Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-08-2025 | CORRIGENDUM | Other | 07-08-2025 |
| 2 | 28-07-2025 | CORRIGENDUM | Date | 07-08-2025 |
| Sl. No. | Item Description |
| 1 | Civil works of 6.0 MLD STP and 16 KLD septage Co-Treatment Facilities |
| 2 | Design, Construction, Supply of all materials, Erection and Commissioning of co treatment facilities (6.0 MLD STP and minimum 16.0 KLD Co-treatment) with all the civil, electrical , mechanical, instrumentation and scada system, LT/HT panel, sub station building, DG set foundation, admin buidling, laboratories, meter room and campus development [Construction of Internal Road (CC Road, 3.5m wide, area approx 2000sqm.), staff quarters as per requirement and specification, external water supply (20KL tank including tube well and pumping arrangement, electrification & street llighting and sanitation work) etc. all complete for STP with co-treatment facilities. STP shall be based on SBR Technology OR any proven technology. The effluent quality for agricultural uses (PH-6.5 TO 8.3, SS-30 mg/l, Oil&Grease-10 mg/l, BOD-10mg/l) , COD-30 mg/l , Residual chlorine-nil , TKN-10mg/l, Nitrate N-10 mg/l, F.C.-230 MPN/100 ml, Dissolved P-5 mg/l (preferable 2 mg/l). ) shall be maintained asper CPHEEO manuals. Latest NGT norms for effluent discharge shall be adhered. The cost is inclusive of MPS(Peak flow 28.55 MLD) (civil works). |
| 3 | INTERCEPTOR SEWERExcavation below G.L. upto depth as specified for laying sewer and manhole ordinary soil (earth, sand, loam and clay) including cutting of joints pits ramming dressing) leveling, refilling of trenches in 20 cm layer watering and ramming the same including (8% reduction due to excavation already taken in manhole and SCC) |
| 4 | (a)0.00 to 1.50 m |
| 5 | (b) 01.50 to 03.00 m |
| 6 | (c) 03.00 to 04.50 m |
| 7 | (d) 04.50 to 06.00 m |
| 8 | Provide and fix close timbering in trenches for the depth as specified below G.L. consisting of 40 mm thick approved country wood plank for polling board 125 x 75 mm eucalyptus-Safeda-Sal Wood wallers and 100 mm dia ballies for shuttering at 1.5 m C/C including all labour etc , complete(a)1.5 to 3 m |
| 9 | (b) 03.00 to 06.00 m |
| 10 | Same as item No. 3 but for open timbering (No timbering for depth <1.50m) |
| 11 | (a) 1.50 to 03.00 m |
| 12 | Supply of following sizes of RCC spigotted and socketed non pressure pipes( Dia. In mm ) with structural strength as per IS 458 : 2003 and its latest amendment(s).NP3 |
| 13 | 200 mm dia pipe |
| 14 | 250 mm dia pipe |
| 15 | 300 mm dia pipe |
| 16 | 350 mm dia pipe |
| 17 | 400 mm dia pipe |
| 18 | 500 mm dia pipe |
| 19 | 600 mm dia pipe |
| 20 | 900 mm dia pipe |
| 21 | Carting following sizes of R.C.C. Hume pipe NP3 Class Socket / spigot rubber ring jointing and specials from store to the work lowering and laying the same in to the trenches upto depth as specified below G.L. true to alignment200 mm dia pipe |
| 22 | 0.00 - 0 1.50 m |
| 23 | 250 mm dia pipe |
| 24 | 00.00 - 0 1.50 m |
| 25 | 01.50 - 0 3.00 m |
| 26 | 300 mm dia pipe |
| 27 | 00.00 - 0 1.50 m |
| 28 | 01.50 - 0 3.00 m |
| 29 | 03.00 - 04.50 m |
| 30 | 350 mm dia pipe |
| 31 | 00.00 - 0 1.50 m |
| 32 | 03.00 - 04.50 m |
| 33 | 400 mm dia pipe |
| 34 | 03.00 - 04.50 m |
| 35 | 500 mm dia pipe |
| 36 | 04.50 - 06.00 m |
| 37 | 600 mm dia pipe |
| 38 | 01.50 - 0 3.00 m |
| 39 | 03.00 - 04.50 m |
| 40 | 04.50 - 06.00 m |
| 41 | 900 mm dia pipe |
| 42 | 01.50 -0 3.00 m |
| 43 | 03.00 - 04.50 m |
| 44 | Cement concrete work in bedding below G.L. at specified depth with cement, coarse sand and 20 mm gauge approved stone ballast (1:2:4) including supply of all materials, labour, T&P etc. required for the proper completion of work. |
| 45 | (a) 00.00 to 01.50 m |
| 46 | (b) 01.50 to 03.00 m |
| 47 | (c) 03.00 to 04.50 m |
| 48 | (d) 04.50 to 06.00 m |
| 49 | Filling granular material (well graded crushed rock or gravel maximum size 20mm) into the trenches for class B bedding (granular bedding) including watering compaction, labour T&P etc. for completion of work. (As per statement) |
| 50 | (b) 01.50 to 03.00 m |
| 51 | Supply (excluding cartage) of granular material (well graded crushed rock or gravel of maximum size 20mm)for class B bedding (granular bedding) |
| 52 | Construction of circular type brick masonry HD (HD20) manhole (with Extra Heavy Duty type manhole cover) with top slab made of cement concrete 1:1.5:3 with graded granite stone aggregate (12 mm nominal size), wall made of brick masonry using 1st class bricks having crushing strength between 100 to 149 kg/cm² in cement mortar 1:4 inside plastering 12 mm thick 1:4 finished smooth with neat cement, pinning, outside plaster 1:4 and making channels with cement concrete 1:2:4 graded granite stone aggregate (12 mm nominal size) complete with including Plastic Encapsulated M.S. foot Rest staggered at 0.375 mtr interval, including excavation, reinforcement |
| 53 | 900mm internal dia., 1.65m deep |
| 54 | 1200mm internal dia., 3.30m deep |
| 55 | 1500mm internal dia., 4.95m deep |
| 56 | Extra for every additional depth of 1 m or part there of in following size of circular manholes. |
| 57 | 900mm internal dia., 1.65m deep |
| 58 | 1200mm internal dia., 3.30m deep |
| 59 | 1500mm internal dia., 4.95m deep |
| 60 | Dismantling/Cutting of the following type of road for laying sewers, manholes, sewer connection chambers etc.including shorting out and stacking serviceable materials and disposal of unserviceable materials as per direction of Engineer Incharge. |
| 61 | Bituminous road |
| 62 | Concrete road |
| 63 | Interlocking tile road |
| 64 | B.O.E road |
| 65 | Reinstatement of the following type of road for laying sewers, manholes, sewer connection chambers etc.including shorting out and stacking serviceable materials and disposal of unserviceable materials as per direction of Engineer Incharge. |
| 66 | Bituminous road |
| 67 | Concrete road |
| 68 | Interlocking tile road |
| 69 | B.O.E road |
| 70 | Tack & SDBC Coat on existing BT Road (remaining area after reinstatement) |
| 71 | Providing and erecting temporary barricading at site as per drawing/ direction of Engineer-in-Charge which includes hiring of Ballies and arrangement for traffic diversion such as traffic signals during construction at site as directed by the Engineer-in-Charge. The barricading provided shall be retained in position at site continuously i/c shifting of barricading from one location to another location as many times as required during the execution of the entire work till its completion. Rate include its maintenance for damages, painting, all incidentals, labour materials, equipments and works required to execute the job. The barricading shall not be removed without prior approval of Engineer-in-Charge. (Note :- One time payment shall be made for providing barricading from start of work till completion of work i/c shifting. The barricading provided shall remain to be the property of the contractor on completion of the work). The rate is for unit length of pipe laying. |
| 72 | Disposal of Surplus Earth as per direction of Engineer Incharge. |
| 73 | Provision for shifting and reinstatement of electric and telephone poles during excavation and laying of sewer lines. |
| 74 | Construction of Boundary Wall 2.0 m ht. above plinth level 0.23m width with RCC Column @3m c/c with plinth beam and foundation avg. 1.2m depth including reinforcement and RCC coping on top of wall with plaster (1:4) and painting (apex painting 3 coat) as per type design and drawing at the STP site |
| 75 | MS gate (3.6m wide with 1.50m wicket gate with 0.35 m x0.35m RCC piller) |
| 76 | Cnstruction of Intermediate Pumping Station (IPS) as per specification, accesory building & design approved by Engineer in Charge |
| 77 | Sewage Rising main from IPS Excavating trenches for pipes including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering etc., and disposing of surplus excavated soil as directed, within a lead of 50 m.do - in all kindes of soil - 100% |
| 78 | 0.0 to 1.5 mtr. Depth (do - in all kindes of soil) |
| 79 | Clearing jungle including uprooting of rank vegitation, grass, brush wood trees and saplings of girth upto 30cm measured at a height of 1m above ground level and removal of rubbish upto a distance of 50m outside the periphery of the area cleared. |
| 80 | Supply of 200mm dia. DI K7 pipe and special for the pumping mains including all complete pipes conforming to IS : 8329- 200 mm including specials. |
| 81 | For 200 mm dia. PipeProviding and fixing C.I. sluice valves (with cap) complete with bolts,nuts, rubber insertions etc. (the tail pieces if required will be paid extra. (200mm dia)(Qtn. & UPJN 2446) |
| 82 | Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (100mm dia.) (18.59.3, DSR 2023) |
| 83 | Laying, jointing, carting of 200mm dia DI K7 pipe and specials from store to the work lowering the same in to the trenches upto depth as specified below G.L. inclduing testing of pipes etc. |
| 84 | Providing & Constructing masonry Chamber 1.5x1.5x1.5 m inside, in brick work in cement mortar 1:3 (1 cement : 3 coarse sand) for valve, withcast insitu RCCslab with necessary reinforcment.The valve chamber shall be plastered with CM 1:4, A levelling coars of M10shall be provided.The cost is inclusive of excavation , disposal and construction of valve chamber with moduar bricks plasting with cement mortar with all lead and lift etc., as per specification & drawing. |
| 85 | Sluice valve, Air valve chambers |
| 86 | Dismantling/cutting of the BOE road for laying sewers, manholes, sewer connection chambers etc.including shorting out and stacking serviceable materials and disposal of unserviceable materials upto distance of 50 m. |
| 87 | Reinstatement of the BOE road for laying sewers, manholes, sewer connection chambers etc.including shorting out and stacking serviceable materials and disposal of unserviceable materials upto distance of 50 m. |
| 88 | Interception and diversion (I&D) Structure works |
| 89 | Cnstruction of Interception and Diversion Structure works as per specification, accesory building & design approved by Engineer in Charge |
| 90 | Treated Effluent line (450mm Dia AC pipe) (STP to Disposal point (Malan river) |
| 91 | Clearing jungle including uprooting of rank vegitation, grass, brush wood trees and saplings of girth upto 30cm measured at a height of 1m above ground level and removal of rubbish upto a distance of 50m outside the periphery of the area cleared. |
| 92 | Excavating trenches for pipes including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering etc., and disposing of surplus excavated soil as directed, within a lead of 50 m.do - in all kindes of soil - 100% |
| 93 | 0.0 to 1.5 mtr. Depth |
| 94 | Supply of ISI Marked A.C. Pipe confirming to IS-1592/2003 or itss latest amendment(s) including cost of one no. of AC coupling with a set of 3 rubber rings per meter length, including third party inspection charges, packing and forwaridng charges, transit insurance charges, road transportation charges etc. all complete. Class 15Pipes conforming to IS-1592/2003 - 450 mm |
| 95 | Laying, jointing, carting From Store, Laying, Jointing & Testing 450mm dia Class I & II A.C. Pipe With specials and Fittings. |
| 96 | Dismantling/cutting of BOE road for laying sewers, manholes, sewer connection chambers etc.including shorting out and stacking serviceable materials and disposal of unserviceable materials upto distance of 50 m. |
| 97 | Reinstatement of BOE road for laying sewers, manholes, sewer connection chambers etc.including shorting out and stacking serviceable materials and disposal of unserviceable materials upto distance of 50 m. |
| 98 | Cleaning of existing drains for smooth functioning of the system and disposal of silt and debris |
| 99 | Strengthening of Existing Drains as and where required for uninterrupted functioning of the system |
| 100 | Excavation in foundation in ordinary soil (loam, clay & sand) including lift upto 1.5m and lead upto 50m watering & ramming of excavated earth into the trenches or into the space between the building and the sides of the foundation or into the plinth and disposal of surplus earth upto a distance0.00 to 1.50 m |
| 101 | Providing lay in PCC in following proportion in foundation and floor including supply of all materials, labour, T&P etc. complete required for the work 1:4:8 with coarse sand and 4cm gauge stone ballast. |
| 102 | PCC |
| 103 | RCC work with cement, coarse sand and graded stone aggregate 20mm nominal size in proportion of 1:1.5:3 excluding supply of the reinforcement and its bending but including its fixing and binding with 0.5mm thick binding wire (to be supplied by the contractor) & including necessary centering and shuttering, supply of all materials labour, T&P etc. required for proper completion of work. |
| 104 | Base slab |
| 105 | Wall |
| 106 | Mild steel or iron work in R.C.C. work wrought to required shape as necessaty including bending for proper completion of work including supply of steel & wastage etc. In Slab |
| 107 | in Slab |
| 108 | Misc works |
| 109 | E&M Works |
| 110 | STP ( 6 MLD ) And Co Treat ment Plant ( 16 KLD ) |
| 111 | A. Design, Supply of all Materials, Erection, Testing,Commissioning and 3 month trial run Of Electrical, Mechanical & Instrumentation Equipments at STP (6 MLD )with all required electrical& mechanical works, PLC/SCADA work, electrification & street lighting work and Online Continuous Effluent Monitoring System (OCEMS) etc. all complete as per tender documentfor STP.The effluent quality for agricultural uses ( PH-6.5 TO 8.3,SS-30 mg/l, Oil & Greases -10mg/l, BOD- 10mg/l,COD-30 mg/l,Residual Chlorine-nil, TKN-10mg/l, Nitrate-10mg/l, FC-230MPN/100ml Dissolved P-5mg/l (preferable 2mg/l).) shall be maintained as per CPHEEO mannuals Latest NGT norms for effluent discharge shall be adhered. The rate is Considered for SBR Technology. The STP shall be capable to treat the raw sewage having minimum concentrationmentiond in CPHEEO mannual. Firm has to complete Design, Supply, Erection, Testing,Commissioning and 3 month trial run of Substation Work like HT Panel, Transformer & its associated equipments and DG Set Work with AMF Panelwith considering load of STP and MPS both.B. Design, Supply of all Materials, Erection and Commissioning and 3 month Trial Run of Co-Treatment Plant ( 16 KLD ) having manual screen with-SS 304 with bar size (50 mm x 10mm) and gaping 20 mm, Screw Pumps (3 Kl/h 1W+1S), Screw Press Machine (6 KL/H) with double cylinder having MOC SS-304 with VFD operated, Screw Press Machine should have cleaning facility with a 2000 Lit water tank and submersible bore with motor, all type pipe and fittings, LT panel and cabling material,Dewatering Pumps (1W+ 1S), 5HP Blower with 6 Nos Diffusers etc complete. including Supply and 3 month trial run. |
| 112 | E./M. Works at MPS |
| 113 | Electrical WorksH.T.Panel( Comprising with 1 -I/C and 2 -O/G. (panels should be TYPE TESTED ASSEMBLY ( TTA) type only) |
| 114 | SITC of Indoor Type Floor mounted HT Panel with11 KV, 630 Amps 3 phase, 50 Hz Vacuum Circuit Breaker (VCB) Panel Fabricated by System Integrator of VCB Manufacturer as per IEC 62271-1,100,200 Standard made from Powder painted pre-fabricated, CRCA sheet steel /High quality Aluminium-Zinc (Aluzinc) coated sheet steel. Fabrication shall be done through CNC turret press and CNC bending machine having a rupturing capacity of 500 MVA, 26.3 KA breaking capacity for 3 sec, Internal arc type tested for 26.3KA for 1 sec with AFLR clasification with suitable capacity of bus bar connected with the incoming and outgoing panels as per given details- |
| 115 | Supply installation testing and commissioning of Incoming Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCBoperationg mechanism should be of M2 duty for minimum 10000 mechanicaloperation. - Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)- VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be floor mounted and to be connected from the back side of the panel.- Numerical relay (should be VCB manufacturer\"s own make) having protections of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input , programable 6 Digital Output and programable 4 nos. LED at HMI.- Ammeter with Selectorswitch and Volt meter with Selector switch- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,KVAR, PF, KWH, KVARH, KVAH, A,V etc.- Trip circuit supervision relay (feature of numerical relay)- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC) and 8/12 window Annunciator. (1 set, included in above E&M STP Costing) |
| 116 | Supply Installation Testing and Commissioning Outgoing Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCBoperationg mechanism should be of M2 duty for minimum 10000 mechanicaloperation. - Closing & tripping coil of VCB should be of continious rating to achive minimalfailure. - Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)- Numerical relay (should be VCB manufacturer\"s own make) having protectionsof 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,programable 6 Digital Output and programable 4 nos. LED at HMI.- Ammeter with Selectorswitch and Volt meter with Selector switch- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,KVAR, PF, KWH, KVARH, KVAH, A,V etc.- Trip circuit supervision relay (feature of numerical relay)- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC). (2 sets, included in above E&M STP Costing) |
| 117 | Providing & Laying XLPE insulated as per IS:7098/II/85 H.T.cable as per PWD specification for electrical Works for working voltage 11 K.V.(E) in existing RCC / Hume /Stoneware / PVC pipe/ open duct/cable trench, on existing cable trays or on surface etc. including making necessary connection, testing etc. (included in above E&M STP Costing)3 core X 120sq.mm. armored HT Cable (From HT Panel to Transformers)- 60 meterTrench making and covering of trench in all respect. Ref.E130300, E130400, E130500 and E130700 - 60 meterSITC of 11 KV End Termination Kit Indoor type (3 core, 120sq.mm) - 4 sets11 KV, 2.5 mm thick with proof voltage 22 KV / 3 min. and Break Down Voltage 45 KV -2.5 sqm |
| 118 | Transformer: with Off -LTC (+5% to - 10% @ 2.5%) : S I T C of star rated Copper wound distribution Transformer of suitable capacity (on stp & mps both load) rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & losses as defined as per IS 1180 part I 2014. including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C& 40-45 degree C for above 800 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer complete in all respect.(1w+1s)---(2 nos. included in above E&M STP Costing) |
| 119 | L.T. Panel (panels should be TYPE TESTED ASSEMBLY ( TTA) type only)SITC of 0.415 kV L.T. control panel for pumping plant-L.T. control panel suitable to operatedon 415 ± 6 %volt , 3 Phase , 50 Hz, AC supply as per details given below-(A) 2 Nos incoming ACB panels and 1 outgoing ACB panel, each consisting of following items -(i) 4 pole Microprocessor based release Draw out type ACB (Motorised charging type) ,630 A Rating ,50 kA- 1 No.(ii)C.Ts of suitable ratio- 1 No.(iii)Ammeter with selector switch - 1 No.(iv) Voltmeter with selector switch- 1 No. (v)Power factor meter(0.5 Lag&0.5Lead) - 1 No.(vi)Frequency meter-1 No.(vii)KWH meter - 1 No. (viii)2 Pole over current relay& one pole earth fault relay - 1 No.(B)Bus bar chamber having 3 Nos. bus bars for phase and 1 No. bus bar for neutral of suitable size – 1 No. (C) 6 Nos. composite panels for pumping plants, each consisting of following items –(i) 4 pole MCCB 160 A current rating, 50 KA short circuit breaking capacity With Microprocessor based release with adjustableadjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection -1 No.(ii)C.Ts. of suitable ratio- 1 No.(iii)Ammeter with selector switch - 1 No.(iv) Automatic start / stop device according to level in the sump- 1 No.(v)Indicating lamps(Auto/manual/low level/ reverse rotation) - 1 Set (D) 3 Nos. outgoing panels for miscellaneousworks, each consisting of following items – (i) MCB of 40 A capacity- 1 No.(ii) C.Ts. of suitable ratio- 1 No. (iii) Ammeter with selector switch - 1 No.(iv) Indicating lamps- 1 Set (E)APFC Panel for total load.(F) 4 pole Microprocessor based release Draw out type (Motorised charging type) ,630 A Rating ,50 kA Panel for DG sets incoming - 1 NO (G) Bus coupler arrangement in panels |
| 120 | LT Cable laying and jointing |
| 121 | Power and control cable-Supply of 185 sq. mm 3.5 core cable - 2 Run required for power fromeach Transformer to each L.T. panel , 50 sq. mm X3 core-1 run cable for power from starters to Motor including lugging and jointing, laying, trench excavation and compaction as well as complete cabling of automation systemetc. complete in all respect. |
| 122 | Earthing |
| 123 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. |
| 124 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. \" B \" class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 withperforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof polypropylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. |
| 125 | Supply & Laying of 50mmX6mm size GI earth strip in horizontal or vertical run in ground/surface/recess including riveting,soldering, saddles, Jointing shall be done by overlapping and with 2 set of GI nut bolt & spring washer spaced at 50cm making connection etc.(20meter for each earthing) |
| 126 | Charges of Electrical safety Clearance |
| 127 | Expenditure on B&L Form, Challan etc. |
| 128 | Proper fencing of substation portion as per I.E. rules. |
| 129 | STARTER PANEL |
| 130 | SITC of Compraising of Soft Starter, suitable to meet the basic requirement of motor protections and suitable to run 20 HP motor (To be fixed in composite panel of LT Panel)- |
| 131 | Mechanical Works |
| 132 | PumpThesubmersible non clog pumpset should be single stage having two vanes enclosedimpellercoupled with submersible motor of 20 HP Rating 400 Volt ±10%,3 phase 50 Hz, solid handling capacity 125mm, suitable to pump raw sewage with an specific gravity 1.03 having followingCasing-2% Ni Cl. IS.210 grade F.G.220 with hardness 275 BHN. construction of material with 10 Met. cable as offered. (4W+2S)Impeller-Stainless steel CF-8Mshaft-stainless steel AISI-410Discharge of pump= 2610 lpmTotal Head= 17 M or as per designSpeed=980Quantity of pumps. |
| 133 | Guid Rail SystemGuide rail system (Automatic coupling system) for 20 HP submersible pump setscomplete for above pump set. - 6 setsLifting Chain , MOC- alloy steel, lifting chain with oval ring @ 1m & with D/Bow shackle - 6 sets(All above included in pump costing) |
| 134 | Main piping and Valves.Main piping and valves 200 mm dia delivery, 400 mm diacommon header line. |
| 135 | Valves.Confirming to IS 780/2906 or as applicable PN rating- 1.0Type of liquid to be handled-potable water |
| 136 | Material of constructionBody-CI,IS-210 grade FG 200Wedge-CI IS210 Grade FG200Spindle-Stainless steel AISI304Sheet and face Ring-SS ASTMA 743 Grade C.F.8 MChannel& Shoe-S.S.AISI,.304Drain& Air plug-S.S.AISI.304Bushing arrangement-Halprene on bronzeRivets-AISI:304Fasteners-MS |
| 137 | Motor Operated Sluice Valves |
| 138 | Motor operated Sluice Valve 200 mm dia. |
| 139 | Motor operated Sluice Valve 400 mm dia. |
| 140 | Reflux Valve |
| 141 | Reflux valve 200 mm dia N.B. |
| 142 | PipingsNote : Regarding the size of pipes, Tee, Bend etc, contrctor is required to designed them self and may got it approved by the department before execution of works along with layout drawing taking 200mm pipe 60m and 400 mm pipe 15m. |
| 143 | 200 mm, K9 delivery pipes for all six pumping plant |
| 144 | 400 mm, K9 common header pipes |
| 145 | Specials like bend, tee, D Joint etc. |
| 146 | Nut Bolt, Washer Rubber packing etc |
| 147 | INSTALLATION, TESTING & COMMISSIONING |
| 148 | Installation & Commissioning of all 6 Nos. Pump set,Piping & Valves as mentioned in above |
| 149 | Level Transmitter (For Hi-Lo cut-off & alarms) |
| 150 | SITC of Radar type level transmitter shall be provided in the pump house for measuring the sewage level in wet sump. The indicator shall be digital type showing depth in meters and shall be capable for input to PLC or HMI touch sceen for display. |
| 151 | Electro magnetic flow meter |
| 152 | SITC of CE/UL certified Electro magnetic flow metersuitable to measure 0 to 30 MLD flow to be fitted in 400 mm dia main header line. |
| 153 | E.O.T. Crane |
| 154 | SITC of 3 Tonn E.O.T. crane providing, erecting and commissioning single girder electrically operated rectangular over head travelling crane with 6 m lift complete with wire rope hoist, class II duty, all three motions electrically operated by suitable rating motor IP 54, control panel and down pendent control block. |
| 155 | Chequerred plate and guards |
| 156 | SITC of 3mm thick M.S chequerred plate over all the run of cables trenches to cover properly and M.S. grill and M.S. guard over all pipes ducts and other point where required as per site condition (Ref. UP Jal Nigam, GM Gzb Rate) (3X0.75+3X0.9+7X0.6+1X0.9)X1=10.05sqmm. |
| 157 | PAINTING |
| 158 | Painting of all pumps piping and valves with two coat enamel paint. |
| 159 | LIGHT WIRING & Electrification |
| 160 | Complete Internal Electrification of LT Panel room with 2 Nos. Exhaust Fan |
| 161 | Complete Internal Electrification of HT Panel room with 2 Nos. Exhaust Fan |
| 162 | Campus lighting with Solar Panel and LED Light of 3 sets. |
| 163 | D.G. SET AND ACCESSORIES |
| 164 | SITC of Radiator Cooled and Turbo charged Silent type suitable capacity DG set , engine ,alternator capable of developing required power (designed at st & mps both load) at 415+6%, 50 Hz AC at 0.85 P.F. lagging and self exciting coupled with suitable BHP diesel engine through flexible coupling and mounted on common base plate complete with fuel tank inside the acousting system and inbuilt control panel, Governor, Manual & electric Start , Batteries with battry charger, Engine instruments panel,AVM pads, All controls for operationof DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessiblefrom outside. T , 3 Met exhaust pipe, D.G. set shall be mounted under open sky resting on the foundation as per design. it should comply cpcb 4 rating (1set, included in above E&M STP Costing) |
| 165 | SITC of PLC Based Auto main failure (AMF) Panel forDG Set fabricated from CRCA sheet steel 2 mm Thick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, operator interface panel complete in all respect.(1set, included in above E&M STP Costing) |
| 166 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. \" B \" class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 withperforated holes of 12 mm dia ,including all accessories like nut, bolts,reducer, nipple, wire meshed funnel, and Heavy duty weather proof polypropylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, BottomDia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required.(2 Job, included in above E&M STP Costing) |
| 167 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/charcoal, testing of earth resistance for value of 5 ohms or less as required. (2 Job, included in above E&M STP Costing) |
| 168 | Supply & Laying 50 mm X 6mm sizeGI earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. (40 met., included in above E&M STP Costing) |
| 169 | Providing and Laying cable for DG Set to Panel 185 sq mm X 3.5 core x 2 run( armored aluminium ) (50 met., included in above E&M STP Costing) |
| 170 | Supplying and making one end termination with heavy duty brass compression gland (as per IS 12943- 1990) SIBG type, heavy duty aluminium lugs (as per IS 8309 - 1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade for 3.5 core X 185 sq mm. (4 jobs, included in above E&M STP Costing) |
| 171 | SCREENS AND GATES: |
| 172 | Rising type thimble mounted CI Sluice Gates of reputed make at pumping station. |
| 173 | Multirake type Stainless steel ( SS-304) at mid year peak discharge, Mechanical Coarse Bar Screen-20 mm gaping), Ultrasonic type differential level sensor, control panel for coarse bar screens, belt coveyor etc. complete with following specification 1. Screen shall be equipped with torque protection switch in order to avoid any damage to screen mechanism.2. Scraper wiper shall be made of PP/PVC,shaft shall be EN8.3. Lower sprocket bearing shall have SS casing including a shaft made of white cast iron and a ceramic (calcium carbide) friction bushing.4. Upper sprocket bearing shall have a paint coated CI casing and include ball bearing that are greased for life and shall be double sealed with nilos rings.5. The cleaning elements consisting of rake and comb plate shall be screwed and replaceable.6. Screens shall be equipped with SS cover thickness 1.25mm 7. Bars shall have flat bar profile with cross section of 60x8 mm or 60x10mm. 8. Dead plate thickness shall be 4mm9. Discharge chute shall be made of minimum 2.5mm thickness 10. Frame thickness shall be 4mm with min cross section of 125x102mm.11. Roller tracks shall be bolted to frame,so that they can be easily replaceable. 12. Each chain have strength of 12.3tons.Drive chain,chain guide,sprockets and their bearings shall be replaceable without removing screen from the channel.chain roller shall be made of Polyamide and shall have diameter of 70mm n shall be minimum of 32mm wide. 13. Rakes shall include rake bars made of 6mm thick channel profile having cross section of 110x86mm.14. The scrapper bar made of 3mm thick channel profile with minimum cross section 40x70mm and an adjustable 10mm thick wiper made of polyethylene. |
| 174 | Stainless steel Manual Screen (20 mm gaping) and bar size 50 mm x 10 mm at mid year peak discharge |
| 175 | Packing and Frieght |
| 176 | Installation, Testing and Commissioning |
| 177 | AUTOMATION OF MPS |
| 178 | CE& UL certified PLC/RTU with redundant CPU & power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redundant CPU & power supply with annalog & digital paramter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations as specified in tender technical specification including full developed version of scada software with customization of software with laptop/desktop etc to monitor and control the ips from remote places. |
| 179 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer & gather data from remote sites to control stations all accessories included with signal enhancer antenna made for pumping plant internet charges as specified in tender technical specification. |
| 180 | CE/UL certified intellignet Smart Energy Meter |
| 181 | Auto phase reversal unit with inbuilt time delay & enclosure (confirm to IEC-60947-1 & IEC-60947-b-1) |
| 182 | 160 AMP rating |
| 183 | Electronic sensor type pressure measuring device suitable for pressure measurements of sewage flow in delivery and common header line. The material of construction of housing and other parts in contact with sewage shall be of stainless steel. These shall be of required protection category and complete with signal transmitting device and digital pressure indicator. |
| 184 | CE/UL Certified Surge protector for control panel. |
| 185 | CE/UL Certified 7\" HMI touch screen suitable to communication with PLC/RTU for local display & control ofp rocess parameters. |
| 186 | Security Survillance IP Camera with recorder |
| 187 | Installation, commissiong & testing of above automation work |
| 188 | Trial run of automation work for 3 month period for IPS |
| 189 | Three month Expenditure on Operator (MPS) in 3 Shift |
| 190 | Diesel Consumption During Trial and Run Period (MPS & STP) |
| 191 | Electricity consumption during period of Trail and Run period, payment will be done as per actual UPPCL Bill for MPS & STP |
| 192 | E&M WORK AT IPS |
| 193 | Electrical Works at IPS |
| 194 | L.T. Panel (panels should be TYPE TESTED ASSEMBLY ( TTA) type only) |
| 195 | SITC of 0.415 kV IP 54 protected L.T. control panel for pumping plant-L.T. control panel suitable to operatedon 415 ± 6 %volt , 3 Phase , 50 Hz, AC supply as per details given below-(A) 2 Nos incoming panels and 1 outgoing panel, each consisting of following items -(i) 4 pole MCCB With Thermal Magnetic release ,200Amp , 25 kA, adjustable O/L & adjustable S/C setting- 1 No.(ii)C.Ts of suitable ratio- 1 No.(iii)Ammeter with selector switch - 1 No.(iv) Voltmeter with selector switch- 1 No. (v)Power factor meter(0.5 Lag&0.5Lead) - 1 No.(vi)Frequency meter-1 No.(vii)KWH meter - 1 No. (viii)2 Pole over current relay& one pole earth fault relay - 1 No.(B)Bus bar chamber having 3 Nos. bus bars for phase and 1 No. bus bar for neutral of suitable size – 1 No. (C) 4 Nos. composite panels for pumping plants, each consisting of following items –(i) 4 pole MCCB With Thermal Magnetic release ,100 Amp , 25 kA, adjustable O/L & adjustable S/C setting with Inbuilt Instantaneous and Ground fault Protection -1 No.(ii)C.Ts. of suitable ratio- 1 No.(iii)Ammeter with selector switch - 1 No.(iv) Automatic start / stop device according to level in the sump- 1 No.(v)Indicating lamps(Auto/manual/low level/ reverse rotation) - 1 Set (D) 3 Nos. outgoing panels for miscellaneousworks, each consisting of following items – (i) MCB of 40 A capacity- 1 No.(ii) C.Ts. of suitable ratio- 1 No. (iii) Ammeter with selector switch - 1 No.(iv) Indicating lamps- 1 Set (E)APFC Panel for total load.(F) 4 pole MCCB With Thermal Magnetic release ,100 Amp , 25 kA, adjustable O/L & adjustable S/C setting Panel for DG set incoming - 1 NO.(G)Rubber resistance sheet and fire extinguisher complete in allrespect. |
| 196 | LT Cable laying and jointing |
| 197 | Power and control cable-Supply of 120 sq. mm 3.5 core cable - 1Run required for power fromeach Transformer to each L.T. panel , 95 sq. mm X3 core-1 run cable for power from starters to Motor including lugging and jointing, laying, trench excavation and compaction as well as complete cabling of automation systemetc. complete in all respect. |
| 198 | Earthing |
| 199 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. Ref.14.3 (PRE BSR 2022) |
| 200 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. \" B \" class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 withperforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof polypropylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. |
| 201 | Supply & Laying of 50mmX6mm size GI earth strip in horizontal or vertical run in ground/surface/recess including riveting,soldering, saddles, Jointing shall be done by overlapping and with 2 set of GI nut bolt & spring washer spaced at 50cm making connection etc.(20meter for each earthing) |
| 202 | Charges of Electrical safety Clearance |
| 203 | Expenditure on B&L Form, Challan etc. |
| 204 | Proper fencing of substation portion as per I.E. rules. (Ref. Ongoing AMRUT Work Aligarh Sewarage) |
| 205 | STARTER PANEL |
| 206 | SITC of Compraising of Soft Starter, suitable to meet the basic requirement of motor protections and suitable to run 30 HP motor (To be fixed in composite panel of LT Panel) |
| 207 | SITC of Variable Frequency Drive , suitable to meet the basic requirement of motor protections and suitable to run 30 HP motor (To be fixed in composite panel of LT Panel) |
| 208 | Mechanical Works |
| 209 | PumpThesubmersible non clog pumpset should be single stage having two vanes enclosedimpellercoupled with submersible motor of 30 HP Rating 400 Volt ±10%,3 phase 50 Hz, solid handling capacity 100 mm, suitable to pump raw sewage with an specific gravity 1.03 having following construction of material with 10 Met. cable as offered. (2W+2S)Casing-2% Ni Cl. IS.210 grade F.G.220 with hardness 275 BHN.Impeller-Stainless steel CF-8Mshaft-stainless steel AISI-410Discharge of pump= 2020 lpmTotal Head= 31 M or as per designSpeed=980Quantity of pumps. |
| 210 | Guid Rail SystemGuide rail system (Automatic coupling system) for 30 HP submersible pump setscomplete for above pump set.- 4 setsLifting Chain , MOC- alloy steel, lifting chain with oval ring @ 1m & with D/Bow shackle. - 4 sets |
| 211 | Main piping and Valves.Main piping and valves 150 mm dia delivery, 200 mm diacommon header line. |
| 212 | Valves.Confirming to IS 780/2906 or as applicable PN rating- 1.0Tpe of liquid to be handled-potable water |
| 213 | Material of constructionBody-CI,IS-210 grade FG 200Wedge-CI IS210 Grade FG200Spindle-Stainless steel AISI304Sheet and face Ring-SS ASTMA 743 Grade C.F.8 MChannel& Shoe-S.S.AISI,.304Drain& Air plug-S.S.AISI.304Bushing arrangement-Halprene on bronzeRivets-AISI:304Fasteners-MS |
| 214 | Motor Operated Sluice Valves |
| 215 | Sluice Valve 150 mm dia |
| 216 | Sluice Valve 200 mm dia |
| 217 | Reflux Valve |
| 218 | Reflux valve 150 mm dia N.B. |
| 219 | PipingsNote : Regarding the size of pipes, Tee, Bend etc, contrctor is required to designed them self and may got it approved by the department before execution of works along with layout drawing taking 150 mm pipe 40 m and 200 mm pipe 15m. |
| 220 | 150 mm, K9 delivery pipes for all six pumping plant |
| 221 | 200 mm, K9 common header pipes |
| 222 | Specials like bend, tee, D Joint etc. |
| 223 | Nut Bolt, Washer Rubber packing etc. |
| 224 | INSTALLATION, TESTING & COMMISSIONING |
| 225 | Installation & Commissioning of all 4 Nos. Pump set,Piping & Valves as mentioned in above |
| 226 | Level Transmitter (For Hi-Lo cut-off & alarms) |
| 227 | SITC of Radar type level transmitter shall be provided in the pump house for measuring the sewage level in wet sump. The indicator shall be digital type showing depth in meters and shall be capable for input to PLC or HMI touch sceen for display. |
| 228 | Electro magnetic flow meter |
| 229 | SITC of 200 mm diaCE/UL certified Electro magnetic flow metersuitable to measure 0 to 30 MLD flow to be fitted in 300 mm dia main header line. |
| 230 | E.O.T. Crane |
| 231 | SITC of 3 Tonn E.O.T. crane providing, erecting and commissioning single girder electrically operated rectangular over head travelling crane with 6 m lift complete with wire rope hoist, class II duty, all three motions electrically operated by suitable rating motor IP 54, control panel and down pendent control block. |
| 232 | Chequerred plate and guards |
| 233 | SITC of 3mm thick M.S chequerred plate over all the run of cables trenches to cover properly and M.S. grill and M.S. guard over all pipes ducts and other point where required as per site condition (Ref. UP Jal Nigam, GM Gzb Rate) (3X0.75+3X0.9+7X0.6+1X0.9)X1=10.05sqmm. |
| 234 | PAINTING |
| 235 | Painting of all pumps piping and valves with two coat enamel paint. (Ref.UP Jal Nigam E&M SOR, 2019) |
| 236 | LIGHT WIRING & Electrification |
| 237 | Complete Internal Electrification of LT Panel room with 2 Nos. Exhaust Fan |
| 238 | IPS Campus with Solar Panel and LED Light of 3 sets. |
| 239 | D.G. SET AND ACCESSORIES |
| 240 | SITC of Radiator Cooled and Turbo charged Silent type DG set , engine ,alternator capable of developing 100 kVA at 415+6%, 50 Hz AC at 0.85 P.F. lagging and self exciting coupled with suitable BHP diesel engine through flexible coupling and mounted on common base plate complete with fuel tank inside the acousting system and inbuilt control panel, Governor, Manual & electric Start , Batteries with battry charger, Engine instruments panel,AVM pads, All controls for operationof DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessiblefrom outside. T , 3 Met exhaust pipe, D.G. set shall be mounted under open sky resting on the foundation as per design. |
| 241 | SITC of PLC Based Auto main failure (AMF) Panel suitable for 62.5 kva dg set, fabricated from CRCA sheet steel 2 mm Thick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, operator interface panel complete in all respect. ( pwd bsr 2022- 23.29.3) |
| 242 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. \" B \" class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 withperforated holes of 12 mm dia ,including all accessories like nut, bolts,reducer, nipple, wire meshed funnel, and Heavy duty weather proof polypropylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, BottomDia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required.( pwd bsr 2022- 14.1) |
| 243 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/charcoal, testing of earth resistance for value of 5 ohms or less as required.( pwd bsr 2022- 14.3) |
| 244 | Supply & Laying 50 mm X 6mm sizeGI earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 245 | Providing and Laying cable for DG Set to Panel 120 sq mm X 3.5 core x 1 run( armored aluminium ) |
| 246 | Supplying and making one end termination with heavy duty brass compression gland (as per IS 12943- 1990) SIBG type, heavy duty aluminium lugs (as per IS 8309 - 1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade for 3.5 core X 50 sq mm. |
| 247 | SCREENS AND GATES: |
| 248 | Rising type thimble mounted CI Sluice Gates of reputed make at IPS |
| 249 | Stainless Steel Manual Bar Screen (20 mm gaping) at peak discharge with bar size 50 mmx 10 mm (1 working + 1 standby) |
| 250 | Packing and Frieght |
| 251 | Installation, Testing and Commissioning |
| 252 | AUTOMATION OF IPS |
| 253 | CE& UL certified PLC/RTU with redundant CPU & power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redundant CPU & power supply with annalog & digital paramter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations as specified in tender technical specification including full developed version of scada software with customization of software with laptop/desktop etc to monitor and control the ips from remote places. |
| 254 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer & gather data from remote sites to control stations all accessories included with signal enhancer antenna made for pumping plant internet charges as specified in tender technical specification. |
| 255 | CE/UL certified intellignet Smart Energy Meter |
| 256 | Auto phase reversal unit with inbuilt time delay & enclosure (confirm to IEC-60947-1 & IEC-60947-b-1) |
| 257 | 160 AMP rating |
| 258 | Electronic sensor type pressure measuring device suitable for pressure measurements of sewage flow in delivery and common header line. The material of construction of housing and other parts in contact with sewage shall be of stainless steel. These shall be of required protection category and complete with signal transmitting device and digital pressure indicator. |
| 259 | CE/UL Certified Surge protector for control panel. |
| 260 | CE/UL Certified 7\" HMI touch screen suitable to communication with PLC/RTU for local display & control ofp rocess parameters. |
| 261 | Security Survillance IP Camera with recorder |
| 262 | Installation, commissiong & testing of above automation work |
| 263 | Trial run for 3 month period for IPS |
| 264 | Three month Expenditure on Operator (IPS) in 3 Shift |
| 265 | Diesel Consumption During Trial and Run Period (IPS) |
| 266 | Electricity consumption for STP, MPS & IPS during period of Trail and Run payment done as UPPCL Bill |
| 267 | Cesspool Vehicle Cesspool Vehicle ( 1500 Litre Volumetric Capacity)having 5 mm thick steel plates. Complete equipment is mounted on reputed make Truck chassis with cabin BS 6 with all other specifications given in tender document (with Registration Certificate and insurance papers), with 3 month trial run. |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy