| 1 | INTERNAL ELECTRIFICATION |
| 2 | Taking down point wiring with aluminum conductor cable of light point fan & socket light & power complete including light fittings any type switches, sockets, ceiling rose, switch boards, bell/buzzer, bell push, tube light fitting, regulator etc, and making good to the disturbed surfaces of walls/ floor etc to match with existing surfaces including white washing/colour washing/ distemper to match with existing wall/floor/ceiling finishes. |
| 3 | Taking down sheet metal enclosure DB, MCB, main switch etc and making good disturbed surfaces to match with existing surfaces. complete all as specified and directed. |
| 4 | Taking down sub main wiring of any size/ capacity complete all as specified and making good disturbed surfaces to match with the existing surfaces complete all as specified and directed. |
| 5 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed. Note :- laying of cable route is same as old cable route complete all as specified and directed. |
| 6 | M&L point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in and including electrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marked medium grade concealed on wall/ceiling including FRLSH PVC insulated unsheathed earth wire with multistranded copper conductor of size 1.50 sqmm pressed steel modular boxessunk on wall for mounting of modular switches, switch sockets, fan regulator etc including modular coverwith frame any size complete all as specified and making good disturbed surfaces for one light point controlled by one, one way switch. Note :- Cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate.All switches, fan, sockets, ceiling roses and holders shall be connected to common earth dolly. |
| 7 | As per item No 1.50 above but One ceiling /exhaust fan point controlled by one switch and regulator complete all as specified and directed. |
| 8 | As per item No 1.50 abovebut One 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed. |
| 9 | As per item No 1.50 above but One 3 pin 5 amps socket out let point on independent board complete all as specified and directed. |
| 10 | All as per item No 1.50here in before but wiring with 2.5 sqmm multi stranded cable and earth wire with copper conductor of size 2.5 sqmmfor 15 amps power point complete all as specified and directed. |
| 11 | As per item No1.50 above but One light point controlled by two way switches complete all as specified and directed. |
| 12 | As per item No1.50 abovebut One bell/buzzer point controlled by one bell push complete all as specified and directed. |
| 13 | M&L point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in existing PVC conduit concealed on wall/ceiling including FRLSH PVC insulated unsheathed earth wire with multistranded copper conductor of size 1.50 sqmm pressed steel modular boxessunk on wall for mounting of modular switches, switch sockets, fan regulator etc including modular coverwith frame any size complete all as specified and making good disturbed surfaces for one light point controlled by one, one way switch. Note :- Cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate.All switches, fan, sockets, ceiling roses and holders shall be connected to common earth dolly. |
| 14 | As per item No 2.20 above but One ceiling /exhaust fan point controlled by one switch and regulator complete all as specified and directed. |
| 15 | As per item No 2.20 abovebut One 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed. |
| 16 | As per item No 2.20 above but One 3 pin 5 amps socket out let point on independent board complete all as specified and directed. |
| 17 | All as per item No 2.20here in before but wiring with 2.5 sqmm multi stranded cable and earth wire with copper conductor of size 2.5 sqmmfor 15 amps power point complete all as specified and directed. |
| 18 | As per item No 2.20 above but One light point controlled by two way switches complete all as specified and directed. |
| 19 | As per item No 2.20 abovebut One bell/buzzer point controlled by one bell push complete all as specified and directed. |
| 20 | M&L for sub main wiring with two single core PVC FR LSH insulated unsheathed stranded copper conductor and earth wire 1100 volt grade and drawing into PVC conduit not less than 20 mm medium grade concealed inwall of the following sizes :- 2x2.5 Sqmm with earth wire of 1x2.5 Sqmm complete all as specified and directed. Note :- Accessories for point/sub main wiring like PVC junction box, bend, Tee, elbow shall be of same make. |
| 21 | As per item No 2.90 abovebut 2x4.0 Sqmm with earth wire of 1x4.0 Sqmm complete all as specified and directed. |
| 22 | As per item No 2.90 above but 2x 6.0 Sqmm with earth wire of 1x6.0 Sqmm complete all as specified and directed. |
| 23 | Supply and fix ceiling rose surface type 3 terminal 5 ampscomplete all as specified and directed. |
| 24 | S&F Bell ding dong,AC 230 volts, single phase complete all as specified and directed. |
| 25 | Supply and fix lamp holder insulated body with back plate suitable for angle/ batten fittingcomplete all as specified and directed. |
| 26 | Supply and fix Modular switch one way 6A, 1 module complete all as specified and directed. |
| 27 | Supply and fix Modular switch one way 16A, 1 module complete all as specified and directed. |
| 28 | Supply and fix Modular switch two way 6A, 1 module complete all as specified and directed. |
| 29 | Supply and fix Modular bell push 6A, 1 module complete all as specified and directed. |
| 30 | Supply and fix Modular Socket 6A 2/3 pin combined 2 module complete all as specified and directed. |
| 31 | Supply & Fix Modular Socket 6A/ 16A2/3 pin combined 2 module complete all as specified and directed. |
| 32 | Supply and fix Modular Fan step regulator,120 watt 2 module 5 step complete all as specified and directed. |
| 33 | Taking down carefully 20/10 watttube light fittings for reuse at site or carrying to the store complete all as specified and directed. |
| 34 | Refixing LED light fitting 20/10 watt 220 V AC decorative type with driver, holder and LED tubelight including connecting up with three core flexible copper conductor cable of suitable size from ceiling roses complete all as specified and directed. |
| 35 | Supplying and fixing 20 Watt LED Tube light fittings completewith aluminum body including tube rod, driver with not less than 2000 Lumen O/P andI/p rated voltage 240V connecting with3 core 1 sqmm copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 36 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 37 | Supplying and fixing 20 watt, 4ft LED inverter batten fittings, works on AC supply in Normal mode and DC supply in inverter mode, with inbuilt battery back up of upto 4 hours, high efficiency completewith aluminum body including tube rod, driver with not less than 2000 Lumen O/P andI/p rated voltage 240V connecting with3 core 1 sqmm copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 38 | Supply and fixing 20 watt, 4ft inbuilt sensor based smart LED auto dimmable batten, dimming from 100% of rated wattage to 30% on sensing of movement / occupancy, made from powder coated extruded aluminium housing, opaque glare free diffuser, pre wired with all accessories including tube rod, driver with not less than 2000 Lumen O/P andI/p rated voltage 240V connecting with3 core 1 sqmm copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 39 | Supply and fixing 3 watt LED goose neck wall light with chrome finish wall lamp housing with movable string, metallic base, complete with driver to operate on 240V AC 50Hz, suitable for indoor application complete all as specified and directed. Make : Jaquar Cat Part No. DWL-CHR-LBED01R003XW |
| 40 | Supply and fix building security lightLED25 W with Lumen O/P 1800 with driver withrated voltage 240 V, 50Hz,including mounting GI (made out of 25 mm dia light grade pipe 0.8 m bent two shape including FI clamps nut bolts etc. complete all as specified and directed. |
| 41 | Supply and fixsheet metal enclosure single pole & neutral for 240 volts 8 way with 200 Amp rated bus bar flush /surface mounting double door. complete all as specified and directed. |
| 42 | Supply and fixsheet metal enclosure triple pole & neutral for 415 volts 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed. |
| 43 | Supply and fixsheet metal enclosure vertical triple pole & neutral(VTPN) with MCCB 63 amps for 415 volts 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed. |
| 44 | Supply and fixMCB single pole 240 volt 6 to 40 amps 10 KA breaking capacity, \"C\" series complete all as specified and directed. |
| 45 | Supply and fixMCB single pole and neutral240 volt 6 to40 amps 10 KA breaking capacity, \"C\" series, complete all as specified and directed. |
| 46 | Supply and fixMCB triple pole and neutral 415 volt 40 to 60 amps 10 KA complete all as specified and directed. |
| 47 | Earthing complete with galvanized street earth plate electrode 600x600x6mm thick buried directly in ground (earth plate not less than 2.25mtr deep below normal ground level) with top edge of the plate not less then 1.50 mtr.below the normal ground level connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washer of galvanized iron or steel all as shown in electrical plate No 5 connected to earthing test point all as specified and testing on completion including the material and labour for :-(a) Excavation and earth work or drilling hole for electrode in any type of soil (b)PCC pit in cement concrete 1:2:4 TYPE B-1 (c)Pre cast RCC cover with suitable handle 40mm thick in PCC 1:2:4 reinforced with welded steel wire fabric weighting not less than 1.87 Kg/sqmm (d)Funnel with watering pipe of GI 20mm nominal bore medium grade and Aluminum lugs etc all as specified.(e)15mm nominal bore medium grade GI protection pipe up to 7.50 meter long for protection of earthing lead.(f)Requisite quantity of charcoal and common salt (g) Connection to earthing test point and testing on completion. |
| 48 | Disconnect and insulate electric supply wireand taking down carefully ceiling/exhaust/cabin/ wall fans of any make and sweep dismantling blades, check for repairs required Note : Repairs/ Replacement of spares shall be carried out under appropriate items complete all as specified and directed. |
| 49 | Hanging only ceiling fans of any make and sweep connecting the complete with & including provision of copper conductor cord 3 core PVC insulated and sheathed from ceiling rose to fan connector , painting with spray paint and testingMaking of MES No as directed and specifiedNote : The fan shall be fitted with new set of clamps rubber shackle split pins and top and bottom nut bolts etc. |
| 50 | M & L Painting of ceiling fan complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc complete all as specified and directed. |
| 51 | Opening up of fan motor of ceiling/Exhaust/ wall/cabin fans cleaning starter rotor, cleaning of all parts greasing oilingof bush and bearing reassembling and testing for smooth functioning complete all as specified and directed. |
| 52 | M&L for taken down burnt/damaged winding, cleaning stator and rotor including slots etc, rewinding with suitable gauge of super enameled copper insulated wire for ceiling fan 1200 mm sweep all as specified and as directed |
| 53 | Supply and Fix bearingof replacement for Ceiling fan 1200mm sweep complete all as specified and directed. |
| 54 | S & F gun metal bushfor ceiling fan 1200mm sweep complete all as specified and directed. |
| 55 | S & F for replacement of condenser AC 230 Volt 2.5 MFD complete all as specified and directed. |
| 56 | S&F ceiling fan blades 1200mm sweep complete with nuts and bolts as per sample complete all as specified and directed. |
| 57 | M&L for shaft work of ceiling fan of any make and sweep complete including filling metal and lathe machining complete all as specified and directed. |
| 58 | M&L for down rod for ceiling fan of any make and sweep made out of medium grade GI tubing 15mm dia duly painted with two coat of enamel paint and provision of holes for electric wire at top and bottom also arrangement for fitment of ceiling fans complete all as specified and directed. |
| 59 | Taking down carefully geyser/water heaterof any Maketype & size including disconnecting water connection plug water flow, for repairs and refixing the same to original position after repairs including decaling the inner tank and tubing and marking of MES No with synthetic enamel paint, black colour complete all as specified and as directed.Note:- (i) Spares required for replacement shall be measured and paid separately as Supply and Fix under respective items of this schedule.(ii) Quoted rates shall be deemed to be included for anyGIFitting, screwing, required during connecting/ disconnecting water supply. |
| 60 | Supply and Fixthermostat any type, suitable for geyser, ISI mark complete all as specified and as directed. |
| 61 | Supply and Fix PVC threaded tough rubber flexible pipe/ tubing of standard length 450 mm for geysers inlet/outlet connections complete all as specified and as directed. |
| 62 | Supply and Fix three pin plug top 15 amps complete all as specified and as directed. |
| 63 | Supply and Fix PVC insulated copper conductor PVC sheathed three core 2.50 sq mm flexible cable complete all as specified and as directed. |
| 64 | M&L for brazingthe inner tank of geyser of any size and type after thorough check of leak complete all as specified and as directed. |
| 65 | Supply and Fix water heaterelement any type ( Cup/ Triangular /square) of capacity2.0KW complete all as specified and as directed. (MAP Accn Type) |
| 66 | Supply and Fix non-return valvemade of brass 15mm dia ISI marked complete all as specified and as directed. |
| 67 | Supply and fix stop valve cast copper alloy, fancy type chrome plated screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed for 15 mm dia pipe complete all as specified and directed. |
| 68 | M&L for dusting / cleaning removing burrs on outer surface of geyser of any type complete for painting and spray painting with two coats of synthetic enamel paint of approved colour, for50 ltrs capacity complete all as specified and as directed. |
| 69 | M&L for dusting / cleaning removing burrs on outer surface of geyser of any type complete for painting and spray painting with two coats of synthetic enamel paint of approved colour, for25 ltrs capacity complete all as specified and as directed. |
| 70 | Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed |
| 71 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed |
| 72 | Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed . |
| 73 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 40mm outer diameter and 32 mm inner Diameterwith IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directedMake:- Dura. Line/Tijaria/REX/Ketron/SFMC |
| 74 | Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables ( heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 6 sq mm 4 core including testing after laid and jointed all as specified and as directedMake :- Gloster/ Polycab/Havells/KEI |
| 75 | Supply and fixing LED fittings IP 65 rated inverted Pyramid Tripod type LED Bollard (white/warm white) with soft 360 degree light distribution 9/10 Watt, 230V, 50Hz complete on suitable PCC 1:2:4 base alonwith suitable connectors to connect with 6sqmm x 4 core cable having protection from water and soil complete all as specified and as directed. Make : Crompton Cat Part No. LBLSN-10-CDLor equivalent make. |
| 76 | Materials and labour for earth continuity conductor or main earthing lead fixed to wall orbatten or recess or chases as required 25 x 3 mm Aluminium strip complete all as specified and directed. |
| 77 | Materials and labour for earth continuity conductor or main earthing lead fixed to wall orbatten or recess or chases as required 32 x 6 mm GI strip complete all as specified and directed. |
| 78 | M&LAir termination, single pointed aluminium rod 12 mm dia and 300 mm long complete all as specified and directed. |
| 79 | Material and labour for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex. Head screw.complete all as specified and directed. |
| 80 | S&L complete pipes, galvanised, medium grade including fittings 40 mm dia, including clamps, nuts, bolts, holes on pipe and fixing arrangement for mounting of Air Termination rod on roof/ recess complete all as specified and as directed. |
| 81 | S&L complete pipes, galvanised, light grade including fittings 40 mm dia, including clamps, nuts, bolts and fixing arrangement for cable protection on polescomplete all as specified and as directed. |
| 82 | S&F porcelain insulator of required size not exceeding 10 cm long with two Nos hole each on both end for fixing properly with nuts and bolts on wall of buildings for separated to lightining conductor or earthing strip from building all as required at site complete all as specified and as directed. Note :- The distance between two insulators fixed on the wall not more than 1 mtr length. |
| 83 | Materials and labour as in replacement for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized ironand connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40 mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1(d) 40 mm thick Pre-cast RCC cover with suitable handle.(e) Funnel with watering pipe of GI 20 mm nominal bore ,mediumgrade & copper lug etc. (f) 40 mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead.(g) Requisite quantity of charcoal and common salt.(h) Connection to earthing test point and testing on completion. |
| 84 | EXTERNAL ELECTRIFICATION |
| 85 | Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed |
| 86 | Excavation in trenches in any type of hard/dense soil/hard standing not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed |
| 87 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed |
| 88 | Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed . |
| 89 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50mm outer diameter and 38 mm inner Diameterwith IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directedMake:- Dura. Line/Tijaria/REX/Ketron |
| 90 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size63 mm outer diameter and 51 mm inner Diameterwith IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directedMake:- Dura. Line/Tijaria/REX/Ketron |
| 91 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size120 mm outer diameter and 103 mm inner Diameterwith IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directedMake:- Dura. Line/Tijaria/REX/Ketron |
| 92 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed. Note :- laying of cable route is same as old cable route . |
| 93 | Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables ( heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 70sq mm, 3.5 core including testing after laid and jointed all as specified and as directedMake :- Gloster/ Polycab/Havells |
| 94 | All as per item No. 10.90 but cable size 50 sq mm 3.5 core all as specified and as directed. |
| 95 | All as per item No.10.90 but cable size 35 sq mm 3.5 core all as specified and as directed. |
| 96 | All as per item No.10.90 but cable size 16 sq mm 4 core all as specified and as directed. |
| 97 | Material and labour for cable route indicator made out of PCC (1:2:4) type B1 of size 60cm x 15cm x 5cm thick grouted in PCC (1:2:4) type B1 pillar fo size 30 cm x 30 x 45 cm in ground with and including necessary foam work and making on board MES LT Cable (1100 Volt) with arrow indicating cable path (marking shall be engraved and colour painted), complete all as specified and directed. |
| 98 | Supply and fix Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 120 Sq mm.Note :- Any Excavation and earth work ,Returning and filling, Removing involved shall be measured and paid seperatelay |
| 99 | All as per item No. 11.40but cable size25 - 50 sq mm cable size complete all as specified and directed. |
| 100 | Supply and fix in repairs thermoplastic cable entry junction boxes of size 250 x 220 x 135mm and IP-65 protection level with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 5-32 amps, \"C\" series, breaking capacity 10 KA, \"C\" curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs etc., separate (detachable) gland plate, bakelite connector 4 way 20 amp, dust and vermin proof, front door opening with hinges and locking arrangement, complete all as specified and as directed.Make:- Sintex/Hensel or equivalent |
| 101 | Supply and fix in repair of bracket for street light fittings made out of 32 mm dia GI pipe of light grade 1.5 m long each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 30 x 5 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fitting including taking down old unserviceable bracket of any shape and size all as specified and as directed. |
| 102 | M&L for preparing surfaces of electric poles of RCC type of anysizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of weather proof paint completely andalternate layer of yellow and black synthetic enamelled paint of 150 mm strips at the bottom of pole 1.5 mtr above coping all as specified and asdirected. |
| 103 | Supply and fixing in repair of LED street light fitting 70 Watt230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 104 | Supply, erecting & fixing in repair of steel tubular swaged pole complete with base plate, pole cap, nut bolt washer etc 9.00 meters long type 410 SP-31 swaged poles conforming to IS 2713 (Part-I to III) 1980 all as specified including two coats of black bitumen paint through out internally and externally upto planting depth and applying two coats of aluminum paint over one coat of red oxide primer (externally) andNumbering of poles as directed including excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of size 600x600x1500mm height upto ground level and using PCC 1:2:4 B-1 for coping with size 450x450x300mm including necessary formwork complete with taking down old unserviceable pole all as specified and as directed. |
| 105 | Supply and fixing in repair of smart integrated 36 Watt Smart Bright, All in one Solar Street Lightincluding suitable bracket for hanging on existing pole / wall,with Infra Red Remote, with built in mono crystalline panel, Lithiumferro phospate (Lite PO 4) Battery , MPPT charge controller and PIR sensor with colour teperature 6000-6500 K, including nuts, bolts and washers etc,complete all as specified and directed. Make : Philips/ CG / Havells |
| 106 | Supply and fixing of smart integrated 36 Watt Smart Bright, All in one Solar Street Lightincluding galvanized steel pole (6 Mtr pole height) with suitable bracket for hanging, with Infra Red Remote, with built in mono crystalline panel, Lithiumferro phospate (Lite PO 4) Battery , MPPT charge controller and PIR sensor with colour teperature 6000-6500 K,including nuts, bolts, washers, excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of suitable size recommended by the manufacturer and using PCC 1:2:4 B-1 for coping with suitable of size including necessary formwork etc, complete all as specified and directed. Make : Philips/ CG / Havells |
| 107 | S&F LED strip light 18 m long min 5 W per mtr length tricolor 240V 50Hz with drivers and fixing arrangement on poles/walls/structure etc complete all as specified and directed. |
| 108 | Fabrication, Supplying Installing, testing & Commissioning outdoor type feeder pillar box with rain cowl weather / verminproof , factory madefrom any CPRI approved manufacturer having dismensions of Suitable size with sufficient space between MCCB cable coonection place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out ofCRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door, the cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with satinless steel locking handle arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 300 mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 600 Amps (60mm x 10mm) alumunium bus bar duly insulated.(b) Multifunctioning meter to measure Voltage,Current,Frequency,PF,KWH,KW,KVA,KVAR -01 Nos (c) One set of 3 pilot lamp - 01 Nos(d) Incoming MCCB 400 amps 4 Pole 415 volts 36 KAIcs=100% of Icuthermal magnetic setting type- 01 Nos (e) Outgoing MCCB 200 amps 4 Pole 415 volts 36 KA Ics=100% of Icuthermal magnetic setting type- 01 Nos (f) Outgoing MCCB 100 amps 4 Pole 415 volts 16 KAIcs=100% of Icu thermal magnetic setting type- 02 Nos(g) Outgoing MCCB 63 amps 4 Pole 415 volts 16 KAIcs=100% of Icu thermal magnetic setting type- 01 Nos (h) Outgoing MCB TPN 32 amps415 volts 10 KA Ics=100% of Icu thermal magnetic setting type-02Nos(i) Outgoing MCB TPN 16 amps415 volts 10 KA Ics=100% of Icu thermal magnetic setting type- 02 Nos Location :- Near Training Shed Arty |
| 109 | Earthing complete with galvanized street earth plate electrode 600x600x6mm thick buried directly in ground (earth plate not less than 2.25mtr deep below normal ground level) with top edge of the plate not less then 1.50 mtr.below the normal ground level connected to galvanized iron strip 32x6 mm as earthing lead by means of bolts nuts check nuts & washer of galvanized iron or steel all as shown in electrical plate No 5 connected to earthing test point all as specified and testing on completion including the material and labour for :-(a) Excavation and earth work or drilling hole for electrode in any type of soil (b)PCC pit in cement concrete 1:2:4 TYPE B-1 (c)Pre cast RCC cover with suitable handle 40mm thick in PCC 1:2:4 reinforced with welded steel wire fabric weighting not less than 1.87 Kg/sqmm (d)Funnel with watering pipe of GI 20mm nominal bore medium grade and Aluminum lugs etc all as specified.(e)15mm nominal bore medium grade GI protection pipe up to 7.50 meter long for protection of earthing lead.(f)Requisite quantity of charcoal and common salt (g) Connection to earthing test point and testing on completion. |
| 110 | NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.)[(-) Rs. 87,935.00] |