Tender For Additional Electrical Work Of New Iucaa-2 Building; 1 Supplying, erecting, testing & commissioning 11 kV, 630A, 21kA/3sec, 5 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested consisting of 2 Nos. feeder with 2 LBS and 3 Nos. feeder with 3 VCB with required protection relays and accessoriescompliant to IEC 62271-100, 200 and 102 as per technical specification. 2 Supplying, erecting, testing & commissioning 11 kV, 630A, 21kA/3sec, 4 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested consisting of 2 Nos. feeder with 2 LBS and 2 Nos. feeder with 2 VCB with required protection relays and accessories compliant to IEC 62271-100, 200 and 102, as per technical specification 3 Supplying, erecting, testing & commissioning 11 KV800A, 21 KA indoor VCB Panel with C & R Panel and required protection relays and accessories for 11KV OG Feeder as per technical specification 4 Supply, Installation, Testing & Commissioning of Silicon coated touchproof indoor/outdoor termination joint kit (MSEDCL approved) for 11 Kv (E) XLPE 3C X 300 Sq. mm HT Cable with required material & accessories including termination of Cable to the RMU/VCB/Kiosk/CSS. 5 Supplying and erecting distribution class, 11 kV, 10 kA thyrite type lightning arrester UV, weather-resistant with nut bolts as per specification 6 Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority including required hardware etc. 7 Supplying, erecting, testing & commissioning GI corrugated pre coated sheet 0.6 mm (24 SWG) having zinc coating of 275 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of shed including cutting, bending, drilling, welding, riveting etc. with as per specification 8 Providing and laying, Casting Ready Mix cement concrete in M15 of trap / granite / quartzite /gneissmetal for foundation and bedding / steps including steel cantering, form work, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpalium etc. (Wooden cantering will not be allowed.), with fully automatic microprocessor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) 9 Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly flushed to wall with required cutting, drilling, chiselling and finishing with cement mortar / POP as per required to match the background surface/wall 10 Supplying and erecting PVC box trunking of size 100x50x50 mm with separate partition for power & data cables and required accessories on RCC wall/ceiling as per specification 11 SITC of 3 Module Plate with IP65 Outdoor type Box (Waterproof) with required material & accessories etc. 12 SITC of 19 C x 2.5 Sq. mm Copper Armoured multistrand cable in underground RCC/PVC pipe/ trenchwith required material Lugs, Glands & accessories etc. 13 SITC of End Termination of19C x 2.5 Sq. mm Copper Armoured multistrand cablewith required material Lugs, Glands & accessories etc. 14 SITC of 10 C x 2.5 Sq. mm Copper Armoured multistrand cablein underground RCC/PVC pipe/ trench with required material Lugs, Glands & accessories etc. 15 SITC of End Termination of10C x 2.5 Sq. mm Copper Armoured multistrand cablewith required material Lugs, Glands & accessories etc. 16 SITC of 3C x 2.5 Sq. mm Copper unarmoured shielded cablein underground RCC/PVC pipe, trench with required material Lugs, Glands & accessories etc. 17 SITC of End Termination of3C x 2.5 Sq. mm Copper unarmoured shielded cablewith required material Lugs, Glands & accessories etc. 18 SITC of 4C x 2.5 Sq. mm Copper Armoured multistrand cablein underground RCC/PVC pipe/ trench with required material Lugs, Glands & accessories etc. 19 SITC of End Termination of4C x 2.5 Sq. mm Copper Armoured multistrand cablewith required material Lugs, Glands & accessories etc. 20 SITC of 6C x 2.5 Sq. mm Copper Armoured multistrand cablein underground RCC/PVC pipe/ trench with required material Lugs, Glands & accessories etc. 21 SITC of End Termination of6C x 2.5 Sq. mm Copper Armoured multistrand cable with required material Lugs, Glands & accessories etc. 22 Supplying, laying, erecting & terminating Green Colour FRLS XLPE insulated unarmoured cable 1100 Volt 1 core 70 Sq. mm. copper multistrand conductorin the provided underground RCC/PVC pipe/trench complete as required as per specification. Rate of all cables includes cost of lugs, glands, etc. required for erection and connection of cable. 23 Supplying, laying, erecting & terminating Green Colour FRLS XLPE insulated unarmoured cable 1100 Volt 1 core 25 Sq. mm. copper multistrand conductorin the provided underground RCC/PVC pipe/trench complete as required as per specification. Rate of all cables includes cost of lugs, glands, etc. required for erection and connection of cable. 24 Supplying, laying, erecting & terminating Green Colour FRLS XLPE insulated unarmoured cable 1100 Volt 1 core 16 Sq. mm. copper multistrand conductorin the provided underground RCC/PVC pipe/trench complete as required as per specification. Rate of all cables includes cost of lugs, glands, etc. required for erection and connection of cable. 25 Supplying, laying, erecting & terminating Green Colour FRLS XLPE insulated unarmoured cable 1100 Volt 1 core 10 Sq. mm. copper multistrand conductorin the provided underground RCC/PVC pipe/trench complete as required as per specification. Rate of all cables includes cost of lugs, glands, etc. required for erection and connection of cable. 26 SITC of 4 Way ETPN DB with outdoor panel with canopy including 40 Amp FP MCB -1 No. as incomer & 6/16A SP MCB - 12 Nos. as outgoing with necessary wiring & accessories etc.Outdoor panel with canopy must have locking facility. 27 Supply, Installation, Testing and Commissioning (SITC) of Reinforced Cement Concrete (RCC) cover with frame of size 1200 mm x 1500 mm, designed for heavy-duty applications with a load-bearing capacity of 20 Metric Tons, as per the latest revision of IS:12592 – Part 1. Concrete Grade of minimum M-30 or higher, Top Surface Finish: Anti-skid chickened design for safety, Provision for lifting hooks/handles for ease of handling. The finishing civil work required to install the Chamber frame & cover should be considered in this item.