Supply, Delivery, Installation Of 20 Hp Submersible Pump Motor Set And Electrical Control Panel With Allied Works In Newly Constructed Replaced Well At Dumping Ground Dtw Based Pumping Station (P.H No-03) Of Rajarhat Zone-Ii
Tender Overview
Project Description
Supply, Delivery, Installation Of 20 Hp Submersible Pump Motor Set And Electrical Control Panel With Allied Works In Newly Constructed Replaced Well At Dumping Ground Dtw Based Pumping Station (P.H No-03) Of Rajarhat Zone-Ii
BOQ
| Sl. No. | Item Description |
| 1 | Mechanical works |
| 2 | Supply and delivery of clear water vertical wet type submersible pump suitable for borewell conforming to IS:8034 (and as amended therafter) with standard MOC for potable clear cold water and BEE 3 star rated capable of discharging noted M3/hr against headof water column. The pump shall be directly coupled with a continuous rated 2-pole suitable wet type vertical squirel cage induction motor conforming to IS : 9283 (and as amended therafter), suitable for operation in AC Three phase 415V, 50Hz (categoryB motor). For 20HP, Stage-5, 50m head of WC & 90m3/hr discharge. |
| 3 | Installation of 20HP submerisble pump motor set for any length of pump assembly exceeding 18 meter length by using necessary requisite tools and plantes by lowering the same within the tubewell housing pipe by fitting fixing column pipes and other accessories, fixtures with necessary nuts, bolts and washer and suspending the entire assembly set vertically fixing the same supported by M.S clamps over the top of houysing pipe etc, including transportation of submersible pump motor and all other accessories and equipment from store to worksite as per direction of EIC. |
| 4 | S & D of 125 mm dia / 150 mm dia (5\"/6\") standard duty PVC/MS Adoptor. Mk-Ashirbad/C.R.I./Raksha. |
| 5 | S &D of 125mm dia/150 dia (5\"\"/6\") heavy duty PVC column pipe length -10\"(3.1m).Mk-Ashirbad/C.R.I/Raksha. |
| 6 | Supply of Enlarger of size 100mmx125mm (MOC-M.S) |
| 7 | Supply of pump-motor protective device cage (M.S) comprising of clamps etc as per direction of EIC. |
| 8 | Supply of safety clamp for the P/M set 10 mm X 50 mm sectionas per direction of EIC. |
| 9 | Supply,fitting & fixing Split type M.S fabricated suitable tube well cover for the tube welletc as per direction of EIC. |
| 10 | Supplying including cost of installation of cast iron mechanical joint Double socket 90° Bend as dim entionally described in IS : 13382/2004 for connecting two plain ends of Cl/DI pipes with C.I body and follower gland, zinc coated MS. fasteners and sealing rubber gasket of EPDM quality as per IS:13382:2004 complete. for 150mm diameter. |
| 11 | Supplying , fitting and fixing of Pressure Gauge & Acessories of approved make and quality all complete as per direction of Engineer in charge.i) Pressure Gauge 2\" Dial |
| 12 | Cast iron double flanged single door swing Non-Return Valve generally conforming to IS 14846 having body, door cover in graded cast iron to IS 210 Gr. FG 200, body and door rings and bearing block of leaded tin bronze to I.S 318 Gr. LTB 2, hinge pin of ST AISI410 valves suitable for maximum working pressure of 10/16 kg/cm2 and body tested 15/24 kg/cm2. |
| 13 | Cost iron double flanged manually operated sluice valves generallyconforming to IS 14846 : 2000, having four faces and spindle nut ofgunmetal, inside screw non- rising type quality gunmetal /AISI 410spindle: seat tested to 10kg/CM2 and body tested to 15kg/CM2, flangesflat faced and drilled to 1S. : 1538 : 1993. Painted black all over withasphalt base paint. Valves tested by closed end method. 150mm |
| 14 | Construction of supporting pillar supporting platform for the resting of valves for easy operation with neat cement finish as per direction of EIC. |
| 15 | Electrical works |
| 16 | Supply, deliveryof 415V, 3Ph, 50Hz, auto-maunual 20kW stardelta starter control panel for Sub. P/M set. (as per enclosed details). Mk-Sellwin/Electromech/AC Power/Equivalent as per direction of EIC. |
| 17 | Installation of415V, 3Ph, 50Hz, auto-maunual 20kW stardelta starter control panel for Sub. P/M set. |
| 18 | Supplying of following XLPE insulated aluminum conductor armored cables of 1.1kv grade as per is 7098 (part 1) 1988 with up to date amendments. (rate in rs. Per mtr). 3.5 core , 35 sq. mm. |
| 19 | Laying of two cables upto 35 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr. as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed . |
| 20 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm onwall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting. |
| 21 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below. For 3½ core 35 sqmm . |
| 22 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. For 3½ core 35 sqmm |
| 23 | S/F M. S. loop box (10 SWG) of size 10.3/4 “x 8.3/4” x 5\"(269mm x 219mm x125mm) having almirah type cover complete with special type locking arrangement including S/F 8 “x6” x1/4\" (200mm x 150mm x 6 mm) bakelite sheet 1 no. 4-way ebonit connector block, 1 No. 15 Amp fuse unit fitted inside the box andsuitable size danger board riveted on cover of the box outside & fixing the box with pole by means of M.S. Clamps of 1\"x1/4\" (25mm x6mm) of suitable length andencasing the box by 1:3:6 cement concrete with graded stone chip (3/4\" down). The depth of the concrete should be 60cm x 54cm x 54cm including plastering and neat cementing and S/F 2 Nos. compression gland of suitable size and making all necessary connections as reqd. |
| 24 | AddGST @18% |
| 25 | Add LWC @ 1% |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender