| 1 | Provisioning of 415 Volt LT Feeder Pillar Panel Box at Type-V Residential Quarter Area and Replacement of Street Light Marshaling Boxes along the road from Gate-I to Phapshi Gate. |
| 2 | Labour for excavating trenches in hard/ dense soil not exceeding 1.5 m wide & not exceeding 1.5 m depth for laying of electrical power cable and getting earth out. |
| 3 | Labour for returningthe excavated earth in trench including spreading, levelling & well ramming in layers not exceeding 25 cm. |
| 4 | M & L for sand filling in trenches including spreading, levelling & well ramming. |
| 5 | M & L for continuos brick edging, with width equal to the depth of the brick, laid dry with burnt clay bricks of sub class B with old size bricks. |
| 6 | Labour for demolition of cement concrete or black bituminous hard standing of any description and in any position not otherwise specifically provided. |
| 7 | Material & Labour for cement concrete of type C2 (1:3:6) with 40 mm graded aggregate in making cable trenches for power cable. |
| 8 | M & L for 100 MM Bore Dia Galvanised Tubes of Light Grade with all fittings Laid in Trenches. |
| 9 | M & L for 40 MM Bore Dia High Density Polyethelene Pipes (HDPE) of Pressure Rating 6 KgF/Cm2 Laid in Trenches. |
| 10 | Laying of one number PVC insulated & PVC Sheathed Power Cable of 1.1 KV Grade of 185 Sq. MM to 400 Sq. MM Size direct in ground including excavation, sand cushioning, protective covering and refilling the trench as required. |
| 11 | Laying of one number of PVC insulated and PVC sheathed power cable of 1.1 KV grade of size upto 35 Sq. MM in the existing HDPE/GI pipe. |
| 12 | Supplying & making end termination with brass compression gland and aluminium lugs for 3.5 Core 25 Sq. MM (28 MM) PVC Insulated and Sheathed aluminium conductor cable of 1.1 KV grade as required. |
| 13 | Supplying & making end termination with brass compression gland and aluminium lugs for 3.5 Core 50 Sq. MM (35 MM) PVC Insulated and Sheathed aluminium conductor cable of 1.1 KV grade as required. |
| 14 | Supplying & making end termination with brass compression gland and aluminium lugs for 3.5 Core 240 Sq. MM (62 MM) PVC Insulated and Sheathed aluminium conductor cable of 1.1 KV grade as required. |
| 15 | Earthing with GI earth pipe 4.5 metre long, 40 mm dia including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 16 | Supplying & fixing cable route marker with 10 cm x 10 cm x 5 mm thick GI plate with inscription there on, bolted/welded to 35 mm x 35 mm x 6 mm angle iron, 60 cm long and fixing the same in the ground as required. |
| 17 | SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 415 V , 50 HZ, AC, IP-54 OR BETTER, DOUBLE DOOR TYPE OUTDOOR FEEDER PANEL BOX DULY POWDER COATED & FABRICATED FROM 2 MM THICK METAL SHEET, HAVING DETACHEABLE GLAND PLATE & CABLE TIE SUPPORT AND ELECTRICAL SWITCH GEARS AS BELOW:-a) APPROX. DIMENSION: HEIGHT-1520 MM, WIDTH-1700MM, DEPTH-700MM.b) 2 NOS. OF 400 A, 4 POLE MCCB WITH ON, OFF, TRIP INDICATION ALONG WITH 1 NO. DIGITAL VOLTMETER & AMMETER TO BE PROVIDED IN EACH OUT GOING FEEDER.c) 2 NOS. OF 200 A, 4 POLE MCCB WITH ON, OFF, TRIP INDICATION WITH 1 NO. OF DIGITAL AMMETER IN EACH OUT GOING MCCB FEEDER.d) 4 NOS. OF 100 A, 4 POLE MCCB WITH ON, OFF, TRIP INDICATION WITH 1 NO. OF DIGITAL AMMETER IN EACH OUT GOING MCCB FEEDER.e) 1 NO. OF MULTI-FUNCTIONAL METER TO BE PROVIDED IN OUT GOING MCCB FEEDER.f) ALUMINIUM BUS BAR OF CURRENT CARRYING CAPACITY 1000A IS TO BE PROVIDED FOR 3 PHASE AND NEUTRAL LINE.g) TOP OF FEEDER PANEL SHALL BE DESIGNED SO THAT WATER WILL NOT ENTER INSIDE THE MARSHALLING BOX.h) 2 NOS. OF EARTH STUD TO BE PROVIDED. i) THE PANEL SHALL BE SO DESIGNED THAT IT WILL HAVE SPACE FOR INCOMING CABLE TERMINATION.j) TYPE TEST CERTIFICATE FROM ANY GOVT. OR NABL ACCREDITED LABORATORY TO BE PROVIDED.k) Make: For MCCB- ABB/GE/L&T/SIEMENS/SCHNEIDER ELECTRIC/CROMPTON GREAVES/KIRLOSKAR ELECTRIC, For Voltmeter, Ammeter & Multifunctional Meter- AE/MECO/L&T/SCHNEIDER ELECTRIC/HPL/RISHABH, For LED Indication Lamp- ALTOS/BINAY/JAI BALAJI/TEKNIC/SCHNEIDER/VAISHNO/ESSEN, For Panel Wiring- FINOLEX/POLYCAB/V-GUARD/HAVELLS/RR CABLES/KEI.l) Make of LT Panel: OEM or Reputed Factory Made. |
| 18 | SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 415 V , 50 HZ, AC, IP-54 OR BETTER, SINGLE DOOR TYPE OUTDOOR MARSHALLING BOX DULY POWDER COATED & FABRICATED FROM 2 MM THICK METAL SHEET, HAVING DETACHEABLE GLAND PLATE FOR IN & OUT OF CABLE AND ELECTRICAL SWITCH GEARS AS BELOW:a) APPROX. DIMENSION: HEIGHT-300 MM, WIDTH-250MM, DEPTH-200MM.b) SUITABLE SIZES METAL CLAMP WITH NUT & BOLTS ARE TO BE PROVIDED WITH THE MARSHALLING BOX FOR FIXING IN SWAGED TUBULAR POLE OF VARIOUS SIZE.c)1 NO. OF 6A, MCB TO BE PROVIDED IN EACH MARSHALLING BOX.d) 8 NOS. OF PORCELAIN CONNECTORS FOR 16 SQ. MM CABLE SIZE & 32 A RATING, FIXED IN DIN RAIL.e) 2 NOS. OF EARTH STUD TO BE PROVIDED.f) ADJUSTABLE HOLE IN CLAMP AS WELL AS MARSHALLING BOXE TO BE PROVIDED FOR 8 MM DIA NUT & BOLTS.g) EARTH BAR TO BE PROVIDED IN THE MARSHALLING BOX. h) SUITABLE GI CLAMP WITH 3 MM THICK & 25 MM WIDTH TO BE PROVIDED FOR FIXING OF MARSHALLING BOX.i) TOP OF MARHALLING BOX SHALL BE DESIGNED SO THAT WATER WILL NOT ENTER INSIDE THE MARSHALLING BOX. j) IT ALSO INCLUDES REMOVAL OF OLD EXISTING METALLIC MARSHALLING BOX BY DISCONNECTING INCOMING AND OUTGOING CABLE AS WELL AS LIGHT CIRCUIT WIRINGS.k) IT INCLUDES CONNECTION/TERMINATION OF INCOMING, OUTGOING CABLES AS WELL AS LIGHT CIRCUITS BY USING PROPER METALLIC GLAND AND AL./CU. LUGS.l) TESTCERTIFICATE IN RESPECT OF MARSHALING BOX ORLT PANEL CATEGORY FROM ANY GOVT. OR NABL ACCREDITED LABORATORY TO BE PROVIDED.m) TENTATIVE DRAWING IS ENCLOSED HEREWITH FOR REFERENCE.n) Make : For MCB- Polycab/Havells/V-Guard/Legrand/Schneider, For Porcelain Connector- ELMEX/WAGO/CONNECT WELL ETC. o) Make of Marshalling Box- OEM or Reputed Factory Fabricated. |