REPAIR/ MAINT OF PUMP, MOTOR, STARTER, DOZING SYSTEM, SWIMMING POOL COMPRESSOR, RAISING MAIN, GATE VALVE, PERIODICAL CLEANING OF TANKS & OTHER MISC WORKS AT AFTC, 2 DC AREA & AFS JALAHALLI EAST WEST AREA; M&L for taking down defective centrifugal pump set 100 HP capacity by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lath work, re-assembling and shifting from workshop to site, re-installation at same location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :-(a)The spares shall be measured and paid seperately in the relevent items given below.(b) Cost of labour for replacement of spares and transportation are deemed to be included in the quoted rate. (c)The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. Thecontactor is responsible for making alternate arrangement of pump set in case of time required more than one week.(d)In case services affected due to delay in repair of pump set, a penalty @ Rs 1000 per day will be levied from the contactor.(e)Please note that this penalty is exclusively other than the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.(f)The decision of the Accepting Officer in this regard shall be final and binding. 2 Supply only Ball bearing suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed.Make : Tata/SKF/NBC 3 Supply only coupling Rubber Bush suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 4 Supply only split casing gaskets suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 5 Supply only shaft sleeves suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 6 Supply only coupling bolt with nuts suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 7 Supply only water seal suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 8 Supply only Air cock grease nipple suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 9 Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 100 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 10 Supply only bronze impeller suitable for 100 HPcapacity motor pump as per manufacturers design complete all as specified and as directed. 11 M&Lfor suitable size of gland packing for 100 HP pump set as per manufacturers design complete all as specified and as directed. 12 Supply & fix in replacement of 3 Pole power contactor AC 415 V 160 Amps ,AC3 ( inductive load ) type with Aux contact 2 NO + 2 NC50 Hz Model No. as per existing framesuitable for 100 HP Pump sets complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 13 M & L for servicing of starter by checking and servicing the contactor coil , over load relay coiland any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drillingtesting the panel complete all as specified and directedfor the100 HP capacity pump setsNotes :-(i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be include in quoted rate. 14 Supply & fix in replacement adjustable CT/Direct operated thermal over load relay 105 to 156 A for 100 HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 15 M&L for rewinding ofsquirrel cage induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load complete all as specified and directed for 100HPmotor capacity. 16 M&L for taking down defective centrifugal pump set 60 HP capacity by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lath work, re-assembling and shifting from workshop to site, re-installation at same location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :-(a)The spares shall be measured and paid seperately in the relevent items given below.(b) Cost of labour for replacement of spares and transportation are deemed to be included in the quoted rate. (c)The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. Thecontactor is responsible for making alternate arrangement of pump set in case of time required more than one week.(d)In case services affected due to delay in repair of pump set, a penalty @ Rs 1000 per day will be levied from the contactor.(e)Please note that this penalty is exclusively other than the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.(f)The decision of the Accepting Officer in this regard shall be final and binding. 17 Supply only Ball bearing suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed.Make : Tata/SKF/NBC 18 Supply only coupling Rubber Bush suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 19 Supply only coupling bolt with nuts suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 20 Supply only shaft sleeves suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 21 Supply only split casing gaskets suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 22 Supply only water seal suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 23 Supply only Air cock grease nipple suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 24 Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 60 HP capacity motor pump as per manufacturers design complete all as specified and as directed. 25 Supply only bronze impeller suitable for 60 HPcapacity motor pump as per manufacturers design complete all as specified and as directed. 26 Supply and fix in replacement of mechanical flexible UT tyre rubber coupling suitable for 60 HP centrifugal pump set with cast iron flange, natural rubber coupler, mild steel clamping ring, high tensile strength Grade suitable size of Hex bolts, including aligning motor - centrifugal pump with a tolerance of +- 4mm, testing complete all as specified and directed. 27 M&Lfor suitable size of gland packing for 60 HP pump set as per manufacturers design complete all as specified and as directed. 28 M & L for servicing of starter by checking and servicing the contactor coil , over load relay coiland any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drillingtesting the panel complete all as specified and directedfor the60 HP capacity pump setsNotes :-(i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate. 29 Supply & fix in replacement of 3 Pole power contactor AC 415 V AC3 ( inductive load ) type 100 Amps, AC3 type 2 NO + 2 NC50 Hz Model No. as per existing frame suitable for 60 HP Pump sets complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 30 Supply & fix in replacement adjustable CT/Direct operated thermal over load relay75 to 110 A for 60 HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 31 Supply & fix in replacementSingle phase preventer for motor in the existing panel board with new one at water supply installations complete all as specified and as directed. 32 Supply & fix in replacement Star Delta timer 0-30/60 sec complete all as specified and as directed. 33 M&L for rewinding ofsquirrel cage induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load complete all as specified and directed for 60 HPmotor capacity. 34 Taking down defective centrifugal pump set 25 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a)The spares shall be measured and paid seperately in the relevent items given below.(b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c)The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. Thecontactor is responsible for making alternate arrangement of pump set in case of time required more than one week.(d)In case services affected due to delay in repair of pump set, a penalty @ Rs 500 per day will be levied from the contactor.(e)Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.(f)The decision of the Accepting Officer in this regard shall be final and binding. 35 Supply only Ball bearing suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed.Make : Tata/SKF/NBC 36 Supply only split casing gaskets suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 37 Supply only Air cock grease nipple suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 38 Supply only water seal suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 39 Supply only coupling bolt with nuts suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 40 Supply only coupling Rubber Bush suitable for 25HP motor pump as per manufacturers design complete all as specified and as directed. 41 Supply only shaft sleeves suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 42 Supply only bronze impeller suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 43 Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 25 HP motor pump as per manufacturers design complete all as specified and as directed. 44 M&Lfor suitable size of gland packing for 25 HP pump set as per manufacturers design complete all as specified and as directed. 45 Supply & fix in replacement adjustable CT/Direct operated thermal over load relay30 to 43 A for 25 HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 46 Supply & fix in replacement of3 Pole power contactor AC 415 V AC3 ( inductive load ) type 40 Amps with add on aux contact 2 NO + 2 NC50 Hz Model No. as per existing framesuitable for 25 HP Pump set complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 47 M & L for servicing of starter by checking and servicing the contactor coil , over load relay coiland any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drillingtesting the panel complete all as specified and directedthe25 HP capacity pump setsNotes :-(i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate. 48 M&L for rewinding ofsquirrel cage induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load complete all as specified and directed for 25 HPmotor capacity. 49 Supply and fixing in repair of3 phase star delta pump starter suitable for 25 HP centrifugal pump with over load relay of suitable current rating,timer relay ,single phase preventor fixing in existing enclosure including all connected accessories complete all as specified and directed Make : L&T/Indoasian/Schenider/Havells 50 Supply and fix as in repair 4 Pole MCCB ,415 volts,fixed type ,160 Amp, 50 Hz, with rupturing capacity 25 KA in theexisting pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indoasian/L&T/ Legrand 51 Taking down and relaying of existingDI water pipe lines of size 300 mm bore but of any type including all fittings after removal of scaling, cleaning and flushing etc complete all as specified and directed.Note:Excavation & earthwork shall be measured & paid seperately 52 Taking down and relaying of existingDI water pipe lines of size 200 mm bore but of any type includings all fittings after removal of scaling, cleaning and flushing etc complete all as specified and directed.Note:Excavation & earthwork shall be measured & paid seperately 53 M&L as in replacement for Ductile Iron Pipe (DI Pipes), ISI marked, Class K-7, 300 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grease etc complete all as specified and directed.Note :- DI fitting/special shall be measured and paid separately.Note:Excavation & earthwork shall be measured & paid seperately 54 Supply and fixing in replacement Sluice valve of size 300 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed 55 Material and Labour for dismantling the brassspindle from 300 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed. 56 Material and Labour for gland packing in leaking Sluice Valves of 300 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed . 57 Cutting the existing broken / cracked CI/DI/GI/Asbestos Cement Pipe line of size upto 300mm dia, by dewatering the leakage water from site and removing the old pipe line and addition / alteration to pipe by providing new pipe,welding,bending,grinding,including all accessories such as tee,elbow,collar etc , and ensure no leakage with pressure test complete all as specified and directed , Note : Pipes and mechanical collar shall be measured and paid seperately 58 M&L for specials fittings suitable for Cast iron / ductile iron /Asbestos cement pipe made out of MS Plate of 12 mm thick complete with mechanical/detachable type arrangement as per site requirementwith MS bolts and nuts of suitable size and MS sheet fabricated to required dia of pipe for prepration of collar/flange, on any pipe leak or cracks of pipe for arresting the leakage complete including rubber ring, packing rubber sheet,set of two collar rings of size 300 mm borecomplete all as specified and as directed. 59 M&L as in replacement for Ductile Iron Pipe (DI Pipes), ISI marked, Class K-7, 200 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grease etc complete all as specified and directed.Note :- (i)DI fitting/special shall be measured and paid separately. (ii)Excavation & earthwork shall be measured & paid seperately 60 S&F in replacementfoot valve (confirming to IS-4038) cast iron of size 200 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed. 61 Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 200 mm ISI marked, CIbody suitable for 200 mm dia pipe line complete all specified and directed 62 Supply and fix replacement of U/S leather packing suitable for foot valve 150 to 200 mm dia, suction pipe flanged connected to pumpsets including replacement ofnuts and bolts etc all as specified and directed 63 Supply and fixing in replacement Sluice valve of size 200 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed 64 Material and Labour for dismantling the brassspindle from 200 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed. 65 Material and Labour for gland packing in leaking Sluice Valves of 200 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed . 66 Material & Labour as in repair for Construction ofValve pit having inner dimensions 1200 mm x 1200 mm x 1200 mm with foundation PCC 1:4:8 type D2 using 40mm grade stone aggregate, brick work with sub class B old size bricks built in Cement mortar 1:6, PCC 1:2:4 type B1 using 20mm stone aggregate for Coping, 15 mm thick rendering plaster in CM 1:4 inluding MS cover with locking arrangement all as specified and as directed.Note :- MS work as in chamber cover shall be measured and paid separately under relevant item of this schedule. 67 Cutting the existing broken / cracked CI/DI/GI/Asbestos Cement Pipe line of size upto 200mm dia, by dewatering the lekage water from site and removing the old pipe line and addition / alteration to pipe by providing new pipe,welding,bending,grinding,including all accessories such as tee,elbow,collar etc , and ensure no leakage with pressure test complete all as specified and as directed. Note : Pipes and mechanical collar shall be measured and paid seperately 68 M&L for specials fittings suitable for Cast iron / ductile iron /Asbestos cement pipe made out of MS Plate of 12 mm thick complete with mechanical/detachable type arrangement as per site requirementwith MS bolts and nuts of suitable size and MS sheet fabricated to required dia of pipe for prepration of collar/flange, on any pipe leak or cracks of pipe for arresting the leakage complete including rubber ring, packing rubber sheet,set of two collar rings of size 200 mm borecomplete all as specified and as directed. 69 Clearing the bushes trunk girth not exceeding 10 .00 cm and area around valve chambers upto 1.0 mtrs and depositing at a distance not exceeding 50 mtrs from starting point complete all as specified and directed 70 Demolition of Brickwork or precast concrete block walling including wall quoins, arches, pillars, etc, but excluding ashlar facings, dressed stone work and concrete articles built in cement mortar complete all as specified or directed. 71 M&L for Pre-cast cement concrete block masonry in PCC (1:3:6) type C-1 using 20mm grade stone aggregate with solid blocks, exc.10 cm in width and setting in cement mortor 1 : 4, complete, in walls all as specified and directed. 72 Over hauling and repair to Chemical Dosing Pump Granual based chloronome plants at Range pump houseby cleaning the FRP 150 Ltrs Tank, and cleaning of filters and NRV , checking and cleaning the delivery pipe line for chocking , cleaning of chlorination plant and maintainig properly including checking the level of oil in the gauge and topping up as and when required, checking the glands and maintain the plant in all respect and replacement of minor spare for smooth functioning of Chlorination Plant all as directed by Engineer in charge. Note:- The unit rate quoted shall be deemed to include for the cost of replacement of minor spares such as O rings , nut/screws,washers,bolt, cleaning waste , toolsfor routine day to day maintenance and necessary servicing to keep the plants in running condition on all days includingSunday and holidays, Replacement of other major spares shall be measured and paid for separately under respective item of BOQ 73 All as per item No 72 but at E & ITI OH Tank complete all as specified and directed. 74 All as per item No 72 but at Double Tank complete all as specified and directed. 75 All as per item No 72 but at ETI OH Tank complete all as specified and directed. 76 Supply onlyO-tolodine chlorine solution in packing of 200ml bottle for testing of chlorine content in water 77 Supply onlyChlorine dosing pistonpump unit complete 78 Supply only Rubber ring for mixing chamber 79 Supply onlyPVC NRV set with glass ball for suction and delivery adopter 20 mm dia 80 Supply onlyTeflon gland square type 3 mm for smooth functioning of Chlorination plant 81 Supply only PVCdiaphram valve 25 mm dia heavy duty 82 Supply only Agitator mixing assembly with motor 83 Supply only Chlorine test kit with coloured sample Complete with all testing fitments and OT - solution in Rexene finished box Complete all as specified and as directed 84 Supply of calcium based high strength chlorination chemical for water in granular form chlorine concentration level having 65%-70% chlorine content packed in 45 Kg capacity in factory sealed HDPE Container superior quality suitable for treatment of drinking water complete all as specified and directed.Note:The material shall be delivered at watersupply installation as per direction of AGE E/M as & when required during the contract period. 85 Material and labourfor Attending day to day water supply service related complaintslike choking of rising main pipes of buildings, blockage in control valves/ float valves/ pipe fittings, etc, applying necessaryengineering efforts like dismantle of pipes and fittings to clean and remove blocking objects, descaling of pipes, re-fixing of pipes on wall, etc to restore the proper flow of water to service tanks all as specified and directed. 86 Note :- (a) The contractor has to attend above mentioned job in any location of AFTC, 2 DC and entire AFS jalahalli East and West area 87 (b)The service tanks are positioned on roof top of multi storied buildings upto three storey. Contractor is responsible to ensure that the labour employed should be equipped with safety items like industrial helmet, safety belt, extensible ladder of 40 feet length, plumbing and cuttings tools, etc. 88 (c) The cost of rethreading of GI pipes of 25mm dia and adding of new GI nipple of suitable length after rethreading is deemed to be included in the quoted rate. 89 (d) Due to shortage of water in the station, the repair work and testing required under this item need to be carried out during water supply distribution hours i.e. 5:30 AM to 7:30 AM. Nothing extra shall be permitted in this regard. 90 (e) The cost of repair to the damages of cemented surfaces/ external finishes/ metal clamps of rising pipes are also deemed to be included in the quoted rate. 91 (f)In case of any delay in attending the complaint more than 6 hrs after handing over routine/urgent complaints, the contractor shall be liable to pay the penalty as described in penalty clause given here as under. 92 (g)If the delay is more then 06 hrs period and the GE is not satisfied with the reason for delay then penalty at the rate of Rs 100/- per job shall be deducted from the dues of the contractor. Please note that this penalty is exclusively other then the condition 67 of IAFW - 2249 and shall be treated as interim condition of the contract and shall be enforce above as and when delay in individual job is noticed and no claim whatsoever on this account shall be entertained by the Deptt. 93 (h) The decision of the Accepting Officer in this regard shall be final and binding. 94 Supply and fix Nipple suitable for HDPE water tankof size 20 mm complete all as specified and as directed. 95 Supply and fix Nipple suitable for HDPE water tankof size 25 mm complete all as specified and as directed. 96 Supply and fix in repairs lids for polyethylene water storage tanks, threaded or hinged type as per existing incl PTMT nuts/binding wire suitable up to 1000Ltrs cap of tanks complete all as specified and directed by Engineer-in Charge 97 Supply and fix in replacement PVC Ball valve ISI marked high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed of size 20 mm complete all as specified and directed 98 Supply and fix of PVC water tank 500 ltrs capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part-I ,complete all as directed incl disconnecting existing tank of any description and any capacity complete. 99 Supply and fixingin repair 25 mm dia Unplasticiced PVC Pipes of pressure rating 10kgf/cm2including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed. 100 Supply and fixing in repair20 mm dia Unplasticiced PVC Pipes of pressure rating 10kgf/cm2including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed. 101 Supply and fixingin repair UPVC Gate Valve of size 25 mm dia , ISI marked complete all as specified and as directed. 102 Supply and fixingin repair UPVC Gate Valve of size 20 mm dia, ISI marked complete all as specified and as directed. 103 Supply and fixingin repair 20 mm dia Chlorinated PVC (CPVC) Pipes of pressure rating 10kgf/cm2including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed. 104 Supply and fixingin repair 25 mm dia Chlorinated PVC (CPVC) Pipes of pressure rating 10kgf/cm2including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed. 105 Supply and fixingin repair Chlorinated PVC Gate Valve of size 20 mm dia, ISI marked complete all as specified and as directed. 106 Supply and fixingin repair Chlorinated PVC Gate Valve of size 25 mm dia, ISI marked complete all as specified and as directed. 107 Supply and fix in repairs lids for polyethylene water storage tanks, threaded or hinged type as per existing incl PTMT nuts/binding wire suitable for1001 to 5000 Ltrs cap of tanks complete all as specified and directed by Engineer-in Charge 108 Supply and fix in replacement PVC Ball valve ISI marked high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed of size 25 mm complete all as specified and directed 109 Supply and fix of PVC water tank 1000 ltrs capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part-I ,complete all as directed incl disconnecting existing tank of any description and any capacity complete. 110 Taking down and relaying of existingserviceable GI tubing / connection in new or old positions including cleaning, cutting, threding all as directed, along with new GI fittings where ever replaced and required at site of size 40 to 50 mm bore complete all as specified directed. Note:Excavation & earthwork shall be measured & paid seperately 111 Taking down and relaying of existing serviceable GI tubing / connection in new or old positions including cleaning, cutting, threding all as directed, along with new GI fittings where ever replaced and required at site of size 25 mm bore complete all as specified directed. Note:Excavation & earthwork shall be measured & paid seperately 112 Taking down and relaying of existingserviceable GI tubing / connection in new or old positions including cleaning, cutting, threding all as directed, along with new GI fittings where ever replaced and required at site of size 20 mm bore complete all as specified directed. Note:Excavation & earthwork shall be measured & paid seperately 113 Taking down and relaying of existingserviceable GI tubing / connection in new or old positions including cleaning, cutting, threading all as directed, along with new GI fittings where ever replaced and required at site of site of size 15 mm borecomplete all as specified directed. 114 Supply & Fix as in replacement of GI tubing medium grade of size 50 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed.Note:Excavation & earthwork shall be measured & paid seperately 115 S&F in replacement Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 50mm complete all as specified and directed. 116 Supply & Fix as in replacement of GI tubing medium grade of size 40 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed.Note:Excavation & earthwork shall be measured & paid seperately 117 S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 40 mm complete all as specified and directed. 118 Supply & Fix as in replacement of GI tubing medium grade of size 25 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note:Excavation & earthwork shall be measured & paid seperately 119 S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 25 mm complete all as specified and directed. 120 Supply & Fix as in replacement of GI tubing medium grade of size 20 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note:Excavation & earthwork shall be measured & paid seperately 121 S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 20 mm complete all as specified and directed. 122 Supply & Fix as in replacement of GI tubing medium grade of size 15 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note:Excavation & earthwork shall be measured & paid seperately 123 S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 15 mm complete all as specified and directed. 124 S & F in replacement Bib taps, cast copper alloy chromium plated with crutch or butterfly handle, screwed down, screwed for iron pipe fixed of size 15 mmfor brass ferrule fancy type and fixed complete all as specified and directed. 125 Supply and fix Nipple suitable for HDPE water tankof size 40 mm complete all as specified and as directed. 126 Supply and fix in replacement PVC Ball valve ISI marked high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed of size 40mm complete all as specified and directed 127 Supply and fix PVC water tank 2000 Ltrs Capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I, complete all as directed incl disconnecting existing tank of any description and capacity complete. 128 Supply and fixingFramed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, hinges and handles etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 for valve pit chamber, raising main support and motor foundation supports etc.complete all specified and directed. 129 M & L for Over hauling and repair/replacement of unserviceable items ofPortable RO unit of capacity 80 LPD by disconnecting all pipe lines, filters catridges, RO Membrane , motor, float valveand water storage tank,all filter catridges(Pre Activated carbon ,Post Activated carbon, inline sedimant , pre particle filter), motor carbon brushes, pressure pump diaphram, float valve,solenoid valve,12/24v SMPS power supply unit , damaged piles lines , bends ,tee , elbow, water flow restrictor including cleaning of water storage tanks and testing (TDS ), fixing of pre filtersall respect and replacement of minor spare such as carbon brush ,tee ,elbow,pipe line,teflon tape,screws,nuts etc include in this quoted rate for smooth functioning of RO Plant complete all as specified and as directed.Note : Major spare parts shall be measured and paid seperately as supply only under relevant items of BOQ. 130 Supply only Reverse Osmosis membrane with clamps suitable for RO unit all as specified 131 Supply only Inline sediment filter with clamps suitable for RO unit all as specified 132 Supply only pre particle filter with food grade housing arrangement and with clamps suitable for RO unit all as specified 133 Supply only pre-activated carbon filter with clamps suitable for RO unit all as specified 134 Supply only Pressure pump 12/24vsuitable for RO unit all as specified 135 Supply only float switch suitable for RO unit all as specified 136 Supply only Post-activated carbon filter with clamps suitable for RO unit all as specified 137 Supply only RO pressure Pump Diaphram Head unitsuitable for RO unit all as specified 138 Supply only TDS,PH,Chlorine mesauring digital device all as specified 139 Supply only solenoid 12/24vsuitable for RO unit all as specified 140 Supply only 12/24v SMPS suitable for RO unit all as specified 141 Supply and fixing as in repair pre filter housingelementwithsuitable size of filter to protect RO includingPVC pipe of required length and all connected items complete all as specified and directed. 142 Supply, install, testing and commissioning ofChemical Dosing system havingtop dia 540mm x bottom dia 480mm x height 575 mm, net capacity 95 - 100 Ltr consisting of (i) water inlet line (ii) Dosing pump inlet arrangement (iii) Drain (iv) Overflow (v) Level Gauge (vi) inspection port (vii) Agitator 120 watt 800 - 900 RPM Single Phase flange mounted motor with plastic shaft and impeller (ix) provision of mounting Pump on Lid/wall along with dosing Injector of the following specification. Adjustble dosing pump max pressure 5kg/cm square& max flow rate 0 - 50 ltr / hr including all accessories such asLead tubing, Connecting Ferrules, check valves, non return valve all as directed. Power input 230V, 50 Hz, 40 SPM 1/30 fractional Horsepower, etc complete all as specified and directed. Make: - Model No. VST 1011 of Ravi Enterprise or equivalent as per E-in-Cs approved make.Note: Unit quoted rate shall be inclusive of taking down of old unserviceableplant and depositing same to MES store yard . 143 M&L for dewateringof Swimming Pool of size 50m x 25m (Olympic size pool ),Cleaning of Swimming pool bed,vertical walls complete with high pressure water jet to remove all masses, algae and dirt and removal of dirty waterwith sludge using non clog sludge machine and disposal of the same to a safe distance & applying of anti bacterial sterlization spray to walls, floors and applying muriatic acid, caustic soda or any other cleaning agent without damaging the existing tiles. Finally washing total surfaces with fresh water and make ready for fill up and ceilings all as directed.Note: (a) The Rate quoted by the contactor is deemed to include labours,tools and acessories andprovision of stickering of date of cleaning on the existing boardletter / figures White or Black colour and size as per existing font. (Date of Cleaned in format of (DD/MM/YY) Note : chemicals used for cleaning/PH level stablizer/anti Baterial/anti algae controller shall be supplied under relevant items 144 All as per Sl Item No. 143 here-in-before but Diving Pool of size 20 x 20 Meter complete all as specified and as directed. 145 All as per Sl Item No. 143 here-in-before but Balancing Tank of capacity 1,00,000 Gallon complete all as specified and as directed. 146 Supply only swimming pool grade Copper Sulphate crystal of superior qualityincluding stocking/ Handling and shifting complete all as specified and directed. 147 Supply only Swimming pool grade Hydro Chloric Acid (HCL) for regulating PH value of the pool complete all as specified and as directed. 148 Supplyonly swimming pool grade calcium based(Sodium Hypochloride) for water disinfectant as liquid form insealedcontainerhaving, chlorine concentration level not less than 12% and adding/mixing complete all as specified and as directed. 149 Supply only non ferrous Alum powder/crystal free from impurityclass Isuitable for swimming pools and adding/mixing as per direction of Engr-in-Charge to maintain water qualityincluding stocking/ Handling and shifting complete all as specified and directed. 150 Supply only Soda ash free from impurityclass Isuitable for swimming pools and adding/mixing as per direction of Engr-in-Charge to maintain water qualityincluding stocking/ Handling and shifting complete all as specified and directed. 151 Supply only Algae control gel/liquidfree from impurityclass Isuitable for swimming pools and adding/mixing as per direction of Engr-in-Charge to maintain water qualityincluding stocking/ Handling and shifting complete all as specified and directed. 152 Supply only chemically non reactive/lab quality Plastic mug 1 ltrs capacity complete all as specified and as directed. 153 Supply and fix in replacement ofchemically non reactive/Lab qualityPlastic bucket 35 ltrs capacity complete all as specified and as directed. 154 Supply and fix in replacement of nylon brush (soft quality) with wooden/HDPEbase of size 3 feet long, 2.5 (Inch) wide localy available best quality, suitable for fix with suction sweeper.complete all as specified and as directed. 155 Supply and fix in replacement ofnylon brushwithHDPEbase of size >18 Inch wide and handle > 20 feet long wide localy available best quality for cleaning walls of swimming pool complete all as specified and as directed. 156 Supply and fix in replacement offlexible pipe from suction sweeper pumps and Supply & fix PVC flexble hose pipe50mm OD including necessary jubilee clamps complete all as specified and as directed. 157 Supply and fix in replacement of nylon rope 25mm dia for suctionsweeper ( as per sample) complete all as specified and as directed. 158 Material and labour for opening the pressure filter vessel located in swimming pool of dia 2.8 Meter and height 2.6 meter for the following works:-(a)Opening the man hole cover and taking out entire filter media ie, existing stone aggregate , sand, quartz , slugde, algae etc(b)Cleaning of entire surfaces of sides , top and bottom of vessel by applying hydrochloric acidand thorough rinsing and make the vessel fit for re-filling the filter media.(c)Applying one coat of approved anti corrosive paint to entire internal surfaces of pressure filter including preparation of surfaces.(d) Re-fill the filter media with approved material of stone aggregate, river sand and white quartz in layers and properly packed upto existing level.All the material shall be rinsed thoroughly by using hydochloric solution and maintain the PH value at the range of 3 to 5.(e)Applying two coat of synthetic enamel paint to external surface of pressure filter vessel including preparation of surface etc and all as directed. 159 M&L for carrying out repair to trolley of suction sweeper pump set, including removing the pump and motor assembly carefully, dismantling rusted, bent or damaged MS frame members, cleaning entire surface, cutting and replacing corroded angle/channel sections with new mild steel of suitable size, welding, grinding and aligning to restore structural integrity. Work includes replacement of defective or jammed trolley wheels with new heavy-duty rubber/PU wheels of suitable load capacity, including fabrication of axle if required, welding, fitting and alignment. Entire metal frame surface shall be cleaned of rust and old paint using wire brush/scraper, then applied with one coat of red oxide primer and two coats of synthetic enamel paint of approved shade. Pump and motor set shall be re-mounted securely on trolley after repairs, reconnecting all mounting hardware as directed by Engineer-in-Charge, complete all as specified and directed. 160 M&L for carrying out repairs to 900mm wide suction sweeper head including dismantling the existing head assembly, cleaning and removing rust, replacing damaged or worn-out wheels with new nylon/plastic rollers of suitable size, fabricating and welding broken or bent brackets, repairing or replacing the metal body plate with mild steel sheet of suitable gauge, grinding sharp edges, tightening or replacing fasteners, restoring proper alignment of brush head and roller arms. Work includes thoroughly cleaning the base frame and applying one coat of red oxide primer and two coats of synthetic enamel paint for corrosion protection. The nylon bristle brush shall be checked for wear and refixed/replaced if found loose or damaged, ensuring smooth and uniform contact during sweeping operation. Complete all as specified and as directed by the Engineer-in-Charge 161 M&L for rewinding of 3-phase squirrel cage induction motor of capacity up to 3 HP, including removing the motor from its base, opening the end covers, dismantling the rotor, cleaning the stator core, removing burnt winding, preparing slots, rewinding the stator coils with super enamelled copper wire of same gauge and turns as per manufacturers specification, insulating with Class F insulation material, inserting wedges, varnishing with high-grade insulating varnish, oven drying, reassembling all components, aligning bearings, replacing terminal leads, testing for insulation resistance and load performance. Work includes cost of copper wire, insulating materials, varnish, labour, and testing equipment. Motor shall be tested under full load conditions for a minimum of 2 hours to ensure proper functioning. Complete all as specified and directed by the Engineer-in-Charge 162 M&L for carrying out repair to 3-phase DOL (Direct-On-Line) starter up to 5 HP capacity, including opening of enclosure, cleaning of all internal components, checking and tightening of loose terminals, replacing defective parts such as contactor coil, contacts, NO/NC auxiliary blocks, push buttons, overload relay, or indicator lamps with suitable rated spares as per original design, servicing of moving parts, reassembly, insulation testing, and functional testing under load conditions. The job includes cost of consumables like contact cleaner, terminal tags, and minor hardware. All replaced parts shall be measured and paid separately under relevant items. Complete all as specified and as directed by the Engineer-in-Charge 163 Taking down defective centrifugal/Monoblock pump set 10 HP to 15 HPby disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a)The spares shall be measured and paid seperately in the relevent items given below.(b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c)The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. Thecontactor is responsible for making alternate arrangement of pump set in case of time required more than one week.(d)In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contactor.(e)Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.(f)The decision of the Accepting Officer in this regard shall be final and binding. 164 Supply only Ball bearing suitable for 10 HP to 15 HPmotor pump as per manufacturers design complete all as specified and as directed.Make : Tata/SKF/NBC 165 Supply only coupling bolt with nuts suitable for 10 HP to 15 HPmotor pump as per manufacturers design complete all as specified and as directed. 166 Supply only coupling Rubber Bush suitable for 10 HP to 15 HP motor pump as per manufacturers design complete all as specified and as directed. 167 Supply only split casing gaskets suitable for 10 HP to 15 HP motor pump as per manufacturers design complete all as specified and as directed. 168 Supply only Air cock grease nipple suitable for 10 HP to 15 HP motor pump as per manufacturers design complete all as specified and as directed. 169 Supply only shaft sleeves suitable for 10 HP to 15 HP motor pump as per manufacturers design complete all as specified and as directed. 170 Supply only water seal suitable for 10 HP to 15 HP motor pump as per manufacturers design complete all as specified and as directed. 171 Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 10 HP to15 HP motor pump as per manufacturers design complete all as specified and as directed. 172 Supply only bronze impeller suitable for 10 HP to 15 HP motor pump as per manufacturers design complete all as specified and as directed. 173 M&Lfor suitable size of gland packing for 10 HPto 15 HP pump set as per manufacturers design complete all as specified and as directed. 174 Supply & fix in replacement adjustable CT/Direct operated thermal over load relay15 to 21 A for 10 HP to 15 HP motor3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed. Make : L & T / Indo Asian /Schneider 175 M & L for servicing of starter by checking and servicing the contactor coil , over load relay coiland any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drillingtesting the panel complete all as specified and directedfor the10 HP to 15 HP capacity pump setsNotes :-(i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate. 176 Supply & fix in replacement of3 Pole power contactor AC 415 V AC3 ( inductive load ) type 25 Amps with add on aux contact 2 NO + 2 NC50 Hz Model No. as per existing framesuitable for 10 HP to 15 HP Pump sets complete all as specified and as directed.Make : L & T / Indo Asian /Schneider 177 M&L for rewinding ofinduction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load complete all as specified and directed for 10 HP to 15 HPmotor capacity. 178 Taking down defective centrifugal /Monoblock pump set upto 5 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a)The spares shall be measured and paid seperately in the relevent items given below.(b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c)The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. Thecontactor is responsible for making alternate arrangement of pump set in case of time required more than one week.(d)In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contactor.(e)Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.(f)The decision of the Accepting Officer in this regard shall be final and binding. 179 Supply only coupling bolt with nuts suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 180 Supply only Ball bearing suitable for upto 5 HP motor pump as per manufacturers design complete all as specified and as directed.Make : Tata/SKF/NBC 181 Supply only split casing gaskets suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 182 Supply only coupling Rubber Bush suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 183 Supply only Air cock grease nipple suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 184 Supply only shaft sleeves suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 185 Supply only water seal suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 186 Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for upto 5 HP motor pump as per manufacturers design complete all as specified and as directed. 187 Supply only bronze impeller suitable for upto 5 HPmotor pump as per manufacturers design complete all as specified and as directed. 188 Supply and fix as in repair 4 Pole MCCB ,415 volts,fixed type ,125 Amp, 50 Hz, with rupturing capacity 25 KA in theexisting pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indoasian/L&T/ Legrand 189 M&L for rewinding ofelectrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation /base, cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation/ base of sunction sweeperby using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load complete all as specified and directed upto 5 HPmotor capacity. 190 M & L for servicing of starter by checking and servicing the contactor coil , over load relay coiland any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drillingtesting the panel complete all as specified and directedfor theupto 5 HPcapacity pump setsNotes :-(i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate. 191 Supply and fix in replacement single phase 240V50HzDOL starter with OLR relay suitable for upto 4 HP monoblock pump sets inculding proper termination,testing and all connected acessories all as are specified and directed. 192 Cleaning of service tanks of the capacity as mentioned below on roof top of bldgs upto three storey after disconnection from inlet and outlet pipe, removing of float valve of service tank and keep aside safely for reuse drain out water through drain plug, cleaning thoroughly to remove all scales and dirt by brushing internal surface, cleaning properlyinside with soda wash, flushing out with fresh water, re-positioning of tank at same place, re-connecting inlet and outlet pipes, closing of drain plug, re-installation of float valve duly cleaned, writing/ labelling the record of cleaning carried out with white bold letter such asTANK CLEANED ON--------- (month and year), including removing creepers, vegitation and roots of plants, trees branches on or surrounding of service tank complete all as directed.Note:-(i) Unit rate quoted is deemed to be included for testing of water supply in tank both inlet and outlet flow during next supply hours early in the morning or late in evening.(ii) Contractor shall maintain a pucca bound register for cleaning carried out with date and obtain users signature and remarks if any and this register to be submitted alongwith RAR.(iii)Contractor is liable to rectify any damages to the external finishes of the bldg occured during the cleaning process, i.e. scrubbing and touch up with external paints as existing specifications. Unit rate quoted is deemed too be included the cost of the same.(iv)All sort of petty T&P items such as ladder, safety equipment, nuts, bolts, washers etc. required to accomplish the job shall be provided by the contractor with out any extra cost to dept. 193 (a)For RCC /PVC tank exceeding 200 litters and not exceeding 500 ltrs 194 (b)For RCC /PVC tank exceeding 501 litters and not exceeding 1000 ltrs 195 (c)For RCC /PVC tank exceeding 1001 litters and not exceeding 2000 ltrs 196 (d)For RCC /PVC tank exceeding 2001 litters and not exceeding 5000 ltrs 197 (e)For RCC /PVC tank exceeding 5001 litters and not exceeding 25000 ltrs 198 Material and labour for preparation of old painted external surface by brooming down scrubbing with steel wire brush, scraping old distempered and painted surface and applying two coat of cement base paint to service tanks in building and under ground sump/ RCC Tanks all specified for tanks capacity of 200 to 500 Ltrs. 199 Material and labour for preparation of old painted external surface by brooming down scrubbing with steel wire brush, scraping old distempered and painted surface and applying two coat of cement base paint to service tanks in building and under ground sump/ RCC Tanks all specified for tanks capacity 501-1000 Ltrs. 200 Material and labour for preparation of old painted external surface by brooming down scrubbing with steel wire brush, scraping old distempered and painted surface and applying two coat of cement base paint to service tanks in building and under ground sump/ RCC Tanks all specified for tanks capacity 1001-2000 Ltrs. 201 Material and labour for preparation of old painted external surface by brooming down scrubbing with steel wire brush, scraping old distempered and painted surface and applying two coat of cement base paint to service tanks in building and under ground sump/ RCC Tanks all specified for tanks capacity 2001-5000 Ltrs. 202 Taking down and relaying of existingDI water pipe lines of size 150 mm bore but of any type includings all fittings after removal of scaling, cleaning and flushing etc complete all as specified and directed.Note:Excavation & earthwork shall be measured & paid seperately 203 Taking down and relaying of existingDI water pipe lines of size 100/80 mm bore but of any type includings all fittings after removal of scaling, cleaning and flushing etc complete all as specified and directed.Note:Excavation & earthwork shall be measured & paid seperately 204 M&L as in replacement for Ductile Iron Pipe (DI Pipes), ISI marked, Class K-7, 150 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grease etc complete all as specified and directed.Note :- (i)DI fitting/special shall be measured and paid separately.(ii)Excavation & earthwork shall be measured & paid seperately 205 Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 150 mm ISI marked, CI body suitable for 150 mm dia pipe line complete all specified and directed 206 S&F in replacementfoot valve (confirming to IS-4038) cast iron of size 150 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed. 207 Supply and fixing in replacement Sluice valve of size 150 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed. 208 Material and Labour for dismantling the brassspindle from 150 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed. 209 Material and Labour for gland packing in leaking Sluice Valves of 150 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed . 210 Material and Labour for Cutting DI pipes in position for insertion of new tees and socket of size 150 mm dia Complete all as specified and as directed. 211 Supply and fixing in replacement butterfly valve(confirming to IS-13095) of size 150 mm dia Cl body, ISI marked with IS-13095 having double door convex shape to prevent eddies and reaches head loss, neoprene rubber sealing and fitted complete all specified and directed 212 Cutting the existing broken / cracked CI/DI/GI/Asbestos Cement Pipe line of size upto 150mm dia, by dewatering the lekage water from site and removing the old pipe line and addition / alteration to pipe by providing new pipe,welding,bending,grinding,including all accessories such as tee,elbow,collar etc , and ensure any leakage with pressure test complete all as specified and as directed.Note : Pipes and mechanical collar shall be measured and paid seperately 213 M&L for specials fittings suitable for Cast iron / ductile iron /Asbestos cement pipe made out of MS Plate of 12 mm thick complete with mechanical/detachable type arrangement as per site requirementwith MS bolts and nuts of suitable size and MS sheet fabricated to required dia of pipe for prepration of collar/flange, on any pipe leak or cracks of pipe for arresting the leakage complete including rubber ring, packing rubber sheet,set of two collar rings of size 150 mm borecomplete all as specified and as directed. 214 M&L as in replacement for Ductile Iron Pipe (DI Pipes), ISI marked, Class K-7, 100 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grease etc complete all as specified and directed.Note :- (i)DI fitting/special shall be measured and paid separately. (ii)Excavation & earthwork shall be measured & paid seperately 215 Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 100 mm ISI marked, CI body suitable for 100 mm dia pipe line complete all specified and directed 216 S&F in replacementfoot valve (confirming to IS-4038) cast iron of size 100 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed. 217 Supply and fixing in replacement Sluice valve of size 100 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed. 218 Material and Labour for dismantling the brass spindle from 100 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed. 219 Supply and fix replacement ofleather packing suitable for foot valve 80 to 100 mm dia, suction pipe flanged connected to pumpsets including replacement ofnuts and bolts etc all as specified and directed 220 Material and Labour for gland packing in leaking Sluice Valves of 100 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed . 221 Material & Labour as in repair for Construction ofValve pit having inner dimensions 900 mm x 900 mm x 900 mm with foundation PCC 1:4:8 type D2 using 40mm grade stone aggregate, brick work with sub class B old size built in Cement mortar 1:6, PCC 1:2:4 type B1 using 20mm stone aggregate for Coping, 15 mm thick rendering plaster in CM 1:4 inluding MS cover with locking arrangement all as specified and as directed.Note :- MS work as in Chamber Covers shall be measured and paid separately under relevant item of this schedule. 222 Material and labour for Fabricate supply and fix valve chamber coversmade out of suitable size MS angle/MS plate/flat/rod, hinges, locking arrangement including painting with two coats of synthetic enamel paint over one coat of red oxide primer including removimg existing unserviceable rusted cover all as directed. 223 Material and labourfor Painting with two coats of synthetic enamel paint over a coat of zinc chrome on surfaces of any description, over 10cm in width or girth,not otherwise described complete all specified and directed. 224 Material and labourCleaning of valve pit chamber for sluice/gate valve of 50/80/100/150/200/ size by removing mud/ grass/ sludge/ other waste materialsfrom the chamber and from surroundings upto 1mtr distance, carryout petty cement repairs with cement mortar 1:4, apply one coat of white wash on cemented surfaces and one coat of synthetic paint on steel surfaces complete to make an operator friendly valve chamber complete as specified and directedNote :- Periodicity and locations of valve chambers shall be given as per requirement by the Engineer-in-Charge. 225 Cutting the existing broken / cracked CI/DI/GI/Asbestos Cement Pipe line of size upto 100mm dia, by dewatering the leakage water from site and removing the old pipe line and addition / alteration to pipe by providing new pipe,welding,bending,grinding,including all accessories such as tee,elbow,collar etc , and ensure any leakage with pressure test complete all as specified and as directed.Note : Pipes and mechanical collar shall be measured and paid seperately 226 M&L for specials fittings suitable for Cast iron / ductile iron /Asbestos cement pipe made out of MS Plate of 12 mm thick complete with mechanical/detachable type arrangement as per site requirementwith MS bolts and nuts of suitable size and MS sheet fabricated to required dia of pipe for prepration of collar/flange, on any pipe leak or cracks of pipe for arresting the leakage complete including rubber ring, packing rubber sheet,set of two collar rings of size 100 mm borecomplete all as specified and as directed. 227 Supply and Fixing as in replacement MCCB, 4 poles 415 Volts, 100 Amps, 16 KA, 50 Hz, AC, adjustable thermal and magnetictype in the existing pump starter panel including connecting up incoming/out going cable with suitable lugs and testing complete all as specified and as directed.Make : Legrand/Indo asian/L&T 228 M&L as in replacement for Ductile Iron Pipe (DI Pipes), ISI marked, Class K-7, 80 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grease etc complete all as specified and directed.Note :- (ii) DI fitting/special shall be measured and paid separately. (i)Excavation & earthwork shall be measured & paid seperately 229 M & L for DI specials and fittings as per IS for spigot and socketed pipes or flanged pipe for water mains branch lines such as bends(any type radious and angle ) tapers any type (straight, bend,increasing,decresing,or double socket etc) tee pices,single branch,Y juntion, double branch, cross, including connecting pieces one end flanged and other socket or spigot and bell mouth pices suitable for rubber joint,tyton joint up to 150 mm bore and conforming to IS-9523: 2000 complete all as specified and directed. 230 Note :-(a) In case of laying of CI/GI/DI pipe line is to be executed in civil area, it will be the responsibility of the contractor to obtain necessary permission for cutting of road & berm from BWSSB. 231 (b) For this purpose amount to be paid online to BWSSB, same is deemed to be included in unit quoted rate. 232 (c) The T&P like JCB, Drill Machine, Moveable Generator etc required for cutting of road shall be arranged by the contractor & no extra cost shall be paid for the same. 233 (d) After execution of work, the contractor will make good disturbed portion of road with bitumen or PCC complete as directed by Engineer-in-Charge. Cost of the same is deemed to be included in unit quoted rate. 234 Supply and fixing in replacement Sluice valve of size 80mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed. 235 Material and Labour for dismantling the brass spindle from 80 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze, spindle nuts with brass ring, gland nuts complete all as specified and as directed. 236 Material and Labour for gland packing in leaking Sluice Valves of 80 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed . 237 S&F in replacementfoot valve (confirming to IS-4038) cast iron of size 80 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed. 238 Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 80 mm ISI marked, CI body suitable for 80 mm dia pipe line complete all specified and directed 239 Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 65 mm ISI marked, CI body suitable for 65 mm dia pipe line complete all specified and directed 240 Material and Labour for Cutting DI pipes of size 200/150/100/80 in position for insertion of new tees and socket of size15/20 mm dia Complete all as specified and as directed. 241 Material and Labour for Plain Cement Concrete (1:2:4), type B1 (using 20 mm graded crushed stone aggregate) as in Coping, bands benching etc including finishing the concrete surfaces even and smooth without using extra cement including necessary form work Complete all as specified and directed. 242 Supply and fixing in replacement of Air Release Valve of size 40 mm dia Cl body, ISI marked of IS 14845 of 1.6 PNincluding fixing arrangement of existing 150 mm dia DI pipe line with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed. 243 Making arrangement to flush out the existing pipe line of any type upto 50mm bore and upto 100m length, applying 4.5 N/sqmm pressure to remove scalings/ sludges/ other blocking materials to make smooth flow of water including testing all as specified and directed. 244 Making arrangement to flush out the existing pipe line of any type 63 to 100 mm bore and upto 100m length, applying 4.5 N/sqmm pressure kg/sq cm pressure to remove scalings/ sludges/ other blocking materials to make smooth flow of water including testing all as specified and directed. 245 Material and labour for Making arrangement to flush out the existing pipe line of any type 110 to 150mm bore and upto 100m length, applying 4.5 N/sqmm pressure to remove scalings/ sludges/ other blocking materials to make smooth flow of water including testing all as specified and directed. 246 Material and labour for Making arrangement to flush out the existing pipe line of any type 160 to 200 mm bore and upto 100m length, applying 4.5 N/sqmm pressure to remove scalings/ sludges/ other blocking materials to make smooth flow of water including testing all as specified and directed. 247 Note for item 243 to 246 :-(i)The Contractor is deemed toarrange necessary tools and equipments, removing or alteration of fittings from existing pipe lines, arragement of plugging devices, etc to build up specified pressure required to wash out the pipes. This will be inclusive in quoted rate. (ii)Excavation and earth work required shall be measured and paid seperately. (iii)The flushing out shall be carried out with fresh filled water of well only duly chlorinated with specified sodium hypochlorite solution to disinfect the pipe lines from all pathogens and Coliform organisms.This will be inclusive in quoted rate. 248 Material and labour for dewatering & Cleaning ofRCC Over Head Tanks of the followingcapacities by comprisingof the followings 09 (NINE) stage of cleaning process complete all as specified and directed:-(i)De-watering by high pressure submersible pump all complete (Notes for item No 249 to 261) :- The Bidder shall take into consideration for following points while quoting his rate for this item andthe unit rate is deemed to be included for :-(i) The contractor shall provide dewatering pump of suitable capacity and mobile generatorfor operation of dewatering by high pressure submersible pump (or) Diesel driven high pressure pump and the rate quoted is inclusive of rent/hiring charges complete. (ii) Cuttingand filling, cleared of shrubs, vegetation, grass bush, weed, trees and sapling not exceeding 30 cm in girth, measured at a height of two metre above ground level. Useful material shall be stacked.(iii) Material removed from the tank shall be disposed off to out side MD land.(iv) Tank shall be made available for cleaning for a period of 8 hours only and contractor has to arrange sufficient labour/ T&P to complete the job with the given period only. or otherwise penalty shall be imposed @ Rs 500/- per day.(v) All safety gadgets like safety Belts, special safety ladder, Helmets, Heavy Duty Gum Boots,Gloves, Safety Goggles, Masks, Aprons, etc. for complete security safe operations, Storage and Cleaning equipment’s like Scrubbers/Wipers, Storage drums, Sludge Collectors and Cisterns, etc. must be integral part of system. (vi) Removal of sludge fromRCC Over Head Tanks(vii)Cleaning of walls, floors, ceiling etc by high pressure jet pump 80-180 bar pressure all complete(viii)Removing dirt and sludge by vacuum pump(ix) Anti- Bacterial Treatment of inside of tank effective againstall pathogens all complete.(x) Sterilization of the tank atomosphere by UV radiation inside of the tank.(xi) Applying one coat of white wash to internal surfaces.(xii)Replace nylon net for vent pipes &man hole cover(xiii)Writing letter in bold with white paint on black colour back ground such as sump number, capacity, cleaned on Date & Due on Date etc 249 250000 gallon capacity22 Mt heightat ETI Tank 250 150000 gallon capacity22 Mt heightat Bhatiya tank 251 150000 gallon capacity15 Mtr height at GLR 1 and GLR 2 Double tank 252 150000 gallon capacity12.5 Mtr height at IMH Area 253 150000 gallon capacity22 Mt height at E&ITI Tank 254 100000 gallon capacity 18 Mtr height at Bhatia tank,West 255 75000 gallon capacity 18 Mtr height at Umbrella tank 256 50000 gallon capacity18 Mtr height at Domestic Area 257 30000 gallon capacity25 Mtr height at CE Complex 258 25000 gallon capacity16 Mtr height at MAP, 54 Civ. 259 25000 gallon capacity18 Mtr height at Double tank168 WO 260 20000 gallon capacity12 Mtr height at Height at KV School 261 20000 gallon capacity12 Mtrheight at 90 CIV Pump House 262 M & L for Fixing in repairs Water Level Indicator consisting of float ball, nylon rope, Scale for water level indication made out of MS frame with pulley and indicating pointer for OHT at different places all as specified and directed . 263 Supply and fixing as in repair for aluminium earth continuity conductor or main earthing lead fixed to wall /roof top for lightning arresterfixed to OHT or other indicated situation for loop earthing etc. as required for 25 mm x 3 mm thick, aluminium using porcelain clit/post insulators with screw / selfdril GIscrew with rubber washer , complete all as specified and directed. 264 Supply and fix as in repair TPN MCB ,415 volts,fixed type ,40 Amp, 50 Hz, with rupturing capacity 10 KA in theexisting pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indoasian/L&T/ Legrand 265 S&F as in repair single core multistrand flexible copper cable of size 35 Sqmm x 1 core , includinglugs , connecting up with nuts and bolts, insulation tape wrappingetc , the selection of cable as per colour code all as specified and directed Make : Havells /Polycab/RPGAsian 266 Excavation in trenches not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level and laying of pipelines etcinany type of soil, complete all as specified and directed. 267 Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed. 268 Removing surplus excavated material (soil) not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and directed. 269 Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed.Note :- (i)Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment. 270 Material and labour for well burnt bricks ‘B’ class as mechanicalprotection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and directed. 271 Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earthwork, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :-The tenderer shall take into consideration for following points while quoting rate for this item andthe unit rate is deemed to be inclusive for :-(i) Earth work and excavation in any type of soil(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed.(iii) Removing excavated material to out side MD.(iv)Laying of any type/any bore of pipe in trenches including taking down. Supply of pipe shall be measured and paid separately(v)150 mm thickPCC 1:2:4 type B1 using 20mm graded stone aggregate as inroad to make good existing disturbed surfaces. 272 Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure. 273 Material and labour in repair for 3 ½ core 70 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items. 274 Material and labour in repair for 3 ½ core 50 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items. 275 Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 630 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- 276 (a) ON load change over switch 4 Pole, 415 V of capacity 400 Amp, 36 KA - 01 No. (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity400 Amp,36 KA- 02 Nos.(c) Multifunction Meter (V,I,PF) with suitable capacity of CTs- 01 No(d) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (e) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(vi) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). 277 Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire colour lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 3 2Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old unserviceable LT panel board and reconnecting existing LT UG Cable with new panel board complete all as specified and all as directed. This comprising of the following:- 278 (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp, 25 KA - 01 No (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity63 Amp,10 KA- 05 Nos (OG).(c) Multifunction Meter (V,I,PF) with suitable capacity of CTs- 01 No(d) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (e) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(vi) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). 279 Supply, installation, testing & commissioning of maintenance free chemicalearthing system comprising of 17mm dia copper bondedrod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducingliquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed..Make : Model HTSP 317 of safeTrode or equivalent in Snaga/ Cubes 6 Global 280 The quoted rate shall also deemed to be included the following :- (i)Prior toinstallation of maintenance free chemicalearthing, soil resistivity test to be carried out at the location where earthingwork to be donein presence of Engr-in- Charge/JE (E/M),user and the report has tosubmitto Garrison Engineer with recommendation of manufacturer, if required additional interconnection ofearthing (not more than 08 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testingandsubmission of report with recommendationdeemed to be included in the quoted rate. 281 (ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors. 282 (iii) Rateofearth energizer compound of 25 Kg of 02 bags and earthresistance reducingliquid 10 litre per cane for each pit deemed to be included in the quoted rate. 283 (iv)Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor along with the sample approval 284 (v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete. 285 (vi) Copper strip of size 20 x 3 mm shallbe fixed on proper post insulator at the instrument end (copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately). 286 (vii)Testing of earth shall be carriedout in presence ofdepartmental and user representativeand report shall be submitted to Garrison Engineer duly signed by all concerned. 287 (viii)Earth resistance tester will be provided by the contractor.Tester should be calibrated from authorised company/ lab. 288 (ix)Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned.After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained. 289 (x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion. 290 (xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock. 291 (xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained. 292 (xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period. 293 (xiv) The electrode shallcarry manufacturers name . 294 (xv) The connection clamp shall be permanentlly welded to the copper boundedrodto avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination. 295 (xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm. 296 (xvii)Earth work such as auguring andmaking good the surrounding area shall carried out in any type of soil. 297 (xviii)The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material. 298 (xix) Sign boardof mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxideZinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge. 299 Material and labour for Earth pit cover madeof heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit complete including taking down old unserviceable pit cover of any decription all as specified and directed.Make : Model SEPC 250 of SAFE TRODE or equivalent in Snaga/ Cubes 6 Global 300 S&F in repair copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing old unserviceable copper strip etc, complete all as specified anddirected. Note : - All Joints should be joined by Exothermic Welding or Brazing. 301 Supply and fix for GI pipe light grade 50 mm dia for cable protection on road crossings /plinth protection with fixed to the pole wall etc along withsuitable fittings for cable protection etc complete all as specified and directed. 302 Material and labour in repair for3 ½ core 25 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items. 303 Material and labour in repair for 4 core 10 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items. 304 Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- 305 (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amps, 25 KA- 01 No (Incomer).(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160Amps, 25 KA- 01 Nos.(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63Amps, 10 KA- 01 Nos.(d) Multifunction Meter (V,I,PF) with suitable capacity of CTs- 01 No.(e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.(f) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(vi) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). 306 Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- 307 (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amps, 36 KA- 01 No (Incomer).(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200Amps, 25 KA- 01 No.(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160Amps, 25 KA- 03 Nos.(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amps, 10 KA- 02 No(c) Multifunction Meter (V,I,PF) with suitable capacity of CTs- 01 No.(d) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.(e) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(vi) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). 308 Material and labour for dewatering & Cleaning of RCC UG sumps of the followingcapacities by comprisingof the followings 09 (Nine) stage of cleaning process complete all as specified and directed(i)De-watering by high pressure submersible pump complete (Note for item No 309 to 316 :-The Bidder shall take into consideration for following points while quoting his rate for these items andthe unit rate is deemed to be included for :-(i) The contractor shall provide dewatering pump of suitable capacity and mobile generatorfor operation of dewatering by high pressure submersible pump (or) Diesel driven high pressure pump and the rate quoted is inclusive of rent/hiring charges complete. (ii) Cuttingand filling cleared of shrubs, vegetation, grass bush, weed, trees and sapling not exceeding 30 cm in girth, measured at a height of two metre above ground level. Useful material shall be stacked.(iii) Material removed from the tank shall be disposed off out side MD land.(iv) Tank shall be made available for cleaning for a period of 8 hours only and contractor has to arrange sufficient labour/ T&P to complete the job with the given period only. or otherwise penality shall be imposed @ Rs 500/- per day.(v) Removal of sludge from sump(vi)Cleaning of walls, floors, ceiling etc by high pressure jet pump 80-180 bar pressure all complete(vii)Removing dirt and sludge by vaccum pump(viii) Anti- Bacterial Treatment of inside of tank is effective againstall pathogens all complete.(ix) Sterilization of the tank atomosphere by UV radiation inside of the tank.(x) Applying one coat of white wash internal surfaces.(xi)Replace nylon net for vent pipes &man hole cover(xii)Writing letter in bold with white paint on black colour back ground such as sump number, capacity, cleaned on Date & Due on Date etc 309 Underground sump of capacity 200000 gallon at Range pump house. 310 Semi underground sump of capacity 200000 gallon at Ayyappa Temple/ pump house. 311 Semi underground sump of capacity 120000 gallon at Service tank Pump house 312 Underground sump of capacity 50000 gallon at Gurukul 313 Semi underground sump capacity of 50000 at AFTC Pump House 314 Underground sump of capacity50000 gallon at AFTC Pump House, range pump house 315 Underground sump of capacity 20000 gallon at 91 CIV Pump house 316 Underground sump of capacity 10000 gallon at CE Complex/ pump house 317 M & L for Fixing in repairs Water Level Indicator consisting of float ball, nylon rope, Scale for water level indication made out of MS frame with pulley and indicating pointer for UG sumpat different places all as specified and directed . 318 Cleaning of UGopen static Water Tank (SWT) of the followingcapacities by comprisingof the followings 07 (Seven) stage of cleaning process for the undermentioned capcities complete all as specified and directed:-(i)De-watering by high pressure submersible pump all complete (ii) Removal of sludge/mud/silt/sand from sump and disposal out side MD land(iii)Cleaning of walls, floors, ceiling etc by high pressure jet pump 80-180 bar pressure all complete(iv)Removing dirt and sludge by vacuum pump(v) Applying one coat of white wash internal surfaces.(vi)Replace nylon net for vent pipes &man hole cover(vii)Writing letter in bold with white paint on black colour back ground such as sump number, capacity, cleaned on Date & Due on Date etc Note : The contractor shall arrange mobile generatorfor operation of dewatering by high pressure submersible pump (or) Diesel driven high pressure pump and the unit quoted rate is inclusive of rent/hiring charges complete. 319 20000 Gallons capacity at ETI. 320 15000 Gallons capacity at E & ITI. 321 10000 Gallons capacity near SSC. 322 S&F as in repair single core multistrand flexible copper cable of size 25 Sqmm x 1 core , includingof lugs , connecting up with nuts and bolts, insulation tape wrappingetc , the selection of cable as per colour code all as specified and directed Make : Havells /Polycab/RPGAsian 323 Material and labour for removing the submersible pump set of capacity for 7.5 to 15 HP including pipes and submersible cables complete from the exisiting bore well of depth up to 200 mtr by any suitable method i.e either manual.vehicle mounted motorized system and disconnecting the pump motor to locate the faults in presence of Engr-in-Charge, transporting to Wksp and carry out repairs, reassembling, lowering to bore well after repairs, testing and commissioning complete all as specified and directed 324 M&L for taking out, dismantling pump and motor of submersible pump set of capacity for 7.5 to 15 HP to carry out repairs and replacements , duly rewinding and replacing worn out parts, applying one coat of spray painting with synthetic enamel paint of existing colour and testing and inserting in borewell after repair complete all as specified and directed.Note :- (a)The spares shall be measured and paid seperately in the relevent items given below as supply only.(b) Cost of labour for replacement of spares and transportation are deemed to be included in the quoted rate. (c)The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. Thecontactor is responsible for making alternate arrangement of pump set in case of time required more than one week.(d)In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contactor.(e)Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.(f)The decision of the Accepting Officer in this regard shall be final and binding. 325 Supply only GM Bush suitable for 7.5 HP to 15 HP submersible pumpset as per manufacturers design complete all as specified and as directed. 326 Supply only SS coupling bearing suitable for 7.5 HP to 15 HP submersible pumpset as per manufacturers design complete all as specified and as directed. 327 Supply only sleeve MS key for impeller suitable for 7.5 HP to 15 HP submersible pumpset as per manufacturers design complete all as specified and as directed. 328 Supply onlySand Guard suitable for 7.5 HP to 15 HP submersible pumpset as per manufacturers design complete all as specified and as directed. 329 Supply only oil seal thrust bearing suitable for 7.5 HP to 15 HP submersible pumpset as per manufacturers design complete all as specified and as directed. 330 M&L flat three core PVC Insulated & PVC Sheathed Industrial Cable for Submersible Pump Motors 1100 Volt, conforming to IS 694, 6 Sqmm nominal area complete including taking out old unserviceable cable complete all as specified and directed. Make :- Havells/Polycab/Finolex/KEI 331 S & F in repair Over load Relay range of (1.6 -2.5 Amps ) , max-10A (as per sample) for 1.5 HP starter (Dol/Star delta) complete all as directed. 332 S & F as in replacementONload change over switch 4 pole 250Amps in sheet metal enclosure complete all as specified and as directed. make :-Havells /L&T/Indo Asian 333 M & L for servicing of submersible starter by checking and servicing the contactor coil , over load relay coiland any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drillingtesting the panel complete all as specified and directedfor the7.5 HP to 15 HP capacity pump setsNotes :-(i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate. 334 Supply and fix as in repair TPNMCB ,415 volts,fixed type ,63 Amp, 50 Hz, with rupturing capacity 10 KA in theexisting pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indoasian/L&T/ Legrand 335 S&F as in repair single core multistrand flexible copper cable of size 16 Sqmm x 1 core , including of lugs , connecting up with nuts and bolts, insulation tape wrappingetc , the selection of cable as per colour code all as specified and directed Make : Havells /Polycab/RPGAsian 336 S & F in repair Over load Relay range of (0.1 -1.5 Amps ) , max- 5A (as per sample) for 0.5 HP starter (Dol/Star delta) complete all as directed . 337 Note :- An amount of Rs 1,91,800.00 on account of credit schedule for schedule A part II shall be deducted from the total amount of BOQ to arrive at the contract sum.