| 1 | CIVIL WORK (PART A) |
| 2 | Demolishing brick work manually/ by mechanical meansincluding stacking of serviceable material and disposal ofunserviceable material within 50 metres lead as per direction of Engineer-in-charge.In cement mortar |
| 3 | Removing aluminium/Gypsum partitions, doors, windows,fixed glazing and false ceiling including disposal ofunserviceable material and stacking of serviceable materialwith in 50 meters lead as directed by Engineer-in-charge. |
| 4 | Brickworkwith F.P.S. bricks of class designation 75 insuperstructure above plinth level upto floor V level in allshapes and sizes in Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 5 | Carriage of Building Rubbish Stone metal (Grit and ballast etc.) for lead upto 10KM |
| 6 | Providing and fixing Granite stone slab mirror polishedand machine edge cut in walls, pillars, steps, Shelves, Sills Counters,Floorsetc. laidon12mm(Av.)thickbaseofcement mortar 1:3 (1 cement : 3 coarse sand) jointingwithwhite cement mortar 1:2 (1white cement : 2marble dust) with pigment tomatch the shade of themarble slab including grinding, rubbing and polishing complete.South Zed BlackAbove 3601 Cm2 Slabs |
| 7 | P & F 1st qualityHeavy Duty Vitrified Polished Digital tileson floor, skirting and steps etc.in different sizes (thickness minimum 10mm) with water absortion less than or equal 0.08% and conforming to IS 15622 of approved make in all colour and shade, laid with 20 mm thick CM 1: 4 including grounting the joints with white cement and matching pigmen etc complete. |
| 8 | ELECTRICAL WORK (PART B) |
| 9 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"sISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 10 | Short point (up to 3 mtr.) |
| 11 | Medium point (up to 6 mtr.) |
| 12 | Long point(up to 10 mtr.) |
| 13 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR On board |
| 14 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 15 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 16 | Single pole MCB (With B/C curve tripping Characteristics) 6 A to 32 A rating |
| 17 | Double pole MCB(With B/C curve tripping Characteristics) 50/63 A rating |
| 18 | Four pole MCB (With B/C curve tripping Characteristics)50/63 A rating |
| 19 | SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 20 | 4 pole MCCB With Thermal Magnetic release up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 21 | Providing & Fixing of IK08 and IP-30 Recessed/surface mounting heavy duty Enclosuresuitable for mounting 3 / 4 pole MCCB, Inbuilt neutral linkmade out from Galvanized steel / CRCA sheet not less then 1.2 mm thickconforming to IS-8623-1 & 3 /IEC 61439- 1 & 3. powder painted complete with din railmaking internal DBterminations,detachable gland plate, including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . Suitable to accommodate up to 70 sqmm 3.5 core Al arm. Cable |
| 22 | Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protectionwith ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA,provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 35sq.mm. , IP 20 contact protection with existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR Four pole 30 mA sensitivity 63 A rating |
| 23 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 24 | Glazed door (single phase) IK-09 and IP-43 with Metal end box 12 Way (12+2) |
| 25 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .10 SWG tinned copper. Wire |
| 26 | Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole (b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts |
| 27 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.(e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 28 | 25 mm thick and 3 Mtr. Long |
| 29 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR 35.0 Sq. mm 3.5 core |
| 30 | Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen efficacy ≥100 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . Minimum lumen output 1000 lm |
| 31 | Providing & Fixing of energy efficient direct fit (Retrofit)Polycarbonate/ GlasshousingSMD Mid Power LED tube rod(with integral driver & alumn. heat sink ), on existing fixture.system lumen efficacy ≥ 100 lm/Watt output, internal surge protection of 2.5 KV ,THD < 20% ,p.f.≥0.95,CRI >80 , life time of minimum35000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80)certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 32 | 600mm , Min. Lumens output 1800 lmLED Tube rod with Polycarbonate Housing |
| 33 | 1200mm , Min. Lumens output 2000 lmLED Tube rod with Polycarbonate Housing |
| 34 | LIFT INSTALLATION (PART C) |
| 35 | Supplying , installation , Testing and commissioning of passenger elevator, rated speed Adjustable up to 1.0 mtr /sec having following main features from (a) to (p) mentioned below and all as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with P.W.D. Electrical B.S.R. 2022. |
| 36 | (a) MOTOR : Gearless( MRL)lift drive comprising of high starting torque lift duty, 3 phase 415 Volts A.C. permanent magnetic synchronous motor of proper rating with high efficiency shall be used. |
| 37 | (b) Operation / Drive : Microcessor based /PLC, AC Variable Voltage variable frequency variable speed (V3F) vector control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be full collective selective operation hall call demand response, UP/Down hall stops, main, Up/Down contactor with overload and phase reversal relay and safety controls . |
| 38 | (c) Traction Media: main hoist flat coated steel belt / rope . Thimbles of spring permit adjustment of uniform tension for smooth operation of the elevator Pulse belt monitoring system to avoid the cut in the belt. |
| 39 | (d) Car : car should be with M S platform with bracings of adquate size and to sustain the impact load cabin plus passengers with safety factor of fire for steel withAnti skid PVC flooring and side panels should be of Stainless steel with hair line finish of sheet of grade 304 duty with S.S. handrails . Car ceiling shall be steel finish with aesthetic appearances with LED ceiling lights .The size of the car shall be taken as per available lift well size and relevant BIS code of lifts. Car panel will also be of S S 304 grade finished with emergency stop device, emergency alarm, mechanical door safety device ,full length infra-red curtain in car door , facility of auto/attended mode. All car panel buttons and all floor switches must be with brail language as per lift act. Agency shall also make provision for install one No. CCTV Camera in the car complete with connecting cables & accessories (To be connected with existing CCTV system in the Building, cost of camera provided by department) .The inspection unit shall be provided at the top of the car. |
| 40 | (e) Landing Doors : All landing door shall be fully automatic centre opening / telescopic made of hair line finish stainless steel grade 304 with key holes and infrared curtains with unlocking facility from outside. |
| 41 | (f) Emergency light: Appropriate rechargeable battery operated LED emergency light in the car and along with alarm switch shall be provided. |
| 42 | (g) ARD: Automatic rescue Device (ARD) shall be provided according to passenger capacity with SMF batteries of approved brands as per BSR. |
| 43 | (h) Audio-Visual lndication : Audio visual indication in the lift car, showing over loading such that doors kept open till excess load is removed. |
| 44 | (i) Scrolling lndicators: Digital scrolling indicator system for up-down arrow with floor position indicator shall be provided inside the car and at all stops/floors. |
| 45 | (j) Buffers: Spring buffers/PU Buffers shall be provided. |
| 46 | (k) Car Fan : ENERGY EFFICIENT Car fanlblower with automatic sleep timer shall be provided. |
| 47 | (l) Voice Annunciator: Voice annunciator with suitable music shall be provided in lift car. |
| 48 | (m) Self diagnostics system for operational and safety parameters shall be provided in control panel |
| 49 | (n) Mechanical/Electronic over speed governor, door key holes in the floor doors, fireman switch shall be provided . |
| 50 | (o) Lift machine hoisting arrangement in the lift (MRL), counter balance to promote smooth and economic operation complete with steel guide rails for the car & counter weight, Trap Door, Lifting hooks as required and monkey ladders for lift pit should be provided by the agency along with all other steel structure works, foundations for the machine etc as required. |
| 51 | (p) Agency has to provide all working drawings and documents to comply latest BIS specifications and make proper liasion services for obtaining all necessary permissions. |
| 52 | 8 Passenger MRL Elevator with 4 stops speed 1.0 M/s |