Tender For Electrification Work Of Defence Lab Road (Baggikhana Road) Jodhpur - Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure A attached with this BSR 2 2 x 1.5 sq.mm 3 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure A attached with this BSR 4 16.0 Sq. mm 5 4 core 6 Labour charges for Dismantling of following existing street light electric poles with street light fixtures, underground cable, MS box and other electric items of the pole coming along the alignment of the road and removal and re- rolling MS poles/PCC poles of different sizes as well as handing over the same to DISCOM/UIT/MCstore and as per the direction of Engineer Incharge and clean the site good as per the requirementand submit the receipt from concering authority,all complete works. 7 Providing and Laying RCC Foundation for Octagonal/ Conical Street Light poles, High mast Poles as per Drawing attach at TableP-4with Following Procedure& All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 8 A) Excavation of Pit for Foundation Size upto required depth from Ground level 9 B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. 10 C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness 11 D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. 12 E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal 13 F) Providing & Fixing of 2 no. Required SizePLB HDPE Pipe& Foundation Bolt with template as per OEM Recommendations. 14 G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. 15 H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. 16 Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. 17 Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV gradedirect in ground including excavation of trench of size 75 cm (Depth) x 35 cm(Width) ,with procedure as per followingpoints:- (a) Make a river sand bed of height 125 mm along the trench,(b) Lay the cable in the middle of the trench,(c) Provide river sand bed of height 125 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thicknessand 225 mm widejust above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth 18 Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same 19 Add extrain item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. 20 Add Extrain item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. 21 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 22 Single pole MCB (With B/C curve tripping Characteristics) 23 6 A to 32 A rating 24 Plate Earthingas per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20mm dia. G.I. B class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 25 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 26 8 SWG G.I. ( Hot Dipped) Wire 27 Supply of 8 mtr.Decorative GI Pole Bottom Dia-140mm,Top Dia-89 mm,Lentgh-8000 mm,Thickness-3.4 mm,MS Base Plate 300*300*16 mm,Integrated junction Box with earthing provision backelite Sheet with 4 way connector,PU Paint without wire,450 mm foundation Bolt.Decorative Pole made with pipe of ERW Standard as per IS 1239 having decorative cast Iron embellishment for beautification with hot dip galvanised completely covered with minimum 70-80 microns.The Pole is coated with epoxy zinc phosphate primer of 40 microns and finished using polyurethane based paint.The Pole is provided with flush door at bottom with the proper strngthen to cut of the door opening;with special panel lock key and safety chain.All this arrangement will be mount upon heavy duty Bakelite sheet into the Pole.Hardware used is non-corrosive grade SS304.Complete fitting is pure polyester based powder coated with high corrosion resistance and chemical chromicised protection,also available with multiple coats of weather polyurethane paint in various colours. Double arm Decorative Pole : 8 mtr. 28 Supply of 8 mtr.Decorative GI Pole Bottom Dia-140mm,Top Dia-89 mm,Lentgh-8000 mm,Thickness-3.4 mm,MS Base Plate 300*300*16 mm,Integrated junction Box with earthing provision backelite Sheet with 4 way connector,PU Paint without wire,450 mm foundation Bolt.Decorative Pole made with pipe of ERW Standard as per IS 1239 having decorative cast Iron embellishment for beautification with hot dip galvanised completely covered with minimum 70-80 microns.The Pole is coated with epoxy zinc phosphate primer of 40 microns and finished using polyurethane based paint.The Pole is provided with flush door at bottom with the proper strngthen to cut of the door opening;with special panel lock key and safety chain.All this arrangement will be mount upon heavy duty Bakelite sheet into the Pole.Hardware used is non-corrosive grade SS304.Complete fitting is pure polyester based powder coated with high corrosion resistance and chemical chromicised protection,also available with multiple coats of weather polyurethane paint in various colours. Single arm Decorative Pole : 8 mtr. 29 Supply of IP 65 ProtectedDecorativeLed Post Top suspended lantern range made up of spun aluminum canopy with die cast aluminum spigot.Fitted with glare free opticallydesigned prismatic diffuser protected LED decorative Post Top lantern with Low glare optical design & Acrylic diffuser 90W 220-240V, 50Hz (Integrated driver) driver shall be high efficiency having efficiency > 85% and in compliance ti IEC standard (Integral with ligit fixture) system life of 25000 burning hours 70% of initial lumens maintained. system efficency should greather thanor equal 75Lm/W Power Factorv > 0.95 and CRI 70 decorative LED Top 90Watt(ww/w) 30 Supply & Installation of Unified Regulation System (URS) for existing street light that meets the following specification.The system must feature a 240MHz dual core processor with GSM/GPRS communication capabilities and support for OTA firmware updates.It should come with an internal class 1.0 energy metering system that can provide real time data of crucial electric load parameters along with fault and theft alerts.The URS must include remote load scheduling and control functionalities with a feedback time of less than seconds.the enclosure confirms to IP55 standards,and be fire retardant,weatherproof,and rustproof. The system should use a lightweight protocol for secure ,real-time communication and include cloud based software for comprehensive device management and remote control. it should be able to control single phase 5.5KW and 3 phase street light load upto 8.5KW and should come with 2pole/4pole MCB upto 25A/40A at output for short circuit protection.Having a 2-year warranty URS will be installed at site as per direction of engineering incharge. (Size 570x 520x190mm)