| 1 | Name of Work: Supply & Installation of Transfarmer, DG Set & Connection Accessories work in Indoor Sport Complex Jhansi CLUB at Jhansi.Note :-(1)-GST Excluded on the aforesaid work. |
| 2 | Supply, installation, testing and commissioning of following capacity(continuous loading) BEE 5 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase,50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door/indoor applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sqmm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and duly ISI Marked and as per CPWD specifications complete in all respects etc as required at site.400 KVADSR 2025 Item no 3.9 & 3.9.4 |
| 3 | Supply, installation, Testing & Commissioning of \"Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo-Tag of manufacturing location, rating plate as per relevant IS Code etc.320 KVADSR 2025 Item no 6.1 & 6.1.12 |
| 4 | Ring main unit for 11 kv (Load above 200 kva and upto 1000kva)uppcl cost data (annexure-27) |
| 5 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required.240sqmm DSR E&M 10.5 & 10.5.3 |
| 6 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. (a) 185 sq. mm x 3-1/2 core SOR 2024&(20a.1.17) |
| 7 | (b) 240 sq. mm x 3-1/2 core(20a.1.18) |
| 8 | Supply and laying of2.5 sq. mm x 4 core Copper CableStock Issue 2024-25 |
| 9 | Supply 11 KV HT XLPE Cable 3C x 185 Sq.mmuppcl cost data (annexure-9) |
| 10 | Laying of one number of PVC insilated & PVC sheathed / XLPE power cable of 11 kv grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sqmm and upto 400 sqmm DSR E&M 8.1 & 8.1.2 |
| 11 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer- Incharge (q)185 sq. mm 3-1/2 core SOR 2018-503 |
| 12 | (r)240 sq. mm 3-1/2 core |
| 13 | Supply and fixing ofplain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.(i)95 SqmmSOR 2018- 504 |
| 14 | (I) 185 sq. mm |
| 15 | (m)240 sq. mm |
| 16 | Supply and burrying of 75 mm Dia 3 Mtrs. Long Electrode casted with maintenance free, conductive concrete, non corrosive mixture ( Ultra low Resistive carbon 0.001 ohm/Mtr) in the ratio of 3:1:1 (marconite :cement : water) on M.S. Rod wiih hole (16 mm diameter X3 Mtrs ) will be vertically installed for earthing with 1 Mtr G.I strip (25 mm X 2.5mm) connected with SS nutbolt. The earth electrode will be installed into the 100 mm pit up to 3000 mm depth. noraml soil will be used as backfill material. Make : As approved in U.P.P.W.D & C.P.R.I. Certified.SOR 2018 729 (C ) |
| 17 | Providing and Fixing25MM x 5MM Copper Flat Strip on surface or in recess for Connection etc as required DSR E&M 5.14 |
| 18 | Providing and Fixing25MM x 5MM GI Flat Strip on surface or in recess for Connection etc as required DSR E&M 5.15 |
| 19 | Supply and Laying of PVC Flexible FR Wire 1C x 95 Sq.mm, Copper Multistranded CompleteMR |
| 20 | Supply, receive at site, store, unpack, assemble and connect Exhaust pipe with Class-B MS pipewith flanges, fire fly gaskets, hardware, Rockwool and aluminium sheet cladding etc. inclusive of all supports of wall/ceiling etc. For 1 x 150 mm - 200 MM DIA, MS Class B Pipe WALL THICKNESS as per IS Standardfor each DG Set or as per Manufacturers recommendated size Straight Horizontal + Vertical Exhaust pipe including Bends as required with two coats of zinc chromate painting & Rockwool of standarddensity finished with 24 Guage aluminium sheet cladding per DG Set with Rain Cowl with supports for Pipe MR |
| 21 | MS SUPPORT STRUCTURES FOR EXHAUST - Supply, fabrication and erection of Hot Dip Galvanised [100+ Micron] steel structure , with required Nut Bolt & Accessories .SOR 2022 civil 502 |
| 22 | RCC Foundation for Exhaust Structure with foundation boltMR |
| 23 | Making Plinth for Transformer & DG Set complete as per Direction of Engineer in Charge MR |
| 24 | Yard Fencing with Wire Mesh Chain Link 100MM x 100MM x 10MM Wire with Civil Work & Gate complete in all respect as per direction of the Engineer-Incharge. MR |
| 25 | Supply & Fixing of MS Febricated Steel with One Cote Redoxide & 1 Cote of Black Enamel Paint complete in all respect as per direction of the Engineer-Incharge MR |
| 26 | Supply & Fixing 11 KV Danger Board as per Direction of Engineer in Chargeuppcl cost data (annexure-17) |