Tender For Sitc Of Panel For Newly Constructed Laundry SITCofacubicaltypefloormountingswitchboardmadefrom75x40x6sizeCchannelbaseframeand2mmthickMSsheet,powdercoatedinsuitablecolouroveracoatofprimer,copperbusbarsofsizethatrequiredtocarrydesignedampere(200A)withsleevedwithheatshrinksleeves,bakelitefuseunitswith2AHRCfuses,colouredphaseindicationlamps(LED)andswitches,separatecableentry/wirewayboxesfortheswitcheswithdetachablefrontcover,providingrubberbeedings,earthingallmetalpartsandswitcheswith25x6mmcopperstrips,givingrigidconnectionsfrom200AMCCBtobusbarwithsuitablesizetinnedcopperbusbarandbusbartosubswitcheswith4SWGtinnedcopper,sleevedwithheatshrinksleevesandmarkingtheidentificationofswitcheswithwhitepaint,fixingdangernoticeboardand3phaseenergymetersuitableforenergymeasurementalongwithsuitableCTforconnectinginsidetheseparatecabinhavinghingeddoorwithglassforkWhenergymeterreadingfromoutside(3phase4w,5AL&Tenergymeter)etcasrequired.(Thedrawingofthepanelboardisattachedwiththeestimate) Switches Incomers :- 200amps25kA4poleMCCBwithvaryingdepthrotary handle. Outgoing :- 100amps16kA4poleMCCBwithvaryingdepthrotaryhandle-1No,63amps16kA4poleMCCBwithvaryingdepthrotaryhandle-3Nos&40amps16kA4poleMCCBwithvaryingdepthrotaryhandle- 1 No 3phaseenergymetersuitableforenergymeasurementalongwithsuitableCTforconnectinginsidetheseparatecabinhavinghingeddoorwithglassfokWhenergymeterreadingfromoutside(3phase 4w ,5A L&T energy meter.)- 1 No Theunitasawholeshouldbedustandverminproof.Theminimumclearancefromthebottomswitchhandle to the ground level should be 60 cm. 2 10 mtrs Layingandfixingofonenumber1.1kVgradeAluminiumconductorXLPEinsulatedPVCsheathedarmouredpowercableof4Cx16sq.mmsize,clampingonwallusingsuitablemetalclampsspacingnot exeed 50 cm etc. as required. mtr ANNEXURE II Schedule of rates and approximate quantities PAC: Rs. 523585/- Name of Work:SITC of Panel for newly constructed Laundry Unit 1 1 No Each Item No Quantity Description Rate ( In figures and Words ) Amount Page 12 of 178 3 10 mtrs Layingandfixingofonenumber1.1kVgradeAluminiumconductorXLPEinsulatedPVCsheathedarmouredpowercableof3.5Cx25sq.mmsize,clampingonwallusingsuitablemetalclampsspacingnot exeed 50 cm etc. as required. mtr 4 30 mtrs LayingofonenumberPVCinsulatedandPVCsheathed/XLPEpowercableof1.1KVgradeof3.5Cx150sq.mmintheexistingcabletrayasrequired. mtr 5 2 Nos Supplyingandmakingendterminationwithbrasscompressionglandandaluminiumlugsfor4CX16sq.mmsizeofPVCinsulatedandPVCsheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. Each 6 2 Nos Supplyingandmakingendterminationwithbrasscompressionglandandaluminiumlugsfor3.5Cx25sq.mmsizeofPVCinsulatedandPVCsheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. Each 7 2 Nos Supplyingandmakingendterminationwithbrasscompressionglandandaluminiumlugsfor3.5Cx150sq.mmsizeofPVCinsulatedandPVCsheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. Each 8 1 No Supplyingandfixing63ampsrating,415Volts,CcurveminiaturecircuitbreakersuitableforinductiveloadofFourpoleintheexistingMCBDBcompletewithconnectIons,testingandcommissioningetcasrequired. Each 9 70 mtrs Supplyingofonenumber3.5Cx95Sq.mmsizeAluminiumconductorXLPEinsulatedPVCsheathedpower cable of 1.1 kV grade etc. as required. mtr 10 50 mtrs LayingofonenumberPVCinsulatedandPVCsheathed/XLPEpowercableof1.1KVgradeof3.5Cx95sq.mmintheexistingcabletrayasrequired. mtr 11 20 mtrs Layingandfixingofonenumber1.1kVgradeAluminiumconductorXLPEinsulatedPVCsheathedarmouredpowercableof3.5Cx95sq.mmsize,clampingonwallusingsuitablemetalclampsspacingnot exeed 50 cm etc. as required. mtr 12 2 Nos Supplyingandmakingendterminationwithbrasscompressionglandandaluminiumlugsfor3.5Cx95sq.mmsizeofPVCinsulatedandPVCsheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. Each 13 70 mtr Chargesforremovingtheexisting3.5Cx50sq.mmXLPEAluminiumarmouredcablefromthecabletrayandremoveconnectionfrompanelboardandconveyanceofthematerialstothegodownwithoutany damage. mtr 14 1 No Supplyandprovidingonenumberof2mx1m12mmsizeornearestsize,electricallygraded,rubbermat(IS:5424 / 1969) in front of the main switch board. Each Page 13 of 178 15 2 Nos Supplyandprovidingplateearthing(AsperIS3043:1966)withcopperearthplate600mmx600mmx3mmthickincludingaccessories,andprovidingmasonryenclosurewithcoverplatehavinglockingarrangementandwateringpipeof25mmdiaand2.7meterlongwithfunneletc.(butwithoutcharcoal/coke and salt) as required. Each 16 13 Mtrs Supplyingandlaying25mmx5mmcopperstrip,fromthebottomoftheearthplatetothetestjoint,includingconnection/terminatingwithnut,bolt,springwasheretc,asrequired.(Jointingshallbedonewith 3 sets of GI nut, bolt & spring washer) mtr 17 80 mtr Supplyingandlaying25mmx3mmcopperstripat0.50meterbelowground/clampingonwallasstripearthelectrode,includingconnection/terminatingwithnut,bolt,spring,washeretc.asrequired.(Jointingshallbedonebyoverlappingandwith2setsof brass nut bolt & spring washer spaced at 50 mm) mtr 18 120 Kg SupplyingandprovidingExcelEarthingcompoundincluding mixing with excavated fine soil and water to makeitasslurryandfillingaroundtheearthplateetc.as required. Kg 19 10 Nos SupplyingandfixingcabledetailstagsusingAluminiumsheetofsize10cmX3cmX2mmorneareston the existing cable. Each 20 1 No Supplyingandfixing160A,16kA,4pole(ThreepoleandNeutral),415V,Mouldedcasingcircuitbreaker(MCCB)withrotaryhandle,thermalmagneticreleaseandterminalspreaders(ifrequired)inexistingcubiclepanelboardincludingdrillingholesincubiclepanel,makingconnectionsetc,asrequired.(Note:Theworkrequiredtoremovetheexisting3PMCCBfromthepanelandtoreplacewiththenew4PMCCB.Soitsrequiredminorfabricationtothedoorandtothebusbarforfixingthe4PMCCBtotheexisting 3P MCCB) Each 21 1 No Supplyingandfixing160A,16kA,4pole(ThreepoleandNeutral),415V,Mouldedcasingcircuitbreaker(MCCB)withrotaryhandle,thermalmagneticreleaseandterminalspreaders(ifrequired)inexistingMCCBDB,makingconnectionsetc,asrequired.(Note:Theworkrequiredtoreplacetheexisting4PMCCBwithlowerratingtothe160AMCCBwhichissuitabletolegrandMCCBDB,dpx160 model) Each 22 20 mtrs LayingofonenumberPVCinsulatedandPVCsheathed/XLPEpowercableof1.1KVgradeof3.5Cx50sq.mmintheexistingcabletrayasrequired. mtr 23 30 mtrs Layingandfixingofonenumber1.1kVgradeAluminiumconductorXLPEinsulatedPVCsheathedarmouredpowercableof3.5Cx50sq.mmsize,clampingonwallusingsuitablemetalclampsspacingnot exeed 50 cm etc. as required. mtr Page 14 of 178 24 2 Nos Supplyingandmakingendterminationwithbrasscompressionglandandaluminiumlugsfor3.5Cx50sq.mmsizeofPVCinsulatedandPVCsheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. Each 25 10 mtrs Supplyingandinstalling300mmwidthX50mmdepthX1.6mmthicknesssizeofperforatedHotdippedGalvanisedIroncabletrayswithperforationnotmorethan17.5%,inconvenientsections,joinedwithconnectors,suspendedfromtheceilingwithGI.suspendersincludingbolts&nuts,paintingsuspenders etc as required. mtr 26 3 Pts Wiringforlight/fanpointswith1.5sqmmFRLSPVCinsulatedcopperconductorsinglecorecableinsurface/recessedmediumclassivorycolouredPVCconduitwithmodularswitch,modularplate,suitableG.Iboxearthingthepointwith1.5sqmmgreencolouredFRLSPVCinsulatdcopperconductorsinglecore cable etc, as required. (Group C) Each 27 30 mtrs Supplyingandfixingof20mm(mediumclass)ivorycolouredrigidPVCconduitalongwithaccessoriesinsurface/recessincludingcuttingthewallandmakinggood the same in case of recessed conduit as required. mtr 28 30 mtrs Supplyingandfixingof25mm(mediumclass)ivorycolouredrigidPVCconduitalongwithaccessoriesinsurface/recessincludingcuttingthewallandmakinggood the same in case of recessed conduit as required. mtr 29 40 mtrs Supplyinganddrawing3x4sqmmFRLSPVCinsulatedcopperconductor,singlecorecableintheexistingsurface/recessedsteel/PVCconduitasrequired. mtr 30 2 Nos Supplyingandfixing6-32Arating,240/415V,10kA,Ccurve,SinglepoleminiaturecircuitbreakersuitableforinductiveloadofsinglepolesintheexistingMCBDBcompletewithconnections,testingand commissioning etc. as required. Each 31 2 Nos Supplyingandfixing32AmodularDPswitchontheexistingmodularplate&switchboxincludingconnectionsbutexcludingmodularplateetc.asrequired.( 2 MD) Each 32 2 Nos Supplyingandfixing3pin25Amodularsocketontheexistingmodularplate&switchboxincludingconnectionsbutexcludingmodularplateetc.asrequired. Each 33 4 Nos Supplyingandfixing2modules,PVCOpenBox/GIboxalongwithmodularbase&coverplateformodularswitchesinrecessorsurfaceetc.asrequired.( Site Visit Recommended) Each Page 15 of 178 34 1 No Supplyingandfixing3phase6way,doubledoor,suface/recessmounting,verticaltype,415V,TPNdistributionboardwithprovisionforfixingMCCBasincomerandTPMCBasoutgoing,completewith200Atinnedcopperbusbar,commonneutrallink,earthlink,dinbarformountingMCBs,detachableglandplate,interconnections,earthing,phosphatizedandpowderpainted,fixingusingboltandnut,givingconnectionsetc.asrequired.(ButwithoutMCCBandwill be provided by NITC ) Each 35 60 Mtrs Layingofonenumber8SWGgoodqualitybarecopperconductorforloopearthingalongwithexistingXLPEinsulatedPVCsheathedarmouredpower cable as required. mtr 36 1 No RemovalofFourpoleMCCBfromtheexistingDBandrefixingitinthenewlyfixedMCCBDB,completewithconnections,testingandcommissioning etc. as required. mtr 37 1 No Removalofexisting6wayVTPNDBandrefixingitinanotherpositions,completewithconnections,testing and commissioning etc. as required. Each 38 13 Nos RemovalofsinglepoleMCBanditsconnectionsfromtheexistingDBandrefixingitinthenewlyfixedMCCBDB,completewithconnections,testingand commissioning etc. as required. Each 39 1 No Supplyingandfixing210x155x92mmornearestsizewaterproofrigidpolycarbonateloopinloopoutboxwithdetachablefrontcover,includingsupplyof4waybusbarconnectorwithbaseinsulator,fixingusingsuitablesizemetalclampsandgivingconnectionsetc,asrequired.(ForTerminating3Cx50Sq mm Al Cable)