Annual Maintenance Of Park Light In Sector-82, 91, 92, 93, 93A, 93B, 104, 105, 108, 110 And Village Gejha Tilptabad And Hazipur, Noida. - Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc.(Kalinga, Grandlay, Skytone, Havells make) 2 1) 25 Sq.mm. x 2 Core (AOR) 3 2) 16 Sq.mm. x 4 Core(PS No. 501) 4 3) 35 Sq.mm. x 3.5 Core(PS No. 501) 5 4) 50 Sq.mm. x 3.5 Core(PS No. 501) 6 S/F of cable Lug(socket) to the cable lead. Complete in all respects as per PS No. 504 7 (1) 16 Sq.mm. 8 (2) 25 Sq.mm. 9 (3) 35 Sq.mm. 10 (4) 50 Sq.mm. 11 S/Laying of90 mm dia (OD 90 mm & ID 76 mm nominal) size of (DWC) HDPE Pipes ISI marked along wigh all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. as per DSR 2018 item no. 14.16.2 page no. 52 12 Supply and buring of safe earthing electrode T-19 (Hot dip galvanized), length up to 2000mm outer type 50mm, inner pipe, 22mm terminal dia 12mm, outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip galvanization up to 100 micron filled with crystalline conductive mixture(CCM) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good micture of retaining capicity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25x3 G.I. strip will be extra as per PS No. 725A 13 Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted) ElectricalDSR 2018 Item No. 11.5 page no. 39 14 Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres.DSR-2018 Item No.14.06 15 Cement Concrete with 2 cm gauge stone grit, coarse sand & cement in proportion of 4:2:1 including supply of all material, Labour , tools & plants etc. Required for proper completion of work. SOR No. 279(a) 16 Hiring of welding set charges running time @ 6 hrs (AOR) 17 Hiring of Gas cutter set with oxygen and LPG running time 6 hrs (AOR) 18 Supply and laying of 25mm x 3mm G.I. strip from earthelectrode directly in the ground as required complete in all respect.P.S. No. 716 19 Supply and Fixing of Bus Bar Support Connector 4 way with Backsheet complete in all respects as per E/I. (AOR) 20 Supply and Fixing of 50 Amp to 63 Amp. SPMCB (10KA) CAT-A. P. S. No. 1003(B) 21 Supplying, installing, testing & commissioningof following ratings MCCB / MCB duly enclosed in weather proof (Outdoor Type) enclosures in following capacities with cable end boxes etc. a) 63 A, TPN, switch disconnector fuse unit (Panel mounted type)with lSI marked HRC fuses DSR/2018-1602 22 Supply of 1200 mm. dia Ceiling Fan. AOR- 23 Supplying, installation, testing & commissioning of thefollowing outdoor type light fixtures complete with LED lamp and Driver and origin of LED chip to be specified. THD for the lights should not be more than 10, current less than 8% and voltage less than 5%, SDMC of less than equal to 5 with maximum CCT variation permissible is 125 K and UV should not be more than +/- 0.002. Lumens should be atleast 125 lumens / watt ot to be specified. Vendors to specify the shift in CCT due to the reflectors used. Operating temeprature for LED should be >60 Deg. C. For all the light fixtures M79 & LM80 certification required and vendor should provide the 3 Years on site replacement warranty for all light fixtures. 10 Watt LED step light fixture suitable for illuminating ghat steps etc.Make- BAJAJ, Philips, Havells 24 12 Watt LED ground burial up lighter suitable for illuminating plants.Make- BAJAJ, Philips, Havells 25 Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000mm, outer Dia 50 mm inner Dia 25 mm, terminal Dia 12mm, outer GI pipeof 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing lead of 25mm x3mm G.I. strip, upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. PS No. 725 (B) 26 Supplying and fixing of 63 amp. TP MCB (10 K.A) (CAT - A)PS No. 1017 27 Supplying and fixing of 40 amp. DP MCB (10 K.A) (CAT - A)PS No. 1010 28 POINT WIRING-Wiring point for light with 1.5 sq mm. FR PVC insulated multistrand single core copper conductor cable in PVC conduit concealed in the wall, complete with 1.5 sq mm. FR PVC insulated multistrand single core copper earth wire, piano type switch & ceiling rose/ angle/ battem holder on 3 mm thick phenolic laminated backelite sheet etc., complete in all respects, as directed including matching colour wash. PS No. 131 (C) 29 SUPPLY AND FIXING OF LIGHT FIXTURES, FANS & ACC.-Supply and Fixing of LED Tube Light with natten suitable for up to 1 x 22 watt LED tube light complete including tube etc on surace complete in all respect. PS No. 1413 Cat AAA 30 Supply and fixing of recess / Surface / Pendent mounting round 12 to 15 Watt LED Down lighter having powder coated die cast aluminium housing with heat sink, diffuser / reflector and driver set complete in all respect. PS NO. 1402 Cat AAAMake- BAJAJ, Philips, Havells 31 Supply and fixing of decorative 40 to 45 Watt LED Post Top indirect light luminaire having pressure die cast aluminium body and clear glass with driver set confirming IP 65 and above protection complete in all respect. PS No. 1443 cat AAAMake- BAJAJ,Havells, klite, Neri, Vak 32 Supply installation testing and commisioning of LED FIXTURE -Ground Buried Light ,10-15W,3000K, IP67 The housing in light weight, made of high strength die cast aluminium and coated by static powder making it weather resistant.Protection screen in tempered glass with high impact resistance (=>IK08). Premium thermal management by high heat conductivity aluminum alloy and thermal fins. SS Cover. Pure Polyester powder coating. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP67 rated. Length-380mm,Height – 110mm, Width.-90mm, Weight - 2.45Kgs. Power LED Module with high efficacy LEDs(CREE/OSRAM with ESD>=8kV & ceramic package), on Printed Circuit Board with metal core plate. 33 Electronic Power Supply for LED Module,which offers Protection against Short Circuit, Over- Voltage Over- Current & with in-built surge protection. Lens made of PC offers different beam angles-10deg./12deg./25deg./35deg. to serve different lighting needs..Estimated LED Lifetime is 70,000 hours minimum. LM80 report from LED Manufacturer should be submitted. Light fixture Lumen output is minimum 1000Lumens. Sample Should be submitted for concerned engineer incharge for approval of light fixture.Make- BAJAJ, Philips, Havells, Klite 34 Repair of 63 KVA Transformer incl. changing of HV & LV Coil, Bushing, Gasket & Fresh Transformer oil without returning of old & unservicable material. Complete in all respect as per direction of E/I. (AOR) 35 Dis/Re-fixing of 63 kva transformer with connection loading & unloading, cartage charge from site to repairing at worshop complete in all respects as per direction of E/I (AOR) 36 S/F of 11 KV TPMO Relco/Rama make 9 Nos. insulator of jai Shree/BHEL make complete in all respects as per direction of E/I. UPERC P-48 37 S/F of out door type 11KV fuse set Relco/Rama/Rastriya make with insulator Jai shree/BHEL make complete in all respects as per direction of E/I..(AOR) 38 Painting of the electric pole with 2 Coats of aluminium paint over red oxide primer complete in all respects. P.S. No. 634 39 Supply and fixing ofMast Nut, Bolt & templates suitable for 30 Mtr High mast. Complete in all respects as per directiion of E/I.(AOR) 40 Supply and fixing ofWinch Machine assembly suitable for 30 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) 41 Supply and fixing of SS Rope Wire 16Mtr/30 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) 42 Supply and fixing ofLantern Carriage made of 2.5 outer dia G.I. Pipe Class B heavy duty for mounting the luminaries suitable for 16Mtr/30 Mtr High mast. Complete in all respects as per directiion of E/I.(AOR) 43 Supply and fixing ofHead Frame with Pulley suitable for 16Mtr/30 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) 44 Dismantling of 30 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. Complete in all respect . As per direction of E/I. (AOR) 45 Fixing of 30 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. on existing foundation. Complete in all respect . As per direction of E/I. (AOR) 46 Dismantling of 16 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. Complete in all respect . As per direction of E/I. (AOR) 47 Fixing of 16 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. on existing foundation. Complete in all respect . As per direction of E/I. (AOR) 48 Supply and fixing ofWindow Door/Cover size as per16Mtr/30 Mtr High mast made of 3mm thick MS Sheet with 2 Nos heavy duty lock shutter type incl. hinged. Complete in all respects as per directiion of E/I. (AOR) 49 Supply and fixing ofAviiation Lightsuitable for 16Mtr/30 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) 50 Supply and fixing ofMS Lighting arrestor rod suitable for 16Mtr/30 Mtr High Mast. Complete in all respects as per directiion of E/I. (AOR) 51 Supply and fixing of fibre Junction Box suitable for 16Mtr/30 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) 52 Supply and fixing ofMast Nut, Bolt & templates suitable for 16 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) 53 Supply and fixing ofWinch Machine suitable for 16 Mtr High mast. Complete in all respects as per directiion of E/I.(AOR) 54 Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.1- 16 sq. mm 2 core (DSR-2018 9.3.1) 55 2- 25 sq. mm 2 core (DSR-2018 9.3.2) 56 3- 25 sq. mm 3.5 core (DSR-2018 9.3.17) 57 4- 50 sq. mm 3.5 core (DSR-2018 9.3.19) 58 5- 70 sq. mm 3.5 core (DSR-2018 9.3.20) 59 Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.(DSR-2018, 12.42) 60 Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. DSR Electrical 2018/ I. No. 11.3.3(8.0 metre and upto 10.0 metre) 61 Location and pin pointing of 11KV HT cable fault exposing the same in the underground 11 KV cables including digging of trench upto the depth of the cable. Cutting the faulty cable and sealing of the faulty cable, by providing fault locator machines with operator (Cable Fault Locator) (AOR) 62 Location and pin pointing of LT cable fault exposing the same in the underground LT cables including digging of trench upto the depth of the cable. Cutting the faulty cable and sealing of the faulty cable, by Expert technical staff. (AOR) 63 Location and pin pointing of LT cable fault exposing the same in the underground LT cables including digging of trench upto the depth of the cable. Cutting the faulty cable and sealing of the faulty cable, by providing fault locator machines with operator (Cable Fault Locator) (AOR)