supply installation testing and commissioning Of Lt Panel At Gokulpuri Bps-Supply, Installation, testing and Commissioning of Cubical Type Main Distribution cum Starter Panel, Indoor Type suitable for 415 Volt, 3 phase 4 Wire, 50Hz AC Supply System fabricated in compartmentalised design from 2MM thick CRCA Sheet of Size for frame work and covers, having gland plate not less than 2mm including cleaning and finishing complete with powder Coating in approved shade, having Main Bus Bar not less 250A capacity. The bus Bar shall be ofelectrical grade Aluminium, high conductivity fitted on DMC/SMC bus bar supports with short circuit withstand capacity of 31MVA for 1 Sec. Bottom base Frame of MS Section shall not be less than 75MM In Height. Entire panel shall have a common copper earth bus of suitable size at the rear with Earth stud on Both Sides, solid connections from main bus bar to switch gears with requires size of Aluminium Bus bar (Wherever required) and control wiringshall be done with 1.5 sqmm PVC insulated copper conductor single core cables.Including Providing and Fixing the following switchgear as mentioned below for 40 HP (pump set) : Switchgear Section. Main Incomer - i) 200A FP Change Over Switch. (Make: LK/Havells/HPL) : 1 Nos. ii) Indication Lamp for Phase Sequence Correction (Make: LK/ABB): 2 Nos. a) RED Indication Lamp, 220-240V A.C. b) GREEN Indication Lamp, 220-240V A.C. iii) 200A FP MCCB, 25KA Breaking Capacity, with Thermal Magnetic Release, bearing accessories such as Phase Seperators, Extended ROH and Spreader Terminals (Make: LK/ABB/Havells): 1 Nos.B8. iv) Phase Indication Lamps (Make: LK/ABB) : 3 Nos. a) R-Phase Indication Lamps. b) Y-Phase Indication Lamp. c) B-Phase Indication Lamp. v) 6A SP MCB, 10KA Breaking Capacity for Control Protection (Make: LK/ABB/Havells) : 3 Nos. vi) Multifuntion Meter with following parameters such as: (Make: Trinity/L&T/ABB) V, A, F, PF, kW, kVA, Old energy, Load hours, site selectable kWh/ kVAh. Vii) CT 200/5, CL 1.0, 05VA Burden value, tape wound type (Make: AE/Trinity) : 3 Nos. viii) Indication Lamp for MCCB (Make: LK/ABB): 1 Nos. a) RED Indication Lamp, 220-240V A.C. Outgoing Section - i) 100A TP MCCB, 25KA Breaking Capacity, Motor Protection type, with Thermal Magnetic Release, bearing accessories such as Phase Seperators & Extended ROH (Make: LK/ABB/Havells/DJB Approved): 3 Nos. ii) Three Pole Power Miniature Circuit Breaker, 10KA Breaking Capacity (Make: LK/ABB/Havells) : 6 Nos. Rating : 50A. iii) Power Contactors (Make: LK/ABB/Havells) : 3 Nos. Rating : 32A Aux Supply : 220-240V A.C, Type : AC-3 Duty. iv) Add-On block (Make: LK/ABB/Havells) : 09 Nos. Type : 2NO+2NC. v) Thermal Overload Relay with built-in Single Phasing Prevention (Make:LK/ABB/Havells) : 3 Nos. Rating : 20-33A. vi) 6A SP MCB, 10KA Breaking capacity for Control Protection (Make: L&T/ABB/Siemens) : 3 Nos. vii) Starter Indication Lamps, 220V-240V AC (Make: LK/ABB) : 9 Nos. Red : Starter ON Indication Green : Starter OFF Indication, Amber: Starter TRIP Indication. Viii) Push Button for Starter Operation (Make: LK/ABB) : 06 Nos. Red : Starter ON Push Button, Green : Starter OFF Push Button. ix) Auto manual Selector Switch (Make: LK(Salzer)/Vaishno) : 3 Nos. Rating : 6A. x) Star to Delta Conversion timer (Make:LK/ABB) : 3 Nos. Aux. Supply : 220-240V A.C. xi) 3 Phase Current Sensing Phase Failure Relay with Overload, Over Current, Phase Failure, Reverse Phasing, Current Unbalance, Lock Rotor, Stalling, Short Circuit, Earth Fault, Seperate Display with logging of last 10 faults with inbuilt CT 1 to 60 AMP. (Make: LK/Minilec) : 3 Nos. xii) Single Phase Digital Type Ampere Meter, 3 Phase 4 Wire System, Flush type 96 sqmm. (Make: LK/Trinity) : 3 Nos. Class : 1.0 CT Input: 5A,Aux. Volt : 220V, A.C., xiii) Ampere Selector Switch (Make: LK/Trinity) : 3 Nos. Rating : 6A. xiv) CT 100/5, CL 1.0, 05VA Burden value, tape wound type (Make: AE/Trinity) : 9 Nos. xv) Power Miniature Circuit Breaker Rating : 32A, TP, 10KA Breaking Capacity : 3 Nos. 2 Dismantling of existing L T Panel and electrical system after disconnecting incoming and outgoing connections, removing the existing material using labour tools and tackles etc. as per site requirement. 3 Charges for shipping the panel up to the site including labour, lifting charges, loading and unloading charges and other charges for shifting the panel up to the place it has to be installed. 4 Fixing of the new LT Panel with base frame at the site with the help of fasteners / welding and grouting of nut bolts and including all other work as per site requirements. 5 Making the incoming connections to both incomers the Panel by making required Cable connections between the main supply and the panel after laying and proper thimbling etc. of cable including providing & fixing of consumables as per requirement. 6 Fabrication and supply of base frame made out of angle iron of suitable size for fixing the above starters and suitable for making outgoing /incoming cable entries in the starter panels. It should be duly painted and ready with provisions for installing at the site. 7 Supply of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor Armoured power cable of 1.1 kV grade of following size as required (Make: Havells/Grandley/Polycab) a) 3.5C X 95SQMM 8 Supply of one number PVC insulated and PVC sheathed / XLPE Copper conductor Armoured power cable of 1.1 kV grade of following size as required (Make: Havells/Grandley/Polycab). a) 3C X 16SQMM 9 Laying & Fixing of one number PVC Insulated & PVC sheathed XLPE Power Cable of 1.1KV Grade of following size on wall surface including proper clamping etc. as required. a) 95sqmm to 185sqmm 10 Laying & Fixing of one number PVC Insulated & PVC sheathed XLPE Power Cable of 1.1KV Grade of following size on wall surface including proper clamping etc. as required. a) upto 35 Sqmm 11 Supplying and Making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed XLPE Aluminium conductor cable of 1.1KV grade etc. as required. a) 3.5CX95 Sqmm. 12 Supplying and Making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed XLPE Aluminium conductor cable of 1.1KV grade etc. as required. a) 3CX16 Sqmm. 13 Testing and Commissioning of the Panel Board first at NO LOAD and then at ON LOAD and Operations as per the satisfaction of engineer in charge.