Tender For Electrification Of Floor-3 &3M Of Block-102A And Associated Works At Inrpc, Barc, Tarapur.
Tender Value
95 Lakhs
Estimated cost
Bid Submission
07 Jul 2025
0 days left
EMD
1.90 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
tarapur → Maharashtra
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Electrification of Floor-3 &3M of Block-102A and associated works at INRPC, BARC, Tarapur.
BOQ
| Sl. No. | Item Description |
| 1 | Supply of following configuration415V, 3-phase, 4 wire, double door,with R Y B Phase indication and mcb position indication through glass front, IP-54,Prewired with HFFR copper wires, horizontal type, metallic Double Door, Phase Segregated three pole and neutral MCB Distribution Board fabricated out of 2 mm thick ,powder coated with RAL7035 shade , pre-galvanised G.I. sheet steel, suitable for surface mounting/ installation in existing enclosure complete with appropriate rating of tinned copper bus bar/ Cu wire, neutral bus bar, earth bar, din bar,brass neutral link, brass earthing studs, phase distribution drawing, danger board, name plate, 2 mm thick removable gland plate on both top and bottom side with required number of knock out holes , neoprene gasket, etc as as per drawing, specifications & generally as per relevant IS & as per instructions of Engineer-in-charge. |
| 2 | MCB DB with Incomer of 25A, Isc=10kA, Type C, TPN MCB with 2-Pole, 25A, Isc=10kA, (100mA) RCBO for each phase and 36 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 3 | Supply |
| 4 | Installation |
| 5 | MCB DB with Incomer of 25A, Isc=10kA, Type C, TPN MCB with 2-Pole, 25A, Isc=10kA, (100mA) RCBO for each phase and 18 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 6 | Supply |
| 7 | Installation |
| 8 | MCB DB with Incomer of 16A, Isc=10kA, Type C, TPN MCB with 2-Pole, 16A, Isc=10kA, (100mA) RCBO for each phase and 18 nos. of 6A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 9 | Supply |
| 10 | Installation |
| 11 | Supply of following configuration240V, 1-phase, 2 wire, double door,with Phase indication and mcb position indication through glass front, IP-54,Prewired with HFFR copper wires, horizontal type, metallic Double Door, MCB Distribution Board fabricated out of 2 mm thick ,powder coated with RAL7035 shade , pre-galvanised G.I. sheet steel, suitable for surface mounting/ installation in existing enclosure complete with appropriate rating of tinned copper bus bar/ Cu wire, neutral bus bar, earth bar, din bar,brass neutral link, brass earthing studs, phase distribution drawing, danger board, name plate, 2 mm thick removable gland plate on both top and bottom side with required number of knock out holes , neoprene gasket, check nuts etc as required as as per drawing, specifications & generally as per relevant IS & as per instructions of Engineer-in-charge. |
| 12 | MCB DB with Incomer of 50A, Isc=10kA, Type C, DP MCB and 8 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 13 | Supply |
| 14 | Installation |
| 15 | MCB DB with Incomer of 40A, Isc=10kA, Type C, DP MCB and 8 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 16 | Supply |
| 17 | Installation |
| 18 | MCB DB with Incomer of 25A, Isc=10kA, Type C, DP MCB and 4 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 19 | Supply |
| 20 | Installation |
| 21 | MCB DB with Incomer of 16A, Isc=10kA, Type C, DP MCB and 12 nos. of 6A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 22 | Supply |
| 23 | Installation |
| 24 | Supply of the following Surface mounted Industrial MCB switches with pre-galvanized powder coated GI Box, all accessories and mounting arrangement as per Technical specifications. |
| 25 | 2 nos. of 6A, Single Pole, Isc=10kA, Type C-Curve, MCB along with pre- Galvanised powder coated GI sheet steel box, suitable din-rail, face plate, suitable copper lugs, SS screw/nut bolts for surface mounting. |
| 26 | 4 nos. of 6A, Single Pole, Isc=10kA, Type C-Curve, MCBalong with pre- Galvanised powder coated GI sheet steel Face Plate and Box with suitable DIN rail, copper lugs, SS screw/nut bolts and mounting arrangements as per technical specification. |
| 27 | Installation and commissioning of the following Surface mounted Industrial MCB switches with pre-galvanized powder coated GI Box, all accessories and mounting arrangement as per Technical specifications. |
| 28 | 2 nos. of 6A, Single Pole, Isc=10kA, Type C-Curve, MCB along with pre- Galvanised powder coated GI sheet steel box, suitable din-rail, face plate, suitable copper lugs, SS screw/nut bolts for surface mounting. |
| 29 | 4 nos. of 6A, Single Pole, Isc=10kA, Type C-Curve, MCBalong with pre- Galvanised powder coated GI sheet steel Face Plate and Box with suitable DIN rail, copper lugs, SS screw/nut bolts and mounting arrangements as per technical specification. |
| 30 | Supply of the following Industrial MCB and metal clad plug sockets with suitable industrial plug tops (3-pin) alongwith pre-Galvanized powder coated GI sheet steel box suitable for surface mounting, suitable DIN-rail, face plate, suitable copper lugs, with chained metal cover for the socket outlet, complete with connections, SS screw/nut bolts for surface mounting including all accessories and mounting arrangement for completing installation. |
| 31 | 1 nos. of 6/ 10A, Single phase Industrial Socket with Isc=10kA, Type C-Curve, Industrial type MCB for each Socket in pre- Galvanised powder coated 2mm thick GI sheet steel Box, suitable for surface mounting, Industrial plug tops with chained metal cover for the socket outlet, suitable din-rail, face plate, suitable copper lugs, plug-tops, SS screw/nut bolts for surface mounting. |
| 32 | 1 nos. of 6/10A and 1 nos. of 16A/20A, Single phase Industrial Socket with Isc=10kA, Type C-Curve, Industrial type MCB for each Socket in pre- Galvanised powder coated 2mm thick GI sheet steel Box, suitable for surface mounting, Industrial plug tops with chained metal cover for the socket outlet, suitable din-rail, face plate, suitable copper lugs, plug-tops, SS screw/nut bolts for surface mounting. |
| 33 | Installation, Testing and Commissioning ofthe following Industrial MCB and metal clad plug sockets with suitable industrial plug tops (3-pin) alongwith pre-Galvanized powder coated GI sheet steel box suitable for surface mounting, suitable DIN-rail, face plate, suitable copper lugs, with chained metal cover for the socket outlet, complete with connections, SS screw/nut bolts for surface mounting including all accessories and mounting arrangement for completing installation. |
| 34 | 1 nos. of 6/ 10A, Single phase Industrial Socket with Isc=10kA, Type C-Curve, Industrial type MCB for each Socket in pre- Galvanised powder coated 2mm thick GI sheet steel Box, suitable for surface mounting, Industrial plug tops with chained metal cover for the socket outlet, suitable din-rail, face plate, suitable copper lugs, plug-tops, SS screw/nut bolts for surface mounting. |
| 35 | 1 nos. of 6/10A and 1 nos. of 16A/20A, Single phase Industrial Socket with Isc=10kA, Type C-Curve, Industrial type MCB for each Socket in pre- Galvanised powder coated 2mm thick GI sheet steel Box, suitable for surface mounting, Industrial plug tops with chained metal cover for the socket outlet, suitable din-rail, face plate, suitable copper lugs, plug-tops, SS screw/nut bolts for surface mounting. |
| 36 | Installation of 14 SWG heavy duty rigid GI conduit pipe of 25mm sizes along with all accessories such as inspection bends, junction box, socket, check nut, etc. making threads, removing burrs, connection of accessories, drawing of GI fish wire as required under the instruction of Engineer-in-in charge. (GI conduit,will be supplied as FIM. Accessories such as JBs, Inspection bends as required, Spacer-saddle at 1 metre distance, SS screw etc. should be supplied by contractor.) |
| 37 | Laying of 14 SWG bare tinned solid copper conductor throughout along the conduit including fixing with copper clip, brazing of conductor etc as required. ( 14 SWG conductor will be supplied as FIM. Accessories such as copper clip at every 600mm for mounting on 25mm conduit should be supplied by contractor.) |
| 38 | Supply and Installation of 25mm flexible GI conduit pipe including cleating with heavy duty GI saddles or suit to site clamps on RCC wall, column, steel structure, SS screws etc. as required under the instruction of Engineer-in-charge and as per tender specification. |
| 39 | Supply |
| 40 | Installation |
| 41 | Supply of following LED light fittings complete with light fitting accessories, including supply of fixing SS accessories, flexible GI metallic conduit sleeves, PVC conduit bushes, Cu cable lugs, suitable PVC terminal box as per tender specification. |
| 42 | Industrial box type (approx dim.130mm x 95mm x 1219mm), surface mounted 4ft fixture along with one nos. of 18W, 2340 lm,minimum 130 lm/w system efficacy, CCT 6500K and CRI>80, THD<10%, PF>0.95, 4ftLED tube. The luminaire shall meet IP20 rating. The fixture shall have single piece construction made of white powder coated CRCA sheet steel suitable for above LED tube light. The LED shall be mounted on extruded aluminium box which acts as heat sink with extruded poly carbonate material which gives diffused light. The total power consumption should not exceed 19W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 43 | Industrial box type (approx dim.130mm x 95mm x 1219mm), surface mounted 4ft fixture along with two nos. of 18W, 2340 lm,minimum 130 lm/w system efficacy, CCT 6500K and CRI>80, THD<10%, PF>0.95, 4ftLED tube. The luminaire shall meet IP20 rating. The fixture shall have single piece construction made of white powder coated CRCA sheet steel suitable for above LED tube light. The LED shall be mounted on extruded aluminium box which acts as heat sink with extruded poly carbonate material which gives diffused light. The total power consumption should not exceed 38W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 44 | 4ft Functional Batten (approx dim.140mm x 105mm x 1219mm)with 2x18W LED Tube (acid & corrossion proof) with a nominal system lumen output of 4320 lumens and a minimum system efficacy not less than 120lm/W.The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. The luminaire housing should made of • Body - glass reinforced polyester (GRP), RAL 7035 • Gasket - polyurethane • Diffuser - UV stabilised prismatic acrylic material. The total power consumption should not exceed 38W(including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 45 | LED Bulkhead with a nominal system lumen output of 700 lumens and a minimum system efficacy of 105 lm/W. The luminaire should have a CCT of 6500K and CRI > 70. The luminaire shall meet IP65 rating and IK 08 rating with THD < 20% and PF > 0.9. The luminaire housing should made of High pressure die cast Aluminium with high quality PMMA diffuser. The total power consumption should not exceed 6.5W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 46 | LED Bulkhead (Acid and Corrosion proof) with a nominal system lumen output of 700 lumens and a minimum system efficacy of 105 lm/W. The luminaire should have a CCT of 6500K and CRI > 70. The luminaire shall meet IP65 rating and IK 08 rating with THD < 20% and PF > 0.9. The luminaire housing should made of High pressure die cast Aluminium with high quality PMMA diffuser. The total power consumption should not exceed 6.5W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 47 | 4ft Functional Batten (approx dim.140mm x 105mm x 1219mm) with 2 x 36W LED Tube (Flameproof proof) with a nominal system lumen output of 8640 lumens and a minimum system efficacy not less than 120lm/W.The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specification. The mounting shall be ceiling suspended with Hot dipped GI rod, SS Screws, Anchor fastners etc. and includes all accessories for complete installation. |
| 48 | SITC ofLED light fittings complete withlight fitting accessories, includingsupply of fixing SS accessories, flexible GI metallic conduit sleeves, PVC conduit bushes, Cu cable lugs, suitable PVC terminal box, LED Highbay with a nominal system lumen output of 18000 lumens and a minimum system efficacy of not less than 140 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70B50. The luminaire should have a CCT of 5700K and CRI > 70 and SDCM<5. The luminaire shall meet IP66 and IK 08 rating with THD < 10% and PF > 0.95 and in-built surge protection of 4kV. The luminaire housing should made of High Pressure die cast Aluminium with wide beam optics and having gasket of heat proof silicone rubber ring. The total power consumption should not exceed 130W(including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 49 | 85W, 240V, 50Hz, LED Bulb with threaded fitting (40mm thread) along with Non- integral driver and control, Suitable GI powder coated box for driver mounting with complete accessories for cell lighting as per technical specification. |
| 50 | Installation and Commissioning of following LED light fittingswith minimum 130 lm/W efficacy, CCT 6500K, CRI>70, THD <10%, PF >0.95 complete withlight fitting accessories, aluminum/SS heat sink, SS housing for corrosion proof,LED driver, twin twisted tinned 1.5 sq. mm copper flexible cords for terminal connections, PVC connector, 16 SWG copper wire forearthing , flexible GI metallic conduit sleeves, PVC conduit bushes, Ceiling Rose for light fixture, SS Screw, GI conduit/mounting arragement for ceiling suspended type, copper lugs etc. as per technical specification: |
| 51 | Industrial box type (approx dim.130mm x 95mm x 1219mm), surface mounted 4ft fixture along with one nos. of 18W, 2340 lm,minimum 130 lm/w system efficacy, CCT 6500K and CRI>80, THD<10%, PF>0.95, 4ftLED tube. The luminaire shall meet IP20 rating. The fixture shall have single piece construction made of white powder coated CRCA sheet steel suitable for above LED tube light. The LED shall be mounted on extruded aluminium box which acts as heat sink with extruded poly carbonate material which gives diffused light. The total power consumption should not exceed 19W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 52 | Industrial box type (approx dim.130mm x 95mm x 1219mm), surface mounted 4ft fixture along with two nos. of 18W, 2340 lm,minimum 130 lm/w system efficacy, CCT 6500K and CRI>80, THD<10%, PF>0.95, 4ftLED tube. The luminaire shall meet IP20 rating. The fixture shall have single piece construction made of white powder coated CRCA sheet steel suitable for above LED tube light. The LED shall be mounted on extruded aluminium box which acts as heat sink with extruded poly carbonate material which gives diffused light. The total power consumption should not exceed 38W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 53 | 4ft Functional Batten (approx dim.140mm x 105mm x 1219mm)with 2x18W LED Tube (acid & corrossion proof) with a nominal system lumen output of 4320 lumens and a minimum system efficacy not less than 120lm/W.The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. The luminaire housing should made of • Body - glass reinforced polyester (GRP), RAL 7035 • Gasket - polyurethane • Diffuser - UV stabilised prismatic acrylic material. The total power consumption should not exceed 38W(including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 54 | LED Bulkhead with a nominal system lumen output of 700 lumens and a minimum system efficacy of 105 lm/W. The luminaire should have a CCT of 6500K and CRI > 70. The luminaire shall meet IP65 rating and IK 08 rating with THD < 20% and PF > 0.9. The luminaire housing should made of High pressure die cast Aluminium with high quality PMMA diffuser. The total power consumption should not exceed 6.5W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 55 | LED Bulkhead (Acid and Corrosion proof) with a nominal system lumen output of 700 lumens and a minimum system efficacy of 105 lm/W. The luminaire should have a CCT of 6500K and CRI > 70. The luminaire shall meet IP65 rating and IK 08 rating with THD < 20% and PF > 0.9. The luminaire housing should made of High pressure die cast Aluminium with high quality PMMA diffuser. The total power consumption should not exceed 6.5W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 56 | 4ft Functional Batten (approx dim.140mm x 105mm x 1219mm) with 2x36W LED Tube (Flameproof proof) with a nominal system lumen output of 8640 lumens and a minimum system efficacy not less than 120lm/W.The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specification. The mounting shall be ceiling suspended with Hot dipped GI rod, SS Screws, Anchor fastners etc. and includes all accessories for complete installation. |
| 57 | SITC ofLED light fittings complete withlight fitting accessories, includingsupply of fixing SS accessories, flexible GI metallic conduit sleeves, PVC conduit bushes, Cu cable lugs, suitable PVC terminal box, LED Highbay with a nominal system lumen output of 18000 lumens and a minimum system efficacy of not less than 140 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70B50. The luminaire should have a CCT of 5700K and CRI > 70 and SDCM<5. The luminaire shall meet IP66 and IK 08 rating with THD < 10% and PF > 0.95 and in-built surge protection of 4kV. The luminaire housing should made of High Pressure die cast Aluminium with wide beam optics and having gasket of heat proof silicone rubber ring. The total power consumption should not exceed 130W(including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 58 | 85W, 240V, 50Hz, LED Bulb with threaded fitting (40mm thread) along with Non- integral driver and control, Suitable GI powder coated box for driver mounting with complete accessories for cell lighting as per technical specification. |
| 59 | Supply, Installation, Testing and Commissioning of Ceiling mounted dual type occupency sensor with inbuilt or external power pack and auxiliary relay having min 15 mtr sensing range in 180 deg orientation and time delay ranges from 30sec to 30min and should have output relay capacity of 1000W (for LED lighting fixtures). |
| 60 | Supply |
| 61 | Installation |
| 62 | Supply, Installation, Testing and Commissioning of Occupancy sensor bypass switch box having 3 pole rotary switch fixed on GI enclosure with cover. |
| 63 | Supply |
| 64 | Installation |
| 65 | Supply of Single Core flexible HFFR wires (Copper) of size mentioned below in voltage grade 1100V as per the IS:3961- part V, IS 17048: 2018 (latest edition) and as per conductor class 2 of IS: 8130/1984 as per technical specification |
| 66 | 1.5 Sq.mm |
| 67 | 2.5 Sq.mm |
| 68 | Installation/drawing through concealed/ surface conduit and wiring and termination at both ends of Single Core HFFR wires (Copper) of size mentioned below in voltage grade 1100V as per the IS 17048: 2018, IS 732 as per conductor class 2 of IS:8130/1984 as per technical specification. |
| 69 | 1.5 Sq.mm |
| 70 | 2.5 Sq.mm |
| 71 | Supply and Installation of 2.5sqmm Radiation Resitance Cable (Polyimide & PEEK insulation) as per IEC 60544-4 and relevant IS withuseful raditaion dose of 1 x 107 Gy and Breakdown Strength of 480 V/mil as per technical specification and direction of EIC. |
| 72 | Supply |
| 73 | Installation |
| 74 | Supply and fixing vertical air termination made up of 20mm dia, 1 mtr long copper rod attached to 145 mm dia. Copper sphere having drilled and tapped holes for fixing 5 nos. of 390mm long spikes and square copper base plate of 150 mm length and 10 mm thickness as per technical specification and approved drawing. |
| 75 | Supply |
| 76 | Installation and Testing |
| 77 | Supply and Installation of 25 mm X 3 mm thick copper strip including connection/ terminating with brass nut, brass bolt, spring, washer etc. as required. |
| 78 | Supply |
| 79 | Installation, Testing and connection |
| 80 | Supply and Installation of Busbar Insulator of size M8 x 40mm, MOC: Epoxy as per tender specification. |
| 81 | Supply |
| 82 | Installation |
| 83 | Supply, Fabrication and Installation of MS structural steel sections as per IS 2062 Br Grade for light frame, base frame, brackets for supporting equipments and cable tray supports etc. including all accesories such as 8/12mm anchor fastner, SS screw, bolts etc. Fabrication shall include drilling , entiling, welding by qualified welder, LPT of welds, wire brush cleaning, removing burs, supply of all consumables like gas, welding rods. After fabrication two coats ofepoxy based primer and two coats of finish paints shall be applied. |
| 84 | Supply of required material and making of straight exothermic braze joints of copper conductors (95 sqmm) as per technical specification. |
| 85 | Supply of required material and making of \"T\" type exothermic braze joints of copper conductors (95 sqmm) as per technical specification. |
| 86 | Supply and laying of 10 sq. mm tinned copper conductor, connection with earth pad at one end and DBs at other end clamping, brazing etc. and as tender technical specifications. |
| 87 | Supply |
| 88 | Laying of conductor after chasing floor or wall and finishing the same. |
| 89 | Supply and Installation of 2mm thick pre-galvanished GI sheet including marking,cutting (as per site requirement)and erection on top of JB openings on wall and ceiling at approximate height of 5mtrs. |
| 90 | Supply |
| 91 | Installation |
| 92 | Junction box/Cable pull box of size 100mm x 100mm x 50mm fabricated out of 2mm thick GI sheet, cable gland plate at the bottom, punched hole for conduit entry on all sides, suitable to terminate 2nos. of 3 core x 2.5 Sq.mm Cu conductor, 8 nos. of terminals, etc. as required. |
| 93 | Supply |
| 94 | Installation |
AI Tender Summary
Tender Timeline
Jun 21, 2025
11:30 IST
Tender Published
Tender notice published.
CompletedJul 07, 2025
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedJul 08, 2025
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender