Construction Of 220/132Kv, 1X200mva And 132/33Kv, 1X50mva Gss At Bhadoti (Dist. Sawaimadhopur) With 33 Kv, 5.43 Mvar Capacitor Bank At Bhadoti,2X220kv Bay At 220Kvgss Gangapur City And 2X132 Kv Bay At 132Kv Gss Batoda (Turnkey Project) Bn-9018002515 - Circuit Breakers 3 220 kV Circuit Breakers 4 220kV circuit breakers (3 Ph.) Along with support Structure 5 2500 A, 50 kA 6 132 kV Circuit Breakers 7 132 kV circuit breakers (3 Ph.) Along with support Structure 8 1250 A, 40 kA 9 33 kV Circuit Breakers 10 33 kV circuit breakers (3 Ph.) Along with support Structure 11 1250 A, 25 kA 12 Instrument Transformers 13 Capacitor Voltage Transformer 14 Single-Phase, 220 kV, 4400 pf CVT 15 Single Phase 132 kV , 4400 pf CVT 16 33 kV Potential Transformer 17 33/√3 kV /110-110√3 18 Current Transformer (1-Phase) 19 220 kV CT 20 1000/1 A, 5C(Live Tank Type only) 21 132 kV CT 22 1000/1 A, 3C(Live Tank Type only) 23 500/1 A, 3C(Live Tank Type only) 24 33 kV CT 25 1000/1 A, 4C 26 500/1A, 2C 27 C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II) 28 New Substation 29 Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB 30 Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB 31 Control Panel for 220 kV Feeder Type: SAS-FCB 32 Relay Panelfor 220 kV Feeder Type: SAS-FRB 33 Control Panel for 220 kV Bus Coupler Type: SAS-BCCB 34 Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB 35 220 kV Busbar Protection Relay Panel Type: SAS-BBRB 36 Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB 37 Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB 38 Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA 39 Control Panel for 132 kV Feeder Type SAS-FCA 40 Relay Panel for 132 kV Feeder Type SAS-FRA 41 Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA 42 Control and Protection Panel for 33 kVFeeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD 43 Station HMI [Industrial grade Computer with 21TFT monitor as per specification requirements] 44 Station HMI (Hot Standby)[Industrial grade Computer with 21TFT monitor as per specification requirements] 45 HMI View Node[Industrial grad Computer with 21TFT monitor as per specification requirements] 46 A3 Size B&W Laser Printer 47 Substation Automation System Network Panel Type SAS-NW 48 Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC] 49 Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired 50 Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification. 51 Substation Auxiliary Monitoring Panel Type SAS-SAMP 52 Other Items: 53 Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements. 54 Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards. 55 Surge Arresters 56 220 kV LA 57 132 kV LA 58 33 kV LA 59 Substation LT Transformer 60 33/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil 61 Batteries & Battery Charger 62 Batteries (Sizing shall be as per requirement of technical specification) 63 220 V [Min. 600 AH] 64 48 V [Min. 600 AH] 65 Battery Charger System 66 220 V Float and Boost 67 50 V Float and Boost 68 Lighting System 69 Outdoor Lighting & other Works 70 Lighting Fixture Type FL-1 71 Lighting Fixture Type FL-2 72 Outdoor Receptacle 73 Type-RP 74 Type-RO 75 Substation Premises Lighting 76 Lighting poles 77 Type-L1 78 Type-D1 79 Street Lighting Type-SL-L1 for mounting on poles 80 Street Lighting Type-SL-D1 for mounting on Poles 81 Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc. 82 Lighting PanelType ACP-2 as per technical specification 83 Lighting PanelType ACP-3 as per technical specification 84 Indoor Lighting & Other Works 85 Electrification 86 Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room,Hall and administrative office building as per the requirements of the specifications 87 Illumiation 88 Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories andmounting arrangements) 89 Indoor Lignting Panels 90 Lighting Panel (Indoor)Type ACP-1 as per technical specification 91 Lighting Panel (Indoor)Type DCP as per technical specification 92 Wall mounted fans Approx. 400 mm sweep 93 Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator 94 Exhaust Fans 95 DCP Type 96 i) 5 Kg. 97 ii) 10 Kg. 98 Carbon di oxide type – 6 Liters. 99 Foam Type- 9 Liters 100 Sand type 101 i) GI Buckets 9 liters capacity 102 ii) Steel Stands for four buckets 103 Air Conditioning System 104 Air Conditioning for the Rooms specified in the specifications 105 1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building] 106 Power Cables(XLPE) 107 1Cx630 sq.mm 108 3.5Cx300 sq.mm 109 Power Cable(PVC) 110 1Cx150 sq.mm 111 3.5Cx70 sq.mm 112 3.5Cx35 sq.mm 113 4Cx16 sq.mm 114 4C x 6 Sq. mm 115 2C x 6 Sq. mm 116 Control Cable (PVC) 117 4 CX4 Sq. mm 118 4 CX2.5 Sq. mm 119 3Cx2.5 sq.mm 120 5Cx2.5 sq.mm 121 7Cx2.5 sq.mm 122 10Cx2.5 sq.mm 123 14Cx2.5 sq.mm 124 19Cx2.5 sq.mm 125 Substation Structures 126 Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]: 127 Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements] 128 Isolators 129 220 kV (3-Phase) (Horizontal DOUBLE BREAK) 130 1600A, 50KA, isolator with one E/S 131 Post insulators for above Isolator 132 1600A, 50KA, isolator without E/S 133 Post insulators for above Isolator 134 1600A, 50KA, isolator without E/S (TANDEM Type) 135 Post insulators for above Isolator 136 132 kV (3-Phase) (Horizontal DOUBLE BREAK) 137 1250A, isolator with one E/S 138 Post insulators for above Isolator 139 1250Aisolator without E/S 140 Post insulators for above Isolator 141 33 kV (3-Phase) (Horizontal DOUBLE BREAK) 142 1250A, isolator without E/S 143 Post insulators for above Isolator 144 800 Aisolator without E/S 145 Post insulators for above Isolator 146 800Aisolator withE/S 147 Post insulators for above Isolator 148 Switchyard Erection 149 Busbar & Interconnections 150 New Substation/ Switchyard 151 220 kV Switchyard Works: 152 Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/PorcelainLong Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays] 153 Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays] 154 Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays] 155 220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangementand specification requirements[ for 1 Bay] 156 Twin ACSR Zebra 157 Single ACSR Zebra 158 Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps,connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following: 159 220 kV DMT-type layout 160 Line bay 161 Transformer bay 162 Bus-Coupler 163 Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps,connectors, junction box including of all accessories etc. 164 132 kV Switchyard Works: 165 Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays] 166 Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays] 167 132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay),Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangementand specification requirements[ for 1 Bay] 168 Twin ACSR Zebra 169 Single ACSR Zebra 170 Single Panther 171 Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV TransformerBay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps,connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following: 172 132 kV Main & Aux-type layout 173 Line bay 174 Transformer bay 175 Bus-Coupler 176 Bus Sectionalizer 177 Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps,connectors, junction box including of all accessories etc. 178 33 kV Switchyard Works: 179 Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays + Bus Coupler] 180 Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays + Bus Coupler] 181 33 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangementand specification requirements[ for 1 Bay] 182 Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps,connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following: 183 33 kV Main & Aux-type layout 184 Line bay 185 Transformer bay 186 Bus-Coupler 187 LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors 188 Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps,connectors, junction box including of all accessories etc. 189 Bus Post Insulators (BPI) 190 220 kV 191 132 kV 192 33 kV 193 Earthing & Lightning Protection System 194 Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area 195 28 mm Dia MS Rod 196 28mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven. 197 28mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven. 198 28mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link 199 28 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works 200 50X12 mm GS Flat 201 50X6 mm GS Flat 202 Earth Enhancing Compound for treated pits as above and other requirement as per specification 203 Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat 204 Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats 205 Earth Wire for Shielding Protection of Switchyard 206 7/3.15 Galvenized Steel Wire 207 Earthwire tension clamps with D Shackle assembly 208 PG calmp to suit 7/3.15 mm GS earth wire 209 Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat 210 Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat 211 Lug to suit 7/3.15 mm earth wire 212 Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire 213 Bay Marshalling KIOSK 214 200 way (Stud Type Connectors) 215 AC Distribution Boxes (Outdoor Type) 216 Outdoor AC Distbibution Box (Double Front type) 217 Outdoor AC Distbibution Box (Single Front type) 218 Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building] 219 Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washersetc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works] 220 LT Switchgear 221 LT AC Main Panel 222 LT AC Distribution Board 223 Main Lighting Distribution Board 224 Emergency Lighting Distribution Board 225 220VDCDB 226 48V DCDB 227 PLCC EQUIPMENTS 228 220 kV Wave trap (1250A, 0.5 mH, 40 kA) 229 132 kV wave trap (1000A, 0.5 mH, 40 kA) 230 4 KHZ to 16 Khz channel digital PLCC carrier terminal with digital protection coupler (DTPC) IEC 101/104 data and 4W E&M speech applications 231 4 KHZ to 16 Khz channel digital PLCC carrier terminal without digital protection coupler (DTPC) IEC 101/104 data and 4W E&M speech applications 232 Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level. 233 HF Armoured Coaxial cable having 75 Ohms unbalanced impendance. 234 Microprocessor based 24/8 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility 235 Telephone Sets (Push Button Type) 236 20 pair Jelly Filled and armoured telephone cable with copper conductor of 0.63 mm 237 10 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm 238 5 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm 239 VFT Equipment (Modem) suitable for transmission of data through PLCC link based on FSK modulation technique programmable for baud rate 50,300,600,1200 and center freq. through switches or jumper 240 1G MPLS IP Connectivity (Ring Topology ) from two 132 KV Ckt Comprising IEC 104 Data transmission through DCU, VoIP Phone , Vedio Camera and Internet connectivity from associated 132 kVC circuits and integration with existing system 241 TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS 242 (A) TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements] 243 Insulation Tester (5000 Volts, Digital) 244 SF6 Leakage Detector 245 Digital Multimeter 246 Digital Clamp Meter 247 PLCC Maintenance/Testing Equipments: 248 200Hz to 620KHz selective level meter including impedance return loss measuring attachments compatible with level generator (at sl.ii below) 249 Level generator with a range at 50Hz to 620kHz including facility for synchronization with SLM 250 8 digit time interval & frequency counter with the frequency range of 10 Hz to 10MHz & timer range of 1 microsec to 1 sec in decade steps. 251 Dual range 15 MHz oscilloscope with a display screen 8x10 sq.cm and the input impedance of 1 M ohm/25 pF with a deflection coefficient of 5Mv/div to 20 V/div. 252 4-1/2 digit LCD Multimeter with input impedance of 10Mohm & with a range of 0.1 mV to 1000 V DC, 0.1mV to 600v AC, 0-10 AMP AC,(40hz to 10KHz) & 0-20 Mohm With builtin power –supply. 253 Print testing Kit for PLCC terminal, protection coupler, EPAX , As per specifications appended at Annexure- V2-P3-S19-2, Volume-II, Part 3, Section-XIX 254 (B) Maintenance Tools& Tackles 255 Oil Sampling Bottle (1 Liter Capacity) 256 Vaccum Cleaner 257 Telescopic ladder aluminium 6 meter height 258 Ring spanner set 259 Tube spanner set 260 Pipe wrench 24 inch 261 Pipe wrench 18 inch 262 Hydraulic crimping tools up to 630 sq.mm 263 Threading die set for pipe threading 264 Welding machine (arc welding) 10kVA 265 Heavy duty drilling machine 266 Bench Vice 267 Insulated cuttingplier 12 inch 268 Insulated cuttingplier8 inch 269 Screw driver 18 inch 270 Screw driver 12 inch 271 Hammer 8 lbs 272 Hammer 2 lbs 273 Chain pulley block 5 ton 274 Pipe derrick 275 Allen Keys 276 Box Spanners 277 (C )Office and Miscellaneous Equipments/ Items 278 Insulation Rubber mat (1mX2mX 12 mm) 279 Isulation Rubber Gloves (15 kV Tested) 280 Furniturefor Control Room Building: 281 SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification 282 Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet) 283 Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet). 284 Library Shelf with Glass Door (min 4 Shelf) 285 Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane. 286 Archival Storage 4 Drive Type 287 Lateral Filing Cabinets 288 3 Drawer Unit 289 4 Drawer Unit 290 Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system. 291 Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system. 292 Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 22 guage or better with two waylocking system. 293 Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments (22 guage). 294 Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG. 295 Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage 296 Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round. 297 Key board (wooden) with Glass door 298 First Aid Box 299 Shock Treatment Chart [Laminated with Frame] 300 Safety Instruction Boards [ Laminated with Frame] 301 (D) Drinking Water Arrangement 302 Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr) 303 RO/ Water Purifier 304 Refrigirator (380 Lt.) 305 Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner] 306 Danger Plate [Size and Color etc. be got approved from owner] 307 MANDATORY SPARES 308 (C )Circuit Breakers 309 220 KV 310 (One pole of circuit breaker with grading capacitor complete with pole column and interrupter with M.B. but without support structure and operating mechanism. 311 Rubber gaskets, ‘O’ rings and seals 312 Fixed Contacts 313 Moving Contacts 314 Terminal pads and connectors 315 Closing Assembly Valve 316 Trip Assembly Valve 317 Auxiliary Switch Assembly 318 Operation Counter 319 Closing Coils 320 Tripping coils 321 Support insulator complete for one pole of breaker 322 145 kV 323 One pole of circuit breakerwithout support structure and operating mechanism. 324 Rubber gaskets, ‘O’ rings and seals 325 Fixed Contacts 326 Moving Contacts 327 Terminal pads and connectors 328 Closing assembly valve 329 Trip assembly valve 330 Auxiliary switch assembly 331 Operation counter 332 Closing Coils 333 Tripping coils 334 Support insulator (set complete for one pole of breaker) 335 Instrument Transformer 336 Spare of 245kVCapacitive Voltage Transformer 337 (i)Complete CVT 338 Spare of 145kVCapacitive Voltage Transformer 339 (i)Complete CVT 340 Spare of 245kVCurrent Transformer 341 (i)Complete CT [1 No. each type supplied) 342 Spare of 145kVCurrent Transformer 343 (i)Complete CT (1 No. each type supplied) 344 Spare of 33 kVCurrent Transformer 345 (i)Complete CT (1 No. each type supplied) 346 (E) C&R panels (similar items as used in the quoted panels) 347 Bay Control Unit (220 kV Side of offered type) 348 Bay Control Unit (132 kV Side of offered type) 349 Bay Control & Protection Unit (33 kV Side of offered type) 350 Bay Unit (For 220 kV Busbar Protection of offered type) 351 Bay Protection Unit (Distance for 220 kV Feeders of offered type) 352 Bay Protection Unit (Line Distance cum Differential for 220 kV Feeders of offered type) 353 Bay Protection Unit (Distance for 132 kV Feeders of offered type) 354 Bay Protection Unit (Differential for 220 kV Transformers of offered type Main-I) 355 Bay Protection Unit (Differential for 220 kV Transformers of offered type-Main-II) 356 Bay Protection Unit (Differential for 132 kV Transformers of offered type) 357 Bay Protection Unit (Back-up Overcurrent & E/F of offered type) 358 Breaker failure relay (numerical type) 359 Trip circuit supervision relay 360 Self reset trip relay 361 Hand reset trip relay 362 Timer relay 363 DC supervision relays 364 Flag relays 365 Auxiliary relays 366 Multifunction Panel Meter 367 Fiber Optic Cable with Connectors 368 Transducers (Each Type used in the autoamtion system) 369 Ethernet Switch (of offered type) 370 (F) Station Transformer 371 10% of total Transformer Oil quantity in non-returnable drums 372 HV bushing 373 LV bushing 374 Pressure relief device 375 Tap charger contact 376 Set of valves 377 Set of gasket 378 Silica gel required for five replacements 379 (G) Surge Arrester 380 220kV class 198 kV rating LA complete as specified. 381 132kV class 120 kV rating LA complete as specified. 382 33 kV Class of 30kV rating LA Complete as specified 383 2 Nos. Terminal connector of each type as spare 384 (H) Battery & Battery Charger 385 220 V& 48 V Type Battery 386 Spare battery cell without electrolyte 387 Terminal connectors with bolts & Nuts 388 Float level indicators 389 Vent Plugs 390 220V/ 50V Battery Chargers 391 Set of Control Cards 392 Set of relays 393 Set of contactor 394 Micro-switches 395 Filter Capacitors 396 Thyristor/ Diode 397 Set of switches 398 Set of wound resistors 399 Potentiometers 400 Fuses of Thyristor with indicators 401 (I) L.T. SWITCHGEAR : 402 Relays 403 CTs AND PTs 404 Switches/Push buttons and Meters 405 TPN Switches/MCB 406 L.T. Breaker spares 407 a) Spring charging motor 408 b) Aux. Contact sets 409 c) Busbar Seal off insulators 410 d) Arc-chutes 411 e) Moving contacts 412 f) Arcing contacts (Fixed/Moving) 413 g) Springs (Closing/Opening) 414 h) Closing coil 415 i) Tripping coil 416 j) Aux. finger contact 417 k) Limit switches 418 l) Jaw contacts 419 Busbar 420 a) Busbar insulators 421 b) Interphase barrier 422 c) Busbar strip 1mm (Aluminium) 423 (J) LIGHTING SYSTEM 424 Single Pole MCB 425 Triple pole MCB 426 Fluorescent tube & Starter 427 a) Choke 428 b) Bottom Strips 429 c) Top covers & reflector (if applicable) 430 d) Holders 431 e) Complete fittings 432 Sodium vapour/Mercury vapour Lamps a) Lamp 433 b) Ballast 434 c) Condenser/ Igniter 435 d) Lamp holder 436 e) Lamp holder 437 f) Complete fittings 438 Incandescent lamp 439 a) Bulbs 440 b) Holders 441 c) Complete fittings 442 Switches and sockets 443 Junction box 444 Celing Fan 445 (K) Clamps & Connectors Set 446 (L) Fire Protection System 447 NIFPES System 448 Fitted Nitrogen Cylinder [48 Lit Water Capacity] 449 Hose Pipe with Fittings 450 Heat Sensor Assembly 451 Fire Survival Cable [sufficient for 1 system] 452 PNRV 453 Limit Switches for Fire Detector 454 Fire Detector (for NIFPES System) 455 Thermostat 456 Heating Element 457 (M) Isolators 458 220 kV 459 Solid core Insulator Stacks (Requirement of one Isolator) 460 Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered. 461 Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered 462 Motor with gear assembly and bevel gear assembly. 463 Bearings (Requirement of one Isolator) 464 Current carrying assembly total (Requirement of one Isolator) 465 132 kV 466 Solid core Insulator Stacks (Requirement of one Isolator) 467 Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered. 468 Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered 469 Motor with gear assembly and bevel gear assembly. 470 Bearings (Requirement of one Isolator) 471 Current carrying assembly total (Requirement of one Isolator) 472 33 kV 473 Solid core insulator Stacks ( Requirement of one Isolator) 474 Limit switches and auxiliary switches ---Each Set containing one no. of each type andrating as offered 475 Bearings (requirement of one isolator) 476 Currentcarrying assembly 2000A total(requirement of one isolator) 477 Motor with gear assembly and bevelgear assembly. 478 Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type andrating as offered 479 Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.