Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 04-09-2025 | Corrigendum_4 | Date | 15-09-2025 |
| 2 | 04-09-2025 | Corrigendum_3 | BOQ | 15-09-2025 |
| 3 | 29-08-2025 | Corrigendum_2 | BOQ | 11-09-2025 |
| 4 | 27-08-2025 | Corrigendum_1 | Date | 11-09-2025 |
| Sl. No. | Item Description |
| 1 | SCHEDULE \"A\" Part - I (BUILDINGS/STRUCTURES WORK)Details of Buildings are given here-in-before:- |
| 2 | Construction of 01 block of Sub station building in including toilet in single storey configurationwith RCC framed structure and permanent specification complete all as specified and as shown in drawing. |
| 3 | Construction of 01 block of Car Parking(For 03 Cars) in single storey configurationwith RCC framed structure and permanent specification complete all as specified and as shown in drawing. |
| 4 | Construction of 01 block of Scooter Parking(For 17 Scooters) in single storey configurationwith RCC framed structure and permanent specification complete all as specified and as shown in drawing. |
| 5 | SCHEDULE \"A\" PART- II ( SITE CLEARENCEAND AREA DEVELOPMENT) Details of prepriced Schedule is given in tender documents |
| 6 | SCHEDULE \"A\" PART- III(INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents |
| 7 | SCHEDULE \"A\" PART- IV(INTERNAL WATER SUPPLY)Details of prepriced Schedule is given in tender documents. |
| 8 | SCHEDULE \"A\" PART-V (ROAD/PATH/CULVERT )Details of prepriced Schedule is given in tender documents. |
| 9 | SCHEDULE \"A\" PART- VI (AREA DRAINAGE)Details of prepriced Schedule is given in tender documents. |
| 10 | SCHEDULE \"A\" PART- VII(SEWAGE DISPOSAL)Details of prepriced Schedule is given in tender documents. |
| 11 | SCHEDULE \"A\" PART- VIII (SECURITY FENCING AND GATE)Details of prepriced Schedule is given in tender documents |
| 12 | SCHEDULE \"A\" PART- IX(FIRE POINT SHED)Details of prepriced Schedule is given in tender documents |
| 13 | SCHEDULE \"A\" PART- X(COVERED REFUSE BIN)Details of prepriced Schedule is given in tender documents |
| 14 | SCHEDULE \"A\" PART- XI(EXTERNAL ELECTRIFICATION)Details of prepriced Schedule is given in tender documents. |
| 15 | SCHEDULE \"A\" PART- XII(LIGHTENING PROTECTION)Details of prepriced Schedule is given in tender documents. |
| 16 | SCHEDULE \"A\" PART -XIV (MISCELLANEOUS ITEMS)Note:- Srl Item No.2.00 to 4.00 and Schedule XIII and this scheduleis not pre-priced by MES and the pre-priced rate indicated as \"Rs 0.00\" under Col.\" F \" signifies this fact only. |
| 17 | INTERNAL ELECTRIFICATIONSupply and fixing Modular metal flush box with modulat white cover plate with frame 8 module, completeallasspecifiedandasdirected. |
| 18 | S&F LED security light fitting not less than1X35 watt with integral reflector made of alluminium alloy LM6 with LED dirver, lamp, surge protector and all accessories pre wired including connection with three core PVC insulated, sheathed copper conductor cable of suitable size complete with GI bracket 1.5 meter long bend to shape of dia 25/40 mm GI medium grade pipe with MS clamp all as specified and directed. |
| 19 | Supply and fix MCB 230 Volts, 50 Hz, SPN, 16 Amps, 10 KA with \"C\" curve complete all as specified and directed. |
| 20 | M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x6mm thick elecrode and 4 mm dia galvanised iron wire as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI wire 4mm dia as earth lead by means ofbolts, nuts, check nuts and washers of galvanised iron or steel and connected to board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing Medium grade for watering and 15mm GI tubing Light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I (2020) complete all as specified and directed. |
| 21 | INTERNAL WATER SUPPLYS&F angle valve of 15mm bore, cast copper alloy with crutch or burret handle, chromium plated with long shank and cup, fancy type, screwed down, high pressure, screwed both ends for iron pipe or for brass ferrule complete all as specified and directed. |
| 22 | SEWAGE DISPOSALM&L for RCC Septic tank with flow filter of 50 users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls , Base Slab , Baffle walls and Roof Slab including beams etc with Vent shaft , manhole openings with cover connection etc., complete with effective depth of 1.5 meter and overall depth of 3 meter, complete all as specified and directed. |
| 23 | M&L Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M 30 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M30 SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 1.20 m dia x 3 m deep, complete all as specified and directed. |
| 24 | EXTERNAL ELECTRIFICATIONSupply, installation, commisioning and testing of HT 33 KV ,3 phase, 50 cycles totally enclosed metal clad outdoor type SF6 Switchgear of rating 630Amp, 26.3KA. PCVCB with Manual/230V AC Motor Operated Spring Charging Mechanism with 110V DC Closing /Opening Shunt trip coils, Aux. Switch, Mechanical On/Off Push Button, and mechanical Operating Counter and with hot dip galvanized Base Fram having Rupturing capacity upto 350 MVA, overload and earth fault protection, ammeter, voltmeter complete withcontrol relay indoor panel for 33KV PCVCB with following measuing and protection devices complete all as specified and directed :-(i) Metering(a) Digital Ammeter with selector switch.(b) Digital Volt Meter with selector Switch.(ii) Protection(a) 2 OC + 1 EF Relay (Micro Processed based Non-Directional IDMT).(b) Master Trip Relay Model No. - AVAJH - 13. (c) 8 Window Annunciator Model No. SI-80.1 (iii) Indication Lamps(a) VCB off / on / auto trip/ Trip circuit healthy/spring charge indication.(b) Buzzer.(c) Breaker control switch (T-N-C).(d) Local Remote Switch.(e)Power pack – 230V AC- 110V DC.(f) Control Wiring with appropriate colours.(g)Space Heater with ON/OFF Switch and Thermostat, Single phase switch with socket, LT Cubical illumination Lamp with Door Limit switch and MCB’s for AC / DC Control.(iv) MS Steel Sheet enclosure suitable for Indoor Installation.(v)Earth Bar Aluminium – 40x6mm. |
| 25 | Supply and installation of 33 KV, single phase, out door oil cooled CT of ratio 400/5- 5 Amp, class 1.0 / 5P10, burden 15 VA (For 02 no HT 33KV VCB), complete all as specified and directed |
| 26 | Supply and installation of 33 KV, singlephase, out door oil cooled PT of ratio 33KV/rt3/110 V/rt3/110/rt3, class 0.5-3, Burden 50VA(For 02 no HT 33KV VCB), complete all as specified and directed |
| 27 | Supply, installation, testing and commissioning power transformer double wound with copperwinding outdoor type complete filled with oil with standard fittings, HT 33KV secondary 11KV, 3Phase with On load tap changer (OLTC) (in range +5% to -15% in stpeof 1.25%) with remote tap changer (RTCC) panel and automatic voltage regulator (AVR),all as per IS:2026ofcapacity 3150 KVA, step down outdoor type floor mountinh ,double copper wound core type 3phase50Hz AC oil innersed with IS :335 ISI mark filtered & dehydrated transformer oil with ONAN type cooling with external cooling tubes/radiators having nolaod voltage ratio 33/11KV (corresponding to princial tapping) delta connection on primery side (HV connection) Star connection on secondary side(Secondary outgoing) inaccordance with vector group symbol (DYN-11) confirming to IS :2026 (EEL-2)and including initial oil filling to approprite level ,control cable and following standard fittings complete all asspecified and directed including following(Transformer for HPR))(a)Oil conservator with oil filling hole cap and drain plug(b)01 No prismatic oil level gauge mounted on conservator wall with first fill of charge up to maximum level(c) Silica gel dehydration breather with oil seal and first fill of charge(d)Pressure release valve with automatic resetting arrangement after relaese of pressure-01 set(e)Adequate number of thermometer pocket including one thermometer (f) Top oil filter valve(g) Botom oil filter cum drain valve(h) Rating diagram and terminal markingplate(i) Earthing terminal 04 Nos (j) Lifting lugh - 02 set(k) Jacking pads 01 Set |
| 28 | (Srl Item No. 27.00 Contd...)(l) under carriaige with 04 Nos plain roller(m) Air relige plug on main transformer tank (n) Adequate No of cooling radiatores (o) 100mm dial type oil tramperature indicator with maximumread pointer and reseting device(p) Air insulated cable box on HV and LV side(q) Buchholz Relay (having Contacts for Alam & Trip), DMCR Relay(r)OTI (Heving Contacts for Alam & Trip)(s) WTI (having Contacts for Alam & Trip)(t)Marshalling Box (Having TTB Only)(u) On Load Tap Changer (OLTC) + Remote Tap Cubicef Changer (RTCC) Psnet+ Autormatic Voltasge Regulator (AVR)(v) HV Bare Bushing- . ( Location :- HPR Sub Stn)Note : Routing test shall be carried out as per IS 1180. NOTE :- (i) Pre-dispatch inspection at OEM facdtory premises shall be carried out by Rep of Accepting officer.(ii) Prior to manufacturethe contractor shall get the general errangement , drawing and design details of the transformer approved grom GE(iii) After installation of Transformer at site, the pre-commissioning test shall be carried out by SEI/EI.(iv) Cost of necessary plinth foundation for the transformer shall deemed to be included in quoted rates. |
| 29 | Supplying, Installation, Testing & Commissioning indoor type panels shall be constructed from CRCA /Aluminium Zinc coated steel of 2mm thickness, floor mounted metal enclosed ,11 KVVCB panel with VCBs (2 INCOMER, 1 BUSCOUPLER, & 3 OUTGOINGS), totally enclosed and fully interlocked, horizontal draw outhorizontal isolation type breaker as per IEC-62271-1 100,200, as amended upto dateand additional Specification , having capacities as mentioned below, single break, Trip free mechanism, manually charged and manually closing breaker suitable for use on 11 KV, 3 phase, 50 Hz A.C. supply with short circult fault level of 26.3KAfor 3 sec with under voltage relay, overvoltage relay, panel shall be full internalarc tested i.e.in all three chambers at 26.3KA for 1 sec for safety purpose (AFLR), complete with self concained, fully interlocked, rack in and rack out mechanism, air insulated HT sleeved (PVC sleeveis not accepted) self supported cu busbars of 630 amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip coll and auxillary switch of 4 NO +4NC and ccouipped with flooowing switchgears and accessories Make of Vacuum interrupter, circult breaker, Panel, relays & maters shall be same. Cable compartment suitablefor 2RX3C x 240 sq. mmXLPE 11 KV cable (Cable entry from bottom) end termination with heat shrinkable jointingmaterial etc as reqd. There must bea viewing window on VCB chamber door and same must be as per internal arc test report. The basicinsulation level of entre panel shall be 25 KV(RMS)/ 75 KV (Peak) (a)Incoming - 2 No - 630 Amp VCB from twopower Transformers. (a)Buscoupler 1 No + 1 Bu Raiser with VCB 630A. Outgoing - 3 No 630 Amp VCB (one outgoing for mainTransformer , one for standbyTransformer and one outgoing for spere for work load) (11 KV PT to be provided for eachincomer and Double core CT of ratio 300-150/1-1 A to be provided for each VCB complete all as specified and directed. |
| 30 | (Srl Item No. 29.00 Contd...)(i) Incoming - 2 Nos VCB and each shall be consisting of(a) 630Amp VCB- 01 Nos(b) 11 KV/110 Volts PT Cable 0.5 accuracy and 50 VAburden with 1 No. Voltmeter (0-15 KV), digitel type selector for voltmeter andProtection fuses/ MCB for HT metering upto12 KV on incomer, (0.50-100A) comply with IS 3156. PT must not be on the top of the panel. It mustbe floor rooled placed rear side of panel or on the CB trolley - 1 Set(c) Degitel type multi function meter andDegital type Ammeter & Voltmeter -01 No(d) Flusn mounted type Microprocessor basednumeroial IDMT relay (VCB panel manufacturer\"s own Make) with O/L and S/C communicable on modus protocal for prolection and status monitoring with Master trip and Trip CklSupervision relay . Relay shall have programable 4 digital inputs and 6 outputs-1 No(e) Dual core/ single core, sepsrete set, dual retio 3 Nos CTs 200/100/1A of 5 VA burden and accuracy clase 0.5 for meteringand class SP10 for protection comply wit IS 2705-1 set(f) R.Y.B ON, OFF , Trip indication with control MCB-1 set(g) A nnunciator -8Window-01 set(h) Powerpack with 220V AC input & 110V DC continios output suitable for closing /tripping/indication etc(ii) Bus coupler-01 No(a) 630Amps VCB -01 Nos(b)Digital type multi function meter & Digital ammeter -01 Nos(c) Flush mounted Microprocesser based numericla IDMT relay with O/L,E/L and S/C ,Arc fault protection communicable on modbus protocat for protection and status monitoring with master trip and trip ckt supervision rlay.Relay shall have programable 4digit input and 6 output-01 Nos |
| 31 | (Srl Item No. 29.00 Contd...)(d)Dual core dual ratio 100/50/1 A of 5VA burden and accuracy class -0.5 for metering and class5P10 for protection-03 Nos(e) Annuncator-8Windows-01 Nos(f) Hooter-01 Nos(g)Flush mounted Aux Relay as required for OTI,WTI & Buchloz alarm & Trip functions(h) Trip supervision relay-01 Nos(i) Powerpack with 220V AC input & 110V DC continios output suitable for closing /tripping/indication etc.-01 set(iii) Outgoing-03 Nos 630Amps VCB and each shall be consisting of(a) 630Amps VCB -01 Nos(b)Digital type multi function meter & Digital ammeter -01 Nos(c) Flush mounted Microprocesser based numericla IDMT relay with O/L,E/L and S/C ,Arc fault protection communicable on modbus protocat for protection and status monitoring with master trip and trip ckt supervision rlay.Relay shall have programable 4digit input and 6 output-01 Nos |
| 32 | (Srl Item No. 29.00 Contd...)(d)Dual core dual ratio 100/50/1 A of 5VA burden and accuracy class -0.5 for metering and class5P10 for protection-03 Nos(e) Annuncator-8Windows-01 Nos(f) Hooter-01 Nos(g)Flush mounted Aux Relay as required for OTI,WTI & Buchloz alarm & Trip functions(h) Trip supervision relay-01 Nos(i) Powerpack with 220V AC input & 110V DC continios output suitable for closing /tripping/indication etc-01 set Note:- Configuration and schematics of panel shall be approved from GE before fabrication(ii) Any other parts/items not specified above but havebeen required essential for smooth and safe functioning of panel system shall be quoted rate.(iii) The VCB will be tested at site as primery injector system and relay will be set as per load requirement.(iv)Panel should have heating element with thermostat to avoid moisture condensation in the panel(v) Predispatch inspection, at OEM factory premises shall be carriedout by the Rep of Accepting Officer.(vi) After installation of VCB precommisioning test shall be carried out by SEI/EI |
| 33 | Supply, installation, testing and commissioning transformer of capacity 3150KVAstep down , outdoordouble wound with copperwindingcomplete filled with oil with standard fittings, HT 11KV secondary 0.433KV, 3phase50Hz AC oil innersed with IS :335 ISI mark filtered & dehydrated transformer oil with ONAN type cooling with external cooling tubes/radiators having nolaod voltage ratio 11/0.433KV (corresponding to princial tapping) delta connection on primery side (HV connection) Star connection on secondary side(Secondary outgoing) inaccordance with vector group symbol (DYN-11) confirming to IS :1180 Part-I (2014) or latest amendments (Level-II) and having off load tap changer in stpe of 2.5% on HV sied to take care ofvoltage from (+)7.5%to (-7.5%) to give output on 433V secondary sideand including initial oil filling to approprite level ,control cable and following standard fittings complete all asspecified and directed including following(Location :-Transformer for HPR))(a)Oil conservator with oil filling hole cap and drain plug(b)01 No prismatic oil level gauge mounted on conservator wall with first fill of charge up to maximum level(c) Silica gel dehydration breather with oil seal and first fill of charge(d)Pressure release valve with automatic resetting arrangement after relaese of pressure-01 set |
| 34 | (Srl Item No. 33.00 Contd...)(e)Adequate number of thermometer pocket including one thermometer (f) Top oil filter valve(g) Botom oil filter cum drain valve(h) Rating diagram and terminal markingplate(i) Earthing terminal 04 Nos (j) Lifting lugh - 02 set(k)Jacking pads 01 Set(l) Under carriaige with 04 Nos plain roller(m) Air release plug on main transformer tank (n) Adequate No of cooling radiatores (o) 100mm dial type oil tramperature indicator with maximumread pointer and reseting device(p) Air insulated cable box on HV and LV side(q) Buchholz Relay (having Contacts for Alam & Trip)(r)OTI (Heving Contacts for Alam & Trip)(s) WTI (having Contacts for Alam & Trip)(t)Marshalling Box (Having TTB Only)(Location :- HPR Sub Stn)Note : Routing test shall be carried out as per IS 1180. NOTE :- (i) Pre-dispatch inspection at OEM facdtory premises shall be carried out by Rep of Accepting officer.(ii) Prior to manufacturethe contractor shall get the general errangement , drawing and design details of the transformer approved grom GE(iii) After installation of Transformer at site, the pre-commissioning test shall be carried out by SEI/EI.(iv) Cost of necessary plinth foundation shall deemed to be included in quoted rates. |
| 35 | Supply laying and testing of Overhead covered AAAC conductor of size 185sqmm complete with all fixing accessories all as specified and directed. |
| 36 | Supply and fix HT 33 KV out door gang operated air-break switch 9 insulator rocking type horizontal mounting of 400 Amps rating worked from ground level with earth swich and locking arrangement, complete all as specified and directed |
| 37 | Supply and fix outdoor expulsion type drop out fuse with double stack of insulators mounted on channel base for 33 KV Line, complete all as specified and directed. |
| 38 | Supply, stringing and fixing on existing poles, ACSR conductor of anytype/sizeincluding fixing to insulatorswith binding wire complete for 33 KV, complete all as specified and directed. |
| 39 | Supply, fixing and testing post top insulator in three series including necessary connection with 33 KV distribution system, complete all as specified and directed.Note : Each insulator of 3 series shall be of 33 KV rating. |
| 40 | Supply, fixing and testing disc type insulator in three series including necessary connection with 33 KV distribution system, complete all as specified and directed.Note : Each insulator of 3 series shall be of 33 KV rating. |
| 41 | Supply, Installation, Testing & Commissioning of Compact Sandwich Type Busduct System, 6300A Copper conductor (3 phases +100 % Neutral + Integral Earth) 4 Nos Cu. bus bars , 2 Nos. Copper external earthing strips of suitable size, System voltage 415 Volt (Rated insulation & operating voltage 1000V), AC supply, rated frequency 50Hz, with \"F\" Class multi layer insulation, made of 1.6 mm thick sheet GI enclosure duly painted with powder coating (RAL-7032), IP-55 Including Bends, Neutral Rotation Elements, Flanged End, Adaptor Box etc to complete the work for termination between Transformer & main LT Panel. Compliance standard: IEC-61439 (Part 1&6) & IS- 8623 (Part 1&2),Independent Certification Authority : ASTA-UK /CPRI- India |
| 42 | Supply, Installation, Testing & Commissioning of Compact Sandwich Type Busduct System, 5000A Copper conductor (3 phases +100 % Neutral + Integral Earth) 4 Nos Cu. bus bars , 2 Nos. Copper external earthing strips of suitable size, System voltage 415 Volt (Rated insulation & operating voltage 1000V), AC supply, rated frequency 50Hz, with \"F\" Class multi layer insulation, made of 1.6 mm thick sheet GI enclosure duly painted with powder coating (RAL-7032), Indoor -IP 55 Including Bends, Neutral Rotation Elements, Flanged End, Adaptor Box etc to complete the work for termination between MAIN LT PANEL TO DISTRIBUTION PANEL . Compliance standard: IEC-61439 (Part 1&6) & IS- 8623 (Part 1&2), Independent Certification Authority : ASTA-UK /CPRI- India |
| 43 | Supply, Installation, Testing & Commissioning of Compact Sandwich Type Busduct System, 5000A Copper conductor (3 phases +100 % Neutral + Integral Earth) 4 Nos Cu. bus bars , 2 Nos. Copper external earthing strips of suitable size, System voltage 415 Volt (Rated insulation & operating voltage 1000V), AC supply, rated frequency 50Hz, with \"F\" Class multi layer insulation, made of 1.6 mm thick sheet GI enclosure duly painted with powder coating (RAL-7032), IP-66 Outdoor with External Canopy Including Bends, Neutral Rotation Elements, Flanged End, Thermal Expansion Unit, Adaptor Box etc to complete the work for termination between MAIN LT PANEL TO DISTRIBUTION PANEL . Compliance standard: IEC-61439 (Part 1&6) & IS- 8623 (Part 1&2), Independent Certification Authority : ASTA-UK /CPRI- India- India |
| 44 | Supply, Installation, Testing & Commissioning of Compact Sandwich Type Busduct System, 2000A Copper conductor (3 phases +100 % Neutral + Integral Earth) 4 Nos Cu. bus bars , 2 Nos. Copper external earthing strips of suitable size, System voltage 415 Volt (Rated insulation & operating voltage 1000V), AC supply, rated frequency 50Hz, with \"F\" Class multi layer insulation, made of 1.6 mm thick sheet GI enclosure duly painted with powder coating (RAL-7032), IP-55 Outdoor with External Canopy Including Bends, Neutral Rotation Elements, Flanged End, Thermal Expansion Unit, Adaptor Box etc to complete the work for termination between MAIN LT PANEL TO APFC PANEL . Compliance standard: IEC-61439 (Part 1&6) & IS- 8623 (Part 1&2), Independent Certification Authority : ASTA-UK /CPRI- India |
| 45 | S & F CU Braided Flexible (TPN) for Bus Duct 6300A, complete all as specified and directed. |
| 46 | S & F CU Braided Flexible (TPN) for Bus Duct 5000A, complete all as specified and directed. |
| 47 | S & F Support Structurefor Outdoor type Bus Duct complete all as specified and directed. |
| 48 | S&F of Automatic Power Factor Correction (APFC) Panel for 3 Phase, 415 V & 50 Hz system of capacity 650 KVAR with MDXL capacitor and ACB as incommer controller with following controlling.TP Circuit Breaker, 50KA, TM ОЛ & S/C Trip release of capacity 1600A -01 Nos12 S&F of Automatic Power Factor Correction (APFC) Panel for 3 Phase,415 V & 50 Hz system ofcapacity 650 KVAR with MDXL capacitor andDigital APFC Relay,3 CT, MP Based, with multifunction parameter 230V Aux. Supply with 12 stages -01 set A/M Selector Switch for Auto & Manual-01 Nos(а) Сараcitor Bank 5 KVAR-01 setTP MCCB 18 A, 25 KA, TM O/L & S/C release -01 NosCapacitor Duty Power Contactor, 5KVAR, 220V AC Coil with inrush current damping -01 Nos HD Harmonic Detuned Reator 5 KVAR (7% Cu Filtering Factor) 440V-01 Nos Power Capacitor, Cyl. Capacitor- HD Plus, 7.5 KVAR 480 V AC-01 NoIlluminated Switch For Manual Switching & Step Indication -01 set (b) Capacitor Bank 10 KVAR-02 setTР МССБ 32 A, 25 KA, TM O/L & S/C release - 02 Nos Capacitor Duty Power Contactor, 10 KVAR, 220V AC Coil with inrush current damping - 02 Nos HD Harmonic Detuned Reator 10 KVAR (7% Cu Filtering Factor) 440V-02 Nos Power Capacitor, Cyl. Capacitor- HD Plus, 12.5 KVAR 480 VAC-02 Nos Illuminated Switch For Manual Switching & Step Indication - 02 set |
| 49 | (Srl Item No. 48.00 Contd...)(c) Capacitor Bank 25 KVAR-01 setTP MCCB 63 A, 25 KA TM O/L & S/C release -01 NosCapacitor Duty Power Contactor, 25KVAR, 220V AC Coil with in rush current damping - 01 Nos HD Harmonic Detuned Reator 25 KVAR (7% Cu Filtering Factor) 440V -01 Nos Power Capacitor, Cyl. Capacitor- HD Plus, 30 KVAR 480 V AC-01 NoIlluminated Switch For Manual Switching & Step Indication - 01 set (d) Capacitor Bank 50 KVAR -04 setTP MCCB 125 A, 25 KA, TM O/L & S/C release - 04 NosCapacitor Duty Power Contactor, 50 KVAR, 220V AC Coll with inrush current damping - 04 Nos HD Harmonic Detuned Reator 50 KVAR (7% Cu Filtering Factor) 440V - 04 Nos Power Capacitor, Cyl. Capacitor- HD Plus, (30 x 2 )KVAR 480 V AC-04 Nos Illuminated Switch For Manual Switching & Step Indication -04 set (e) Capacitor Bank 100 KVAR-04 setTP MCCB 250 A, 25 KA, TM O/L & S/C release - 04 NosCapacitor Duty Power Contactor, 100 KVAR, 220V AC Coil with inrush current damping -04 NosHD Harmonic Detuned Reator 100 KVAR (7% Cu Filtering Factor) 440V-04 NoSPower Capacitor, Cyl. Capacitor- HD Plus, 100 KVAR 480 V AC-04 NosIlluminated Switch For Manual Switching & Step Indication -04 setAPFC Panel wi brindderope enclusure with CRCA Sheet Steel(11 Tank Processed) with Cu Bus Bar and ventilated fan complete all as specified and directed |
| 50 | Supply and fixing bracket for street light fitting of any size made out of GI pipe medium grade 40 mm dia, 1.5 mtr length bend to required size and shape including provisiob of clamps and fitting in position and including two coat of aluminum paint over a coat of red oxide primer, complete all as specified and directed. |
| 51 | Supply,installation,testing and commissioning 3 phase and neutral , 415 volts indoor type , CPRI approved,factory made free standing , floor mounting ,dust and vermin proof, cubical type LT Feeder Pillar of size not less than 2800 X 5000 X 1000 mm (H X W X D) fabricated from 2.00 mm thick CRCA sheetwith angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type,double door system,hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coatingwith pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 7000Amps ( Size of copper strip should not be less than 150 x 10 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands, cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following:- |
| 52 | (Srl Item No. 51.00 Contd...)(a)Incoming (i)ACB 5000 Amp, 4P, ICW FOR 3 SEC 65 KA (Manual Draw Out Type, Micro Processor release lsig along with position indication, spring charge indication switch, trip indication switch, door flange, safety shutter and with fault recording + LCD display) - 02 Nos(ii) Mechanical And Electrical interlocking arrangement for ACB 5000A, 4P - 02 Nos (iii)For synchronizing between 2 nos incoming ACB, ACB 5000a, 4P, ICW for 3 sec 65KA (manual draw out type, micro processor release lsig along with position indication, spring charge indication switch, trip indication switch, door flange, safety shutter and with fault recording + LCD display) - 03 Nos (iv) Panel mounteddigital multifunctional meter in 96X96 Sqmm flush mounted case SP, accuracyclass 1.0,0.5,voltage measuring rane 50-520VAC, CT secondary site suitable 1A/5A, programmable CT/PT to measure V,A, F, PF, kW, kVA, kWh/kVAh - 11 sets (v) Indicator Lamp - R - Y - B (Set of three).- 11 Sets (vi) Current Transformer 5000/5A 15VA Cl 1 (Set Of 3 Pcs) - 03 Set (vii) Current Transformer 4000/5A 15VA Cl 1 (Set Of 3 Pcs) - 02 Set(viii) Current Transformer 1600/5A 15VA Cl 1 (Set Of 3 Pcs) - 02 Set(ix) Current Transformer 320/5A 15VA Cl 1 (Set Of 3 Pcs) - 02 Set (x) Current Transformer 100/5A 15VA Cl 1 (Set Of 3 Pcs) - 02 Set(xi) MCB 6A, SP, 10KA FOR PROTECTION (SET OF 3 PCS) - 11 Set |
| 53 | (Srl Item No. 51.00 Contd...)(b)Outgoing(i) ACB 4000 Amp, 3P, ICW FOR 3 SEC 65 KA (Manual Draw Out Type, Micro Processor release lsig along with position indication, spring charge indication switch, trip indication switch, door flange, safety shutter and with fault recording + LCD display) - 02 Nos ( 1 Working + 1 Standby) (ii) Mechanical And Electrical interlocking arrangement for ACB 5000A, 4P - 02 Nos(iii) ACB 1600 Amp, 4P, ICW FOR 3 SEC 50 KA (Manual Draw Out Type, Micro Processor release lsig along with position indication, spring charge indication switch, trip indication switch, door flange, safety shutter and with fault recording + LCD display) - 02 Nos ( For APFC Panel + 01 Standby)(iii)MCCB 320 Amp, 3P, Icu=Ics= 36 KA / 38 KA (adjustable thermal magnetic release) + Rotary Handle + Spredaer links along with double protective layer for higher level safety and insulation voltage= 1000V - 02 Nos ( 1W + 1S) (iii)MCCB63 Amp, 3P, Icu=Ics=36 KA(adjustable thermal magnetic release)along with double protective layer for higher level safety and insulation voltage= 1000V - 02 Nos ( 1W + 1S) (For LT Panel 3) |
| 54 | Supply,installation,testing and commissioning 3 phase and neutral , 415 volts Ouydoor type , CPRI approved,factory made free standing , floor mounting ,dust and vermin proof, cubical type LT Feeder Pillar of size not less than 2000 X 5200 X 1000 mm (H X W X D) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shellwith angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type,double door system,hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coatingwith pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 6000Amps ( Size of copper strip should not be less than 125 x 10 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands, cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following. |
| 55 | (Srl Item No. 54.00 Contd...)(a)Incoming (i)ACB 4000A 4P, ICW FOR 3 SEC 65 KA (Manual Draw Out Type, Micro Processor release lsig along with position indication, spring charge indication switch, trip indication switch, door flange, safety shutter and with fault recording + LCD display)(ii) Panel mounteddigital multifunctional meter in 96X96 Sqmm flush mounted case SP, accuracyclass 1.0,0.5,voltage measuring rane 50-520VAC, CT secondary site suitable 1A/5A, programmable CT/PT to measure V,A, F, PF, kW, kVA, kWh/kVAh - 11 sets(iii) Indicator Lamp - R - Y - B (Set of three).- 11 Sets(iv) Current Transformer 4000/5A 15VA Cl 1 (Set Of 3 Pcs) - 01 Set(v) Current Transformer 600/5A 15VA Cl 1 (Set Of 3 Pcs) - 10Set(vi) MCB 6A, SP, 10KA FOR PROTECTION (SET OF 3 PCS) - 11 Set(b)Outgoing(i)ACB 500 Amp, 3P, ICW for 1 sec 50 ka (manual draw out type, Micro Processor release LSIG along with position indication, spring charge indication switch, trip indication switch, door flange, safety shutter and with fault recording +LCD display)- 10 No ( 8W + 02 S) |
| 56 | Supply,installation,testing and commissioning 3 phase and neutral , 415 volts Outdoor type , CPRI approved,factory made free standing , floor mounting ,dust and vermin proof, cubical type LT Feeder Pillar of size not less than 1000 X 1200 X 400 mm (H X W X D) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shellsheetwith angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type,double door system,hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coatingwith pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 400Amps ( Size of copper strip should not be less than 50 x 4 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands, cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following. |
| 57 | (Srl Item No. 56.00 Contd...)(a)Incoming (i)MCCB 320 Amp, 4P, Icu=Ics= 36 KA / 38 Ka (Adjustable Thermal Magnetic Release) + RotaryHandle + Spredaer links along with double protective layer for higher level safety and insulation Voltage= 1000V(ii) Panel mounteddigital multifunctional meter in 96X96 Sqmm flush mounted case SP, accuracyclass 1.0,0.5,voltage measuring rane 50-520VAC, CT secondary site suitable 1A/5A, programmable CT/PT to measure V,A, F, PF, kW, kVA, kWh/kVAh.(iii) Indicator Lamp - R - Y - B (Set of three).- 03 Sets(iv) Current Transformer 250/5A 15VA Cl 1 (Set Of 3 Pcs) - 03 Set(iv) Current Transformer 250/5A 15VA Cl 1 (Set Of 3 Pcs) - 03 Set(v) MCB 6A, SP, 10KA FOR PROTECTION (SET OF 3 PCS) - 03 Set(b)Outgoing(i)MCCB 320 Amps, 3 Pole, 4P, Icu=Ics= 36 KA / 38 Ka (Adjustable Thermal Magnetic Release) + Rotary Handle + Spredaer links along with double protective layer for higher level safety and insulation Voltage= 1000V -02 No ( 1W + 1 S) |
| 58 | Supply, install, testing and commissioning of LT outdoor Feeder Pillar Box AC 415 V, 50 Hz 3 Phase 4 wire,totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, protection IP 54 suitable for outdoor use double door type, with bottom cable entry with suitable cable glands outdoor structure made out of 3.15 mm thick CRCA steel sheet and indoor structure made out of 2.0mm thick CRCA steel sheet of minimum size (1.0x0.8 x 0.6) m with angle iron frame work and legs of ISA 50X50X5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter, changeover switch and MCCBs with sloping canopy at top, double hinged doors at front with suitable locking arrangement including louvers at sides duly powder coated complete for accomodating & including following accessories:- |
| 59 | (Srl Item No. 58.00 Contd...)INCOMER:-(a) Supply and fixing onload changeover open type 4 pole 415 Volts of 63Amps with 01 No :( for selecting outgoing between 02 Tarnsformers for sub stn panel)(b) Supply and fixing MCCB 4 pole 415 Volts with microprocessor controller of breaking capacity of 16 KA of 40Amps with adjustable overload setting : (0.8 - 1.0 x In) - 01 NoBUSBAR :-(i)Aluminium bus bar 200 Amps, supported on non hygroscopic fibres and brass screws for mounting - 04 NosINDICATING DEVICES:-(a) Supply and fixing LED Indicating lamps for Main Supplyindicating R, Y, B - 03 Nos(b)Supply and fixing Digital Ampere Meter of 0-125 A, 3 phase, class 1 with selector switch including CT having CTR 125/5 - 01 No(c)Supply & fixing Digital Voltmeter 0-500 Volts, 3 phase, class 1 with selector switch- 01 NoOutgoing:-(a) Supply and fixing MCCB 3 pole 415 Volts with of breaking capacity of 16 KA of 32 Amps with adjustable overload setting : (0.8 - 1.0 x In) - 03 No (b) Supply and fixing MCCB 2 pole 415 Volts with of breaking capacity of 16 KA of 16 Amps with Fixed thermal and Fixed magnetic setting- 02 No (c)Supply and fixing Astronomical Timer switch along with contactor 3P 32Amps, 415V, 50Hz for street light controlling |
| 60 | M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x6mm thick elecrode and 32mm x 6mm galvanised iron strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI strip 32mm x 6mm as earth lead by means ofbolts, nuts, check nuts and washers (including welding) of galvanised iron or steel and connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed. |
| 61 | M&L for earthing complete with copper plate 600mm x 600mm x 3mm thick electrode and 20mm x 3mm copper strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to copper strip 20 x 3mm as earth lead by means of tinned copper/ brass bolts, nuts, check nuts and washers (including brazing) connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed. |
| 62 | Supply and fix Pre Galvanized Ladder Cable Tray of size 75mm(H) x 750mm(W) x 3000mm(L) x 2.0mm(T) complete fixing on walls, complete all as specified and directed. |
| 63 | Supply and fix 75 Side Height Straight Connector for connecting cable trays,complete all as specified and directed. |
| 64 | Supply and fix 90 degree bend of size 75mm(H) x 750mm(W) - 90 Deg horizontal Bend for connecting cable trays,complete all as specified and directed. |
| 65 | Supply and fix TEE of size 75mm(H) x 750mm(W) - Cable ladder Tee for connecting cable trays, complete all as specified and directed. |
| 66 | Supply and fix cross over of size 75mm(H) x 750mm(W) - Cable Ladder Intersection for connecting cable trays, complete all as specified and directed. |
| 67 | Supply,installation,testing and commissioning Float cum Boost charger for DC Supply to HT VCB of capacity 24V 3 Ph with 12 Nos 2 V VRLA batteries complete with all accessories all as specified and directed. |
| 68 | Supply and fix cable junction boxes IP 66 “halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry) of minimum size 225 x 295 x 125 mmfor 16/25 sq.mm fixed to pole /wall with suitable FI clamp 20X3 mm nuts , bolts and washers including provision of 01 No miniature circuit breaker (MCBs) single pole , 240 volts 10 kA, 10 Amps and including minium 100 Amps aluminium busbar (04 Nos) with nuts, bolts & washers complete all as specified and as directed. |
| 69 | Supply and fixingPVC insulated and PVC round sheathed, copper conductor industrial cable 1.5 sqmm, three core of copper conductorfor connection of street lightfittings on pole / wall / pillar fromjunction boxincluding termination clip etc complete in all respect through GI tubing or all as specified or directed. |
| 70 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure, complete all as specified and directed. |
| 71 | S&F for cable route/joint indicator made of RCC slab of size 90 cmx 30 cm x10 cm embeded in ground on the route of cable duly marked with HT cable / HT cable joint , complete all as specified and directed. |
| 72 | Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm ,4 core, 1100 Volts grade, complete all as specified and directed. |
| 73 | S&F test point terminal box of size 200 x 100 x 100 mm made out of 2 mm thick hot dip galvanised sheet drilled and screwed including 6 Nos 15 mm long hexagonal head screws complete with test point terminal block made out of Gun metal or Phosphorus Bronze size 75 x 75 x 25 mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexagonal head screws, etc., complete all as specified and directed. |
| 74 | Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/cellings or laying in floors complete of size outer dia 90 mm including all fittings, complete all as specified and directed. |
| 75 | Supply and lay 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/cellings or laying in floors complete of size outer dia 63 mm including all fittings, complete all as specified and directed. |
| 76 | Supply and lay 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked ,IS-15801, PP-R pipes SDR 11 (PN-10) and PP-R plain fittings in trenches/walls/cellings or laying in floors complete of size outer dia 32 mm including all fittings, complete all as specified and directed. |
| 77 | Supply and fix PPR Gate Valves (Brass Insert) of 32 mm bore of outer Dia complete including all fittings, complete all as specified and directed. |
| 78 | Supply and fix PPR Gate Valves (Brass Insert) of 63 mm bore of outer Dia complete including all fittings, complete all as specified and directed. |
| 79 | Supply and fix PPR Gate Valves (Brass Insert) of 90 mm bore of outer Dia complete including all fittings, complete all as specified and directed. |
| 80 | Cutting or screwingexisting steel/PPR tubing for alteration or additions suitable size for 110/160 mm dia., complete all as specified and directed |
| 81 | Cutting or screwingexisting steel/PPR tubing for alteration or additions suitable size for 90 mm dia., complete all as specified and directed |
| 82 | Cutting or screwingexisting steel/PPR tubing for alteration or additions suitable size for 63 mm dia., complete all as specified and directed |
| 83 | Material and Labour for constrution of valves pit chamber of size (900 mm x 900 mm x 900 mm (internal dimension)using PCC (1:4:8) 40 mm graded stone aggregate for foundation 15 cm thick , 23 cm thick wall in CM (1:4), 10 mm thick rendering all around the brick work with 1:6 cement motar, PCC (1:2:4) type B1 coping with 20 mm graded aggregate, for grouting MS top sheet cover with locking arrangement including 50 mm pad lock with double key arrangement MS frame out of 40 x 40x 5 mm thick angle iron including paintaing of steel surface with two coats of synthetic enamel paint over a coat of red oxide primer finishing coat including necessary excavation in any type of soil, returing filling in and removal of surplus soil to adistance not exceeding 50 mtrs all as specified and including demolition / dismantling of existing craked valve chamber complete all as specifeid and directed. |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy