| 1 | Supply and fixing inreplacement of , factory made, indoor type, AMF Panel board, suitable for 320KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 2 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN alluminium bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nutscomplete all as specified and as directed by Engineer in Charge. |
| 2 | (a) 4 Pole 550 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB,500 Amps 4 pole 50 KA 50 Hz - 02 Nos (c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job (d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element-PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No including taking down old U/S AMF Panel |
| 3 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 200KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nutscomplete all as specified and as directed by Engineer in Charge. |
| 4 | (a) 4 Pole 300 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB,350 Amps 4 pole 35KA 50 Hz - 02 Nos (c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job (d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element-PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No including taking down old AMF panel |
| 5 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 160KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nutscomplete all as specified and as directed by Engineer in Charge. |
| 6 | (a) 4 Pole 255 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB,250 Amps 4 pole 35KA 50 Hz - 02 Nos (c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job (d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element-PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No including taking down old AMF panel |
| 7 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 70KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nutscomplete all as specified and as directed by Engineer in Charge. |
| 8 | (a) 4 Pole 100 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB,100 Amps 4 pole 35KA 50 Hz - 02 Nos (c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job (d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element-PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No including taking down old AMF panel |
| 9 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 30KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nutsall as specified and as directed |
| 10 | (a) 4 Pole 63 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB,63 Amps 4 pole 35KA 50 Hz - 02 Nos (c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job (d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element-PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No including taking down old AMF panel |
| 11 | Material and labour in replacement for provision of earthing complete with copperearth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to Copper strip 20x3 mm by means of bolts, nuts, check nuts and washer of copper, watering pipe of 20 mm bore galvanised iron medium grade and 40 mm bore galvanised iron light grade for earth strip protectionincluding all excavation, earth work in any type of soil, PCC pitin PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion. Note : (i)Earth result after installation completely should be less than 5 Ohm .(ii)Quoted rates shall be deemed to include for earth strip with protection pipe of 7.5 M length. |
| 12 | Material and labour in replacement for provision of earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanised mild steel strip 32 x6 mm by means of bolts, nuts, check nuts and washer of galvanized steel, watering pipe of 20 mm bore galvanised iron medium grade and 40 mm bore galvanised iron light grade for earth strip protectionincluding all excavation, earth work in any type of soil, PCC pitin PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion. Note: (i)Earth result after installation completely should be less than 3 Ohm (ii)Quoted rates shall be deemed to include for earth strip with protection pipe of 7.5 M length. (iii) Black soil to be arranged by the conrteractorfor mixing charcol,Crystal salt,Magnesium sulphate & Vegitable oiland also for filling balance portion of pit in layer is deemed to be included in quoted rate(iv) Tools and plants to be required for making depthupto 4 Mtr is to be arranged by the contractor,charges for the same is included in the quoted rate |
| 13 | S&F in repairs 4 Pole, 160 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified and as directed by Engineer in Charge.Make:- L&T (Type MCX 32 and cat no.CS97020) or equivalent of make siemens/ABB |
| 14 | S&F in repairs 4 Pole, 200 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified and as directed by Engineer in Charge. Make:- L&T (Type MCX 33 and cat no.CS97021) or equivalent of make siemens/ABB |
| 15 | S&F in repairs 4 Pole, 225/255 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified and as directed by Engineer in Charge.Make:- L&T (Type MCX 34 and cat no.CS97022) or equivalent of make siemens/ABB |
| 16 | S&F in repairs 4 Pole, 325 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified and as directed by Engineer in Charge.Make:- L&T (Type MCX 41 and cat no.CS97023) or equivalent of make siemens/ABB |
| 17 | S&F in repairs 4 Pole, 400 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified and as directed by Engineer in Charge. Make:- L&T (Type MCX 43 and cat no.CS97025) or equivalent of make siemens/ABB |
| 18 | S&F in repairs 4 Pole, 600/630 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified and as directed by Engineer in Charge.Make:- L&T (Type MCX 45 and cat no.CS97027) or equivalent of make siemens/ABB |
| 19 | Taking out / down old existing LT 1100 volt grade cables ofsize 185 Sqmm 3.5 Core, aluminium conductor, XLPE, armoured,removal to store for re-use or for credit, complete all as specified and as directed by Engineer in Charge.Note : Excavation shall be measured and paid for separately |
| 20 | All as per Serial Item No. 14 here-in-before but 240 Sqmm 3.5 Core size |
| 21 | All as per Serial Item No. 14here-in-before but 300 Sqmm 3.5 Core size |
| 22 | Relaying, jointing, testing and commissioning, already taken out existing LT under ground cables XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor cross sectional area 185 Sqmm 3.5 core, 1100 volts grade, laid in trenches, along poles or passing through pipes or laid under floor or through/on walls etc, complete all as specified and as directed by Engineer in Charge. |
| 23 | All as per Serial Item No. 17 here-in-before but 240 Sqmm 3.5 Core size |
| 24 | All as per Serial Item No. 17here-in-before but 300 Sqmm 3.5 Core size |
| 25 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPE insulated andarmoured, heavy duty, electric power cable, cross sectional area 185 Sqmm 3.5 core aluminum conductor 1100volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed by Engineer in Charge.Note:Returning filling& removal of earth, sand cushioning and bricks for protection of cable shall be measured and paid separately. |
| 26 | All as per Serial Item No. 20 here-in-before but 240 Sqmm 3.5 Core size |
| 27 | All as per Serial Item No. 20here-in-before but 300 Sqmm 3.5 Core size |
| 28 | Supply and laying / fixing , GI pipe light grade 100mm dia bore for cable protection fixed to pole/wall or laid under floor/roadv /pavement, including flat iron clamp, nut, bolt, wahser etc of required size and taking out old & removal, complete all as specified and directed.Note:Boring of holes under road etc. shall be measured and paid separately. |
| 29 | All as per item No 23here - in before butGI pipe 80mm ccomplete all as specified and as directed by Engineer in Charge. |
| 30 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, ccomplete all as specified and as directed by Engineer in Charge. |
| 31 | Excavation trenches not exceeding 1.5m wide and not exceeding 1.5m depth for laying of cables and erectioning of poles and getting out in any Hard /Dense soilcomplete all as specified and as directed by Engineer in Charge. |
| 32 | Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and as directed by Engineer in Charge. |
| 33 | Removal of surplus excavated soil to a distance not exceeding50metre and depositing where directed at a level not exceeding1.5metre above the starting point,complete all as specified and as directed by Engineer in Charge. |
| 34 | Material and labour, sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment. |
| 35 | Supplying and laying un-reinforced precast concrete cable cover, classLV, Type 1, flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer in charge |
| 36 | Laying only old un-reinforced precast concrete cable cover, classLV, Type 1, flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer in charge. |