| 1 | Construction and commissioning of RCC flat slab Over Head Service Reservoir of following capacity and staging including all material and labour charges as per the Scope of work and Technical Specification, consisting of the following main activities: -a) Topographic survey, preparation of site contour plan, conducting SBC testand its approval from departmentbefore construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc.c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.d) Providing and applying two coats of food grade epoxy paint on the inside surface roof slab, and 600 mm height of the vertical wall.e) Successfully hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the top surface of the roof slab.g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc. |
| 2 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top Slab to bottom Slab inside container.i) Providing and fixing of MS section ladder from the last landing to balcony and MS ladder with safety cage from balcony to top slab.j) Providing and fixing water level indicator (float type).k) Providing and fixing of hand railing all around the balcony, roof and staircase, consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle iron vertical post at a maximum spacing of 1500mm centres.l) All MS parts to be painted with two coats of the enamel paint over the primer coat of red oxide.m) Providing and fixing of 150mm wide PVC water bar for the construction joints in the container (vertical wall & cone wall).n) Providing one Aluminium portable ladder of appropriate length to access first landing (3.5 to 4.5m above GL) from ground.o) Lighting arrestor consisting of providing and fixing of 2 Nos.of chemical earthing and connecting it to the conical cover of SS ventilator with two separate GI strips of 50mmX3mmp) CI/DI puddle collar shall be fixed in the bottom/slab for connecting inlet, outlet, overflow and washout pipe of the reservoir. |
| 3 | q) Painting the name of the scheme and other details on the reservoir, and any other work related to structure as per the directions of Engineer-in- Charge, Technical Specification and Scope of Work.r) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. |
| 4 | Rates for RCC OHSR, SBC 10 T/sqm, SEISMIC ZONE-III & STAGING 15 M |
| 5 | 50 KL capacity |
| 6 | Providing and fixing double flanged ISI markedGI pipes medium duty (class B) Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736 with GI fittings excluding valves as vertical pipes for RCC Reservoirs including specials required such as bend, tee etc. providing and fixing with MS clampsat every 3 mtr,jointing materials such as nuts, bolt, rubber packing, hydraulic testingetc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 7 | 65 mm (Washout) |
| 8 | 80 mm (Inlet & Overflow) |
| 9 | Providing and fixing double flanged ISI marked DIClass K-9 pipes as per IS:8329-2000 (amended up to date), asvertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr,jointing materials such as nuts, bolt, rubber packing, hydraulic testingetc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 10 | 100 mm |
| 11 | Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves), Vacuum tight (bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896 part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy (Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 12 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 13 | 80 mm dia |
| 14 | 100mm Dia |
| 15 | Providing, lowering, aligning, fixing in position in pipe line, DI double flanged resilient seated Dual plate check valve of approved make of following Pressure rating & dia complete, as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder (EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410, Hinge SS AISI 316/304, Spring SS AISI 316/304, Bonnet Gasket EPDM, Bush- Brass with EPDM/NBR \"O\" ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel), Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 16 | Class PN 1.6 |
| 17 | 80 mm dia |
| 18 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer.Class PN 1.0 |
| 19 | 80 mm dia |
| 20 | 100mm Dia |
| 21 | Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at synchronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected onC.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as perspecification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 22 | 5.5 KW (7.5 HP) - 1W+1S |
| 23 | SITC DOLStarter type LT Panel of followingrating, all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thickduly Electrostatic Powder Coated with angle frame including other ancillaries (Insulators, Acrylic Sheet , Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral , Saddle & Packing Material) etc. complete as per Technical Specifications and as per direction of Engineer-In-Charge. |
| 24 | DOL STARTER 5.5 KW (7.5HP)- : For 2 motors (1 W+ 1S)I/C -MCB 40A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm (0-500V) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm (0-60A) (1), Amp. Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights (Red-1, Yellow -1) (2), Indicating Lights (Blue - 1) (1), Control MCB 6A SP 10 KA C Curve (3) and O/G-MCB 25A ,TP, 10 KA, C Curve (2), Power Cont 12A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A)(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 (Red - 1, Green - 1)(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 2 Kvar (2) |
| 25 | Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves), Vacuum tight (bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896 part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy (Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 26 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 27 | 100mm Dia |
| 28 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer.Class PN 1.0 |
| 29 | 100mm Dia |
| 30 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU), Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer-In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 31 | EFM100 mm |
| 32 | Providing, lowering, aligning, fixing in position in pipe line, DI double flanged resilient seated Dual plate check valve of approved make of following Pressure rating & dia complete, as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder (EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410, Hinge SS AISI 316/304, Spring SS AISI 316/304, Bonnet Gasket EPDM, Bush- Brass with EPDM/NBR \"O\" ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel), Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 33 | Class PN 1.6 |
| 34 | 100 mm dia |
| 35 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover. |
| 36 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 37 | 16.0 Sq.mm, 4 core |