Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 14-06-2025 | Corrigendum for Date Extended | Date | 23-06-2025 |
| Sl. No. | Item Description |
| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"sISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, Short point (up to 3 mtr.) |
| 2 | ..do.. Medium point (up to 6 mtr.) |
| 3 | ..do… Long point(up to 10 mtr.) |
| 4 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, On board |
| 5 | ..do.. Short point (up to 3 mtr.) |
| 6 | ..do … Medium point (up to 6 mtr.) |
| 7 | ..do.. Long point(up to 10 mtr..) |
| 8 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modularbox of 1.2 mm thickwith earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate,screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR , Short point (up to 3 mtr.) |
| 9 | …do…Medium point (up to 6 mtr.) |
| 10 | …do… Long point(up to 10 mtr.) |
| 11 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR , 20 mm |
| 12 | …do … 25 mm |
| 13 | …do … 32 mm |
| 14 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked ( IS:14927 P - II ) virgin materialUPVC trunking & it\"s accessories, Hot Dipped GalvanizedModular box of 1.2 mm thickwith earth terminal/ Surface Moulded virgin materialUPVCModular Box , 10 A Modular switch,Modular faceplate with grid plate, 3 pin ceiling rose/holder /3 way Connector,screws,making connections, testing etc. as required. For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRShort point (up to 3 mtr.) |
| 15 | …do… Medium point (up to 6 mtr.) |
| 16 | …do… Long point(up to 10 mtr.) |
| 17 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) on surfaceISI marked ( IS:14927 P - II ) virgin materialUPVC Trunking & it\"s accessories, Hot Dipped GalvanizedModular box of 1.2 mm thickwith earth terminal/ Surface Moulded virgin materialUPVCModular Box,modular 10A switch, 3/5 pin6 Amodular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, On board |
| 18 | …do… Shortpoint (up to 3 mtr.) |
| 19 | ..do… medium point(up to 6 mtr..) |
| 20 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make on surfaceISI marked ( IS:14927 P - II ) virgin materialUPVC trunking & it\"s accessories, Hot Dipped GalvanizedModular box of 1.2 mm thickwith earth terminal/ Surface 2 No. Moulded virgin materialUPVCModular Box , 2 Nos 10 A two way Modular switch,3 pin ceiling rose / holder/3 way Connector , Modular face plate with grid plate,screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR Short point (up to 3 mtr.) |
| 21 | ---do – Medium point (upto 6 mtr.) Group-1 |
| 22 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 3 x 1.5 sq.mm |
| 23 | …do… 1 x 2.5 sq.mm |
| 24 | …do… 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 25 | …do … 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 26 | ..do… 4 x 10.0 sq.mm |
| 27 | Supply & drawing Wiring for sub mains ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 10.0 sq.mm |
| 28 | S&F following sizesof ISI marked ( IS:14927 P - II ) virgin materialUPVC trunking along with accessorieslike coupler, inner, outer, elbow, square box, tee, end cap etc. on surfacewithscrews, expansionfastenersas required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR 20 mm x 12 mm |
| 29 | ..do…25 mm x 12 mm |
| 30 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen freefor less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 2.5 Sq.mm 3 core flat / Round |
| 31 | Supply and laying PVC Insulated and PVC Round Sheathed Multi Core copper conductor (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen freefor less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR,1.5 sq.mm x 3 core |
| 32 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, Single pole MCB (With B/C curve tripping Characteristics) ,6 A to 32 A rating |
| 33 | ..do.. Double pole MCB(With B/C curve tripping Characteristics)6 A to 32 A rating |
| 34 | Four pole MCB (With B/C curve tripping Characteristics)50/63 A rating |
| 35 | Providing & Fixing of 240/415 V isolatorISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage,true contact indication,Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting,minimum phase termination capacity of 35sq.mm.IP 20 contact protection and fitted in existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, Double pole isolator , 30 A / 40 A rating |
| 36 | ..do… Four pole Isolator, 80 A/ 100 A rating |
| 37 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, Metal door (single phase) IK-09 and IP-43 with Metal end box, 6 Way (6+2) |
| 38 | …do… 12 Way (12+2) |
| 39 | ..do… Metal door (Three phase) IK-09 and IP-43with Metal end box , 4 Way |
| 40 | ..do… 8 Way |
| 41 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, Suitable for Two / Three / Four module for MCB |
| 42 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box withprovision of incomer suitable for MCB / RCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 100 A rating copper bus bar, neutral bars with shrouds, earth bar , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, Double door IK-09 & IP-43 with Metal end box, 4 Way(8+12) |
| 43 | Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printedmade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 5 step fan regulator 2 Module 360 dgree rotating |
| 44 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification ofWiring accessories refer ChapterE - 07related item & For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 45 | SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 3 pole MCCB With Thermal Magnetic release, up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 46 | ..do.. 4 pole MCCB With Thermal Magnetic release, up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 47 | Providing & Fixing of ISO certified company made TP&N 415 V side handle operated double break fuse switch unit in sheet steel enclosure as per PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999 (W/O HBC fuses) including making connections with suitable lugs, testing etc. as required.Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR, 200 A rating |
| 48 | Providing & Fixing of ISO certified company made Four Pole By pass Change Over Switch conforming to IS:13947(Part 3) : IEC:60947-3-1 and IEC:60947-6-1, Open execution type in the following ratings.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR , 200 A |
| 49 | Providing & Fixing of ISO certified company made bus bar chamber housed in sheet metal box as per PWD specification for electrical Works Confirming to IEC-60439/IS-8623 & IEC-60529/IS-2147 made out from 1.6 mm thick powder coated CRCA sheet,degree of protection IP-31,front openable bus bar made out of Coppersuitable for 200 amp. Capacity, bus barfixed on porcelain/DMC insulators at approved spacingincluding making connections etc. as required. Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR ,450 mm long , 4 strip |
| 50 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %,Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 16.0 Sq. mm, 4 core |
| 51 | ..do.. 25.0 Sq. mm, 3.5 core |
| 52 | ..do ...35.0 Sq. mm, 3.5 core |
| 53 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR, 16.0 Sq. mm, 4 core |
| 54 | ..do.. 35.0 Sq. mm , 3.5 core |
| 55 | Plate Earthing as per IS:3043 withcopper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying3 mtr. below the ground level with 20mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 56 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR,10 SWG copper. Wire |
| 57 | Supply & Laying following size\" B \" class ,G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc.for laying earth conductor/ strip / cable in ground/ surface/ recess as required.All as per pre approved by Engineer in charge.(Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annex ure \"A\" attached with this BSR,40 mm dia. |
| 58 | Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR, 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) |
| 59 | Providing & Fixing ofof M.S. J- hook of standard design made out of 16 mm dia. M.S. round bar and fixed withcement concrete mortar with required support as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 60 | Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR, 225 mm sweep |
| 61 | …do…. 300 mm sweep |
| 62 | Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR, 300 mm sweep(900/1400 RPM) |
| 63 | Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminiumhousing with in built driver, System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR, 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 64 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. (OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR), Recessed Mounting, Minimumlumen output 650 lm |
| 65 | …do…. Minimum lumen output 1300 lm |
| 66 | …do… Minimum lumen output 1950 lm |
| 67 | ..do… Surface Mounting (with extruded alumn. Housing ) , Minimumlumen output 650 lm |
| 68 | ..do… Surface Mounting (with extruded alumn. Housing ) ,Minimum lumen output 1300 lm |
| 69 | ..do… Surface Mounting (with extruded alumn. Housing ) ,Minimum lumen output 1950 lm |
| 70 | Providing & Fixing of IP20, 2\"x2\" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. ( OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR),Recessed Mounting,Minimum lumen output 3000 lm |
| 71 | Providing & Fixing ofIK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles,of high power LED of 3 to 5 watt Nos. . Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10%, driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K±355K.Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR,High Power LED Flood Light Minimum lumen output 6200 lm |
| 72 | …do… High Power LED Flood Light Minimum lumen output 10000 lm |
| 73 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on Nos. LED & should be SMD type of 3 to 5 watt Nos. . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR,LED Street Light fixture with Minimum lumen output 5600 lm |
| 74 | ..do… LED Street Light fixture with Minimum lumen output 7500 lm |
| 75 | Providing & Fixing of Street light bracket made out from following size of \" B \" class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR, 25 mm Dia. |
| 76 | …do….32 mm Dia. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy