| 1 | Taking down carefully copper / Aluminium point wiring including (light, fan, socket or power complete fittings, such as switches, ceiling roses, pendant holders, Batten holders, shades conical fan regulators, light or power sockets etc) removing materials from site and making good disturbed surfaces of walls roofs etc all as directed. |
| 2 | Taking down carefully UNSV main switch and DB\"s including MCBs of any size make, type and capacity and depositing at site as directed. |
| 3 | M & L for concealed point wiring complete with multistranded copper conductor (FRLS)1.5 Sqmm size PVC insulated unsheathed cable 1100 volt grade, conforming IS 694 & color code in conduit system of wiring, drawn in includingPVC conduit not less than 20 mm dia concealed duly fixed with U-Clips, including cutting chases, finising of slote by means of cement mortormakinggood to the existing surface of the wall & touching with the existing colour of wall with three coats and making good disturbed surface complete, sunk in pressed steel terminal boxes of required size not less than 1.2 mm thick factory made and factory painted with top cover 3 mm thick plastic laminated sheet fixed with brass screw and washer with all accessories including single core multistranded copper conductor 1.5 sqmm size solid PVC insulated unsheathed cable (FRLS) as earth wire to common earth and connected to earth dolly drawn in same conduit complete all as specified for the followings:- |
| 4 | One light point controlled by one one/way switch. |
| 5 | One Fan point controlled by one one/way switch. |
| 6 | One 3 pin 5 Amps socket outlet on same board with other switch. |
| 7 | One 3 pin 5 Amps socket outlet on independent board. |
| 8 | One light point controlled by two way switches |
| 9 | One bell point controlled by one way switches |
| 10 | All as per item No. 3 above but using 2.5 Sqmm PVC insulated, unsheathed cable for one 3 pin socket outlet 15 Amps on independent board |
| 11 | M & L for point wiring complete with multistranded copper conductor 1.5 Sqmm size PVC insulated unsheathed cable 1100 volt grade, conforming IS 694 & color code includingPVC casing caping.the existing colour of wall with three coats and making good disturbed surface complete, sunk in pressed steel terminal boxes of required size not less than 1.2 mm thick factory made and factory painted with top cover 3 mm thick plastic laminated sheet fixed with brass screw and washer with all accessories including single core multistranded copper conductor 1.5 sqmm size solid PVC insulated unsheathed cable as earth wire to common earth and connected to earth dolly drawn in same conduit complete all as specified for followings:- |
| 12 | One light point controlled by one one/way switch. |
| 13 | One Fan point controlled by one one/way switch. |
| 14 | One 3 pin 5 Amps socket outlet on independent board with cable of 1.5 sqmm size. |
| 15 | All as per item No. 5 above but using 4 Sqmm PVC insulated, unsheathed cable for one 3 pin socket outlet 15 Amps on independent board |
| 16 | M & L forsub main wiring using two single core 6 Sqmm fire retardant PVC insulated and unsheathed cable with copper conductor 1100 volts grade ISI marked drawing in and including accessories like bends, tee, etc fix on wall and ceiling and connecting to earth dolly and including 6 Sqmm earth wire, PVC insulated & unsheathed all as directed. Note : (i) Two single core cable and one run of earth copper conductor will be measured and paid as one unit length |
| 17 | M & L forsub main wiring using two single core 4 Sqmm fire retardant PVC insulated and unsheathed cable with copper conductor 1100 volts grade ISI marked drawing in and including accessories like bends, tee, etc fix on wall and ceiling and connecting to earth dolly and including 4 Sqmm earth wire, PVC insulated & unsheathed all as directed.Note : (i) Two single core cable and one run of earth copper conductor will be measured and paid as one unit length |
| 18 | S&F switch piano flush type single pole one way 5 Amp 240 Volts. |
| 19 | S&F switch piano flush type single pole two way 5 Amp 240 Volts. |
| 20 | S&F switch socket combination 2 in 1, 3 pin, 5 Amps flush type 240 Volt. |
| 21 | S&F switch socket combination3 pin 5 and 15 Amp 2 in one flush with inbuilt indicating lamp. |
| 22 | S & F Bell switch including Bell ding dong type, one way, 240 volts, AC, ISI marked. |
| 23 | S&F ceiling rose surface bakelite three terminal 65 x 50 mm three terminal 250/230 volts ISI marked. |
| 24 | S&F ceiling fan condenser paper type 2.5 MFD |
| 25 | S&F Modular switch 1 way 6A, 1module |
| 26 | S&F Modular Socket, 6A - 2/3 pin combined 2module |
| 27 | S&F Modular Socket 6A/16A - 2/3 pin combined 2 module |
| 28 | S&F Modular Bell push 6A 1 module |
| 29 | S&F Modular Fan step regulator, 120W - 2 module |
| 30 | S&F Modular White cover plate with frame,1 module |
| 31 | S&F Modular White cover plate with frame,2 module |
| 32 | S&F Modular White cover plate with frame,4 module |
| 33 | S&F Modular White cover plate with frame, 6 module |
| 34 | S&F Modular White cover plate with frame,8 module |
| 35 | S&F Modular Metal flush box 1/2 module |
| 36 | S&F Modular Metal flush box 4 module |
| 37 | S&F Modular Metal flush box 6 module |
| 38 | M&L for opening covers of ceiling fan/Wall Fan, remove the burnt winding, cleaning the slots and rewinding the fan with supper enammeled copper wire of same wire gauge, warnishing after winding, drying, replacing unserviceable fan bearings No 6201/6202 for 250/1200/1400mm sweep, greasing, soldering the copper terminal of winding with single core copper multistraded wire of 0.5 sqmm and re-assembling fan, replace of fan capacitor 1.7/2.5mfd and making connection with fan capacitor and connector block,Including Painting fan and blade with super enamelled paint of two coats and marking of MES No, transoporting back after repair, assembling the blades and hanging the fan in its own position to existing fan clamp and down rod with necessary Nut, bolt and washer and testing for smooth functioning after complete repair all as ditrected at site.Note :Quoted rate deems to inclusive of rate of fan capacitor, fan bearing and transporatation charges. |
| 39 | M&L for opening covers of exhaust fan, remove the burnt winding, cleaning the slots and rewinding the fan with supper enammeled copper wire of same wire gauge, warnishing after winding, drying, replacing unserviceable fan bearings No 6201/6202 for 250 to 450mm sweep, greasing, soldering the copper terminal of winding with single core copper multistraded wire of 0.5 sqmm and re-assembling fan, replace of fan capacitor 1.7/2.5mfd and making connection with fan capacitor and connector block,Including Painting fan and blade with super enamelled paint of two coats and marking of MES No, transoporting back after repair, assembling the blades and hanging the fan in its own position to existing fan clamp and down rod with necessary Nut, bolt and washer and testing for smooth functioning after complete repair all as ditrected at site.Note :Quoted rate deems to inclusive of rate of fan capacitor, fan bearing and transporatation charges. |
| 40 | S/F in repair TPN DBs Vertical type 4 way with provision for FP as incomer and SP as outgoing all as directed. |
| 41 | S/F in repair sheet metal enclosure for single pole and neutral 08 way 240 voilts, 100 Amp rated bus bar. |
| 42 | S & F MCCBTPN 63 Amps 35 KA rupturing capacity 415 volt. |
| 43 | S & F MCB SPN 32 Amps 10 KA rupturing capacity. |
| 44 | S&F MCB SP 6 to 32 Amps 240V, 10 KA \"B\" curve Complete with connection testing and commissioning. |
| 45 | S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd. |
| 46 | M&L earthing complete with galvanized steel earth plate 600 x 600 x 6mm thick buried directly in ground pit not less than 2.25 m deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to & including galvanized iron strips 32 X 6 mm duly encased in 50 mm bore light grade GI protectionpipe both up to 7.5 mtr in length by means of nuts bolts check nut and wahsers of GI starting from earthplate to panel/transformer side all as specified and including necessary excavation earth work . PCC pit 40mm RCC cover made RCC (:2:4) type B1 using 20mm graded stone aggreagate concrete reinforced with 6mm dia bars 75mm C/C both ways with MS handle 12mm dia PGI funel wire mesh and GI pipe light grade 20mm for watering starting from top edge of the plate complete all as specified.The earth plate shall be surrounded with adequate quantity of charcoal dust with common saLV, packed on all side of earth plate in aLVernate layers of thick ness 15 cm each including excavation, earth work in any type of soil, returning and filling in, removal of surplus soil to a distance upto 50 mtr complete all as shown on electrical plate No. 5 of SSR Part- I 1991, Page No. 19 - 49 complete all as specified and directed. |
| 47 | Supply & Fix in replacement of 35 Watt LED Street Light fitting New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING seperate driver compartment with IP66 protection nominal voltage 240 volts, mains current 0.400 luminous efficiency >II3 lux/watts, potted electric LED dimmer (5MPS based constant current supply) with loner THD , CCT 5700 and impact resistance of IK07 with 10KV Built-in Surge Protection Device other safety tests as per IS 15885 Part-2/sec-13 Including bracket with clamp for fixing street light fitting made out of GI pipe of suitable size light grade including bending. |
| 48 | S&F7 W LED Bulb with system lumen output of 600 lumens. System Efficacy should be > 85lm/ W. TheLamp Should have Cool Daylight Colour temp of 6500K . |
| 49 | S&F 9 W LED Bulb with system lumen output of 600 lumens. System Efficacy should be > 85lm/ W. TheLamp Should have Cool Daylight Color temp of 6500K . |
| 50 | Supply and fixing round shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete |
| 51 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. |
| 52 | S&F of 4\" 20W LEDTube With Batten with system lumen output of 1800 lumens. System Efficacy should be > 115lm/ W. The Luminaire Should have Cool Daylight Color temp of 6500K & CRI>80.Life 40K burning hrs with 70% lumen maintenace. PF>0.95 Surge Protecton of 3KV.All the Photometrical & Electrical parametrs must be supported by LM79-08 test report from NABL Accridiated LAB OR UL, R9 Value > 0. Lamp starting time is not more than 1 Sec. The LED tube light conforms to applicable IS. |
| 53 | S&F of 2\" 10W LEDTube With Batten with system lumen output of 1800 lumens. System Efficacy should be > 115lm/ W. The Luminaire Should have Cool Daylight Color temp of 6500K & CRI>80.Life 40K burning hrs with 70% lumen maintenace. PF>0.95 Surge Protecton of 3KV.All the Photometrical & Electrical parametrs must be supported by LM79-08 test report from NABL Accridiated LAB OR UL, R9 Value > 0. Lamp starting time is not more than 1 Sec. The LED tube light conforms to applicable IS. |
| 54 | Taking down and refixing storage type water heater from wall by disconnecting the electric connection and water inlet/outlet connection from main and repairing the water heater storage type capacity 25/35 ltrs of any type and make, checking the serviceablity of all parts such as inner vesser, rubber gasket, non return valve, heating element, thermostat etc and refixing the same after replacing of unserviceable parts and assembly completet (considered as one unit) and installing and testing the same as per the direction of Engineer-In-Charge.(Supply only for parts against unserviceable parts shall be measured and paid for separately under relavent items given below) |
| 55 | S&F for replacement of heating elements, 1.5 KW 230 volts. Make -THEETA/BAJAJ. |
| 56 | S&F for replacement of thermostat immersion point type 15 Amps, 230/250 volts/AC ISI marked Make - THEETA/BAJAJ. |
| 57 | S&F in replacement louver shutter for exhaust fan of 20\"x20\" outer louver made out of MS sheet duly power coated budy for enhanced durability, longevity and 18\"x18\" inner shutter flapper mechanism ensures efficent air flow regulation and vntilation control made out of alluminium light weight for easy to open the air including nut, bolts, & washer as required and directe by Engr-in-Charge. |
| 58 | S&F in replacement louver shutter for exhaust fan of 14\"x14\" outer louver made out of MS sheet duly power coated budy for enhanced durability, longevity and 12\"x12\" inner shutter flapper mechanism ensures efficent air flow regulation and vntilation control made out of alluminium light weight for easy to open the airincluding nut, bolts, & washer as required and directe by Engr-in-Charge. |