| 1 | Material and labour for taking out old unsv cable of any size, GI pipe protection, bricks including separating serviceable brics & set aside for reuse andremoving unsrviceable bricks complete all as specified and as directed. |
| 2 | Supply and laying or passing through pipe XLPE cable insulated galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volt grade with stranded aluminium conductor of size 240 sqmm 3.5core complete all as specified and directed. (Make : KEI/Havells/Gloster/Polycab) |
| 3 | All as per srl item No 2 butsize 50 Sqmm 3.5 core |
| 4 | All as per srl item No 2 butsize 35 Sqmm 3.5 core |
| 5 | All as per srl item No 2 butsize 25 Sqmm 4 core |
| 6 | All as per srl item No 2 butsize 16 Sqmm 4 core |
| 7 | All as per srl item No 2 butsize 10 Sqmm 2 core |
| 8 | Re-laying only LT cable any sizes obtained from item No 01 with all fixing & connecting accessories such as Alluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed. |
| 9 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in any type of soil complete all as specified and directed. |
| 10 | Returning, filling in including, spreading, levilling,watering and well ramming in layers not exe 25 cm thick each complete all as specified and directed. |
| 11 | Removing excavated material to a distence not exc 50m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 12 | Material and labour for Sand cushioning to under ground cable providing with a layer 8cm thick before laying the cable and 15 cm thick after laying the cable. Complete all as specified in clause 19.75 of SSR 2009 Part-I (Specifications) complete all as specified and directed. |
| 13 | Supply and laying for sub class B brick of size 225mm x 115mm x 65mm for protaction of UG cable with width equal to length of bricks as mechanical protection laid dry and flat complete all as specified and as directed. |
| 14 | Reifixing of existing bricks/ cable cover any type of good condition after the cleaning complete all as per specified and directed |
| 15 | Supply and fix GI Tubing (light) grade with all fittings, laid in trenches, or fixed along with walls/poles including brackets, nuts & bolts etc. bore of pipe 80 mm complete all as specified and directed. |
| 16 | Material and labour for horizontal boring across the existing road without disturbing the road surface for inserting 80 mm bore GI pipe all complete all as specified and as directed. (Note :- GI pipe will be measured and paid respective item of sch \"A\"). |
| 17 | Material and labour for cutting the existingconcrete/bituminous road surface width note exceeding 45 cm and making good the surface with 100mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate finished even and fair complete over 100mm thick PCC 1:4:8 type D2 using 40mm grade stone aggregate over consolidated/rammed earth surface all as specified and directed. |
| 18 | Supply, fixing and testing of heat shrink LT cable straight through jointing kit suitable for 1100 volts grade 10-16 Sqmm, 3.5/4.0 core, complete all as specified and as directed. MAKE: 3M/ RAYCHEM/ DENSONS |
| 19 | Supply, fixing and testing of heat shrink LT cable straight through jointing kit suitable for 1100 volts grade 25-50 sqmm 3.5/4.0 core cable complete all as specified and as directed. Make : 3M/ RAYCHEM/ DENSONS |
| 20 | Supply, fixing and testing of heat shrink LT cable straight through jointing kit suitable for 1100 volts grade 185-300 sqmm 3.5/4.0 core cable complete all as specified and as directed. MAKE: 3M/ RAYCHEM/ DENSONS |
| 21 | Supply, fixing and testing of heat shrink LT cable indoor/out door jointing kit suitable for 1100 volts grade 10-16 sqmm 3.5/4.0 core cable complete all as specified and as directed. MAKE: 3M/ RAYCHEM/ DENSONS |
| 22 | Supply, fixing and testing of heat shrink LT cable indoor/out door jointing kit suitable for 1100 volts grade 25-50sqmm 3.5/4.0 core cable complete all as specified and as directed. MAKE: 3M/ RAYCHEM/ DENSONS |
| 23 | Supply, fixing and testing of heat shrink LT cable indoor/out door jointing kit suitable for 1100 volts grade 185-300 sqmm 3.5/4.0 core cable complete all as specified and as directed. MAKE : 3M/ RAYCHEM/ DENSONS |