| 1 | Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr in depth in soft/loose soil for removing the exiting UNSV underground cablesof steel tubular poles / stay pit etc andall as specified and directed by Engineer - in - Charge. |
| 2 | Returning and filling in two parts (i) using riddled soil obtained from excavated soil upto depth of 30 cm (8 cm below cable and remaining above cable for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil complete all as specified and directed. Note- Excavated soil shall be riddled by using sieve to separate composite particles etc as per refilling in trenches as in cable cushioning. |
| 3 | Removing excavated surplus material of item ser No 1 to a distance n exc 50m and depositing where directed at level n. exc 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 4 | Taking down the old bricks/PCC cover and M&L for laying dry bricks old size with subclass \"B\" made of burnt clay best quality locally available with permissible tolerance, laid straight in trench for protection of cable all as specified and directed |
| 5 | M&L for cement concrete (1:4:8) type D2 with 40 mm graded aggregate for poles foundation etcincluding Dismantaining the exisiting all as directed by Engr- in - Charge. |
| 6 | M&L for cement concrete (1:3:6) type C1 with 20 mm graded aggegate for pole coping & road crossing etc including form work including Dismantaining the exisitingcomplete all as specified and directed at site. |
| 7 | Supply and stringing ACSR conductor in replacement of old unserviceable any size conductor in accordance with site requirement and binding on insulators by means of aluminium binding wire complete all as specified and directed by Engr-in-Charge. |
| 8 | S & F in replacement of galvanised steel wire of dia 4 mm for guard wire, continuous earth wire etc complete all as specified and directed. |
| 9 | S & F for replacement of cross arms bracings, supports, clamps and back plates fabricated from structural steel sections incl nut & bolts , washers welding, bending cold or hot drilling holes for bolts, washers in any shape or size as indicated or directd incl one primer coat, one under coat & one finishing coat complete all as specified & directed by Engineer - in - Charge. |
| 10 | S&F in Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 metres long)complete all as specified & directed by Engineer - in - Charge. |
| 11 | S & F for replacement of pin type, porcelain vitreous, white, brown or green insulator incl one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 100 mm height 65mm dia for 1100 Volts grade complete all as specified and directed. |
| 12 | S & F for replacement shackletype porecelain vitreous white brown or green insulator for working pressure 1100 volts of 90mm dia and 75mm height incl galvanised steel straps of 31x3 mm size insulator and 12 mm dia bolt,washer & nuts complete all as specified and directed. |
| 13 | Removing and dismantalling old U/S over head line conductor (ACSR) of any size ( 2/4 line) and then cleaning , restringing in original position incl binding on insulators by means of aluminium binding wire, tapes complete all as specified and directed.(a)The rate quoted are inclusive of cutting/ removing all tree branches/ vegetation around 3 mtrs with 02 run of conductor. (b) Length of span is approx 30 mtrs with 02 run of conductor. (c) Adjusting & tightning of stay assembly shall be done wherever required. |
| 14 | S&F in replacementsynthetic line separator of LT OHlines with nut,bolts & washers straight type horizontal configuration fixed at a point as directed and suitable for single phase 2 wire LT lines all as directed by Engr-in-Charge. |
| 15 | S&F in replacementsynthetic line separator of LT OHlines with nut,bolts & washers straight type horizontal configuration fixed at a point as directed and suitable for single phase 4 wire LT lines all as directed by Engr-in-Charge. |
| 16 | M&L for Cleaning and preparation of surface of MS Tubular pole 9.00 Mtr long and applying, Painting of two coat with aluminium paint over a coat of red oxide primer on MS tubularpole 9 Mtr long. Writing of Pole Nos on 1.5 mtr height from coping of pole, with synthetic enamel paints in 25 CM height complete all as specified & directed by Engr-in-Charge. |
| 17 | S & F in replacement of GI tubing 50mm (Light grade) laid in trenches under roador fixed to wall as mechnical protection of UG cable complete all as specified and directed. |
| 18 | S & F in replacement of GI tubing 80mm (Medium grade) and complete laid in trenches under roadas in mechnical protection of UG cable complete all as specified and directed. |
| 19 | Dismatiling, and Supplying, laying, jointing & testing cable XLPE insulated in repair, IS 7098(Part-I)-1988, marked, screened, PVC sheathedarmoured electric power cable ( heavy duty) with aluminium conductor for working voltage upto and including 1100 Volts of croos sectional area 10 Sqmm 2 core with aluminium stranded, laid in trenches / fixed on pole / wall / passed through pipe complete with jointing material of LT Cable all as specified and directed by Engineer - in - Charge,Note :- Road cutting involved any to be filled with PCC and PCC to be measured separately. |
| 20 | All as per item no 19 above but size 16 sqmm 4 core |
| 21 | All as per item no 19 above but size 25 sqmm 3.5 core |
| 22 | All as per item no 19 above but size 35 sqmm 3.5 core |
| 23 | All as per item no 19 above but size 50 sqmm 3.5 core |
| 24 | All as per item no 19 above but size 70 sqmm 3.5 core |
| 25 | All as per item no 19 above but 95 Sqmm 3.5 core |
| 26 | All as per item no 19 above but 150 Sqmm 3.5 core |
| 27 | Taking down the existing UNSV PVC insulated aluminuim conductor and Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with innersheathing of PVC tape and overall PVC sheathed inservice connections suspended by insulating hangers notmore than 1 metre apart including 4mm suspensionwire, one twin core cable flat or circular of size 10 Sqmm stranded conductor complete all as specified & directed by Engr-in-Charge. (Make - Havells/Plaza/Finolex/Kalinga) |
| 28 | All as per item no 27 above but size 16 sqmm. |
| 29 | S&F in replacement MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 400 Amps with breaking capacity 36 KA, Make :-Havells /Legrand/ABB equavalent Make complete all as specified anddirected by Engineer-in-Charge. |
| 30 | S&F in replaqcementMCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 250 Amps with breaking capacity 36 KA, Make :-Havells /Legrand/ABBor equavalent Make complete all as specified anddirected by Engineer-in-Charge. |
| 31 | S&F in replacement MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 200 Amps with breaking capacity 36 KA, Make : Havells Cat Part No - IHLLSEB40200 or equavalent Make complete all as specified anddirected by Engineer-in-Charge. Make -Havells /Legrand/ABB |
| 32 | S&F in replacement MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 160 Amps with breaking capacity 25/27 KA, Make : -Havells /Legrand/ABB or equavalent Make complete all as specified anddirected by Engineer-in-Charge. |
| 33 | S&F in replacement MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 100 Amps with breaking capacity 25/27 KA, Make -Havells /Legrand/ABB or equavalent Make complete all as specified anddirected by Engineer-in-Charge. |
| 34 | S&F in repair MCCB4 pole 415V, Adjustable thermal and fixed magnetic type of capacity 63 Amps with breaking capacity 27 KA, Make :-Havells /Legrand/ABB or equavalent Make complete all as specified anddirected by Engineer-in-Charge. |
| 35 | Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 63 amps Make : Havells or equavalent as approved by Engineer-in-Charge. |
| 36 | Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 100 amps Make : Havells or equavalent as approved by Engineer-in-Charge. |
| 37 | Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 160 amps Make : Havells or equavalent as approved by Engineer-in-Charge. |
| 38 | Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 200 amps Make : Havells or equavalent as approved by Engineer-in-Charge. |
| 39 | Supply and fix in replacement of on load change over 4 pole with front handle, 415 volt AC, 50/60Hz, 250 amps Make : Havells or equavalent as approved by Engineer-in-Charge. |
| 40 | Supply and fix in replacement of32 amps change overdouble pole with side operated handle, 230 volt AC, 50/60Hz,Make : Havells Cat no IHBFDE0032 or equavalent as approved by Engineer-in-Charge. |
| 41 | Supply and fix in replacement of 63 amps change overfour pole with side operated handle, 415 volt AC, 50/60Hz, Make : Havells Cat no IHBFFE0063 or equavalent as approved by Engineer-in-Charge. |
| 42 | Supply and fix in replacement of 100 amps change overfour pole with side operated handle, 415 volt AC, 50/60Hz,Make : Havells Cat No IHBFFE0100 or equavalent as approved by Engineer-in-Charge. |
| 43 | Supply and Fix in replacment of terminal box made out of PVC with hinged door and locking arrangements of size 240x130x95 mm including four way connector, fixed on pole with necessary clamps complete all as directed.Make Sintex, Cat No- GSJB-2014 |
| 44 | Supply and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m all as speicified and directed by Engineer-in-Charge. |
| 45 | Supply and fix in replacement of Bus bar chamber box in sheet metal enclosure of 100 Amps capacity, 4 way, 415 V complete all as directed by Engineer-in-Charge as per Havells Cat Part No IHBC010004 or equivalent make and model. |
| 46 | Supply, install, testing and commissioning LT cubical Panel of outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangementboth in front and rear side(independent door for each item on front side) mounted on 4 Nos angle iron 50x50x6 mm, 45 cm long embedded in PCC 1:3:6 type C2 complete with aluminium bus bar ofrating 1.5 times the rated capacity of incomer, IP 65 protection, suitable cable gland for incomming and outgoing cables with lugs and connections etc required nuts ,bolts and washer incl complete control wiring with suitable size PVC copper conductor cable and provn of cable lugs etc. Including provision of following accessories/eqpt incl cable gland etc and suitable for fixing of under mentioned items:-(Distribution Panel for 17 Jat Area Khab) Incoming(a) MCCB Adjustable thermal and fixed magnetic 4Pole 250 A 36 KA -No.01 (b) Onload changeover 250 amps -01 (d) Digital Voltmeter 0 to 500 Volt -01 No(e) Digital Ammeter 0 to 400 Amps with CTs and selector switch - 01 set(f) LED Phase Indication lamp (RYB) -01 SetOutgoing(a) MCCB 4Pole 100 Amp 25 KA-No.02 (b) MCCB 4 Pole 63 Amp 25 A KA -No.02 |
| 47 | M & L for Earthing in replacement / renewal complete with galvanised steel earth plate electrode 600x600x6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised strip of size 32 x 6 mm earth continuity coductor by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR-I 2009, connected to main switch board all as specified. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20 mm dia GI Pipe medium grade, funnel with wire mesh and lugs, complete all as specified and directed by Engineer - in - Charge. |
| 48 | Schedule of Credit |