80 or Eq in SEIMENS/GE |
| 60 | S&F in replacement MCB Triple Pole and Neutral 63 Amps,415 V ,10KA breaking capacity complete all as specified & directed.Make: Legrand cat no :4086 83 or eq in SEIMENS /GE |
| 61 | S&F in replacement MCB Single Pole and Neutral 240Volt, 40 Amps, \"C\"series,10KA breaking capacity complete all as specified & directed. Make:Legrand cat no :4086 18 or eq in SEIMENS /GE |
| 62 | S&F in replacement MCB Single Pole 240Volt, upto 40Amps, \" C\" series 10KA breaking capacity complete all as specified & directed.Make: Legrand cat no :408690/92/93/94/95/96 or eq in SEIMENS /GE |
| 63 | Supply & fixRCBOs For earth Leakage , overload & short Circuit Protection Double Pole 30 mA complete all as specified and directed |
| 64 | Supply & Fixing in repair single pole and netural sheet metal enclosure with a two pin and earth plug and socket complete with 01 number single pole MCB 20 Amps complete all as specified & directed.Make: Legrand cat no :5078 11 or eq in SEIMENS /GE |
| 65 | Supply & Fixing Smart bright Batten Series, LED luminaire using LEDs 22 watt, natural white, 2200 Lumen, THD max 10 %, CRI min 80 % with diffuser which ensures uniform distribution and comfort batten series features latest LEDs and delivers consistent light output with wide voltage protection range, stable color start Extruded Aluminum housing, Energy efficient, Flicker free start Inbuilt driver unit Suitable for wall and ceiling mounting using brackets (supplied along with The Luminaire has been tested as per Standard Specification IEC 60598-2-1 / IS: 10322(Parts/Secl), report has established conformity of the product(s) to the requirements of the Standard/Specification complete all as specified & directed. Make : Philips Cat part BN 021 LED 22S4000 PSU GR SI ,crompton or equivalent. |
| 66 | Supply and fix mirror light 12 watts surface/wallmounted fittingwith all accessaries durale and ecofriendly and proper connection from fitting to existing point as per site requirement and making the surface smooth complete all as directed. |
| 67 | Supply & fix in replacement ofLED Security Light Luminaire 25 wattwith 2500 or more lumen warm white, surge protection device upto 4KV, IP65/66 or more, IK07 or more, potted driver suitable for 180 to 270 V, 50 Hz, light engine driver base.pole adapter, powder coated pressure die cast aluminium with heat resistant toughened glass with lens type,GI pipe 25 mm dia medium Grade not less than with 1.2 m.long in any shape with 2 nos ofpole fitting clamps made out of MS flat , nutsand boltsand painting with aluminium paint. complete all as specified and as directed.Make: Philipscat part no: BRP029 LED25/WW MRPSU GR DX orequivalent in Crompton/Havells/GE |
| 68 | S&F decorative wall light fittingmade up of Polycarbonate ,Cylindrical shape ,with LED lamp 9 Watt complete with fixing arrangements on wallcomplete all as specified & directed.Make: HAVELLS or equivalent in /Philips/Wipro |
| 69 | Supply and fixing LED luminaire 600 mm x 600 mm,40 watt, 220 V AC recessed/surface type, as directed, with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified & directed.Make: Philips Cat Part no: RC380B LED42S-6500 G6 L60W60 PSU OD S1or equivalent GE/Havells |
| 70 | Supply and fixing round shape 6 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified & directed. |
| 71 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed/surface type, as directed, with high efficiency PMMA diffuser soft glare free light including switching on/off Automatic PIR sensor complete with driver,suitable for roof ceiling including connecting up with driver three core flexible copper conductorof suitable size complete all as specified & directed.Make: Philips RC383B P LED 36S-6500 G6 PSU OD WH PIR Por equivalent GE/ Havells |
| 72 | Preventive maintenance and checking of Ceiling/Exhaust/wall fan /air circulator / table fan / padestal fans of any size / type / make, checking the serviceability of safety pins, clamps, down rods, rubber bushes, nuts, bolts, canopies, replacement of bearing, and electric connections etc, connecting / hanging in original position, reconnecting the electric cables and writing MES No. and testing complete all as specified & directed. |
| 73 | S & F Metallic box suitable for mounting SPN DB 8way or VTPN DB 4 Way including taking out old unserviceable box from the wall/ location including refixing and makig all themaking good the disturbed surfaces of walls, roof, floors etc to match with the existing surfaces complete all as specified & directed by Engineer-in-Charge.Note: Painting work measured and paid seperately under respective items. |
| 74 | Supply fixing/connecting electronic tamper proofstatic electric energy meter, Single phase, 230 volts AC, 50 Hz, of capacity 10 to 60 Amps, class 1.0 accuracy with LCD display having special features like TOD , tamper Logging and display in absence of power confirming to IS 13779 , including connecting the meter in the existing electrical system/cables and seal by means of sealing wire and lead including disconnecting/taking down u/s burnt energy meters from existing boards/boxes, deposit to E/M store, (Note : (a) Meter reading record shall be maintained before and after replacement.(b)Dismantled u/s energy meter shall be deposited to E/M store yard.) complete all as specified & directed. |
| 75 | Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300msweep with, blades, and frame and louvers of Make : Bajaj / Crompton /havells and also carefully taking down old /unsvitem of any make/model anddepositing it inMES store of AGE E/M (P)Jabalpur complete all as specified and directed. |
| 76 | Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) , Make : Havells , Atomberg, Bajajalso carefully taking down old /unsvitem of any make/model anddepositing it inMES store of AGE E/M (P)Jabalpur complete all as specified and direct |
| 77 | Supply and Fix in repairs driver for LED fitting 2 x 2 of 36/40/45 watt as per sample available complete all as specified and as directed. |
| 78 | Taking down carefully storage type water heaters (Geyser) of any type and make of capacity upto 50 Ltrs, after disconnecting their electrical and water connections.De-scaling the inner container, heating element, base assembly using diluted hydrochloric acid and cleaning thoroughly.Filling the inner container with water and detecting leakage including brazing as required to stop the leakage, if any, reassembling the geysers after replacing the un-serviceable spare parts, filling water and testing the geysers by applying pressure by means of hand/foot operated pump, to ensure leak proof. Refixing geyser in the same original position/location and making the electrical/water supply connections incl testing on completion complete all as specified and directed. Note : Items required to be replaced shall be measured and paid separately under relevent items of the Schedule. |
| 79 | Supplyonly Thermostat suitable for Geyser 25/35/50 ltrcomplete all as specified and directed. |
| 80 | Supply only Geyser Element 1000/1500 Watt of any typecomplete all as specified and directed.. |
| 81 | Supply only Geyser connection pipe 12/18\"\" long with sockets in both end, made of steelcomplete all as specified and directed. |
| 82 | Supply and fixing in replacement of Unserviceable running capacitor 220-240 volt , 50 HZof 2.5 MFD capacity including taking down old running capacitor (Suitable for ceining fan/ ex fan)complete all as specified & directed. |
| 83 | Supply and fixing in replacement of Unserviceable running capacitor 220-240 volt , 50 HZof 4 MFD capacity including taking down old running capacitor (Suitable for ceining fan/ ex fan )complete all as specified & directed. |
| 84 | S&F in repair LED bulk head luminaires 10 W 6000k Environmental friendly, ultra modern, energy saving, surface mounted, decorative hexagon bulk head Back-lit LED luminaire comprising of high brightness LEDs complete all as specified & directed.Make-Havells Cat No.HEXAFT10WLED857SSYMBOPC or eqvt make Philips/Wipro/Havells |
| 85 | Supply & fix in replacement ofBldg LED Security Light Luminaire 45 wattwith 4500 or more lumen warm white, surge protection device upto 4KV, IP65/66 or more, IK07 or more, potted driver suitable for 180 to 270 V, 50 Hz, light engine driver base.pole adapter, powder coated pressure die cast aluminium with heat resistant toughened glass with lens type,GI pipe 25 mm dia medium Grade not less than with 1.2 m.long in any shape with 2 nos ofpole fitting clamps made out of MS flat , nutsand boltsand painting with aluminium paint. complete all as specified and as directed.Make: Philipscat part no: BRP029 LED45/WW MRPSU GR DX or havells cat part no.ENDURASUNDOWNSL45WLED765PASYBOPCIHD or equivalent in wipro/GE |
| 86 | M&L in repairfor GI Tubes,of size 40 mm dia light grade, galvanised, with all fitting , laid in trenchesfor protection of cable in road /drain crossing complete all as specified and as directed. |
| 87 | M&L in repair earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 4 mm dia by means ofnut, bolts, check nuts and washers of galvanised iron or steel complete all as specified and directed including testing on completion including the material and labour of the following complete all as specified & directed : - (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 15 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing. |
| 88 | M&L for providing earthingfunnel with all relevent items and PCC cover including white wash and writing Earth pit No including testing of earth resistance complete including removing complete all as specified and directed. |
| 89 | Taking down carefully unserviceable FLP point wiringincluding making good to disturbed surfaces, matching with existing. Note - Accessories viz switch, Sockets fittings etc shall be measured separately). complete all as specified and directed. |
| 90 | Taking down FLP submain wiring any type and in any size including making good to disturbed surfaces, matching with existing complete all as specified & directed. |
| 91 | Taking down old unserviceable FLP DBs/Main switches any type/size complete with all accessories and remove from site complete all as specified & directed. |
| 92 | Material and labour for point wiring for explosive atmosphere with 1100 volts grade, PVC insulated single core FRLS cable with stranded copper conductor of size2.5 sqmm drawn through and including ERW rigid stove enamelled steel conduit of size 18/19mm dia with bends, elbows, couplings etc., duly approved by CMRI Dhanbad and as per IS, fixed with PVC FRLS, insulated unsheathed multi stranded copper conductor cable of 2.5 sqmm as an earth wire connected to common earth and earth dolly as per IS specification for one light point controlled by one switch complete all as specified & directed. |
| 93 | Supply and fixing in repair LED light fitting 2x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size flexible metalic hose conduit from juction box to tube light fittings not less than 500mm long of size complete all as specified & directed. |
| 94 | Supply and fix in repairs flexible metalic hose conduit from junction box to tube light fittings not less than 500mm long of size M20/3/4\" conduit M x M / FM x M / F 500mm duly approved by CMRIDhanbad complete all as specified & directed.Make :- Sudhirbaliga/ FCG power/ Shyam swich gear. |
| 95 | M&L for flame proof 3/4 way lighting junction box in cast aluminium alloy LM-6 material size 3/4\" ET,100 mm dia, with terminal/connectors 6 Nos, 4Sqmm terminals with flanged cover, earthing external 02 Nos and internal 01 No, 2 Nos 3/4\" ET entry hardware in stainless steel with anti corrosive epoxy powder coated with protection IP-65 equipmet standard as per IS 2148/81 alongwith suitable size flame proof double compression cable gland heavy duty for gas group I/IIA/IIB/IIC approved by CCE and certified as flame proof by CMRI Dhanbadcomplete all as specified and directed.by Engr-in-Charge. Make: Sudhir / Baliga/FlexproNote: The rate quoted shall be inclusive for GI brackets suitable size and fixtures complete all as specified and directed. |
| 96 | M&Lfor submain wiring for explosive atmosphere with two single core 6 Sqmm multi stranded copper conductor, FRLS, PVC insulated, unsheathed cable, ISI marked, drawn into ERW steel conduit including 6 Sqmm FRLS, PVC insulated and unsheathed stranded copper conductor as earth wire in surface/recess making good to the disturbed surfaces to match the existing surfaces complete all as specified and directed. Note : Two runs of 6 Sqmm copper conductor cable, one run of 6 sqmm copper conductor and one run of steel conduit will be measured as one unit. |
| 97 | S&F in repair Switch flame proof rotarytype with termination box inLM6, 16A, single pole 250V complete all as specified & directed. |
| 98 | Supply and Fix in repair flame proof switch, socket and plug combined in LM-6 of capacity 16 amps, 240 Volts, Single phase (2P+Earth) with suitable entry of steel conduit 25mm dia and connecting up complete all as directed. |
| 99 | Supply and Fix in repair flame proof switch, socket and plug combined in LM-6 of capacity 63 amps, 415 Volts, three phase (2P+Earth) with suitable entry of steel conduit 25mm dia and connecting up complete all as specified and directed. |
| 100 | S&F in repair wall mountedflame proof fan 16\"\", 0.25 HPsingle phase ,250V complete all as specified and directed also carefully taking down old /unsvitem of any make/model anddepositing it inMES store of AGE E/M (P)Jabalpur complete all as specified and directed. |
| 101 | Supply and fixing in repairs sheet metal enclosureVTPN DBdouble door suitable for MCCB incomer 160/200 Amp, 415 Volts with 200A rated busbar complete with following accessories all as per requirement complete all as specified and directed. |
| 102 | Suuply and fix in repairs LED flameproof Flatglass type 30W, 230 V, suitabe for gas grp IIA and IIb, Zone 1 and 2, die casting aluminium housing with heat resistant toughned glass /domeglass/external reflector IP-65 protectionfittings to be fixed in hanging with ceiling/fixing in wall any type and providing some hanging /fixing arrangements for the same complete all as specified and directed. |
| 103 | Supply and fix F lame proof exhaust fan, steel body AC single Phase. 230V of size 450 mmsweep with, blades, and frame and louvers of Make :Sudhir, Crompton and also carefully taking down old /unsvitem of any make/model anddepositing it inMES store of AGE E/M (P)Jabalpur complete all as specified and directed. |
| 104 | Suuply and fix in repairs LED flameproof Flatglass type 40W, 230 V, suitabe for gas grp IIA and IIb, Zone 1 and 2, die casting aluminium housing with heat resistant toughned glass /domeglass/external reflector IP-65 protectionfittings to be fixed in hanging with ceiling/fixing in wall any type and providing some hanging /fixing arrangements for the same all a per requiredcomplete all as specified and directed. |
| 105 | Supply and fix in repairs FLP DB TPN 4 way, 415 Volts with 200 ams rated bus bar, for gas grp IIA and IIB, Zone 1, 2 die casting aluminium housing with, IP 45 degree protection, suitable for incoming cable upto 70 Sqmm 3.5 core including fixing on wall using suitale fixing arrangements all as specified and directed complete with following accessories :-Incoming: MCCB TPN-100 A, -1 No. 10 KAOutgoing: (a)MCCB TP 63 A -1 No., 10 KA(b)MCB TP 32 A -1 No., 10 KA(c)MCB DP 16 A -1 No., 10 KA |
| 106 | Material & labour in repair for air termination, single pointed, aluminium rod 12 mm dia and 300 mm long including fixing arrangements complete all as specified and as directed. |
| 107 | M&L in repair for test point terminal block made of gun metal or phosphorus Bronze size 75 x 75 x 25 mm drilled and screwed including 3 Nos, 8 mm dia 25 mm long hexagonal head screw and brass bolts, nuts , washers suspended on down end earth conductor on insulator on either ends conected to existing aluminium or GI strip complete all as specified & directed. |
| 108 | S&F in repair earth continuity conductor or main earth lead of aluminium strip 25 x 3 mm with saddles and fixing screw etc for roof conductorand down conductor fixed to wall on batten or recess or ground for connecting earthing to various equipments as required complete all as specified & directed. |
| 109 | M&L in repair earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below ground level, connecting GI strip of size 32mm x 6mm from earth plate to body of the equipment by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40 mm bore GI light grade pipe for protection of earth lead from earth plate(6 mtrs long), 20 mm GI light grade watering pipe, PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in earhing pit, PCC cover, charcoal or coke & salt fillingand necessary excavation and earth work and all other relevant works including testing all as specified and shown in electrical plate No.3 of MES Schedule Part-I.connected to earthing test point all as specified or indicated including testing on completion complete all as specified & directed. |
| 110 | M & L for Prefabricated Covered perforated /non perforated type Gl cable trays of size 60mmx30mmx2mm for fixing electric cable /conduits including required clamps , screws etc all as directed and completed. |
| 111 | S& F in repairLED highbay luminaire 70 Watt , 50 Hz , 220V with PC Diffuser & 150 lm/W efficacy. Equipped with 4 kV in-built surge protection, IP65 Protection rating. Complete all Specified and directed . |
| 112 | Schedule of credit of amount Rs. 24,851.00 to be deducted during AOC. |