| 1 | A-SUPPLY PART |
| 2 | A-SUPPLY PART(Shifting/Realignment of 33kV Ganika line at Akramabad Doda) |
| 3 | NEW33 KV LINE |
| 4 | 11 Mtr. Long ST Pole (For new line) ST-410 SP56 |
| 5 | GI Channel X-arm including clamps and braces |
| 6 | 150 mm² ACSR Conductor |
| 7 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 8 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 90kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fittings 4 bolts |
| 9 | Galvinized Nuts and Bolts. |
| 10 | Danger Plates with Clamps |
| 11 | Anti-Climbing Device with Clamps |
| 12 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 13 | Red Oxide |
| 14 | Aluminium Paint |
| 15 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
| 16 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 17 | B-ERECTION PART (Shifting/Realingment of 33kV Ganika line at Akramabad Doda) |
| 18 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
| 19 | GI Channel X-arm including clamps and braces |
| 20 | 150 mm² ACSR Conductor |
| 21 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 22 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 90kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fittings 4 bolts |
| 23 | Galvinized Nuts and Bolts. |
| 24 | Danger Plates with Clamps |
| 25 | Anti-Climbing Device with Clamps |
| 26 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 27 | Red Oxide |
| 28 | Aluminium Paint |
| 29 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
| 30 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 31 | PART-C Dismantling of existing 33KV line including carriage and handing over the material in Divisional stores STD Doda |