Electrification Work At Sojati Gate Jodhpur - Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. asrequired. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure A attached with this BS 2 2 x 2.5 sq.mm 3 2 x 4.0 sq.mm 4 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure A attached with this BSR 5 10.0 Sq. mm 6 4 core 7 Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV gradedirect in ground including excavation of trench of size 75 cm (Depth) x 35 cm(Width) ,with procedure as per followingpoints:- (a) Make a river sand bed of height 125 mm along the trench,(b) Lay the cable in the middle of the trench,(c) Provide river sand bed of height 125 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thicknessand 225 mm widejust above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth 8 Providing & Fixing of Street light bracket made out from following size of B class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 9 25 mm Dia. 10 Supply & drawing Wiring for sub mains ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. For additional technical parameters of product / work refer Annexure Aattached with this BSR 11 4.0 sq.mm 12 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) /conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contactprotection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 13 Single pole MCB (With B/C curve tripping Characteristics) 14 6 A to 32 A rating 15 Providing & Fixing of ISO certified company made TP&N 415 V side handle operated double break fuse switch unit in sheet steel enclosure as per PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999 (W/O HBC fuses) including making connections with suitable lugs, testing etc. as required. Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 16 63 A rating 17 Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. B class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 18 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 19 8 SWG G.I. ( Hot Dipped) Wire 20 S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 21 25 mm 22 Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide 23 Extra if square,rectangular hollow tubelar sections are used or grill made by flats only 24 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade 25 Two or more coats on new work 26 Supply & Installation of decorative ornamental stepped pole height 4000 mm bottom made out of 140 mm dia MS pipes 1000 mm and Middle pipe was 76 mm dia. OD MS pipe 3000 mm height Double arm for fixing the light shall have window opening with flush door with looking arrangement at bottom of the pole to accommodate electrical accessories. The decorative pole shall be duty pre treated & painted in UV ray resistant PU coating in approved colour.The pole shall be erected on CC foundation 450mmx 450 mm x1000mm size with 4 nos. foundation bolt 20mmx750 mm length.The pole should having cast iron base at bottom and joint ring at step down of the pole.Double arm decorative pole. 4 meter decorative pole . 27 Supply of IP 65 ProtectedDecorativeLed Post Top suspended lantern range made up of spun aluminum canopy with die cast aluminum spigot.Fitted with glare free opticallydesigned prismatic diffuser protected LED decorative Post Top lantern with Low glare optical design & Acrylic diffuser 45W 220-240V, 50Hz (Integrated driver) driver shall be high efficiency having efficiency > 85% and in compliance to IEC standard (Integral with ligit fixture) system life of 25000 burning hours 70% of initial lumens maintained. system efficency should greather thanor equal 75Lm/W Power Factorv > 0.95 and CRI 70 decorative LED Top 45 Watt(ww/w). 28 Providing of IP66 protected High power LED Flood light system with pressure die cast housing,with suitable lenses on LED to achieve various beam angles,System lumen efficacy>=110lm/w,Driver shall be high efficiency having efficiency>85%,CRI>70,Power factor>0.95,System life of 50,000 Burning Hours with 70%of Initial Lumens maintained.Light output in warm white. 29 LED Flood Light 50W(Warm White/Green) 30 Providing of IP66 protected High power LED Flood light system with pressure die cast housing,with suitable lenses on LED to achieve various beam angles,System lumen efficacy>=100lm/w,Driver shall be high efficiency having efficiency>85%,CRI>70,Power factor>0.95,System life of 50,000 Burning Hours with 70%of Initial Lumens maintained.Light output in warm white. 31 LED Flood Light 140W(Warm White) 32 Supply & Installation of Unified Regulation System (URS) for existing street light that meets the following specification.The system must feature a 240MHz dual core processor with GSM/GPRS communication capabilities and support for OTA firmware updates.It should come with an internal class 1.0 energy metering system that can provide real time data of crucial electric load parameters along with fault and theft alerts.The URS must include remote load scheduling and control functionalities with a feedback time of less than seconds.the enclosure confirms to IP55 standards,and be fire retardant,weatherproof,and rustproof. The system should use a lightweight protocol for secure ,real-time communication and include cloud based software for comprehensive device management and remote control. it should be able to control single phase 5.5KW and 3 phase street light load upto 8.5KW and should come with 2pole/4pole MCB upto 25A/40A at output for short circuit protection.Having a 2-year warranty URS will be installed at site as per direction of engineering incharge. Size (570x520x190mm)