Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 27-11-2025 | Corrigendum 08 | Technical Bid | 15-12-2025 |
| 2 | 20-11-2025 | Corrigendum 07 | Technical Bid | 15-12-2025 |
| 3 | 20-11-2025 | Corrigendum 06 | Technical Bid | 15-12-2025 |
| 4 | 07-11-2025 | Date Extension Corrigendum | Date | 15-12-2025 |
| 5 | 03-10-2025 | Date corrigendum no.4 | Date | 10-11-2025 |
| 6 | 03-09-2025 | Date Extention Corrigendum3 | Date | 08-10-2025 |
| 7 | 30-07-2025 | Date Extension Corrigendum 2 | Date | 08-09-2025 |
| 8 | 04-07-2025 | Date Extention Corrigendum | Date | 30-07-2025 |
| Sl. No. | Item Description |
| 1 | (A). DIVISION SOUTH S-1 |
| 2 | Pipeline |
| 3 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended upto date), with internal cement mortar lining for potable water with rubber ring (EPDM/SBR) joints as per IS: 5382-1985 (excluding special accessories) complete including all material, labour, hydraulic testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 4 | 100 mm |
| 5 | 150 mm |
| 6 | 200 mm |
| 7 | 250 mm |
| 8 | 300 mm |
| 9 | 350 mm |
| 10 | 400 mm |
| 11 | 450 mm |
| 12 | 500 mm |
| 13 | 600 mm |
| 14 | Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes, transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) .Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply may be in coil or straight length in 6 M/12 M. |
| 15 | HDPE PE-100 PN-6 |
| 16 | 110mm dia |
| 17 | Providing, lowering, laying and jointing in trenches, standardlengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by butt fusion/ electro fusion welding method, including all taxes, transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work). Note: Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply of pipe shall be in straight length in 6/12 M. |
| 18 | HDPE PE-100 PN-6 |
| 19 | 125mm dia |
| 20 | 140mm dia |
| 21 | 160mm dia |
| 22 | 180mm dia |
| 23 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 24 | Add extra for over all depth of excavation above 1.5 m and upto 3.0 m over item no 4.1 |
| 25 | Earth work in excavation by mechanical means (Hydraulic Excavator) / manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required. |
| 26 | In ordinary rock. (10 %) |
| 27 | Dismantling of cement concrete pavement for pipe line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. |
| 28 | Dismantling of flexible pavement for pipe line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re_x0002_handling of material/earth to complete the tasks per technical specification and scope of work.. |
| 29 | Bituminous courses |
| 30 | Granular courses |
| 31 | P & F of Open timbering in trenches including strutting, shoring complete (measurements to be taken of the face area timbered). Depth exceeding 1.5 Mtr. but not exceeding 3 Mtr |
| 32 | Carriage of Materials by mechanical transport including loading,unloading and stacking ::Sand, bazri, ballast, kankar- Lead upto 5 Km |
| 33 | Barricading with Sal ballies as per design including tying with vertical post by coconut strings including digging out holes in all types of soil complete in all respect with two horizontal members height 1.2 m upto 1.5m above ground level and vertical supports upto 2.5 centre and upto 3 days period including removal and cleaning the site complete in all respect & including dressing of sides and providing retro reflective tapes for traffic safety as per direction of Engineer-in charge in all types of soil. |
| 34 | Valves |
| 35 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410, Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS, Face to face dimensions as per IS 14846/2000 (amended up to date), Epoxy (Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 36 | Manually operated class PN 1.0 |
| 37 | 250 mm HW |
| 38 | Providing, lowering, aligning, fixing in position in pipe line, CIdouble flangedDual plate check valve of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications:Body & Cover of Grey cast iron ofIS:210/ FG200, Disc / plates - Cast steel, Disc seal ring of EPDM/ NBR (food grade quality), Body seat of SS, Face to face dimensions as per API: 594, Flanges Drilled as per IS:1538.Epoxy (Non-Toxic & suitable for drinking water) applied on body & coverinside and outside . Shaft/Stop Pin of SS- AISI- 304/410 , Hinge SS AISI 316/304 / CS, SpringSS AISI 316/304, Bonnet Gasket EPDM, Bush- Brass with EPDM/NBR \"O \"ring seal. Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel), Insertion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 39 | Class PN 1.0 |
| 40 | 200 mm dia |
| 41 | 250 mm dia |
| 42 | 300 mm dia |
| 43 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Double Acting Kinetic Air Valve with isolating Sluice Valve of approved makes for following pressure rating & dia complete, confirming to IS: 14845-2000 (amended up to date) and of following specifications: Body, Cover and Cowl - Grey Cast Iron as per IS:210- FG 200, Float -Stainless Steel AISI 304 / IS: 3444 , Float Guide_x0002_HBT1.HP Orifice- HTB2/ SS,Body seat ring - Leaded tin bronze/ SS .Seal ring and face ring - PDM/NBR ,Ends flanged according to IS 6418,Fastners - CS, Epoxy paint inside outside of food grade safe for drinking water, Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 44 | Class PN 1.0 |
| 45 | 50 mm dia |
| 46 | Providing, lowering, laying, aligning, fixing in position in pipe line, Resilient Seated D/F DI Sluice valves of approved make & design standard of following dia complete (including jointing & jointing material ) including all material, labour, testing and commissioning along with pipe line as per Technical Specification & as per direction of Engineer. |
| 47 | Manually operated class PN 1.6 |
| 48 | 100 mm dia |
| 49 | 150 mm dia |
| 50 | 200 mm dia |
| 51 | 250 mm dia |
| 52 | 300 mm dia |
| 53 | 350mm dia |
| 54 | 400 mm dia |
| 55 | 450 mm dia |
| 56 | 500 mm dia |
| 57 | Electrically Operated & SCADA Compatible class PN 1.6 |
| 58 | 80 mm dia |
| 59 | 200 mm dia |
| 60 | 250 mm dia |
| 61 | 300 mm dia |
| 62 | 350 mm dia |
| 63 | 400 mm dia |
| 64 | 450 mm dia |
| 65 | 500 mm dia |
| 66 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short body pattern type double eccentric Butterfly valves of approved make of following class & dia complete confirming to BS EN 593/ BS 5155/ IS 13095/1991 amendedup to date and of following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Face to face dimensions as per DIN 3202 F4/ IS 13095Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 67 | Class PN 1.0, Motorised Operated |
| 68 | 200 mm dia |
| 69 | 250 mm dia |
| 70 | 300 mm dia |
| 71 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) Swing type Non Return Valve of approved make of following Pressure rating & dia complete, generally confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Bonnet & disc of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG- 400/12 as per IS 1865 or equivalent grade as per IS : 3896-part2- 1985 and subsequent revisions, Face to face dimensions as per IS 5312 (part-1):2004 Drilled as per IS:1538. Electrostatic Epoxy Powder (EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body, cover and disc inside and outside. Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410, Hinge SS AISI 316/410 ,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 72 | Class PN 1.6 |
| 73 | 450 mm dia |
| 74 | Providing,lowering,aligning,fixinginpositionandJointinginpipe line, DI Body Flanged End Tamper proofKinetic Air Valve class PN 1.6 of approved makes of following pressure rating and dia and as perfollowingspecifications:Governingstandard-AWWAC512/ IS:14845:2000(amendeduptodate)Body,Highpressurecover, Low pressure cover, Cowl andJoint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush:Bronze,FlangesasperIS/BS,DrilledasperIS:1538. ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy(Non- Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fasteners -CS/Galvenisedsteel,Outletofbigorificewillhaveascreento prevent Tamper of float, with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amendedupto date) PN 1.6 ratings Valvesincludingall material, labour,testingandcommissioning as perTechnicalSpecificationsandasperdirectionofEngineerin charge. Note: Rates are exclusive of connecting tee, pipe piece and earth work |
| 75 | 40 mm dia |
| 76 | 50 mm dia |
| 77 | 80 mm dia |
| 78 | 100 mm dia |
| 79 | 150 mm dia |
| 80 | 200 mm dia |
| 81 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 410/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318-LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318-LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. Insertion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 82 | Inlet Pipe from Bisalpur |
| 83 | 250 mm dia |
| 84 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 85 | Class PN-1.0 |
| 86 | 80 mm dia |
| 87 | 100 mm dia |
| 88 | 150 mm dia |
| 89 | 200 mm dia |
| 90 | 250 mm dia. |
| 91 | 300 mm dia. |
| 92 | 350 mm dia. |
| 93 | 400 mm dia. |
| 94 | 450 mm dia. |
| 95 | 500 mm dia. |
| 96 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 97 | 250 mm dia. |
| 98 | 300 mm dia. |
| 99 | 450 mm dia. |
| 100 | 500 mm dia. |
| 101 | National Highway Crossing |
| 102 | Supply laying and pushing of MS casing pipe of specified thickness approved by concerned department authority by trenchless method adopting any suitable technology below ground at required depth under running traffic condition as per Highway/ Railway standard including carrying out survey work at the job site for determining underground cable trenches like telephone, cable, water & sanitary lines and resistivity test for finding the soil strata using necessary equipments for completion of works, mobilizing of machineries and specialized crew at the job site complete in all respect, including excavation of driven pit and exit pit (up to 3 meter depth) with proper protection at these sites with shoring sheets and ISMB. Providing MS cutting edges for front shield and constructing thrust bed at designated level. Necessary dewatering and providing concrete foundation at the base of the driven pit, PVC/Rubber saddle as per the requirement of Highway/Railway authority, crane for handing of pipe and any other machinery, tools, and tackles required, construction of temporary works as per design, drawing and method as per approved byauthority specification and the direction of the Engineer.Apply corrosion, resistant, protection on inside and outside of casing pipeas per technical specification. |
| 103 | 400 mm Dia 8 mm thick casing pipe . |
| 104 | 500 mm Dia 8 mm thick casing pipe . |
| 105 | 600 mm Dia 10 mm thick casing pipe . |
| 106 | Clear Water Reservoir |
| 107 | Construction of RCC (Flat Slab Rectangular) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: |
| 108 | a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approvalfromdepartment beforeconstruction.Submissionandapprovalofconcretemix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour andmaterialchargesincludingprovidingandfixingofaccessoriessuchasSSladder,SS manhole frame and covers, water levelindicator (floattype), SSventilator withSSscreen, float valve, puddle collars, G.I. pipe railing around walk way, Flat/Slab, rectangular .Staircase c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g)Providingandapplyingthreecoatsofcement-basedpaintontheremainingexternal surface area of the structure. |
| 109 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder fromroofslabtobottomSlab,insidecontainer.Providingandfixingwaterlevelindicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k) Providingandfixingof150mmwidewaterbarfortheconstructionjoints inthe container.l)ProvidingandfixingCI/DIpuddlecollarstheverticalwall for connecting inlet, outlet, overflow and washout pipes of the reservoir.m) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. |
| 110 | Rates for RCC Partially Underground type clear water reservoir SBC 10 T/sqm, SEISMIC ZONE-2 |
| 111 | 2400 KL capacity for Tilak Nagar Zone |
| 112 | Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 113 | 450 mm |
| 114 | Providing and making flanged joints to double flanged C.I./ D.I. pipes and specials such as tees, bends, tapers, caps etc. at all level/ depths within trenches complete including all material i.e. rubber insertions, bolts & nuts etc, labour, testing of joint, commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 115 | 450 mm dia |
| 116 | 600 mm dia |
| 117 | Pumping Machinery |
| 118 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover. |
| 119 | Providing, installation, testing and commissioning of Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, lass \"F\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, 415 volt +/- 10%, along with suitable foundation/installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 120 | 90 KW (For Tilak Nagar) |
| 121 | Providing, installation, testing and commissioning of submersible dewatering pump set conforming to relevant IS codes and as per scope of work and Technical Specifications, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft, impeller, pump and motor body. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply, with cable guard. The pump set shall be suitable for direct coupling, with suitable suction strainer etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 122 | 2.2 KW (3.0 HP) |
| 123 | Supply, delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Horizontal Centrifugal Split Casting pumps with motor as per IS 12615-2011 or amended up to date, CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts etc. complete with all respect as per the specification |
| 124 | Tilak Nagar Zone-2 |
| 125 | Discharge 71 to 80 LPS and head 41 to 50 M |
| 126 | Bapu Nagar |
| 127 | Discharge 41 t0 50 LPS and head 31 to 40 M |
| 128 | Discharge 121 to 140 LPS and head 41 to 50 M |
| 129 | Gandhi Nagar |
| 130 | Discharge 161 to 180 LPS and head 31 to 40 M |
| 131 | Discharge 41 t0 50 LPS and head 31 to 40 M |
| 132 | Jyoti Nagar |
| 133 | Discharge 51 to 60 LPS and head 41 to 50 M |
| 134 | Discharge 81 to 90 LPS and head 31 to 40 M |
| 135 | Discharge 101 to 120 LPS and head 31 to 40 M |
| 136 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to Modbus. |
| 137 | 90 KW |
| 138 | MS/DI Specials |
| 139 | Providing, lowering, laying, aligning, fixing in position and jointing at all level/ depths DI standard specials with rubber ring (EPDM)/ nut bolt and insertion sheet and jointing as per IS: 9523-2000 or as amended up to date, such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, taxes, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge (excluding earth work). |
| 140 | Upto 300mm dia |
| 141 | Above 300mm dia and upto 600mm dia |
| 142 | Providing and fixing of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 143 | MS pipe upto 600mm dia (with minimum 5mm thickness sheet) |
| 144 | MS pipe Avove 600mm dia (with minimum 6.3 mm thickness sheet) |
| 145 | ELECTRICAL WORKS |
| 146 | Providing and fixing in position lightening arrester set complete with 600mmx600mmx6mmthickG.I. earthingplate embeddedbelow groundinearthlingpitat3.5metrdepth,G.I.stripofsize 25mmx5mm thick from earthing plate to top of Over head tank, G.I. FinialmadeofGIbar25mmdiaand2mlongfixedontopofOH tankandconnectedtoGIstrip.Theearthlingsetshallcomplyof IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 147 | Pipe Ear thing as per IS: 3043 with perforated 3.0 Mtr. Long, 40 mm dia.‘B’classG.I.Pipeincludingallaccessorieslikenut,bolts, reducer,nipple,wiremeshedfunnel,andC.C.finishedchamber coveredwithhingedtypewithlockingarrangementC.I.Cover,C.I. Frame of size 300mm x 300 mm and embodying the pipe complete withalternatelayers salt and coke/charcoal, testing of earth resistance as required. |
| 148 | Plate Earthling as per IS:3043 with copper Earth plate of size 600mm x 600 mm x 3.0 mm by embodying 3 to 4 mtr. Belowthe ground level with 25 mm dia. G.I. ‘B’ class watering Pipe including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and C.C. finishedchamber covered withhinged type with locking arrangement C.I. Cover, C.I Frameof size 300mm x 300mm complete with alternate layers of saltand coke/charcoal, testing of earth resistance as required. |
| 149 | S & Laying following size ‘B’ Class G.I.Pipe confirming to IS: 1239 P-1 (1990) with accessories for laying earth conductor/ strip/ cable in ground/ surface/ recess as required. |
| 150 | 50 mm dia. |
| 151 | SupplyinganddrawingPVCinsulated&sheathedsolid/stranded copperconductormulticorecontrolcableISImarked(IS:1554)of 1.1kVgradeofapprovedmakeasperchapterE11, inexisting surfaceorrecessedconduit/casingcappingincludingmaking connections etc. as required. |
| 152 | 4 core, 1.5 sq. mm. armoured |
| 153 | 8 core, 1.5 sq. mm. armoured |
| 154 | 8 core, 2.5 sq. mm. armoured |
| 155 | SITC of Soft Starterswithpanel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electricalparameters, state of load &operating time, RS 485 serial link for connections to Modbus. |
| 156 | 30KW |
| 157 | 55KW |
| 158 | 75KW |
| 159 | 90KW |
| 160 | 110KW |
| 161 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kAbreakingcapacity(B/C/Dtrippingcharacteristicaspertypeof loadandsiterequirement)4KV impulsewithstandvoltage, ISI markedIS 8828(1996)/ conformingtoIEC60898-12002,IEC 60947-2,lowwattlosses,tripfreemechanisum, energylimiting of class 3 asperIEC, minimumphaseterminationcapacityof 35sq.mm. , conductor line load reversibility , IP 20 contact protection andfittedinexistingdistributionboard/sheets,minimumelectrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A&aboveratingincludingmakingconnections,testingetc.as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports & All as per pre approvedby Engineer in-charge. For additional technical parameters ofproduct / work refer Annexure \"A\" attached with this BSR |
| 162 | Double pole MCB(With B/C curve tripping Characteristics) , 6 A to 32 A rating |
| 163 | Triple pole MCB(With B/C curve trippingCharacteristics), 6 A to 32 A rating |
| 164 | 50/63 A rating |
| 165 | 125 A rating |
| 166 | Four pole MCB (With B/C curve tripping Characteristics), 6 A to 32 A rating |
| 167 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/free standing floor mounted dust andvermin proof compartmentalised cubical panel asspecificationsand Other parameters requiredas per point (a), (b), (c), (d, (e), (f), (g), (h) as below:- (a) ThicknessofCRCAsheetshallbe2.0mm,cablealley compartmentshavingconcealedhingedtypedoorswithkeytype lock with / withoutdetachable extension type structure. Removable 3mm.thicksheetsteelglandplateswithappropriatesizeof knockouts for cables shall be provided (b) completepanelshallundergoaprocessofdegreasing,Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panelhavingPEfoam/Neoprenerubbergasketofnotlessthan 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. (c) interconnectionbetweenbusbarandswitchgears/cableshall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried outwith1.5Sq.mm,Earthwirewith2.5Sq.mmandCTwith2.5 sq.mmflexiblecopperwireonly.Alljoints/interconnectionsof copper bus bar shall be dully tinned . Clearance between main bus barandrisers/metalpartsshallbeatleast10mmadditionalto widthofbusbarBusbarisinsulatedbyHeatShrinkablesleeves. Earth and Neutral bus bar shall be half of the size of phase bus bar. (CostofBusbar/FlexiblewireforInterconnectionbetweenMain connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f)FloormountedpanelshallbemountedonBaseframeofISMCchannel size 100 x 50 x 5 mm( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute)shallbemeasuredbetweenphases,betweenphaseand neutralandbetweenphaseandearth.bothbeforeandafterhigh voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to befabricatedonlyfromCPRIapprovedfabricatoronly(CPRITest certificates to be submitted)All as per preapproved byEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .busbar and Switchgearis to be Paid Extra ) (d)WiringbetweencomponentswithinswitchgearandIncoming/ outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted.Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads,studswithtwonutsandidentificationstripsandshallhave adequate continuous current rating. For tap-offs, adjacent terminals withshortingstripsshallbeused.10%Spareterminalblocksshall be provided. Wire identification on marking strip shall correspond to thedesignationofthewiringdiagrams.Allwireterminalsonthe equipmentshallalsobemarkedwithdesignationcorrespondingto those of the wiring diagram. (e)Allwiringshallbeenclosedinplasticchannelsandneatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee |
| 168 | SupplyingandfixingofAluminium(IEC60105ISO209-1,2)/ Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwithstandardshortcircuitwithstandcapacity,hightensilenuts and bolts spring washers in existing panel including bending , cutting inrequiredshapeandsizeandcolourcodingwithheatshrinkable PVCsleeves.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 169 | Electrolytic grade Aluminium bus bar 6010 grade |
| 170 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/Frequencymeter/KWHmeter/MultiFunctionMeter/ Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96mmincludingmakingconnectionbyPVCinsulatedcopper conductorwithPVCsleeves/channeletc.asrequired.Allasper preapprovedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,referAnnexure\"A\"attachedwith this BSR . |
| 171 | ThreephaseAMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
| 172 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW +KVA+KVAR+KVARH+KWH+DUALENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 |
| 173 | Providing&FixingofBISapprovedCurrentTransformerasper PWD specification for electrical Works ,ISI marked as perIS 2705-1992/conformingtoIEC60044-1,withsecondaryterminalofCT shallbebroughtoutsuitabletoaterminalblockwhichshallbe easieraccessiblefortestingandterminalconnection,withall necessarysupportinexistingpanelincludingconnectionetc.as requiredCurrenttransformerRingTypeTapeWound/ResinCast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified.ISF<=5,Cucrosssectionofsecondarywire1.5sqmm (minimum),includingallnecessarysupportinexistingpanel includingconnectionetc.asrequired.Allasperpreapprovedby Engineerin-charge.AllasperpreapprovedbyEngineerin-charge. Foradditionaltechnicalparametersofproducts/work,refer Annexure \"A\" attached with this BSR . |
| 174 | C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA |
| 175 | 10 AMP |
| 176 | 16AMP |
| 177 | Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947withintegralcircuit,IP65abovepanel&IP20terminal block,Approx.bodydiaforpanelnot lessthen20mm,lengthmin. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per preapprovedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 178 | Red/yellow/Blue |
| 179 | Red/Gree/ white Colour |
| 180 | Red/Gree/ white Colour |
| 181 | Red/Green |
| 182 | Providing&FixingofflushheadpushbuttonactuatorsIEC60947withintegralcircuit,IP65abovepanel&IP20terminalblock, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze forLed,PCBcontactsshallbeofbrass(tinplated),impulsedielectrictestedfor2.5KV,includingconnectionetc. asrequired.AllasperpreapprovedbyEngineerin-charge.Foradditional technicalparametersofproducts/work,refer Annexure\"A\" attached with this BSR |
| 183 | Non luminous type |
| 184 | Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 withonesideantiskidabberationmarksandpastingthe matwithsyntheticrubberadhesiveasrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 185 | 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) |
| 186 | Providing&FixingofselfhealingIP20MPPtypeshuntcapacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1&2inexistingpanelorparallelwithloadterminals,thecapacitor shallbefittedwithdischargeresistors,pressuresensitive disconnector(PSD)andshallhavedissipationfactorlessthan 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min overcurrentcapacity1.8timesratedcurrent&peakinrushcurrent min.300timesofratedcurrent,llifeexpectancygreaterthan 100000hrs(tempclass-25D)in440V/480VCapacitorandfor 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per preapprovedbyEngineerin-charge.Foradditionaltechnical parametersof products/ work,refer Annexure \"A\" attached with this BSR . |
| 187 | HeavydutyThreephase440V,50Hzcylindricaltypecapacitor (Bank) |
| 188 | Providing& Fixing of IP54 microprocessor based 3CT’s for all 3 phasesensingcompensationpowerfactorcorrectionrelaySize 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having3CTsensing,sensitivityupto50milliamp secondarycurrent,selfanalysingautoc/ksettingaccordingto targeted power factor setting, the relay shall have digit displayunit fordisplayofrealpowerfactor,targetedpowerfactor,lag/lead capacitorswitchingstatus,alarmoutputforundercurrent,over current, insufficient compensation, communication interface with RS 485,indication of switching onunits, auto/manual status, and shall haveoverloadprotection,novoltrelease,havingmultiparameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay includingmakingcoonectionwith1.5Sq.mmcopperwireetc.as required.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 189 | 6 to 8 stage |
| 190 | 12 to 14 stage |
| 191 | Providing&Fixingof440Volt3polecapacitor(AC6B)duty contactor with 3 no. early make and post break auxiliary contacts in serieswithquickdischargedampingresistors/reactorstolimitthe inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1:2000,insulationvoltage1000V,impulsewithstand voltage8 KV, Dinrailmounting type including makingconnections, testingetc. as required.suitableforfollowingcapacitycapacitor bank. All as per pre approved by Engineer in-charge. For additional technicalparametersofproducts/work,refer Annexure \"A\" attached with this BSR. |
| 192 | up to 6 KVAR |
| 193 | 10 KVAR |
| 194 | 15 KVAR |
| 195 | 25 KVAR |
| 196 | 50 KVAR |
| 197 | SITCof3/4polecurrentlimitingMouldedcasecircuitbreaker (MCCB)madeofflameretardent&heatresistantmaterialhaving followingcurrentrating,shortcircuitbreakingcapacityat440/415 V,50Hz;O/L&S/Csettings,conformingtoIS/IEC60947P-2 :2003withfrontfaceandcentralisedadjustable,tripfree mechanisum,truecontactpositionindicator,lineload interchangeability, designed for both horizontal&vertical mounting withoutanyadverseeffectonelectricalperformance,suitablefor operationupto55degreeandwithoutderatingupto40degree,pollution degree 3, having positive isolation capability, push(test) totrip,triptimelessthen10msunders/ccondition,Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock&rotaryhandle,includingmakingconnectionsetc.as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 198 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 199 | 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, |
| 200 | Extended Rotary Handle |
| 201 | Mechanical Interlocking kit |
| 202 | Auxiliary + Trip alarm contact |
| 203 | Spreaders for 400A, 4 Pole MCCB |
| 204 | Spreaders for 630A, 4 Pole MCCB |
| 205 | Providing&LayingP.V.C./XLPEinsulated&P.V.C.sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - Iof1.1KVwithH4-Gradeelectrolyticaluminiumconductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC /Hume/Stoneware/PVCpipe/openduct/cabletrench/Cable tray(withcabletie)includingtestingetc.asrequiredoffollowing size.OEMmusthaveit\"sowninhouseNABLaccrediated LaboratoryfortestingprocedureasperIS:10810.Foradditional technicalparametersofproduct/workreferAnnexure\"A\"attached with this BSR |
| 206 | 4.0 SQMM, 3 CORE |
| 207 | 6.0 SQMM, 4 CORE |
| 208 | 35 SQMM, 3 CORE |
| 209 | 70 SQMM, 3 CORE |
| 210 | 95 SQMM, 3.5 CORE |
| 211 | 120 SQMM,3.5 CORE |
| 212 | 150 SQMM, 3 CORE |
| 213 | 300 SQMM,3.5 CORE |
| 214 | 400 SQMM,3.5 CORE |
| 215 | Supply, Fabricating & installing following sizes of perforatedHot dipped Galvanizediron cable tray (Galvanizedthicknessnotless then 50 microns) with perforation not more then 17.5% in convenient sectionincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended fromtheceilingwithGIsuspendersincludingGIbolts&nuts, fastners,supportsetc.asrequired. Allasperpreapproved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 216 | 100mm x 50mm x 1.6mm |
| 217 | 150mm x 50mm x 1.6mm |
| 218 | 300mm x 50mm x 1.6mm |
| 219 | Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4-GradeelectrolyticaluminiumconductorconfirmingtoIS:8130 class-2ofpurity>99.6%,InsulationScreening:Extruded SemiconductingCompoundfollowedbyhelicallywrappedCopper Tape,round/flatstriparmouringofcables,Inner/outersheath PVCtypeST-2confirmingtoIS:5831inexistingRCC/Hume/ Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it\"s own in houseNABLaccrediatedLaboratoryfortestingprocedureasper IS:10810AllasperpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 220 | 3 core 95.0 Sq.mm |
| 221 | Providing & makingheat shrinkabletypeindoor/outdoor/ straight through terminations/ joint kitsuitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test reportshould be as per IS13573:2011whichcoveredallsequence fortable2forterminationkitandtable3forstreightthroughjoint inclusive thermal & dynamic short circuittest, humiditytest, soil fog test.CrosslinkingshallbedoneoutsidefactorywithE-beam/ peroxidetechnology.ExtrusionprocessshallbeinhouseOEM withinsamevicinity.includingtestingetc.asrequiredoffollowing sizes. All as per pre approved by Engineer in-charge. For additional technicalparametersofproducts/work,refer Annexure\"A\" attached with this BSR . |
| 222 | 3 core 50/70/95 Sq.mm |
| 223 | 3 core 50/70/95 Sq.mm |
| 224 | Supply&Layingfollowingsizeearthstripinhorizontalorvertical runinsurfacebymeansofEarthstripDMCInsulatorincluding riveting/soldering/welding,Jointingshallbedonebyoverlapping andwith2setofBrass(forCustrip) / GI(forGIStrip)nutbolt& springwasherspacedat50cmmakingconnectionetc.as required. AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 225 | 50mm x 6mm copper strip |
| 226 | 25mm x 6mm G.I. ( Hot Dipped) Strip |
| 227 | 32mm x6mm G.I. ( Hot Dipped) Strip |
| 228 | 50mm x 6mm G.I. ( Hot Dipped) Strip |
| 229 | SupplyanderectionofGalvanizedIronpolewith galvanizingdone insingledipping(AveragecoatingthicknessMinimum65Microns) continuouslytaperedpoleshavingOctagonal/Circularcross-sectionsdesignedtowithstandthemaximumwindspeedasperIS 875,Thepoleshaftshallbemadefromsheetsteel(HTSteel ConformingtogradeS355JO)andconfirmingtoBSEN10025and shall be continuously tapered with single longitudinal welding. There shallnotbeanycircumferentialwelding.Theweldingofpoleshaft shallbedonebySubmergedArcWelding(SAW)process.pole shaftsshallbeprovidedwiththerigidflangeplateofsuitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to thepoleshaftattwolocationsi.e.frominsideandoutside.The octagonalPolesshallhavelockabledoorofapproximate500mm length at the elevation of 500 mmfrom the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) insidethepoleatdooropeningforcableconnectionoffollowing lengthanddimensionaspertableP-01withbaseplateand foundationboltontheExistingcementconcretefoundation.Allas perpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure\"A\"attachedwith this BSR . |
| 230 | 7 Mtr., Poles with Octagonal Cross Section |
| 231 | SupplyandFixingofPoleOEMfabricatedhotdippedgalvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in-charge. Foradditionaltechnicalparametersofproducts/work, refer Annexure \"A\" attached with this BSR . |
| 232 | Single arm overhang |
| 233 | ProvidingandLayingRCCFoundationforOctagonal/Conical StreetLight poles, High mast Poles as per Drawingattach at TableP-4withFollowingProcedure&Allasperpreapprovedby Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . A)ExcavationofPitforFoundationSizeuptorequireddepthfrom Ground levelB)DressingofPitandDrystonepitching200mmthickincluding supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D)ReinforcementforR.C.C.workwithTMTbarsincluding straightening,cutting,bending,placinginpositionandbindingall complete.E)Centringandshutteringincludingstrutting,proppingetc.and removal of form work for Footing and Pedestal F)Providing&Fixingof2no.RequiredSizePLBHDPEPipe& Foundation Bolt with template as per OEM Recommendations.G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. |
| 234 | Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 235 | Providing&FixingofIK08IP-66protectedhighpowerLEDflood lightsystemwithsinglepiecePressurediecastaluminiumhousing, toughenedglassdiffuserwithsuitablelensesonLEDtoachieve variousbeamangles,ofhighpowerLEDof3to5watteach. Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate.TheSystemlevelLuminaireefficacy>=125lm/wt.LED driverInputVoltageAC120to270VACwithHighvoltageCutoff @>=300VACandAutoresettingSafety.PowerFactor>0.95, THD(I)<10%,drivercurrent<=750mA.drivershouldbePhaseto phaseprotectionof440Vfor4Hrs.ElectricalConnector,Surge ProtectionMin>=4KVinternaland10KVexternalbutinsidedriver compartment, System life of 50000 Burning hours with 70% of Initial Lumensmaintained,CRI>70andCCT5700K±355K.ManufacturesWordMark/Name Engraved/Embossing/ Screen printing on die cast housing to allow traceability/ authenticity. Fixture shallbeIS10322Complianced.OEMMusthaveitsowninhouse NABLlabsetupforalltestingfacilitiesfor LEDfixtures. (LM79/LM80) Certificate/report withliablewarrantyof product/ accessoriesfromOEMshallbesubmitted.Allasperpre approvedbyEngineerin-charge. Foradditionaltechnical parametersofproducts/ work, refer Annexure \"A\" attachedwith this BSR. |
| 236 | High Power LED Flood Light Minimum lumen output 10000 lm |
| 237 | Providing&FixingofIK08,IP66protectedLEDStreetLight Luminaireonexistingbracket/pole.Fixturemadeofpowdercoated singlepiecepressurediecastaluminummaterialwithheat dissipationfinsonhousingwithUVstabilizedPC(UVstablization reportsubmittedforUVcover)/ToughenedGlasscoverand secondarylensoneachLED&shouldbeSMDtypeof3to5watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with HighvoltageCutoff@>=300VACandAutoresettingSafety, Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. TheluminaireshallbeBIScertifiedandTrademarkcertified.Life ExpectancyEqualormorethan50000burninghrswithMinimum 70%lumenmaintened,CRI>70andCCT5700K+355K.Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside drivercompartment.drivershouldbePhasetophaseprotectionof 440Vfor4Hrs.ManufacturesWordMark/Name Engraved/Embossingondiecasthousingtoallow traceability/authenticity.FixtureshallbeASPERIS10322 Complianced.OEMMusthaveitsowninhouseNABLlabsetupfor alltestingfacilitiesforLEDfixtures. (LM79/LM80)Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 238 | LED Street Light fixture with Minimum lumen output 8700 lm |
| 239 | Providing&FixingofStreetlightbracketmadeoutfromfollowing size of \" B \" class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. asrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 240 | 32 mm Dia. |
| 241 | Providing & FixingofIP - 65 protected impact resistant polycarbonate / Polysterene enclosures withknock outforcable entry/out including fixing with nut, bolt, fatner etc as required complete in all respect of following sizes.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 242 | 180 x 180 x 91 mm |
| 243 | Supply,installation,testing&CommissioningofCopperwound distributionTransformeroffollowingratingand%Impedance, 11/0.433KVDelta-StarConnected,VectorGroupDyn11,ONAN Cooledlosses as per IS 1180 part I 2014 (Fourth Revision) Level-1, withboltlesscoredesignincludingstandardaccessorieslike conservatorwithprismaticoillevelgauge,silicagelbreather, Bucholz relay,pressed steel radiator fins, Radiator Valve(above 800 Kva)SuitablesizeHTcablebox,LTcableboxwithBusbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ),temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device,Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS:335-1953,EpoxyprimerandPUbasedpaintasTopcoat, Unidirectionalrollersforratingupto800kva&bi-directionalabove 800Kvarollerswithlockingarrangementetc.asrequired.The Transformershallbesubjectedtoroutinefactorytests(asper IS:2026 and IS:1180) including Temperature rise test inOEM\"s own lab shall be witnessed by Department engineer Physically. Transformer shall be tested from CTLof discombefore charging of transformer&completeinstallaionmustbecertifiedfromElectrical InspectorateofficeasperIndianElectricityrule,(CTLtesting chargesandElectricalInspectionchargesshallbereimbursedby the department to the contractor)Following tests shall be carried out oneachtransformeratsitebyOEMenginerinpresenceofdepartmentauthorisedrepresentative:-a)Ratiotestoneach tapping.b)Resistanceofwindingsatprincipalandalltapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per preapprovedbyEngineerin-charge. For additionaltechnical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 244 | 630 KVA with % Impedance 4.5 |
| 245 | SITCofstarratedAluminiumwounddistributionTransformerof followingrating11/0.433KVDelta-StarConnected,VectorGroup Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as per IS2026-1977&lossesasdefinedasper2014(FourthRevision) Level-1 . including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise inwinding/oil 35-40 degree C upto 200 KVA& 40-45 degree C forabove200KVA,ISImarkeddrainvalve,DialtypeTemperature gauge,firstfillingoftransformeroilasperIS:335-1953,Epoxy basedpaint,includingcarryingofpre-commissionTesting& Charging of Transformer complete in all respect . TheTransformershallbesubjectedtoroutinefactorytests(asper IS:2026 and IS:1180) including testing from CTLof discombefore charging of transformer & complete installaion must be certified from ElectricalInspectorateofficeasperIndianElectricityrule,(CTL testingchargesandElectricalInspectionchargesshallbe reimbursedbythedepartmenttothecontractor).Allasperpre approvedbyEngineerin-charge. Foradditionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 246 | 315 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 247 | 400 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 248 | Supply & InstallationofD.P.StructureWithAIRBREAKSWITCH having following specifications A, B, C, D, E. All as per pre approved byEngineerin-charge.Foradditionaltechnicalparametersof products/ work, refer Annexure \"A\" attached with this BSR . A)Doublepolestructureon2noISMB(Ibeam)of size150x75 mm, 10 mtrlengthusing7noMSchanneleachofsize100mmx 50mmx2500mmcompleteinallrespectwithnuts,springs washers, clamps as required. B)Offloadtypegangoperated3-poleverticalflutetypeswitch suitablefor11KV;400A,3-ø,centralpostrotatingdoublebreak isolator complete with MS hardware , copper moving & fixed contact ,assemblyof9nospininsulator,GIpipeofsuitablelengthfor operation.C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators D)3piecenonlinearresistortype.lightingarrestorofapproved makesuitablefor3wire,11kvOverheadlinewith ratedvoltageof 9kv rms & nominal discharge current rating of 5 ka & complete with galvanizedclampingarrangementGIbolts,nuts,washeretcas required. E)3no11kvACSRconductorsmountedonpintypeinsularorsas required.6.GENERAL: Thegoshallbeoperatedbyhandoperated liver properly earthed with provision for locking mounted at 3’ |
| 249 | SITCof11kV630Amps21KAfor3Sec.SF6insulated,outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU) manually operated in combination ofVCB modules andLoad Break switchconsistingofCopperbusbarinSF6insulated304(Non-FerriteNon-MagneticGrade)stainlesssteelenclosureofthickness 2.5mmwithmanometer.TheHVswitchgearandcontrolgear shouldbeconfirmingtoIEC-62271-100,IEC-62271-200-2003& IEC-60694-1996.TheRMUshouldbeinternalarctestedfor21KA for1SecondwithIAC-AFLclassificationforgastank.Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feederofRMUshouldhavevoltagepresenceindicator and compringoffollowings:-1no.microprocessorbasedSelfpowered numericalrelaywithoverCurrent/earthfault&shortcircuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden2.5VA,ratio50/1A,ClassofAccuracyclass5P10forO/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1nos.FaultPassageindicator,-Rightanglebootsforallthefeeder ModulesAllthetypetestcertificatesasperIECfromThirdpartyNABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation/SteelStructuretobepaidExtra)Allasperpre approvedbyEngineerin-charge. Foradditionaltechnical parametersofproducts/work,referAnnexure\"A\"attachedwith this BSR |
| 250 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 251 | SITCofHTmeteringcubicalpanelasapprovedByDISCOMs fabricatedout of18SWG CRCAsheet steelintwocompartment& MSangleofsize60mmX6mmhavingprovisionforFollowing: (i) ProvisionforfixingTrivector/Import-ExportMeter(Tobe supplied by DISCOMs)(ii)Provision for fixing of combined CT PT Set withCopperstripforConnection(TobesuppliedbyDISCOMs),(iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5/2.5 Sq.mm copper cable for interconnections, etc. as required.Allasperpreapprovedby Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR. |
| 252 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 253 | Heavy Duty AL & CU Lugs,Double Compression Cable Gland with Nickel Plated, Cable Tie, Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners, Clamps, Clips, Screw, Washers, Electrical Taps, HT Tap, Danger Plates, Condut Pipe, 40mmuPVC Pipe, 4.5 Kg. CO2 type portable fire extinguisher for Panel Room , Fire buckets with floor / wall mounting stand ect. required hardware & accessories for various sizes as per site requirements. |
| 254 | 11KV Switchyard Civil work for Transformers Foundations, DP Structure, Chain Link Fencying 1500mm Height, MS Gate , 40mm Gravels, boundary wall, Earthing Chambers, HT/LT cable Trench,coversect. |
| 255 | 433VAC LT Panel for DMA Remote locationsin cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3+1 Phase 433 voltages, 50Hz, neutrally grounded, IP 5X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The indoor Panel switchegears (MCB, CTs, Contactors, auxiliary contacts, Space heater and lighting, RDOL for electrically operated laves with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel. Outdoor Panels shall be self-fabricate type only with Canopy, PLC & SCADA Compitible, complete operation carried for max. nos RDOL, Size - 450*300*600 mm (for Electrically Operated Valve sin Remote) as per technical specifications and as directed by Engineer in charge. ( Prices are excluding EOV & EMF/BFM & fittings/ 3 Phase Power Connections at Remote locations ) |
| 256 | AUTOMATION & PLC-SCADA WORKS |
| 257 | Chlorine Analyser : Transmitter : Range: 0.05 to 20 ppm, Power Supply 230 VAC, Input: 2 Digital Sensors - one for chlorine and second for pH, Output: 4-20mA HART, IP66/67 Protection / Tx protection cover required / Sensor Range 0-14 pH , able to transmit digital signal to transmitter, calibration data can be transferred to Transmitter , process temp: 65 deg cen/ Sensor range:0.05 to 20 mg/l. |
| 258 | Providing,Installation,TestingandCommissioningofPressure Transmitter : Range:0-10Bar / Power Supply:24 V DC / Output: 4-20mAwithHART/Diaphragm:SS316L/ProcessConnection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 |
| 259 | Providing,installation,testingandcommissioningofDiaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass,Overrangeprotection:125%ofmaximumpressure,Material ofsensorandotherwettedparts:SStype316,Housingmaterial: Die cast aluminum |
| 260 | Providing, installation, testing and commissioning of Diaphragm type Pressure Switches Sensing Element: Bellows / Diaphragm, Material ofsensorandotherwettedparts:SStype316,Housing:Diecast aluminum,Switchtype:Microswitch,Repeatability:±1%ofspan, Switch Contacts: 2 NO + 2 NC |
| 261 | Providing,installation,testingandcommissioningofLevelSwitch( Conductivity)ConductivityProbes,Probeinsulation:Teflon,Probe head protection class: IP 65 of IS 13947 Part I, Probe head housing material: Aluminum |
| 262 | Rigid for lengths ofup to 3 Mtr. |
| 263 | Providing,installation,testingandcommissioningofONLINEUPS SYSTEM,SinglePhase230V,50Hzwith2hourbackupSMF battery bank as per specification |
| 264 | 1 KVA |
| 265 | Design,Manufacture, Supply, Installation, TestingandCommissioning of Indoor type PLC Panel of size approx. 800mm X 500 mm X 2000mm (LBH), Fabricated out ofmin. 2mm thickCRCAsheetcompletewithlatest configuration,necessary programming software for PLC & SCADA and comprising of all accessories not limited to the following:DI 30No.DO 26No.AI6No.AO 2No.MCB 16A DP 2No.MCB 6A DP6No.SMPS 100-240VAC/ 4.5A / 24 VDC 1 No. Selector Switch (Auto/Manual) & Local / Remote2No. Control Relays1LotAnnunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with1No.Electronic Hooter1No.Control Transformer 200VA 1 No. Emergency STOP Push Button1No. Panel Cooling Fan & Filter2No. Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC 3 No. Push Button 3 No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc1LotPanelHardware,lugs,terminations,ferruls, name plate Ect.1Lot UTILITY SOCET 16A, 3 PIN 2No.HMI Display 10 Inch, Colour1 No. Isolators Dual Output, 24VDC1Lot |
| 266 | Design,Manufacture,Supply,Installation, TestingandCommissioningofIndoortypePLC Panelofsizeapprox.800 mm X 500 mm X 2000mm(LBH), Fabricatedout ofmin. 2 mm thick CRCA sheetcomplete withlatest configuration,necessaryprogrammingsoftware forPLC&SCADAandcomprisingofall accessories not limited to the following:DI62No. DO 58No.AI 14No. AO 6 No. MCB 16A DP 2No. MCB 6A DP6No. SMPS 100-240VAC/ 4.5A / 24 VDC 1 No. Selector Switch (Auto/Manual) & Local / Remote2No. Control Relays1Lot Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with1No.Electronic Hooter1No. Control Transformer 200VA1No.Emergency STOP Push Button1No.Panel Cooling Fan & Filter2No.Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC3No. Push Button3No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc1LotPanelHardware,lugs,terminations,ferruls, name plate Ect.1Lot UTILITY SOCKET 16A, 3 PIN2No. HMI Display 10 Inch, Colour1No. Isolators Dual Output, 24VDC1Lot |
| 267 | Modular RTU complete with DI, DO, AI and modbus communication portsandpowersupply24VDCorforvariablepowersupplyusing batteries,rechargeablebatteries,solaror10.8VDCto28.8VDC with integrated modem; connection to control center via Tele Control Basic,DNP3,IEC60870-5-104andCommuncatinprotocols,on-board I/Os min. (8 DI, 4 DQ, 2 AI), configuration and diagnostics per (GSM/UMTS),MiniSIMcard,withadapterMicroSIMcardalso, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3,OpenVPN-Client.PanelEnclosureforCompactRTULocation, wall/floormountedalongwithwiringandrelatedaccessoriesand arrangementofmountingofRTU,ModemhavingIP-5XProtection. Panels shall be self-fabricate type only with Canopy. |
| 268 | SITCofIntelligentManageableEthernetSwitchesproviding24x 10/100/1000FastEthernetports-and2dualpurposeuplink (provisionforCopper/FibreGigaconnectivity)withLANbased Software.TheLANbasedS/Wsupportsenhancedintegrated security,includingNetworkAdmissionControl(NAC),advanced qualityofservice(QoS),availabilityandscalablemanagementto enable new converged applications |
| 269 | ProvidingandlayingStranded/FlexibleAnnealedeBarecopper conductor,XLPE/PVCinsulatedsuitablylaiduptogetheroverall polystertapedAl(innersheatedGISteelwireMylar/Drainwire) alongwithATCdrainwire,round/steelarmouredoverallPVC sheathed (ST-1) overall screenedCore armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 270 | 24 CORE, 1.0 sq. mm. |
| 271 | 4 CORE, 1.0 sq. mm. |
| 272 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (2 Pair * 0.75SQMM) |
| 273 | Quad-bandGPRS/IOT/VPN/GSM/CLOUD 3G/4G/5G modemwithEthernetbridge/router/ serial server (RS232/485) interface. |
| 274 | The Cloud based Water management & Data Monitoring system for the real time data analysis of the field instruments/pumps/valves/actuators located in the CPS / IPS/ any other field remote locations. 16 pump houses & the system working, a dedicated Cloud Server Instance will be provided with Database to store historical data of up to 5 years. The PLC system available in each pump house will send the data through Sim-based Modem to the Cloud at a time interval of 15 seconds. A Dashboard with all mentioned Locations will be created with an Overview of each Pump house & further the status of Pumps, running hours, status of valves, Tank Water Level, Pressure and all-important values will be displayed & stored in database.In total 3 users will be provided with the Monitoring Access of the system & 1 user will be provided with the Operation Access. A Daily/Weekly/Monthly Report Generation & download option will be provided with a standard predefined format. |
| 275 | Cloud based Water management & Data Monitoring systemDash Board (12 Months * 5 years) |
| 276 | Cloud based Water management & Data Monitoring system setup 5-year infrastructure Design & Development |
| 277 | Cloud based Water management & Data Monitoring systemmonthly Recurring Charges (12 Months * 5 years) |
| 278 | Instrumentation |
| 279 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU), Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC -50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 280 | EFM 80 mm |
| 281 | EFM 200 mm |
| 282 | EFM 250 mm |
| 283 | EFM 300 mm |
| 284 | EFM 400 mm |
| 285 | EFM 450 mm |
| 286 | EFM 500 mm |
| 287 | EFM 600 mm |
| 288 | Household Tap Connection |
| 289 | Providing Household Tap Connection as per technical specification and approved drawing as per relevant IS code (amended up to date) from uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using PP/MS saddle piece (Complete job).This job includes digging out suitable size of pits and trench for laying service line in all kinds of soil (excluding road); depositing and refilling of pit & jhiri with watering & ramming /compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting duly approved in accordance with specification for potable water including MS/PP saddle piece, gunmetal ferrule 4.0 mm , GM Full-way Valve (IS:778 Mark) or ball valve (min. weight 165 gm) and specials, below ground level 20 mm nominal dia MDPE pipe PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Three layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above ground level using 20 mm dia PPR-C pipe with standard PPR fittings/ 15 mm dia GI pipe with fittings in the premises for fixing a tap / meter box (excluding) , inc accessories with flushing, cleaning, disinfecting and testing of pipe line complete required for making of service connection complete in all respect including labour charges . The service line should be laid at least 45 cm below ground level.Note: Road cut and restoration is not part of this item and paid separately. |
| 290 | For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr. |
| 291 | Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be doneby using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge.. |
| 292 | Supply, Installation of 15 mm size AMI LoRa WAN/RF based Water Meters, conforming to ISO 4064:2005/ISI standards with MID/ISI approvalincluding Collection & Verification of Consumer Data, Automated Meter Reading in the identified DMAs of MC Jaipur Greater. |
| 293 | Civil Works |
| 294 | Construction of Panel Room on CWR at Tilak Nagar |
| 295 | Providing and fixing precast cement concrete coping 1 : 2 : 4 mix 50 mm thick complete as perspecification : |
| 296 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required ) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. M20 grade Nominal Mix / Design Mix |
| 297 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement for Beams, suspended floors, roofs, griders having lopes up to 15º, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases etc. M20 grade Nominal Mix / Design Mix |
| 298 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel propsand removal Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc.of formwork for upto floor five level for: |
| 299 | Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc. |
| 300 | Columns, pillars, posts and struts etc. |
| 301 | Arches, domes, vaults etc exceeding 6 Mtr span |
| 302 | Add extra for additional height in centring, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan are is to be measured) |
| 303 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor five level. (\"Original producers\" who manufacture billet directly from iron ores and roll the bilets to produce steel conforming to IS:1786) |
| 304 | Cold twisted deformed bars (IS : 1786). |
| 305 | Thermo-mechanically Treated bars (Conforming of relevent IS code) |
| 306 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : |
| 307 | Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 308 | Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 309 | Half brick masonry in Superstructure , above plinth level upto floor V level using bricks of designation 75; 5.8.2 Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 310 | Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades ceramic glazed vitrified tiles with water absortion less than or equal to 0.08% confirming to IS:13753 & IS : 15622 on walls, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar).Size 600mm x 1200mm |
| 311 | Providing & fixing door, window, chowkhats and other frames, including antitermite treatment, M.S. flat, hold fasts of size 250 x 40 x 3mm fixed with M.S. bolt 5mm dia 50mm long duly embedded in cement concrete M-15 grade :Nigeria teak wood Grade - I. |
| 312 | Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure \"A\" : 35 mm thick, commercial Veneer Both side. |
| 313 | Extra for providing external lipping with 2ndclass teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured); for door leaf shutt |
| 314 | Extra for providing other type of fittings as mention in annexure A ( as approved by EI) : Stainless steel fittings. (for door leaf shuter) |
| 315 | Providing and fixing bright finished Mortice lock of approved make Godrej or equivalent with pair of CP handles for doors with necessary screws etc complete (Best make of approved quality) as per direction of Engineer-in-charge. |
| 316 | Providing & Fixing mica of approved make for inner/outer side of shutters with fevicol & nails completeas per approved by engineer in charge.0.8mm thick mica |
| 317 | 9.19 Providing and fixing steel glazed doors windows and ventilator shutters of standard rolled steel section (IS 1038- 1983) joints mitred and welded with steel lugs 13x3mm, 10cm. long embedded in cement concrete block 15x10x10cm. of 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) or with wooden plugs and screws or rawl plugs and screws with fixing clips or with bolts and nuts as required including providing and fixing of plain glass panes 4mm thick with cooper glazing clips and special metal sash putty of approved make or metal beading with screws complete including priming coat of approval steel primer, excluding the cost of metal beading and other fitting except necessary hinges of pivots steel handles peg stay etc. as required |
| 318 | Windows side hung /Ventilators top or centre hung (openable) |
| 319 | Providing brass handles/peg stays and fittings in place of oxidized fitting Sqm. 5% |
| 320 | 5mm thick plain glass instead of 4mm thick plain glass Sqm. 95.00 |
| 321 | Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance. Sqm. 617.00 |
| 322 | Grading roof water proofing treatment with water profing compound: Cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 323 | Providing batta (gola) 75 mm x 75 mm in cement concrete (1 : 2 : 4) including finishing with cement mortar 1 : 3 as per standard design. |
| 324 | Plaster on new surface on walls in cement sand mortar 1:4 including racking of joint etc. complete fine finish : 20 mm thick |
| 325 | 6 mm cement plaster to ceiling of mix 1 : 3 (1 cement : 3 fine sand).; Celling plaster |
| 326 | Making grooves as per design in plaster 10 mm to 20 mm wide.; (add; 20 % R.M.of plaster work.) |
| 327 | Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth completeNew Plastered Surface (three or more coats) |
| 328 | Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade including all scaffolding: Two or more coats on new work including prepartion of base with primer, putty, lippy etc complete in all respect. |
| 329 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specifications including primer coat and protecting coat including scaffolding and safety provision. Trowel Finish av. thickness 2000 to 2500 microns. |
| 330 | 1.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 331 | Short point (up to 3 mtr.) |
| 332 | Medium point (up to 6 mtr.) |
| 333 | Long point (up to 10 mtr.) |
| 334 | 3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexiblecopper earth conductor 1.1 kV grade(IS:694) inrecessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket,Modular face plate with grid plate, screws, making connections, testingetc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E- 05 & E - 07 For additional technical p |
| 335 | On board |
| 336 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 337 | 20 mm |
| 338 | 25 mm |
| 339 | 4.2 Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor of alum. alloy braid in existing surface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 340 | Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TECspecification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair forIdentification etc. as required. For additional technical parameters ofproduct / work refer Annexure \"A\" attached with this BSR;4.3.4 4 pair |
| 341 | P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ;5.1.1 1.2 mm thick M. S. Sheet boxes ; |
| 342 | 100mm x 100mm x 60mm |
| 343 | 200mm x 250mm x 75mm |
| 344 | P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 345 | P & F 1.00mm thick M.S. Recessed concealed box, round of size 150 mm dia, depth 100 mm complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 346 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 347 | Single pole MCB (With B/C curve tripping Characteristics) |
| 348 | 6 A to 32 A rating |
| 349 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947- III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 35sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR;6.2.3 Four pole Isolator; 63 A rating |
| 350 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 351 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 352 | 6 Way (6+2) |
| 353 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial gradePolycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 354 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 355 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 356 | 6/16 A shuttered socket |
| 357 | 7.29 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ; 7.29.1 5 step fan regulator 2 Module 360 dgree rotating |
| 358 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 359 | Modular MCB 6 A to 32 A SP |
| 360 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 361 | 3 Module Each 86.0 |
| 362 | 6 Module Each 114.0 |
| 363 | 8 Module Each 155.0 |
| 364 | 12 Module Each 214.0 |
| 365 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 366 | 11.3 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 367 | 10.0 Sq. mm, 4 core4 core |
| 368 | Providing & Fixing of 1200 mm sweep BLDC technology power saving ceiling fan which can withstand on votage fluctuations from 140 volts to 240 volts ,power factor not less then 0.9 , service value (CMM/W) minimun 6.85, air delivery minimun 220 CMM, speed minimum 330 RPM ( tolerance as per IS:374 2019 ) THD less then 10% and complete with down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe up to 80 cm , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 15.4.1 Without Remote |
| 369 | 15.12 Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 300 mm sweep (900/1400 RPM) |
| 370 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 371 | 17.3.1 Recessed Mounting ;Minimum lumen output 650 lm |
| 372 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required.Gr I |
| 373 | 3x 1.5 sq.mm |
| 374 | 2 x 2.5 sq. mm. + 1x1.5sqmm ( All light and power Ckt) |
| 375 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (AC Ckt) |
| 376 | 4 x 10 sq.mm (Sub main) |
| 377 | 1 x 6 sq.mm (With sub main ) |
| 378 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 379 | For Class-AA loading |
| 380 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m-for pipe size-up to 100 mm |
| 381 | Sluice valve chamber of size 1.17m x 0.95m x1.47mfor pipe size-from 125-to-150mm |
| 382 | Sluice valve chamber of size 1.26m x1.185m x1.88m for pipe size-from 200-to-300mm |
| 383 | Sluice valve chamber of size 1.39m x1.43m x2.245mfor pipe size-from 350-to-450mm |
| 384 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm |
| 385 | For Class-A loading |
| 386 | Sluice valve chamber of size1.26m x1.185m x1.82mfor pipe size-from 200-to-300mm |
| 387 | For in-campus Valve Chambers |
| 388 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm (Shall be made as per GA Drawing and field Requirement) |
| 389 | Construction of RCC Air valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, Plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 390 | For Class-AA loading |
| 391 | Air valve chamber of size0.9m x1m x1.695mfor air valve size-from 50 mm-to-80mm |
| 392 | Air valve chamber of size1m x1.1m x1.945m for air valve size of 100mm |
| 393 | Air valve chamber of size1.05m x1.4m x2.42mfor air valve size of 150mm |
| 394 | Air valve chamber of size1.325m x1.7m x2.875m for air valve size of 200mm |
| 395 | For Class-A loading |
| 396 | Air valve chamber of size0.9m x1m x1.71mfor air valve size-from 50 mm-to-80mm |
| 397 | RTU Structure (20 nos), Repairing of OHSR (7 nos) and Pump House (3 nos) |
| 398 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed : All kinds of soil |
| 399 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. |
| 400 | M15 grade Nominal Mix 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20mm nominal size). |
| 401 | M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 402 | Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement.M20 grade Nominal Mix / Design Mix |
| 403 | Providing and laying in position Ready mix concrete manufactured in fullyautomatic Batching Plant andtransported to site intransit mixer for having continous agitated mixer, manufactured as per approved mix design of specified grade of RCC work including pumping of R.M.C. from transit mixer to site of laying , exculding the cost of centering, shuttering and reinforcement with all lead and lift including cost of admixtures in recommended portion as per IS 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer in charge. All works upto floor V floor M20 grade Design Mix by using cementas per codal provision. |
| 404 | Add extra for providing richer mixes respectively at all floor levels |
| 405 | Providing M-35 grade concrete by using cement as per codal provision instead of M-20 grade design mix. |
| 406 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc. |
| 407 | Half Brick work with mechanised autoclaved flyash lime bricks conforming to IS: 12894 :2002 of class designation 100 in superstructure above plinth level upto floor V level in.Cement mortar 1 : 4 (1 cement : 4 coarse sand) Sqm 586.00 |
| 408 | Random Rubble stone masonry with hard stone in superstructure aboveplinth level and upto five levelabove 30cm. thick walls in :Cement Mortar 1:4 ( 1-Cement : 4-Sand). |
| 409 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting (height upto 10 m) , fixing in position and applying a priming coat of approved steel primer all complete: |
| 410 | Supply and fixing in cement mortar welded hand railing made out of MS round or square bars, flats etc. for staircase or verandah as per design complete in all respect (wooden or PVC hand railing to be paid extra) with priming coat of red oxide. |
| 411 | Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide |
| 412 | Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : |
| 413 | 20mm thick |
| 414 | Painting exterior surface of Wall with 100% acrylic exterior paint of approved brand and manufacture to give an even shade with two or more coats including prepartion of base with sand papering, primer, putty, etc complete in all respect including scaffolding and safety provision |
| 415 | New Work |
| 416 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specificationsincluding primer coat and protecting coat including scaffolding and safety provisionRoller Finish av. thickness 400 to 500 microns.; / ESR & CWR PAINT WORK |
| 417 | Painting with syntheticenamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work.,Note:Pump & other railing works,door windows,including etc, |
| 418 | Painting (two or more coats) on rain water soil, waste and vent pipes and fitting with black anticorrosive bitumastic paint of approved brand and manufacture over and including a priming coat of ready mixed zinc chromate yellow primer on new work : |
| 419 | Lettering with black Japan paint of approved brand and manufacture. |
| 420 | Providing and laying bituminous macadam with hot mix plant using crushed aggregates ofgrading as perTable 500-7 premixed with bituminous binder transported to site with all leads laid over a previously prepared surface withpaver finisher to the required grade, level and alignment and rolled to achieve the desired compaction as per MoRTH Specification Clause 504. |
| 421 | Bitumen (VG-30) |
| 422 | SEAL COAT;-Providing and laying seal coat sealing the voids in a bituminous surface laid to the specified levels, grade and cross fall using Type A, Type B and Type C as per MoRTH Specification Clause 511 |
| 423 | Bitumen (VG-30) |
| 424 | Granular Sub-base with Well Graded Material (Table 400-1) |
| 425 | A). By Mix in Place Method |
| 426 | Construction of granular sub-base by providing well graded material,spreading in uniform layers with Tractor Mount Grade ronprepared surface,mixing by mixinplace method with rotavatoratOMC,and compacting with smooth wheel roller toachievethedesired density,complete as per MoRTH Specification Clause 401. |
| 427 | For Grading II Material |
| 428 | Water Bound Macadam with Crushable Screenings |
| 429 | WBM Grading 1 |
| 430 | Providing,laying,spreadingandcompactingstoneaggregatesof specific sizes to water bound macadam specificationincluding spreading in uniform thickness, hand packing, rolling with threewheel 80-100 kN static roller in stages to proper grade and camber, applying and brooming, crushable screening to fill-up the interstices of coarse aggregate, watering and compacting to the required density Grading 1 as per MoRTH Specification Clause 404. |
| 431 | Using Crusher Broken Aggregate |
| 432 | By Mechanical Means |
| 433 | Carriage of Materials by mechanical transport including loading, unloading and stacking ::Cost of carriage including loading, unloading & stacking for first 50 m. |
| 434 | Earth filling with available surplus soil excavated from foundations and taken only from outside of building plinth in layers not exceeding 20cm in depth, consolidating each deposited layer including ramming and watering and consolidation with lead up to 50 m and lift upto 1.5 m. |
| 435 | Providing and fixing of precast concrete interlocking tiles of desired shape of M 30 grade manufactured from fully computerized automatic stationery hydraulic vibrio pressed machine and fully computerized automatic batching plant of class A1/A2 as per BS 6717:2001. The CC interlocking paving blocks be laid on average 50mm. thick bed of coarse sand and the joint is to be filled with fine sand. Laying procedure on compacted sub-base as defined. Complete job is to be executed as per the instruction of Engineer incharge. The rates to be inclusive of all lead & Lifts etc. complete as per specifications. Tensile splitting strength, abrasion and braking load etc. as per BS 6717:2001, Grey cement |
| 436 | 100 mm thick |
| 437 | Crazy marble stone flooring including filling the gaps with light shade pigment with white cement marble powder mixture (3 parts of white cement : 1 part of marble powder) by weight in proportion of 4:7 (4 cement marble powder mix : 7 white, black or white and black marble chips of sizes from 1mm to 4mm nominal size by volume) and under layer 25mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size) rubbing, polishing and cement slurry etc. complete :30.16.1 18 mm thick crazy marble stone white, black or as specified. |
| 438 | O&M |
| 439 | Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency) as per Scope of Work & terms & conditions of contract for 5 year after defect liability period of one year DLP (except power feeder, IEC & miscellaneous provision) for Water Supply Project |
| 440 | 1st year |
| 441 | 2nd year |
| 442 | 3rd year |
| 443 | 4th year |
| 444 | 5th year |
| 445 | (A). SUB TOTAL OF DIVISION SOUTH-1 |
| 446 | (B). DIVISION SOUTH-2 |
| 447 | Pipeline |
| 448 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended upto date), with internal cement mortar lining for potable water with rubber ring (EPDM/SBR) joints as per IS: 5382-1985 (excluding special accessories) complete including all material, labour, hydraulic testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 449 | 100 mm |
| 450 | 150 mm |
| 451 | 200 mm |
| 452 | 250 mm |
| 453 | 300 mm |
| 454 | 350 mm |
| 455 | 400 mm |
| 456 | 450 mm |
| 457 | 500 mm |
| 458 | 600 mm |
| 459 | Providing, lowering, laying and jointing in trenches, standardlengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes, transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) .Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply may be in coil or straight length in 6 M/12 M. |
| 460 | HDPE PE-100 PN-6 |
| 461 | 110mm dia |
| 462 | Providing, lowering, laying and jointing in trenches, standardlengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by butt fusion/ electro fusion welding method, including all taxes, transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work). Note: Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply of pipe shall be in straight length in 6/12 M. |
| 463 | HDPE PE-100 PN-6 |
| 464 | 125mm dia |
| 465 | 140mm dia |
| 466 | 160mm dia |
| 467 | 180mm dia |
| 468 | Earth work in excavation by mechanical means (Hydraulic Excavator) / manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.: All kinds of soil |
| 469 | Add extra for over all depth of excavation above 1.5 m and upto 3.0 m over item no 4.1 |
| 470 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required |
| 471 | In ordinary rock. (10 %) |
| 472 | Dismantling of cement concrete pavement for pipe line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/ earth to complete the tasks as per technical specification and scope of work. |
| 473 | Dismantling of flexible pavement for pipe line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re_x0002_handling of material/earth to complete the tasks per technical specification and scope of work.. |
| 474 | Bituminous courses |
| 475 | Granular courses |
| 476 | P & F of Open timbering in trenches including strutting, shoring complete (measurements to be taken of the face area timbered). Depth exceeding 1.5 Mtr. but not exceeding 3 Mtr |
| 477 | Carriage of Materials by mechanical transport including loading,unloading and stacking ::Sand, bazri, ballast, kankar- Lead upto 5 Km |
| 478 | Barricading with Sal ballies as per design including tying with vertical post by coconut strings including digging out holes in all types of soil complete in all respect with two horizontal members height 1.2 m upto 1.5m above ground level and vertical supports upto 2.5 centre and upto 3 days period including removal and cleaning the site complete in all respect & including dressing of sides and providing retro reflective tapes for traffic safety as per direction of Engineer-in charge in all types of soil. |
| 479 | Valves |
| 480 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 481 | Manually operated class PN 1.0 |
| 482 | 350 mm with Gear |
| 483 | 450 mm with Gear |
| 484 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 485 | Motorized Sluice Valves with Electric Actuator with integral starter of Class PN 1.0 |
| 486 | Inlet Pipe at Bisalpur line |
| 487 | 250 mm dia |
| 488 | Providing, lowering, aligning, fixing in position in pipe line, CI double flanged Dual plate check valve of approved make of following Pressure rating & dia complete, as per API: 594/ API: 598 and of following specifications:Body & Cover of Grey cast iron ofIS:210/ FG200, Disc / plates - Cast steel ,Disc seal ring of EPDM/ NBR (food grade quality), Body seat of SS, Face to face dimensions as per API: 594 ,Flanges Drilled as per IS:1538. Epoxy (Non-Toxic & suitable for drinking water) applied on body & coverinside and outside. Shaft/Stop Pin of SS- AISI- 304/410, Hinge SS AISI 316/304 / CS, SpringSS AISI 316/304, Bonnet Gasket EPDM, Bush- Brass with EPDM/NBR \"O \"ring seal. Nut-Bolt confirming to IS:1363 and IS:1367 (galvanised steel), Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 489 | Class PN 1.0 |
| 490 | 200 mm dia |
| 491 | 250 mm dia |
| 492 | 300 mm dia |
| 493 | 350 mm dia |
| 494 | 400 mm dia |
| 495 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Double Acting Kinetic Air Valve with isolating Sluice Valve of approved makes for following pressure rating & dia complete, confirming to IS: 14845-2000 (amended up to date) and of following specifications: Body, Cover and Cowl - Grey Cast Iron as per IS:210- FG 200, Float -Stainless Steel AISI 304 / IS: 3444, Float Guide_x 0002_HBT1.HP Orifice- HTB2/ SS, Body seat ring - Leaded tin bronze/ SS .Seal ring and face ring-PDM/NBR, Ends flanged according to IS 6418,Fastners - CS, Epoxy paint inside outside of food grade safe for drinking water ,Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 496 | Class PN 1.0 |
| 497 | 50 mm dia |
| 498 | Providing, lowering, laying, aligning, fixing in position in pipe line, Resilient Seated D/F DI Sluice valves of approved make & design standard of following dia complete (including jointing & jointing material) including all material, labour, testing and commissioning along with pipe line as per Technical Specification & as per direction of Engineer. |
| 499 | Manually operated class PN 1.6 |
| 500 | 100 mm dia |
| 501 | 150 mm dia |
| 502 | 200 mm dia |
| 503 | 250 mm dia |
| 504 | 300 mm dia |
| 505 | 350mm dia |
| 506 | 400 mm dia |
| 507 | 450 mm dia |
| 508 | 500 mm dia |
| 509 | 600 mm dia |
| 510 | Electrically Operated & SCADA Compatible class PN 1.6 |
| 511 | 80 mm dia |
| 512 | 100 mm dia |
| 513 | 150 mm dia |
| 514 | 200 mm dia |
| 515 | 250 mm dia |
| 516 | 300 mm dia |
| 517 | 350 mm dia |
| 518 | 400 mm dia |
| 519 | 450 mm dia |
| 520 | 500 mm dia |
| 521 | 600 mm dia |
| 522 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short body pattern type double eccentric Butterfly valves of approved make of following class & dia complete confirming to BS EN 593/ BS 5155/ IS 13095/1991 amendedup to date and of following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Face to face dimensions as per DIN 3202 F4/ IS 13095Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 523 | Class PN 1.0, Motorised Operated |
| 524 | 200 mm dia |
| 525 | 250 mm dia |
| 526 | 300 mm dia |
| 527 | 350 mm dia |
| 528 | 400 mm dia |
| 529 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) Swing type Non Return Valve of approved make of following Pressure rating & dia complete, generally confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Bonnet & disc of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG- 400/12 as per IS 1865 or equivalent grade as per IS :3896-part2- 1985 and subsequent revisions, Face to face dimensions as per IS 5312 (part -1):2004 Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body, cover and disc inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410, Hinge SS AISI 316/410 ,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 530 | Class PN 1.6 |
| 531 | 450 mm dia |
| 532 | Providing, lowering, aligning, fixing in position in pipe line, DIdouble flanged resilient seated Dual plate check valve of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body and cover inside and outside .Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410 , Hinge SS AISI 316/304,SpringSS AISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick .Suitablesupport structure as per directions of EICincluding jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 533 | Class PN 1.6 |
| 534 | 350 mm dia |
| 535 | Providing,lowering,aligning,fixinginpositionandJointinginpipe line, DI Body Flanged End Tamper proofKinetic Air Valve class PN 1.6 of approved makes of following pressure rating and dia and as perfollowingspecifications:Governingstandard - AWWAC512/ IS:14845:2000 (amendeduptodate)Body,Highpressurecover, Low pressure cover, Cowl andJoint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush:Bronze,FlangesasperIS/BS,DrilledasperIS:1538. ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy(Non- Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fasteners -CS/Galvenisedsteel,Outletofbigorificewillhaveascreento prevent Tamper of float, with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amendedupto date) PN 1.6 ratings Valvesincludingall material, labour,testingandcommissioning as perTechnicalSpecificationsandasperdirectionofEngineerin charge. Note: Rates are exclusive of connecting tee, pipe piece and earth work |
| 536 | 40 mm dia |
| 537 | 50 mm dia |
| 538 | 80 mm dia |
| 539 | 100 mm dia |
| 540 | 150 mm dia |
| 541 | 200 mm dia |
| 542 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 410/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318-LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318-LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. Insertion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 543 | Plunger Type Flow Control Valve |
| 544 | 250 mm dia |
| 545 | 350mm dia |
| 546 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 547 | 100 mm dia PN-1.0 |
| 548 | 150 mm dia PN-1.0 |
| 549 | 200 mm dia PN-1.0 |
| 550 | 250 mm dia PN-1.0 |
| 551 | 300 mm dia PN-1.0 |
| 552 | 350 mm dia. |
| 553 | 450 mm dia. |
| 554 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 555 | 250 mm dia. |
| 556 | 300 mm dia. |
| 557 | 350 mm dia. |
| 558 | 400 mm dia. |
| 559 | 450 mm dia. |
| 560 | 500 mm dia. |
| 561 | 600 mm dia. |
| 562 | Clear Water Reservoir |
| 563 | Construction of RCC (Flat Slab Rectangular) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: |
| 564 | a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approvalfromdepartment beforeconstruction.Submissionandapprovalofconcretemix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour andmaterialchargesincludingprovidingandfixingofaccessoriessuchasSSladder,SS manhole frame and covers, water levelindicator (floattype), SSventilator withSSscreen, float valve, puddle collars, G.I. pipe railing around walk way, Flat/Slab, rectangular .Staircase c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab. |
| 565 | g)Providingandapplyingthreecoatsofcement-basedpaintontheremainingexternal surface area of the structure.h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder fromroofslabtobottomSlab,insidecontainer.Providingandfixingwaterlevelindicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k) Providingandfixingof150mmwidewaterbarfortheconstructionjoints inthe container.l)ProvidingandfixingCI/DIpuddlecollarstheverticalwallforconnectinginlet,outlet, overflow and washout pipes of the reservoir.m)Inlet,outlet,overflow,washoutpipesandvalvesarenotincludedinthiswork, provision for the same shall be taken separately. |
| 566 | Rates for RCC Partially Underground type clear water reservoir SBC 10 T/sqm, SEISMIC ZONE-2 |
| 567 | 1500 KL capacity at Vidhyut Nagar Campus for Vaishali Block-E |
| 568 | 2000 KL capacity for Officer Campus |
| 569 | 2300 KL capacity for Vaisali Nagar A Block |
| 570 | 2800 KL capacity for Triveni Nagar |
| 571 | Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work |
| 572 | 200 mm |
| 573 | 300 mm |
| 574 | 350 mm |
| 575 | 400 mm |
| 576 | 450 mm |
| 577 | Providing and making flanged joints to double flanged C.I./ D.I. pipes and specials such as tees, bends, tapers, caps etc. at all level/depths within trenches complete including all material i.e. rubber insertions, bolts & nuts etc, labour, testing of joint, commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 578 | 450 mm dia |
| 579 | Pumping Machinery |
| 580 | Providing, installation, testing and commissioning of Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, lass \"F\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, 415 volt +/- 10%, along with suitable foundation/installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 581 | 45 KW (For Triveni Nagar and Officer Campus) |
| 582 | 110 KW (For 10B & Vaishali Nagar Block-A) |
| 583 | 125 KW (For Vidhyut Nagar HW- Vaishali Nagar E Block) |
| 584 | Providing, installation, testing and commissioning of submersible dewatering pump set conforming to relevant IS codes and as per scope of work and Technical Specifications, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft, impeller, pump and motor body. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply, with cable guard. The pump set shall be suitable for direct coupling, with suitable suction strainer etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 585 | 2.2 KW (3.0 HP) |
| 586 | Supply, delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Horizontal Centrifugal Split Casting pumps with motor as per IS 12615-2011 or amended up to date, CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts etc. complete with all respect as per the specification |
| 587 | Mahesh Nagar Pumping Station |
| 588 | Discharge 161 to 180 LPS and head 41 to 50 M |
| 589 | Discharge 141 to 160 LPS and head 41 to 50 M |
| 590 | Discharge 121 to 140 LPS and head 41 to 50 M |
| 591 | Chitrkoot Pump House |
| 592 | Discharge 81 to 90 LPS and head 31 to 40 M |
| 593 | Vidhyut Nagar / Guru Jambeswar Nagar (Girnar Colony |
| 594 | Discharge 141 to 160 LPS and head 41 to 50 M |
| 595 | Discharge 101 to 120 LPS and head 31 to 40 M |
| 596 | Vaishali Nagar A Block |
| 597 | Discharge 71 to 80 LPS and head 31 to 40 M |
| 598 | Vaishali Nagar E Block |
| 599 | Discharge 141 to 160 LPS and head 20 to 30 M |
| 600 | Discharge 121 to 140 LPS and head 31 to 40 M |
| 601 | Officer Campus |
| 602 | Discharge 91 to 1000 LPS and head 20 to 30 M |
| 603 | Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at synchronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts, Cement concrete foundation etc. complete with all respect as per the specification and scope of work and direction of Engineer in Charge of following range of duty conditions.Note: Duty condition of required pump shall also be mentioned in BoQ. |
| 604 | Discharge 221 to 240 LPS and head 31 to 40 M |
| 605 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover. |
| 606 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to Modbus. |
| 607 | 45 KW |
| 608 | 110 KW |
| 609 | 132 KW |
| 610 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rolled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 611 | 2 MT Capacity |
| 612 | Span 7 M and Lift 6 M |
| 613 | MS/DI Specials |
| 614 | Providing, lowering, laying, aligning, fixing in position and jointing at all level/ depths DI standard specials with rubber ring (EPDM)/ nut bolt and insertion sheet and jointing as per IS: 9523-2000 or as amended up to date, such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, taxes, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge (excluding earth work). |
| 615 | Upto 300mm dia |
| 616 | Above 300mm dia and upto 600mm dia |
| 617 | Providing and fixing of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 618 | MS pipe upto 600mm dia (with minimum 5mm thickness sheet) |
| 619 | MS pipe Avove 600mm dia (with minimum 6.3 mm thickness sheet) |
| 620 | ELECTRICAL WORKS |
| 621 | Providing and fixing in position lightening arrester set complete with 600mmx600mmx6mmthickG.I. earthingplate embeddedbelow groundinearthlingpitat3.5metrdepth,G.I.stripofsize 25mmx5mm thick from earthing plate to top of Over head tank, G.I. FinialmadeofGIbar25mmdiaand2mlongfixedontopofOH tankandconnectedtoGIstrip.Theearthlingsetshallcomplyof IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 622 | P/Laying P.V.C/XLPE insulated & P.V.C sheathed cable of 1.1 KV grade with Copper conductor of IS: 1554 P-I/IS: 7098 P-I in ground as per IS: 1255 including excavation of 30cm x 75cm size trench, 25cm thick under layer of sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 623 | 2.5 sqmm. Armored 4 core |
| 624 | 1.5 Sq.mm Armoured 6 Core |
| 625 | Pipe Ear thing as per IS: 3043 with perforated 3.0 Mtr. Long, 40 mm dia.‘B’classG.I.Pipeincludingallaccessorieslikenut,bolts, reducer,nipple,wiremeshedfunnel,andC.C.finishedchamber coveredwithhingedtypewithlockingarrangementC.I.Cover,C.I. Frame of size 300mm x 300 mm and embodying the pipe complete withalternatelayerssaltandcoke/charcoal,testingofearth resistance as required. |
| 626 | PlateEarthlingasperIS:3043withcopperEarthplateofsize 600mmx600mmx3.0mmbyembodying3to4mtr.Belowthe ground level with 25 mm dia. G.I. ‘B’ class watering Pipe including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and C.C.finishedchambercoveredwithhingedtypewithlocking arrangementC.I.Cover,C.IFrame of size 300mm x 300 mm complete with alternatelayers of salt and coke/charcoal, testing of earth resistance as required. |
| 627 | S & Laying following size ‘B’ Class G.I.Pipe confirming to IS: 1239 P-1 (1990) with accessories for laying earth conductor/ strip/ cable in ground/ surface/ recess as required. |
| 628 | 50 mm dia. |
| 629 | SupplyinganddrawingPVCinsulated&sheathedsolid/stranded copperconductormulticorecontrolcableISImarked(IS:1554)of 1.1kVgradeofapprovedmakeasperchapterE11,inexisting surfaceorrecessedconduit/casingcappingincludingmaking connections etc. as required. |
| 630 | 4 core, 1.5 sq. mm. armoured |
| 631 | 8 core, 1.5 sq. mm. armoured |
| 632 | 8 core, 2.5 sq. mm. armoured |
| 633 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 634 | 45 KW |
| 635 | 55 KW |
| 636 | 75 KW |
| 637 | 90 KW |
| 638 | 110 KW |
| 639 | 160 KW |
| 640 | SITCofIntelligentManageableEthernetSwitchesproviding24x 10/100/1000FastEthernetports-and2dualpurposeuplink (provisionforCopper/FibreGigaconnectivity)withLANbased Software.TheLANbasedS/Wsupportsenhancedintegrated security,includingNetworkAdmissionControl(NAC),advanced qualityofservice(QoS),availabilityandscalablemanagementto enable new converged applications |
| 641 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kAbreakingcapacity(B/C/Dtrippingcharacteristicaspertypeof loadandsiterequirement)4KVimpulsewithstandvoltage,ISI markedIS8828(1996)/conformingtoIEC60898-12002,IEC 60947-2,lowwattlosses,tripfreemechanisum, energylimitingofclass3asperIEC,minimumphaseterminationcapacityof 35sq.mm. , conductor line load reversibility , IP 20 contact protection andfittedinexistingdistributionboard/sheets,minimumelectrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A&aboveratingincludingmakingconnections,testingetc.as required. OEM shall have submitNABL / CPRI / ERDA accrediated labtypetestreports&AllasperpreapprovedbyEngineerin-charge.Foradditionaltechnicalparametersofproduct/workrefer Annexure \"A\" attached with this BSR |
| 642 | Triple pole MCB (With B/C curve tripping Characteristics), 6 A to 32 A rating |
| 643 | 50/63 A rating |
| 644 | 125 A rating |
| 645 | Four pole MCB (With B/C curve tripping Characteristics), 6 A to 32 A rating |
| 646 | Double pole MCB (With B/C curve tripping Characteristics) , 6 A to 32 A rating |
| 647 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/freestandingfloormounteddustandverminproof compartmentalisedcubical panel as specifications and Other parameters required as per point (a), (b), (c),(d, (e), (f), (g), (h) as below:- (a) ThicknessofCRCAsheetshallbe2.0mm,cablealley compartmentshavingconcealedhingedtypedoorswithkeytype lock with / withoutdetachable extension type structure. Removable 3mm.thicksheetsteelglandplateswithappropriatesizeof knockouts for cables shall be provided (b) completepanelshallundergoaprocessofdegreasing,Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panelhavingPEfoam/Neoprenerubbergasketofnotlessthan 3mm thickness ,required hardware, concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. [c) Interconnectionbetweenbusbarandswitchgears/cableshall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried outwith1.5Sq.mm,Earthwirewith2.5Sq.mmandCTwith2.5 sq.mmflexiblecopperwireonly.Alljoints/interconnectionsof copper bus bar shall be dully tinned . Clearance between main bus barandrisers/metalpartsshallbeatleast10mmadditionalto widthofbusbarBusbarisinsulatedbyHeatShrinkablesleeves. Earth and Neutral bus bar shall be half of the size of phase bus bar. (CostofBusbar/FlexiblewireforInterconnectionbetweenMain connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 648 | (d) Wiring between components within switchgear andIncoming /outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identificationstripsandshallhave adequate continuous current rating. For tap-offs, adjacent terminals withshortingstripsshall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to thedesignationofthewiringdiagrams.Allwireterminalsonthe equipmentshallalsobemarkedwithdesignationcorrespondingto those of the wiring diagram.(e) Allwiringshallbeenclosedinplasticchannelsandneatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee busbar and Switchgearis to be Paid Extra)(f) FloormountedpanelshallbemountedonBaseframeofISMC channel size 100 x 50 x 5 mm (to be paid Extra) (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute)shallbemeasuredbetweenphases,betweenphaseand neutralandbetweenphaseandearth.bothbeforeandafterhigh voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.(h) only outer surface area on all sides shall be measured & panel to befabricatedonlyfromCPRIapprovedfabricatoronly(CPRITest certificates to be submitted)All as per preapproved byEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 649 | SupplyingandfixingofAluminium(IEC60105ISO209-1,2)/ Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwithstandardshortcircuitwithstandcapacity,hightensilenuts and bolts spring washers in existing panel including bending , cutting inrequiredshapeandsizeandcolourcodingwithheatshrinkable PVCsleeves. All as per preapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR. |
| 650 | Electrolytic grade Aluminium bus bar 6010 grade |
| 651 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/Frequencymeter/KWHmeter/MultiFunctionMeter/ Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96mmincludingmakingconnectionbyPVCinsulatedcopper conductorwithPVC sleeves / channel etc. as required. All as per preapproved by Engineer in-charge. For additionaltechnical parameters of products/work, refer Annexure \"A\" attachedwith this BSR . |
| 652 | ThreephaseAMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
| 653 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW +KVA+KVAR+KVARH+KWH+DUALENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 |
| 654 | Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works, ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondaryterminal ofCT shallbebroughtoutsuitable to a terminal block which shall be easier accessiblefortestingandterminalconnection, withall necessarysupportinexistingpanelincludingconnectionetc.as requiredCurrenttransformerRingTypeTapeWound/ResinCast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified.ISF<=5, Cu cross sectionofsecondary wire 1.5sqmm (minimum), includingallnecessarysupportinexistingpanel includingconnectionetc. asrequired. All as perpreapprovedby Engineerin-charge. All as per pre approvedbyEngineerin-charge. Foradditionaltechnicalparametersofproducts/work,refer Annexure \"A\" attached with this BSR . |
| 655 | C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA |
| 656 | C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA |
| 657 | Providing & Fixing ofCam operated rotary (Auto/manual) switches onexistingpanelwith2wayandoffpositionusinghighgrade engineeringmaterialtointernationalstandardswithcamassemblyinsulationofglassfilledpolyamidewithhightrackingindex.For reliable and stable electrical and mechanical endurance double butt contactswithsilverbi-metaloncoppershouldprovidedcontact assemblyis of operating temp range-25 degree C to55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanicallyminimum50000operations@300cycles/hourand electrically10,000operationsat100%rateddutyfor100cycles/ hourincludingmakingconnectionetc. asrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 658 | 10 AMP |
| 659 | 16AMP |
| 660 | Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947withintegralcircuit,IP65abovepanel&IP20terminal block,Approx.bodydiaforpanelnot lessthen20mm,lengthmin. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approvedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,referAnnexure\"A\"attachedwith this BSR . |
| 661 | Red/yellow/Blue |
| 662 | Red/Gree/ white Colour |
| 663 | Red/Gree/ white Colour |
| 664 | Red/Green |
| 665 | Providing&FixingofflushheadpushbuttonactuatorsIEC60947withintegralcircuit,IP65abovepanel&IP20terminalblock, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze forLed,PCBcontactsshallbe ofbrass (tin plated), impulse dielectric tested for 2.5 KV, including connection etc. as required. All as per pre approved byEngineer in-charge.Foradditional technicalparametersofproducts/work,refer Annexure\"A\" attached with this BSR |
| 666 | Non luminous type |
| 667 | Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 withonesideantiskidabberationmarksandpastingthe matwithsyntheticrubberadhesiveasrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 668 | 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) |
| 669 | Providing&FixingofselfhealingIP20MPPtypeshuntcapacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1&2inexistingpanelorparallelwithloadterminals,thecapacitor shallbefittedwithdischargeresistors,pressuresensitive disconnector(PSD)andshallhavedissipationfactorlessthan 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min overcurrentcapacity1.8 times rated current & peak inrush current min. 300 times ofrated current,llifeexpectancygreater than 100000hrs (tempclass- 25 D) in 440 V/480 V Capacitorandfor 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per preapprovedbyEngineerin-charge. For additionaltechnical parametersofproducts/work, refer Annexure \"A\"attachedwith this BSR . |
| 670 | HeavydutyThreephase440V,50Hzcylindricaltypecapacitor (Bank) |
| 671 | Heavy duty Three phase 480 V , 50 Hz cylindrical type capacitor capacitor (Bank) |
| 672 | Providing& Fixing of IP54 microprocessor based 3CT’s for all 3 phasesensingcompensationpowerfactorcorrectionrelaySize 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having3CTsensing,sensitivityupto50milliamp secondarycurrent,selfanalysingautoc/ksettingaccordingto targeted power factor setting, the relay shall have digit displayunit fordisplayofrealpowerfactor,targetedpowerfactor,lag/lead capacitorswitchingstatus,alarmoutputforundercurrent,over current, insufficient compensation, communication interface with RS 485,indication of switching onunits, auto/manual status, and shall haveoverloadprotection,novoltrelease,havingmultiparameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay includingmakingcoonectionwith1.5Sq.mmcopperwireetc.as required.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 673 | 6 to 8 stage |
| 674 | 12 to 14 stage |
| 675 | Providing&Fixingof440Volt3polecapacitor(AC6B)duty contactor with 3 no. early make and post break auxiliary contacts in serieswithquickdischargedampingresistors/reactorstolimitthe inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1:2000,insulationvoltage1000V,impulsewithstand voltage8KV,Dinrailmountingtypeincludingmakingconnections, testingetc.asrequired.suitableforfollowingcapacitycapacitor bank. All as per pre approved by Engineer in-charge. For additional technicalparameters ofproducts/work, refer Annexure \"A\" attached with this BSR. |
| 676 | up to 6 KVAR |
| 677 | 10 KVAR |
| 678 | 15 KVAR |
| 679 | 25 KVAR |
| 680 | 50 KVAR |
| 681 | SITCofDrawouttype3/4poledoorinterlockAirCircuitBreaker (ACB)asconformingtoIS/IEC60947P-2:2003inexistingLT panel suitable for LT installation 440 V, 50 Hz and having adjustable overloadshort-circuit,Instantaneous, earthfault(LSIG) with separate LED indication for each type of fault shall confirm to EMI/ EMC test, LCD/LED display, last 10 trip history, provisionofZSI, Communication, Power metering module, Thermal memory , trip free mechanisum,suitableforambient50degreeandutilization catagaryB. Inbuiltelectrical & mechanical anti pumping feature, 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw (1 sec), U imp-12 KV, break time not more then 25 ms. Provision forelectrical&mechanicalinterlockbetweenACBs, Min.electricaloperation 10000 upto 2000 A ratingand 5,000 for 2500 A to 4000 A. includingmakingconnections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineerin-charge.Foradditionaltechnicalparametersofproduct/ work refer Annexure \"A\" attached with this BSR |
| 682 | 630/800 A Rating ,50 kA |
| 683 | 1600 A Rating ,50 kA |
| 684 | SupplyandfixingoffollowingaccessoriesforAircircuitbreaker (ACB)compatiblewithMAinACBOEMasperPWDspecification forelectricalWorks,conformingtoIS/IEC60947 P-2 :2003 includingmakingconnectionetccompleteinallrespect.OEMshall have submit NABL / CPRI / ERDA accrediated labtypetest certificate before execution. All as per pre approved by Engineer in-charge. For additionaltechnicalparametersofproducts/ work, refer Annexure \"A\" attached with this BSR . |
| 685 | Shunt Trip Release |
| 686 | Under voltage Release |
| 687 | Microswitch for Indication |
| 688 | Operation Counter |
| 689 | Door Interlock |
| 690 | Auxiliary Contact 4 NO + 4 NC |
| 691 | Breaker Control Switch (TNC) |
| 692 | SITC of 3/4 pole current limiting Moulded case circuitbreaker (MCCB) made of flameretardent & heat resistantmaterial having followingcurrentrating,shortcircuitbreakingcapacity at 440/415 V, 50 Hz; O/L & S/C settings, conforming to IS/IEC 60947 P-2 :2003 with front face and centralised adjustable, trip free mechanisum,truecontactpositionindicator, lineload interchangeability, designed for both horizontal&vertical mounting withoutanyadverseeffectonelectricalperformance,suitablefor operationupto55degreeandwithoutderatingupto40degree,pollution degree 3, having positive isolation capability, push(test) totrip,triptimelessthen10msunders/ccondition,Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock&rotaryhandle,includingmakingconnectionsetc.as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 693 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 694 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 695 | 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, |
| 696 | Extended Rotary Handle |
| 697 | Mechanical Interlocking kit |
| 698 | Auxiliary + Trip alarm contact |
| 699 | Spreaders for 250A, 4 Pole MCCB |
| 700 | Spreaders for 400A, 4 Pole MCCB |
| 701 | Spreaders for 630A, 4 Pole MCCB |
| 702 | Providing&LayingP.V.C./XLPEinsulated&P.V.C.sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - Iof1.1KVwithH4-Gradeelectrolyticaluminiumconductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC /Hume/Stoneware/PVCpipe/openduct/cabletrench/Cable tray(withcabletie)includingtestingetc.asrequiredoffollowing size.OEMmusthaveit\"sowninhouseNABLaccrediated LaboratoryfortestingprocedureasperIS:10810.Foradditional technicalparametersofproduct/workreferAnnexure\"A\"attached with this BSR |
| 703 | 400 SQMM,3.5 CORE |
| 704 | 300 SQMM,3.5 CORE |
| 705 | 120 SQMM,3.5 CORE |
| 706 | 185 SQMM, 3 CORE |
| 707 | 150 SQMM, 3 CORE |
| 708 | 120 SQMM, 3 CORE |
| 709 | 95 SQMM, 3 CORE |
| 710 | 70 SQMM, 3 CORE |
| 711 | 50 SQMM, 3 CORE |
| 712 | 6.0 SQMM, 4 CORE |
| 713 | 4.0 SQMM, 3 CORE |
| 714 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 715 | 3 Core |
| 716 | 25.0 Sq. mm |
| 717 | 35.0 Sq. mm |
| 718 | 50.0 Sq. mm |
| 719 | Supply,Fabricating&installingfollowingsizesofperforatedHot dippedGalvanizedironcabletray(Galvanizedthicknessnotless then 50 microns) with perforation not more then 17.5% in convenient sectionincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended fromtheceilingwithGIsuspendersincludingGIbolts&nuts, fastners,supportsetc.asrequired.Allasperpreapprovedby Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 720 | 100mm x 50mm x 1.6mm |
| 721 | 150mm x 50mm x 1.6mm |
| 722 | 300mm x 50mm x 1.6mm |
| 723 | Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4-GradeelectrolyticaluminiumconductorconfirmingtoIS:8130 class-2ofpurity>99.6%,InsulationScreening:Extruded SemiconductingCompoundfollowedbyhelicallywrappedCopper Tape,round/flatstriparmouringofcables,Inner/outersheath PVCtypeST-2confirmingtoIS:5831inexistingRCC/Hume/ Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it\"s own in houseNABLaccrediatedLaboratoryfortestingprocedureasper IS:10810AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 724 | 3 core 95.0 Sq.mm |
| 725 | Providing & making heat shrinkable type indoor/outdoor/ straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test reportshouldbeasperIS13573:2011whichcoveredallsequence fortable2forterminationkitandtable3forstreightthroughjoint inclusive thermal & dynamic short circuittest, humidity test, soil fog test. Cross linkingshall bedoneoutsidefactorywithE- beam/ peroxidetechnology.ExtrusionprocessshallbeinhouseOEM withinsamevicinity.including testingetc.asrequiredoffollowing sizes. All as per pre approved by Engineer in-charge. For additional technicalparametersofproducts/ work, refer Annexure \"A\" attached with this BSR . |
| 726 | 3 core 50/70/95 Sq.mm |
| 727 | 3 core 50/70/95 Sq.mm |
| 728 | Supply&Layingfollowingsizeearthstripinhorizontalorvertical runinsurfacebymeansofEarthstripDMCInsulatorincluding riveting/soldering/welding,Jointingshallbedonebyoverlapping andwith2setofBrass(forCustrip)/GI(forGIStrip)nutbolt& springwasherspacedat50cmmakingconnectionetc.as required.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 729 | 50mm x 6mm copper strip |
| 730 | 25mm x 6mm G.I. ( Hot Dipped) Strip |
| 731 | 32mm x 6mm G.I. ( Hot Dipped) Strip |
| 732 | 50mm x 6mm G.I. ( Hot Dipped) Strip |
| 733 | SupplyanderectionofGalvanizedIronpolewith galvanizingdone insingledipping(AveragecoatingthicknessMinimum65Microns) continuouslytaperedpoleshavingOctagonal/Circularcross-sectionsdesignedtowithstandthemaximumwindspeedasperIS 875,Thepoleshaftshallbemadefromsheetsteel(HTSteel ConformingtogradeS355JO)andconfirmingtoBSEN10025and shall be continuously tapered with single longitudinal welding. There shallnotbeanycircumferentialwelding.Theweldingofpoleshaft shallbedonebySubmergedArcWelding(SAW)process.pole shaftsshallbeprovidedwiththerigidflangeplateofsuitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to thepoleshaftattwolocationsi.e.frominsideandoutside.The octagonalPolesshallhavelockabledoorofapproximate500mm length at the elevation of 500 mmfrom the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) insidethepoleatdooropeningforcableconnectionoffollowing lengthanddimensionaspertableP-01withbaseplateand foundationboltontheExistingcementconcretefoundation.Allas perpreapprovedbyEngineerin-charge.For additional technical parametersofproducts/ work,refer Annexure \"A\" attachedwith this BSR . |
| 734 | 7 Mtr., Poles with Octagonal Cross Section |
| 735 | SupplyandFixingofPoleOEMfabricatedhotdippedgalvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in-charge.Foradditionaltechnicalparametersofproducts/work, refer Annexure \"A\" attached with this BSR . |
| 736 | Single arm overhang |
| 737 | ProvidingandLayingRCCFoundationforOctagonal/Conical StreetLight poles, High mast Poles as per Drawingattach at TableP-4withFollowingProcedure&Allasperpreapprovedby Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . A)ExcavationofPitforFoundationSizeuptorequireddepthfrom Ground levelB)DressingofPitandDrystonepitching200mmthickincluding supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D)ReinforcementforR.C.C.workwithTMTbarsincluding straightening,cutting,bending,placinginpositionandbindingall complete. E)Centringandshutteringincludingstrutting,proppingetc.and removal of form work for Footing and Pedestal F)Providing & Fixing of 2 no. RequiredSize PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. |
| 738 | Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 739 | Providing&FixingofIK08IP-66protectedhighpowerLEDflood lightsystemwithsinglepiecePressurediecastaluminiumhousing, toughenedglassdiffuserwithsuitablelensesonLEDtoachieve variousbeamangles,ofhighpowerLEDof3to5watteach. Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate.TheSystemlevelLuminaireefficacy>=125lm/wt.LED driverInputVoltageAC120to270VACwithHighvoltageCutoff @>=300VACandAutoresettingSafety.PowerFactor>0.95, THD(I)<10%,drivercurrent<=750mA.drivershouldbePhaseto phaseprotectionof440Vfor4Hrs.ElectricalConnector,Surge ProtectionMin>=4KVinternaland10KVexternalbutinsidedriver compartment, System life of 50000 Burning hours with 70% of Initial Lumensmaintained,CRI>70andCCT5700K ±355K. ManufacturesWordMark/NameEngraved /Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shallbeIS10322Complianced.OEMMusthaveitsowninhouse NABLlabsetupforalltestingfacilitiesforLEDfixtures. (LM79/LM80)Certificate/reportwithliablewarrantyof product/accessoriesfromOEMshallbesubmitted.Allasperpre approvedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 740 | High Power LED Flood Light Minimum lumen output 10000 lm |
| 741 | Providing&FixingofIK08,IP66protectedLEDStreetLight Luminaireonexistingbracket/pole.Fixturemadeofpowdercoated singlepiecepressurediecastaluminummaterialwithheat dissipationfinsonhousingwithUVstabilizedPC(UVstablization reportsubmittedforUVcover)/ToughenedGlasscoverand secondarylensoneachLED&shouldbeSMDtypeof3to5watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with HighvoltageCutoff@>=300VACandAutoresettingSafety, Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. TheluminaireshallbeBIScertifiedandTrademarkcertified.Life ExpectancyEqualormorethan50000burninghrswithMinimum 70%lumenmaintened,CRI>70andCCT5700K+355K.Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside drivercompartment.drivershouldbePhasetophaseprotectionof 440Vfor4Hrs.ManufacturesWordMark/Name Engraved/Embossingondiecasthousingtoallow traceability/authenticity.FixtureshallbeASPERIS10322 Complianced.OEMMusthaveitsowninhouseNABLlabsetupfor alltestingfacilitiesforLEDfixtures. (LM79/LM80)Certificate/ report with liable warranty of product/ accessories from OEM shall be submitted.AllasperpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 742 | LED Street Light fixture with Minimum lumen output 8700 lm |
| 743 | Providing&FixingofStreetlightbracketmadeoutfromfollowing size of \" B \" class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. asrequired.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 744 | 32 mm Dia. |
| 745 | Providing&FixingofIP-65protectedimpactresistant polycarbonate/Polystereneenclosureswithknockoutforcable entry/outincludingfixingwithnut,bolt,fatneretcasrequired complete in all respect of following sizes.All as per pre approved by Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 746 | 180 x 180 x 91 mm |
| 747 | Supply , Installation, Testing and Comissioning of wall mounted remote ON/OFF Push Button station for AHU/Air washers made out from powder quoted CRCA sheet of 16 SWG , illuminated ON/OFF push button including making connections etc as equired complete in all respect.All as per pre approved by Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 748 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 749 | Unarmour |
| 750 | 4 core x 2.5 Sq.mm |
| 751 | Supply, installation, testing and comissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified \"Class O\" in Fire Propagation as per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 752 | 38 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 753 | 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 754 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 755 | 20 mm |
| 756 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 757 | 3 KVA |
| 758 | Supply,installation,testing&CommissioningofCopperwound distributionTransformeroffollowingratingand%Impedance, 11/0.433KVDelta-StarConnected,VectorGroupDyn11,ONAN Cooledlosses as per IS 1180 part I 2014 (Fourth Revision) Level-1, withboltlesscoredesignincludingstandardaccessorieslike conservatorwithprismaticoillevelgauge,silicagelbreather, Bucholz relay,pressed steel radiator fins, Radiator Valve(above 800 Kva)SuitablesizeHTcablebox, LTcableboxwithBusbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ),temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device,Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS:335-1953,EpoxyprimerandPUbasedpaintasTopcoat, Unidirectionalrollersforratingupto800kva&bi-directionalabove 800Kvarollerswithlockingarrangementetc.asrequired.The Transformershallbesubjectedtoroutinefactorytests(asper IS:2026 and IS:1180) including Temperature rise test inOEM\"s own lab shall be witnessed by Department engineer Physically. Transformer shall be tested from CTLof discombefore charging of transformer&completeinstallaionmustbecertifiedfromElectrical InspectorateofficeasperIndianElectricityrule,(CTLtesting chargesandElectricalInspectionchargesshallbereimbursedby the department to the contractor) Following tests shall be carried out oneachtransformeratsitebyOEMenginerinpresenceof departmentauthorisedrepresentative:-a)Ratiotestoneach tapping.b)Resistanceofwindingsatprincipalandalltapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per preapprovedbyEngineerin-charge.Foradditionaltechnical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 759 | 630 KVA with % Impedance 4.5 |
| 760 | 1000 KVA with % Impedance 5.0 |
| 761 | SITC of star rated Aluminium wound distributionTransformer of followingrating11/0.433KVDelta-StarConnected, VectorGroup Dyn 11,ONAN Cooled & as per BEE star-1 & BIS approved as per IS2026-1977 & losses asdefinedasper2014(FourthRevision) Level-1 . including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise inwinding/oil 35-40 degree C upto 200 KVA& 40-45 degree C forabove200KVA,ISImarkeddrainvalve,DialtypeTemperature gauge,firstfillingoftransformeroilasperIS:335-1953,Epoxy basedpaint,includingcarryingofpre-commissionTesting& Charging of Transformer complete in all respect . TheTransformershallbesubjectedtoroutinefactorytests(asper IS:2026 and IS:1180) including testing from CTLof discombefore charging of transformer & complete installaion must be certified from ElectricalInspectorateofficeasperIndianElectricityrule,(CTL testingchargesandElectricalInspectionchargesshallbe reimbursedbythedepartmenttothecontractor).Allasperpre approvedbyEngineerin-charge. For additionaltechnical parametersofproducts/ work,refer Annexure\"A\"attachedwith this BSR . |
| 762 | 250 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 763 | 315 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 764 | 400 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 765 | Supply&InstallationofD.P.StructureWithAIRBREAKSWITCH having following specifications A, B, C, D, E. All as per pre approved by Engineerin-charge. Foradditional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .A) Double pole structure on 2 no ISMB (I beam) of size 150 x 75 mm, 10 mtrlengthusing 7 no MS channel each of size 100mm x 50 mm x 2500 mm complete in all respect with nuts, springs washers, clamps as required.B) Off load type gangoperated 3-pole verticalflute type switch suitablefor11KV; 400A, 3-ø,centralpostrotatingdoublebreak isolator complete with MS hardware , copper moving & fixed contact ,assemblyof9nospininsulator,GIpipeofsuitablelengthfor operation. C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators D) 3 piecenonlinearresistortype.lightingarrestorofapproved make suitable for 3 wire, 11kv Overheadline with rated voltageof 9kv rms & nominal discharge current rating of 5 ka & complete with galvanizedclampingarrangementGIbolts, nuts, washer etc as required. E) 3 no 11 KV ACSRconductorsmountedonpintypeinsularorsas required.6.GENERAL: Thegoshallbeoperatedbyhandoperated liver properly earthed with provision for locking mounted at 3’ |
| 766 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated,outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU) manually operated in combination ofVCB modules andLoad Break switch consisting of Copper busbar in SF6 insulated 304 (Non-FerriteNon-MagneticGrade)stainlesssteelenclosure of thickness 2.5mm with manometer. TheHV switchgearandcontrolgear shouldbeconfirmingtoIEC-62271-100,IEC-62271-200-2003& IEC-60694-1996.TheRMUshouldbeinternalarctestedfor21KA for1SecondwithIAC-AFLclassificationforgastank.Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feederofRMUshouldhavevoltagepresenceindicator and compringoffollowings:-1no.microprocessorbasedSelfpowered numericalrelaywithoverCurrent/earthfault&shortcircuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden2.5VA,ratio50/1A,ClassofAccuracyclass5P10forO/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1nos.FaultPassageindicator,-Rightanglebootsforallthefeeder ModulesAllthetypetestcertificatesasperIEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation/SteelStructure to be paid Extra) All as per pre approvedbyEngineerin-charge. For additional technical parametersofproducts/ work, refer Annexure \"A\" attached with this BSR |
| 767 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 768 | SITCofHTmeteringcubicalpanelasapprovedByDISCOMs fabricatedout of18SWG CRCAsheet steelintwocompartment& MSangleofsize60mmX6mmhavingprovisionforFollowing: (i)ProvisionforfixingTrivector/Import-ExportMeter(Tobe supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set withCopperstripforConnection(TobesuppliedbyDISCOMs), (iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections,etc. as required.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 769 | Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 770 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 771 | 100mm x 50mm x 1.6mm |
| 772 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 773 | Heavy Duty AL & CU Lugs,Double Compression Cable Gland with Nickel Plated, Cable Tie, Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners, Clamps, Clips, Screw, Washers, Electrical Taps, HT Tap, Danger Plates, Condut Pipe, 40mmuPVC Pipe, 4.5 Kg. CO2 type portable fire extinguisher for Panel Room , Fire buckets with floor / wall mounting stand ect. required hardware & accessories for various sizes as per site requirements. |
| 774 | 11KV Switchyard Civil work for Transformers Foundations, DP Structure, Chain Link Fencying 1500mm Height, MS Gate , 40mm Gravels, boundary wall, Earthing Chambers, HT/LT cable Trench,coversect. |
| 775 | 433VAC LT Panel for DMA Remote locationsin cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3+1 Phase 433 voltages, 50Hz, neutrally grounded, IP 5X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The indoor Panel switchegears (MCB, CTs, Contactors, auxiliary contacts, Space heater and lighting, RDOL for electrically operated laves with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel. Outdoor Panels shall be self-fabricate type only with Canopy, PLC & SCADA Compitible, complete operation carried for max. nos RDOL , Size - 450*300*600mm (for Electrically Operated Valve sin Remote)as per technical specifications and as directed by Engineer in charge. ( Prices are excluding EOV & EMF/BFM & fittings/ 3 Phase Power Connections at Remote locations ) |
| 776 | AUTOMATION & PLC-SCADA Works |
| 777 | Chlorine Analyser : Transmitter : Range: 0.05 to 20 ppm, Power Supply 230 VAC, Input: 2 Digital Sensors - one for chlorine and second for pH, Output: 4-20mA HART, IP66/67 Protection / Tx protection cover required / Sensor Range 0-14 pH, able to transmit digital signal to transmitter, calibration data can be transferred to Transmitter , process temp: 65 deg cen/ Sensor range:0.05 to 20 mg/l. |
| 778 | Providing,Installation,TestingandCommissioningofPressure Transmitter : Range:0-10Bar / Power Supply:24 V DC / Output: 4-20mAwithHART/Diaphragm:SS316L/ProcessConnection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 |
| 779 | Providing,installation,testingandcommissioningofDiaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass,Overrangeprotection:125%ofmaximumpressure,Material ofsensorandotherwettedparts:SStype316,Housingmaterial: Die cast aluminum |
| 780 | Providing, installation, testing and commissioning of Diaphragm type Pressure Switches Sensing Element: Bellows / Diaphragm, Material ofsensorandotherwettedparts:SStype316,Housing:Diecast aluminum,Switchtype:Microswitch,Repeatability:±1%ofspan, Switch Contacts: 2 NO + 2 NC |
| 781 | Providing,installation,testingandcommissioningofLevelSwitch( Conductivity)ConductivityProbes,Probeinsulation:Teflon,Probe head protection class: IP 65 of IS 13947 Part I, Probe head housing material: Aluminum |
| 782 | Rigid for lengths ofup to 3 Mtr. |
| 783 | Providing,installation,testingandcommissioningofONLINEUPS SYSTEM,SinglePhase230V,50Hzwith2hourbackupSMF battery bank as per specification |
| 784 | 1 KVA |
| 785 | Design,Manufacture,Supply,Installation, TestingandCommissioningofIndoortypePLC Panelofsizeapprox.800mmX500mmX 2000mm(LBH),Fabricatedoutofmin.2mm thickCRCAsheetcompletewithlatest configuration,necessaryprogrammingsoftware forPLC & SCADA andcomprisingofall accessories not limited to the following: DI 30No. DO 26No. AI6 No. AO 2 No. MCB 16A DP 2No. MCB 6A DP6No. SMPS 100-240VAC/ 4.5A / 24 VDC 1 No. Selector Switch (Auto/Manual) & Local / Remote2No.Control Relays 1 Lot Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with1No. Electronic Hooter1No. Control Transformer 200VA1No. Emergency STOP Push Button1No. Panel Cooling Fan & Filter2No. Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC3No. Push Button3No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc1LotPanelHardware,lugs,terminations,ferruls, name plate Ect.1LotUTILITY SOCET 16A, 3 PIN 2No. HMI Display 10 Inch, Colour1No. Isolators Dual Output, 24VDC1Lot |
| 786 | Design,Manufacture,Supply,Installation, TestingandCommissioning ofIndoor type PLC Panelofsizeapprox.800 mm X 500 mm X 2000mm (LBH), Fabricated out ofmin.2mm thickCRCAsheetcompletewithlatest configuration,necessaryprogrammingsoftware forPLC&SCADA andcomprisingofall accessories not limited to the following: DI 62No. DO 58No. AI 14 No. AO 6No.MCB 16A DP2No.MCB 6A DP6No.SMPS 100-240VAC/ 4.5A / 24 VDC 1 No.Selector Switch (Auto/Manual) & Local / Remote2No. Control Relays 1 Lot Annunciator with 24 Windows NOto NC Type MicroprocessorBased,WindowSize 75*42m 110VAC, with 1 No. Electronic Hooter1No. Control Transformer 200VA 1 No. Emergency STOP Push Button 1No. Panel Cooling Fan & Filter2No. Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC3No. Push Button3No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc 1LotPanelHardware,lugs,terminations,ferruls, name plate Ect.1LotUTILITY SOCKET 16A, 3 PIN2No.HMI Display 10 Inch, Colour1No. Isolators Dual Output, 24VDC1Lot |
| 787 | Compact RTU complete with DI, DO, AI and modbus communication ports and power supply. // Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and Communcation protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communications antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card also, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. Panel Enclosure for Compact RTU Location, wall/floor mounted along with wiring and related accessories and arrangement of mounting of RTU, Modem and having IP-5X Protection. Panels shall be self-fabricate type only with Canopy. |
| 788 | Modular RTU complete with DI, DO, AI and modbus communication portsandpowersupply24VDCorforvariablepowersupplyusing batteries,rechargeablebatteries,solaror10.8VDCto28.8VDC with integrated modem; connection to control center via Tele Control Basic,DNP3,IEC60870-5-104andCommuncatinprotocols,on-board I/Os min. (8 DI, 4 DQ, 2 AI), configuration and diagnostics per (GSM/UMTS),MiniSIMcard,withadapterMicroSIMcardalso, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3,OpenVPN-Client.PanelEnclosureforCompactRTULocation, wall/floormountedalongwithwiringandrelatedaccessoriesand arrangementofmountingofRTU,ModemhavingIP-5XProtection. Panels shall be self-fabricate type only with Canopy. |
| 789 | Supply Installation, Testing & Commissioning of Intel i7 4th Generation processor 3Ghz or latest, 4GB RAM with 2TB hard disk, DVD-RW/keyboard/optical mouse/LAN card/24” LED monitor. Minimum 6 USB ports. With pre-loaded licensed Windows 10 or latest software PC |
| 790 | Supply, Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . For SCADA / PLC room. |
| 791 | 1.5 TR ISEER not less then 4.6 |
| 792 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 793 | 50 mm dia per running inch length |
| 794 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 795 | ProvidingandlayingStranded/FlexibleAnnealedeBarecopper conductor,XLPE/PVCinsulatedsuitablylaiduptogetheroverall polystertapedAl(innersheatedGISteelwireMylar/Drainwire) alongwithATCdrainwire,round/ steelarmouredoverallPVC sheathed (ST-1) overall screenedCore armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 796 | 24 CORE, 1.0 sq. mm. |
| 797 | 4 CORE, 1.0 sq. mm. |
| 798 | ProvidingandlayingStranded/FlexibleAnnealedBare copper conductor, XLPE/PVC insulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screened Pair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (2 Pair * 0.75SQMM) |
| 799 | Quad-bandGPRS/IOT/VPN/GSM/CLOUD 3G/4G/5G modemwithEthernetbridge/router/ serial server (RS232/485) interface. |
| 800 | The Cloud based Water management & Data Monitoring system for the real time data analysis of the field instruments/ pumps/valves/actuators located in the CPS / IPS/ any other field remote locations. 16 pump houses & the system working, a dedicated Cloud Server Instance will be provided with Database to store historical data of up to 5 years. The PLC system available in each pump house will send the data through Sim-based Modem to the Cloud at a time interval of 15 seconds. A Dashboard with all mentioned Locations will be created with an Overview of each Pump house & further the status of Pumps, running hours, status of valves, Tank Water Level, Pressure and all-important values will be displayed & stored in database. In total 3 users will be provided with the Monitoring Access of the system & 1 user will be provided with the Operation Access. A Daily/Weekly/Monthly Report Generation & download option will be provided with a standard predefined format. |
| 801 | Cloud based Water management & Data Monitoring systemDash Board (12 Months * 5 years) |
| 802 | Cloud based Water management & Data Monitoring system setup 5-year infrastructure Design & Development |
| 803 | Cloud based Water management & Data Monitoring systemmonthly Recurring Charges (12 Months * 5 years) |
| 804 | Instrumentation works |
| 805 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw / Chlorinated), Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU), Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC -50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 806 | EFM 80 mm |
| 807 | EFM100 mm |
| 808 | EFM150 mm |
| 809 | EFM 200 mm |
| 810 | EFM 250 mm |
| 811 | EFM 300 mm |
| 812 | EFM 400 mm |
| 813 | EFM 450 mm |
| 814 | EFM 500 mm |
| 815 | EFM 600 mm |
| 816 | SITC of Ultrasonic Level Transmitter suitable for measuring water level in reservoir, Normal Powered 24VDC, Type of Transmitter: Two Wire ( 4-20 mA), Cable Entry:1/2\" NPT (F), Sensor Material: PP, slip-on Flange: 2 ½” Flange, Material of Construction for Slip-on flange: PP, output 4~20mA, HART compatible, accuracy +/_ 0.2 % as per detailed Technical specification, scope of work and direction of Engineer in charge. |
| 817 | Measuring range 0.0 to 6.0 mtr |
| 818 | Providing and making flanged joints to double flanged C.I./ D.I. pipes and specials such as tees, bends, tapers, caps etc. at all level/depths within trenches complete including all material i.e. rubber insertions, bolts & nuts etc, labour, testing of joint, commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 819 | 250 mm dia |
| 820 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer.0 to 10.0 kg/cm² |
| 821 | Providing, installation, testing and commissioning of Diaphragm type Pressure Switches Sensing Element: Bellows / Diaphragm, Material of sensor and other wetted parts: SS type 316, Housing: Die cast aluminum, Switch type: Microswitch, Repeatability: ± 1% of span, Switch Contacts: 2 NO + 2 NC |
| 822 | Household Tap Connection |
| 823 | Providing Household Tap Connection as per technical specification and approved drawing as per relevant IS code (amended up to date) from uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using PP/MS saddle piece (Complete job).This job includes digging out suitable size of pits and trench for laying service line in all kinds of soil (excluding road); depositing and refilling of pit & jhiri with watering & ramming /compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting duly approved in accordance with specification for potable water including MS/PP saddle piece, gunmetal ferrule 4.0 mm , GM Full-way Valve (IS:778 Mark) or ball valve (min. weight 165 gm) and specials, below ground level 20 mm nominal dia MDPE pipe PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Three layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above ground level using 20 mm dia PPR-C pipe with standard PPR fittings/ 15 mm dia GI pipe with fittings in the premises for fixing a tap / meter box (excluding) , inc accessories with flushing, cleaning, disinfecting and testing of pipe line complete required for making of service connection complete in all respect including labour charges . The service line should be laid at least 45 cm below ground level.Note: Road cut and restoration is not part of this item and paid separately. |
| 824 | For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr. |
| 825 | Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be doneby using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge.. |
| 826 | Supply, Installation of 15 mm size AMI LoRa WAN/RF based Water Meters, conforming to ISO 4064:2005/ISI standards with MID/ISI approvalincluding Collection & Verification of Consumer Data, Automated Meter Reading in the identified DMAs of MC Jaipur Greater. |
| 827 | Civil Works |
| 828 | Construction of Panel Room on CWR at Vaisali Nagar A-Block , Triveni Nagar, Vidhyut Nagar Campus for Vaishali Nagar E-Block and Officer campus |
| 829 | Providing and fixing precast cement concrete coping 1 : 2 : 4 mix 50 mm thick complete as perspecification : |
| 830 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc.M20 grade Nominal Mix / Design Mix |
| 831 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement for Beams, suspended floors, roofs, griders having lopes up to 15º, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases etc. M20 grade Nominal Mix / Design Mix |
| 832 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel propsand removal Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc.of formwork for upto floor five level for |
| 833 | Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates, anchor blocks, sills, chhajjas, lintel, beam, plinth beam etc. |
| 834 | Columns, pillars, posts and struts etc. |
| 835 | Arches, domes, vaults etc exceeding 6 Mtr span |
| 836 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level.(Original producers who manufactura billet directly from iron ores and roll the billets to produce steel conforming to IS:786) |
| 837 | Cold twisted deformed bars (IS : 1786). |
| 838 | Thermo-mechanically Treated bars (Conforming of relevent IS code) |
| 839 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : |
| 840 | Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 841 | Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 842 | Half brick masonry in Superstructure , above plinth level upto floor V level using bricks of designation 75; 5.8.2 Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 843 | Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades ceramic glazed vitrified tiles with water absortion less than or equal to 0.08% confirming to IS:13753 & IS : 15622 on walls, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar).Size 600mm x 1200mm |
| 844 | Grading roof water proofing treatment with water profing compound :Cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 845 | Providing & fixing door, window, chowkhats and other frames, including antitermite treatment, M.S. flat, hold fasts of size 250 x 40 x 3mm fixed with M.S. bolt 5mm dia 50mm long duly embedded in cement concrete M-15 grade :Nigeria teak wood Grade - I. |
| 846 | Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure \"A\" : 35 mm thick, commercial Veneer Both side. |
| 847 | Extra for providing other type of fittings as mention in annexure A ( as approved by EI) : Stainless steel fittings. (for door leaf shuter) |
| 848 | Extra for providing external lipping with 2ndclass teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured); for door leaf shutt |
| 849 | Providing and fixing bright finished Mortice lock of approved make Godrej or equivalent with pair of CP handles for doors with necessary screws etc complete (Best make of approved quality) as per direction of Engineer-in-charge. |
| 850 | Providing & Fixing mica of approved make for inner/outer side of shutters with fevicol & nails completeas per approved by engineer in charge.0.8mm thick mica |
| 851 | Providing and fixing steel glazed doors windows and ventilator shutters of standard rolled steel section (IS 1038- 1983) joints mitred and welded with steel lugs 13x3mm, 10cm. long embedded in cement concrete block 15x10x10cm. of 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) or with wooden plugs and screws or rawl plugs and screws with fixing clips or with bolts and nuts as required including providing and fixing of plain glass panes 4mm thick with cooper glazing clips and special metal sash putty of approved make or metal beading with screws complete including priming coat of approval steel primer, excluding the cost of metal beading and other fitting except necessary hinges of pivots steel handles peg stay etc. as required |
| 852 | Windows side hung /Ventilators top or centre hung (openable) |
| 853 | Providing brass handles/peg stays and fittings in place of oxidized fitting Sqm. 5% |
| 854 | 5mm thick plain glass instead of 4mm thick plain glass Sqm. 95.00 |
| 855 | Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance. |
| 856 | Providing batta (gola) 75 mm x 75 mm in cement concrete (1 : 2 : 4) including finishing with cement mortar 1 : 3 as per standard design. |
| 857 | Plaster on new surface on walls in cement sand mortar 1:4 including racking of joint etc. complete fine finish : 20 mm thick |
| 858 | 6 mm cement plaster to ceiling of mix 1 : 3 (1 cement : 3 fine sand).; Celling plaster |
| 859 | Making grooves as per design in plaster 10 mm to 20 mm wide.; (add; 20 % R.M.of plaster work.) |
| 860 | Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth completeNew Plastered Surface (three or more coats) |
| 861 | Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade including all scaffolding:INTERIOR; Two or more coats on new work including prepartion of base with primer, putty, lippy etc complete in all respect. |
| 862 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specifications including primer coat and protecting coat including scaffolding and safety provision. Trowel Finish av. thickness 2000 to 2500 microns. |
| 863 | 1.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 864 | Short point (up to 3 mtr.) |
| 865 | Medium point (up to 6 mtr.) |
| 866 | Long point (up to 10 mtr.) |
| 867 | 3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexiblecopper earth conductor 1.1 kV grade(IS:694) inrecessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thickwith earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket,Modular face plate with grid plate, screws, making connections, testingetc. as required. For specification of copper Conductor, PhenolicLaminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E- 05 & E - 07 For additional technical p |
| 868 | On board |
| 869 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 870 | 20 mm |
| 871 | 25 mm |
| 872 | 4.2 Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor of alum. alloy braid in existing surface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 873 | Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TECspecification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair forIdentification etc. as required. For additional technical parameters ofproduct / work refer Annexure \"A\" attached with this BSR;4.3.4 4 pair |
| 874 | P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ;5.1.1 1.2 mm thick M. S. Sheet boxes ; |
| 875 | 100mm x 100mm x 60mm |
| 876 | 200mm x 250mm x 75mm |
| 877 | P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 878 | P & F 1.00mm thick M.S. Recessed concealed box, round of size 150 mm dia, depth 100 mm complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 879 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 880 | Single pole MCB (With B/C curve tripping Characteristics) |
| 881 | 6 A to 32 A rating |
| 882 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947- III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 35sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR;6.2.3 Four pole Isolator; 63 A rating |
| 883 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 884 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 885 | 6 Way (6+2) |
| 886 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial gradePolycarbonate or fire resistant ABS material, brass terminal & captivescrews including making connection testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 887 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 888 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 889 | 6/16 A shuttered socket |
| 890 | 7.29 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captivescrews & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work referAnnexure \"A\" attached with this BSR ;7.29.1 5 step fan regulator 2 Module 360 dgree rotating |
| 891 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 892 | Modular MCB 6 A to 32 A SP |
| 893 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 894 | 3 Module Each 86.0 |
| 895 | 6 Module Each 114.0 |
| 896 | 8 Module Each 155.0 |
| 897 | 12 Module Each 214.0 |
| 898 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 899 | 11.3 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 900 | 10.0 Sq. mm, 4 core4 core |
| 901 | Providing & Fixing of 1200 mm sweep BLDC technology power saving ceiling fan which can withstand on votage fluctuations from 140 volts to 240 volts ,power factor not less then 0.9 , service value (CMM/W) minimun 6.85 , air delivery minimun 220 CMM, speed minimum 330 RPM ( tolerance as per IS:374 2019 ) THD less then 10% and complete with down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe up to 80 cm , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 15.4.1 Without Remote |
| 902 | 15.12 Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 300 mm sweep(900/1400 RPM) |
| 903 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 904 | 17.3.1 Recessed Mounting ;Minimum lumen output 650 lm |
| 905 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required.Gr I |
| 906 | 3x 1.5 sq.mm |
| 907 | 2 x 2.5 sq. mm. + 1x1.5sqmm ( All light and power Ckt) |
| 908 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (AC Ckt) |
| 909 | 4 x 10 sq.mm (Sub main) |
| 910 | 1 x 6 sq.mm (With sub main ) |
| 911 | Construction of boundary wall of Brick/ stone masonry as per enclosed GA drawing, scope of work and technical specifications complete work in all respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonry in CM: 1:6 section of foundation above PCC, 600 mm (W) x 450 mm (D) and 450 mm (W) x 450 mm (D) 4. Superstructure work: Stone masonry in CM: 1:6, W-300, height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5.Cement mortar pointing on Stone masonry and cement mortar plaster 20 mm thick on brick masonry in CM 1:6.6. Expansion joint shall be on every 30 mtr.7. On top of wall there shall be CC Coping 75 mm thick (1:2:4) shall be provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 912 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 913 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 914 | For Class-AA loading |
| 915 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m-for pipe size-up to 100 mm |
| 916 | Sluice valve chamber of size 1.17m x 0.95m x1.47mfor pipe size-from 125-to-150mm |
| 917 | Sluice valve chamber of size 1.26m x1.185m x1.88m for pipe size-from 200-to-300mm |
| 918 | Sluice valve chamber of size 1.39m x1.43m x2.245mfor pipe size-from 350-to-450mm |
| 919 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm |
| 920 | For Class-A loading |
| 921 | Sluice valve chamber of size1.39m x1.43m x2.185mfor pipe size-from 350-to-450mm |
| 922 | For in-campus Valve Chambers |
| 923 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm |
| 924 | Construction of RCC Air valve chamber for different type of valves including earthwork excavation, 100 mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, Plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 925 | For Class-AA loading |
| 926 | Air valve chamber of size0.9m x1m x1.695mfor air valve size-from 50 mm-to-80mm |
| 927 | Air valve chamber of size1m x1.1m x1.945m for air valve size of 100mm |
| 928 | Air valve chamber of size1.05m x1.4m x2.42mfor air valve size of 150mm |
| 929 | Air valve chamber of size1.325m x1.7m x2.875m for air valve size of 200mm |
| 930 | For Class-A loading |
| 931 | Air valve chamber of size0.9m x1m x1.71mfor air valve size-from 50 mm-to-80mm |
| 932 | RTU Structure (49 nos), Repairing of OHSR (14 nos) and Pump house (8 nos) |
| 933 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed : All kinds of soil |
| 934 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. |
| 935 | M15 grade Nominal Mix 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20mm nominal size). |
| 936 | M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 937 | Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement.M20 grade Nominal Mix / Design Mix |
| 938 | Providing and laying in position Ready mix concrete manufactured in fullyautomatic Batching Plant andtransported to site intransit mixer for having continous agitated mixer, manufactured as per approved mix design of specified grade of RCC work including pumping of R.M.C. from transit mixer to site of laying , exculding the cost of centering, shuttering and reinforcement with all lead and lift including cost of admixtures in recommended portion as per IS 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer in charge. All works upto floor V floor M20 grade Design Mix by using cementas per codal provision. |
| 939 | Add extra for providing richer mixes respectively at all floor levels |
| 940 | Providing M-35 grade concrete by using cement as per codal provision instead of M-20 grade design mix. |
| 941 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc. |
| 942 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : |
| 943 | Add extra for additional height in centring, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan are is to be measured) |
| 944 | 5.19 Half Brick work with mechanised autoclaved flyash lime bricks conforming to IS: 12894 :2002 of class designation 100 in superstructure above plinth level upto floor V level in.Cement mortar 1 : 4 (1 cement : 4 coarse sand) Sqm 586.00 |
| 945 | Random Rubble stone masonry with hard stone in superstructure aboveplinth level and upto five levelabove 30cm. thick walls in :Cement Mortar 1:4 ( 1-Cement : 4-Sand). |
| 946 | Providing and fixing 1st quality MAT finished ceremic tile size 300x300mm confirmingto IS : 13755 and IS : 15622 colour such as white, grey, ivory, fume red brown, light green, light blue and other light shades in floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (including the cost of cement mortar bed 1:4).;WALL |
| 947 | P & F 1st qualityHeavy Duty Vitrified Polished Digital tiles on floor, skirting and steps etc.in different sizes (thickness minimum 10mm) with water absortion less than or equal 0.08% and conforming to IS 15622 of approved make in all colour and shade, laid with 20 mm thick CM 1: 4 including grounting the joints with white cement and matching pigment etc complete.; Size 300mm x 450mm |
| 948 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting (height upto 10 m) , fixing in position and applying a priming coat of approved steel primer all complete: |
| 949 | Supply and fixing in cement mortar welded hand railing made out of MS round or square bars, flats etc. for staircase or verandah as per design complete in all respect (wooden or PVC hand railing to be paid extra) with priming coat of red oxide. |
| 950 | Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide |
| 951 | Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : |
| 952 | 20 mm thick |
| 953 | Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth completeNew Plastered Surface (three or more coats) |
| 954 | Painting exterior surface of Wall with 100% acrylic exterior paint of approved brand and manufacture to give an even shade with two or more coats including prepartion of base with sand papering, primer, putty, etc complete in all respect including scaffolding and safety provision |
| 955 | New Work |
| 956 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specificationsincluding primer coat and protecting coat including scaffolding and safety provision Roller Finish av. thickness 400 to 500 microns.; / ESR & CWR PAINT WORK |
| 957 | Painting with syntheticenamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work, Note:Pump & other railing works,door windows,including etc, |
| 958 | Painting (two or more coats) on rain water soil, waste and vent pipes and fitting with black anticorrosive bitumastic paint of approved brand and manufacture over and including a priming coat of ready mixed zinc chromate yellow primer on new work : |
| 959 | Lettering with black Japan paint of approved brand and manufacture. |
| 960 | P & F Liquid Soap Container with brackets complete of approved make: C.P. brass. |
| 961 | P & F Shower arm 15mm dia of approved quality/make. C.P.brass heavy & superior quality 220mmProjection. |
| 962 | P & F Bath Shower of approved quality/make.C.P. brass of Heavy & superior quality, revolving with adjustable key 150mm. |
| 963 | P & F C.P. Health Faucet with 1Mtr. Long Tube & Hook of approved make and heavy as per direction of Enginner-in- Charge |
| 964 | Providing & Fixing Premium Quality white glazed vitreous china Sanitary Wares (IS:2556 Mark) of approved make as per direction of Engineer-in-charge including cutting and making good the wall and floor. Wall Mounting European type W.C. |
| 965 | Providing & Fixing premium qulaity WVC Urinal with PVC waste pipe, dome couplings, concealed iron brackets or screws etc. complete.; Flat Back (large) or half stall size 590 x 375 x 390 mm. |
| 966 | Providing & Fixing premium qulaity WVC Wash basin with C.I. brackets duly painted & 32 mm C.P. brass waste coupling of approved make with PVC waste pipe complete. Size 550 mm x 400 mm dia for counter top. |
| 967 | P&F Looking Mirror 5mm thick of approved make with ornamental frame size 50x12 with 6mm Ply Board on Back Side Complete as per approved sample |
| 968 | Supply of Hydraulic Seat Cover for Europeon WC of superior quality approved make in white Colour |
| 969 | Providing & Fixing premium quality Toilet corner Glass Shelf size 225x225mm with C.P. brass brackets & guard rail edgesrounded of SS frame |
| 970 | Providing & Fixing Premium quality Bottle trap internal portion 32mm, size 250mm long wall connection pipe & wall flange as per approved by Engineer in Charge. |
| 971 | Providing and fixing Premium quality Towel rack 600mm long 260mm wide with lower hangers CP Brass fittings of approved make as per direction of Engineer-in-charge. |
| 972 | P & F 15 mm. Dia Connection Pipe of approved quality/make. PVC pipe with C.P. Brass nuts upto length, 450mm. |
| 973 | P & F Flush Cock / Flush Valve (IS : 9758 Mark) for WC of approved quality make :Brass / GunmetalHalf-turnwt. 1 Kg.ofapprovedquality / make,25mmnominalbore. |
| 974 | Providing and fixing Superior quality CP Brass fittings of approved make as per direction of Engineer-in-charge |
| 975 | Pillar Cock 15 mm nominal size |
| 976 | Bib Cock with long thread 15 mm nominal size |
| 977 | Providing and fixing Superior quality CP Brass fittings of approved make as per direction of Engineer -in-charge Jet Spray (Premium heavy Quality) as approved by Engineerin- Charge |
| 978 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. (Internal work Exposed on wall) |
| 979 | 20 mm nominal size |
| 980 | 25 mm nominal size |
| 981 | 50 mm nominal outer dia pipes |
| 982 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. (Concealed work including cutting chases and making good the walls etc.,) |
| 983 | 20mm nominal outer dia pipes |
| 984 | 32mm nominal outer dia pipes |
| 985 | Providing and fixing premium quality Angular stop cock 15mm with wall flange complete as per sample approved by Engineer in charge |
| 986 | P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2.) approved quality /makeincluding joining the pipe with solvent cement rubber ring and lubricant. 110 mm dia. |
| 987 | P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2.) approved quality /makeincluding joining the pipe with solvent cement rubber ring and lubricant.160 mm dia |
| 988 | P&F rigid PVC pipe fittings (IS: 4985 mark) of approved quality /make including joining the pipe with solvent cement rubber ring and lubricant: |
| 989 | Coupler (socket). 110mm dia |
| 990 | Coupler (socket). 160 mm dia |
| 991 | Plain Tee, 110mm dia |
| 992 | Plain Tee, 160 mm dia |
| 993 | Door Tee, 110mm dia |
| 994 | Door Tee, 160 mm dia |
| 995 | Bend 45, 110mm dia |
| 996 | Vent Cowel, 110mm dia |
| 997 | Socket plug, 110mm dia |
| 998 | Pipe Clip, 110mm dia |
| 999 | Pipe Clip, 160 mm dia |
| 1000 | Plain floor trap, 110mm dia |
| 1001 | P- Trap, 110mm dia |
| 1002 | S- trap, 110mm dia |
| 1003 | Gully trap, 110mm dia |
| 1004 | Construction of chamber in all type of soil with 300 mm thick masonry in CM 1:6 m 10 cm thick C.C. 1:5:10 in foundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring , earthwork etc. complete as per design including disposal of surplus earth within a lead of 50 mtr. |
| 1005 | inside size 450 x 450mm depth upto0.5 M Cement cover with frame |
| 1006 | inside size 600 x 450mm depth upto 0.5 M Cement cover with frame. |
| 1007 | 2.26 P & F PVC Storage Tank ISI Marked (IS : 12701) indicatingthe BIS license No), of approved make with cover, 25mm dia1M long G.I. over-flow pipe & 25 Cm. long wash out pipewith plug & socket, including making connection etc.,complete of approved design:;; 2.26.3 500 -litres capacity. |
| 1008 | Carriage of Materials by mechanical transport including loading, unloading and stacking ::Cost of carriage including loading, unloading & stacking for first 50 m. |
| 1009 | 4.13 Earth filling with available surplus soil excavated from foundations and taken only from outside of building plinth in layers not exceeding 20cm in depth, consolidating each deposited layer including ramming and watering and consolidation with lead up to 50 m and lift upto 1.5 m. |
| 1010 | 9.10 Providing and fixing of precast concrete interlocking tiles of desired shape of M 30 grade manufactured from fully computerized automatic stationery hydraulic vibrio pressed machine and fully computerized automatic batching plant of class A1/A2 as per BS 6717:2001. The CC interlocking paving blocks be laid on average 50mm. thick bed of coarse sand and the joint is to be filled with fine sand. Laying procedure on compacted sub-base as defined. Complete job is to be executed as per the instruction of Engineer incharge. The rates to be inclusive of all lead & Lifts etc. complete as per specifications. Tensile splitting strength, abrasion and braking load etc. as per BS 6717:2001, Grey cement |
| 1011 | 100mm thick |
| 1012 | Providing and fixing 28 mm thick door shutter made of solid PVC foam profile with homogenous fine cellular structure having smooth outer integral skin having 71mm width & 28mm thick as styles and rails. Joints are made using solvent adhesive and GI \"C\" sections (39mm x 19mm x 0.6mm thick) or M S pipe (40mm x 20mm ) stiffener frame insert & telescopic polymeric \"L\" corners .The panel shall be filled with 3mm thick high - pressure compact laminate as per manufacturer\"s specifications and direction of Engineer-in charge, cover moulding shall be provided for covering fixing screws and elegant look. (for W.C. and bathroom door shutter). |
| 1013 | Crazy marble stone flooring including filling the gaps with light shade pigment with white cement marble powder mixture (3 parts of white cement : 1 part of marble powder) by weight in proportion of 4:7 (4 cement marble powder mix : 7 white, black or white and black marble chips of sizes from 1mm to 4mm nominal size by volume) and under layer 25mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size) rubbing, polishing and cement slurry etc. complete :30.16.1 18 mm thick crazy marble stone white, black or as specified. |
| 1014 | O&M |
| 1015 | Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency) as per Scope of Work & terms & conditions of contract for 5 years after defect liability period of one year DLP (except power feeder, IEC & miscellaneous provision) for Water Supply Project |
| 1016 | 1st year |
| 1017 | 2nd year |
| 1018 | 3rd year |
| 1019 | 4th year |
| 1020 | 5th year |
| 1021 | (B). SUB TOTAL OF DIVISION SOUTH S-2 |
| 1022 | (C) DIVISION SOUTH S-3 |
| 1023 | Pipeline |
| 1024 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended upto date), with internal cement mortar lining for potable water with rubber ring (EPDM/SBR) joints as per IS: 5382-1985 (excluding special accessories) complete including all material, labour, hydraulic testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 1025 | 150 mm |
| 1026 | 200 mm |
| 1027 | 250 mm |
| 1028 | 300 mm |
| 1029 | 350 mm |
| 1030 | 400 mm |
| 1031 | 450 mm |
| 1032 | 500 mm |
| 1033 | 600 mm |
| 1034 | Providing, lowering, laying, aligning, fixing in position at and jointing at all level/ depths ISI marked HDPE pipes of PE-100 grade & PN-6 for potable water as per IS 4984 (amended upto date) in trenches in complete including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 1035 | 110mm dia |
| 1036 | 125mm dia |
| 1037 | 140mm dia |
| 1038 | 160mm dia |
| 1039 | 180mm dia |
| 1040 | Earth work in excavation by mechanical means (Hydraulic Excavator) / manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth includingconsolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 1041 | Add extra for over all depth of excavation above 1.5 m and upto 3.0 m over item no 4.1 |
| 1042 | Dismantling of cement concrete pavement by mechanical means using pneumatic tools, cutting theperipheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposalof dismantled materials up to a lead of 1000 metres including allowances for any additional dismantling beyond the drawings (measurement for payment to be as per standard drawings), rehandling of material/earth to complete the task. |
| 1043 | Dismantling of flexible pavement for pipe line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, rehandling of material/earth to complete the tasks per technical specification and scope of work. |
| 1044 | Bituminous courses |
| 1045 | Granular courses |
| 1046 | P & F of Open timbering in trenches including strutting, shoring complete (measurements to be taken of the face area timbered). Depth exceeding 1.5 Mtr. but not exceeding 3 Mtr |
| 1047 | Barricading with Sal ballies as per design including tying with vertical post by coconut strings including digging out holes in all types of soil complete in all respect with two horizontal members height 1.2 m upto 1.5m above ground level and vertical supports upto 2.5 centre and upto 3 days period including removal and cleaning the site complete in all respect & including dressing of sides and providing retro reflective tapes for traffic safety as per direction of Engineer-in charge in all types of soil. |
| 1048 | Valves |
| 1049 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1050 | Manually operated class PN 1.0 |
| 1051 | 300 mm HW |
| 1052 | 450 mm with Gear |
| 1053 | Providing, lowering, aligning, fixing in position in pipe line, CIdouble flangedDual plate check valve of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications:Body & Cover of Grey cast iron ofIS:210/ FG200 , Disc / plates - Cast steel ,Disc seal ring of EPDM/ NBR (food grade quality) ,Body seat of SS ,Face to face dimensions as per API: 594 ,Flanges Drilled as per IS:1538.Epoxy (Non-Toxic & suitable for drinking water) applied on body & coverinside and outside . Shaft/Stop Pin of SS- AISI- 304/410 , Hinge SS AISI 316/304 / CS ,SpringSS AISI 316/304 , Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal.Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick . Suitablesupport structure as per directions of EICincluding jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1054 | Class PN 1.0 |
| 1055 | 200 mm dia |
| 1056 | 250 mm dia |
| 1057 | 300 mm dia |
| 1058 | 350 mm dia |
| 1059 | Providing, lowering, laying, aligning, fixing in position in pipe line, Resilient Seated D/F DI Sluice valves of approved make & design standard of following dia complete (including jointing & jointing material ) including all material, labour, testing and commissioning along with pipe line as per Technical Specification & as per direction of Engineer. |
| 1060 | Manually operated class PN 1.6 |
| 1061 | 100 mm dia |
| 1062 | 150 mm dia |
| 1063 | 200 mm dia |
| 1064 | 250 mm dia |
| 1065 | 300 mm dia |
| 1066 | 350mm dia |
| 1067 | 400 mm dia |
| 1068 | 500 mm dia |
| 1069 | Electrically Operated & SCADA Compatible class PN 1.6 |
| 1070 | 100 mm dia |
| 1071 | 150 mm dia |
| 1072 | 200 mm dia |
| 1073 | 250 mm dia |
| 1074 | 300 mm dia |
| 1075 | 350 mm dia |
| 1076 | 400 mm dia |
| 1077 | 450 mm dia |
| 1078 | 500 mm dia |
| 1079 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) Swing type Non Return Valve of approved make of following Pressure rating & dia complete, generally confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Bonnet & disc of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG- 400/12 as per IS 1865 or equivalent grade as per IS :3896-part2- 1985 and subsequent revisions, Face to face dimensions as per IS 5312 (part -1):2004 Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body, cover and disc inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410, Hinge SS AISI 316/410 ,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earthwork. |
| 1080 | Class PN 1.6 |
| 1081 | 200 mm dia |
| 1082 | 250 mm dia |
| 1083 | 300 mm dia |
| 1084 | 350 mm dia |
| 1085 | 450 mm dia |
| 1086 | Providing,lowering,aligning,fixinginpositionandJointinginpipe line, DI Body Flanged End Tamper proofKinetic Air Valve class PN 1.6 of approved makes of following pressure rating and dia and as perfollowingspecifications:Governingstandard-AWWAC512/ IS:14845:2000(amendeduptodate)Body,Highpressurecover, Low pressure cover, Cowl andJoint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush:Bronze,FlangesasperIS/BS,DrilledasperIS:1538. ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy(Non- Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fasteners -CS/Galvenisedsteel,Outletofbigorificewillhaveascreento prevent Tamper of float, with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amendedupto date) PN 1.6 ratings Valvesincludingall material, labour,testingandcommissioning as perTechnicalSpecificationsandasperdirectionofEngineerin charge. Note: Rates are exclusive of connecting tee, pipe piece and earth work |
| 1087 | 40 mm dia |
| 1088 | 50 mm dia |
| 1089 | 80 mm dia |
| 1090 | 100 mm dia |
| 1091 | 150 mm dia |
| 1092 | 200 mm dia |
| 1093 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 410/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318-LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318-LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. Insertion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1094 | Plunger Type Flow Control Valve |
| 1095 | 300 mm dia |
| 1096 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 1097 | 100 mm dia PN-1.0 |
| 1098 | 150 mm dia PN-1.0 |
| 1099 | 200 mm dia PN-1.0 |
| 1100 | 300 mm dia PN-1.0 |
| 1101 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1102 | 250 mm dia. |
| 1103 | 300 mm dia. |
| 1104 | 350 mm dia. |
| 1105 | 400 mm dia. |
| 1106 | 450 mm dia. |
| 1107 | 500 mm dia. |
| 1108 | Clear Water Reservoir |
| 1109 | Construction of RCC (Flat Slab Rectangular) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: |
| 1110 | a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approvalfromdepartment beforeconstruction.Submissionandapprovalofconcretemix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour andmaterialchargesincludingprovidingandfixingofaccessoriessuchasSSladder,SS manhole frame and covers, water levelindicator (floattype), SSventilator withSSscreen, float valve, puddle collars, G.I. pipe railing around walk way, Flat/Slab, rectangular .Staircase c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g)Providingandapplyingthreecoatsofcement-basedpaintontheremainingexternal surface area of the structure. |
| 1111 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder fromroofslabtobottomSlab,insidecontainer.Providingandfixingwaterlevelindicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k) Providingandfixingof150mmwidewaterbarfortheconstructionjoints inthe container.l)ProvidingandfixingCI/DIpuddlecollarstheverticalwallforconnectinginlet,outlet, overflow and washout pipes of the reservoir.m)Inlet,outlet,overflow,washoutpipesandvalvesarenotincludedinthiswork, provision for the same shall be taken separately. |
| 1112 | Rates for RCC Partially Underground type clear water reservoir SBC 10 T/sqm, SEISMIC ZONE-2 & 3. |
| 1113 | 3500KL capacity for Dev Nagar |
| 1114 | Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 1115 | 450 mm |
| 1116 | Providing and making flanged joints to double flanged C.I./ D.I. pipes and specials such as tees, bends, tapers, caps etc. at all level/depths within trenches complete including all material i.e. rubber insertions, bolts & nuts etc, labour, testing of joint, commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 1117 | 450 mm dia |
| 1118 | Pumping Machinery |
| 1119 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover. |
| 1120 | Providing, installation, testing and commissioning of Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, lass \"F\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 1121 | 90 KW (For Dev Nagar) |
| 1122 | Providing, installation, testing and commissioning of submersible dewatering pump set conforming to relevant IS codes and as per scope of work and Technical Specifications, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft, impeller, pump and motor body. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply, with cable guard. The pump set shall be suitable for direct coupling, with suitable suction strainer etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 1123 | 2.2 KW (3.0 HP) |
| 1124 | Replacement of Existing Pumping machinery |
| 1125 | Supply, delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Horizontal Centrifugal Split Casting pumps with motor as per IS 12615-2011 or amended up to date, CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts etc. complete with all respect as per the specification |
| 1126 | Durgapura Pumping Station |
| 1127 | Discharge 121 to 140 LPS and head 41 to 50 M |
| 1128 | Discharge 121 to 140 LPS and head 31 to 40 M |
| 1129 | Barkat Nagar Pumping Station |
| 1130 | Discharge 61 to 70 LPS and head 31 to 40 M |
| 1131 | MalviyaNagar Sec-2 Pumping Station |
| 1132 | Discharge 181 to 200 LPS and head 31 to 40 M |
| 1133 | Discharge 101 to 120 LPS and head 51 to 60 M |
| 1134 | Surya Nagar |
| 1135 | Discharge 101 to 120 LPS and head 31 to 40 M |
| 1136 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to Modbus. |
| 1137 | 90 KW |
| 1138 | MS/DI Special |
| 1139 | Providing, lowering, laying, aligning, fixing in position and jointing at all level/ depths DI standard specials with rubber ring (EPDM)/ nut bolt and insertion sheet and jointing as per IS: 9523-2000 or as amended up to date, such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, taxes, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge (excluding earth work). |
| 1140 | Upto 300mm dia |
| 1141 | Above 300mm dia and upto 600mm dia |
| 1142 | Providing and fixing of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 1143 | MS pipe upto 600mm dia (with minimum 5mm thickness sheet) |
| 1144 | MS pipe Avove 600mm dia (with minimum 6.3 mm thickness sheet) |
| 1145 | Electrical Works |
| 1146 | Providing and fixing in position lightening arrester set complete with 600mmx600mmx6mmthickG.I. earthingplate embeddedbelow groundinearthlingpitat3.5metrdepth,G.I.stripofsize 25mmx5mm thick from earthing plate to top of Over head tank, G.I. FinialmadeofGIbar25mmdiaand2mlongfixedontopofOH tankandconnectedtoGIstrip.Theearthlingsetshallcomplyof IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 1147 | Pipe Ear thing as per IS: 3043 with perforated 3.0 Mtr. Long, 40 mm dia.‘B’classG.I.Pipeincludingallaccessorieslikenut,bolts, reducer,nipple,wiremeshedfunnel,andC.C.finishedchamber coveredwithhingedtypewithlockingarrangementC.I.Cover,C.I. Frame of size 300mm x 300 mm and embodying the pipe complete withalternatelayerssaltandcoke/charcoal,testingofearth resistance as required. |
| 1148 | PlateEarthlingasperIS:3043withcopperEarthplateofsize 600mmx600mmx3.0mmbyembodying3to4mtr.Belowthe ground level with 25 mm dia. G.I. ‘B’ class watering Pipe including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and C.C.finishedchambercoveredwithhingedtypewithlocking arrangementC.I.Cover,C.IFrameofsize300mmx300mm completewithalternatelayersofsaltandcoke/charcoal,testingof earth resistance as required. |
| 1149 | S & Laying following size ‘B’ Class G.I.Pipe confirming to IS: 1239 P-1 (1990) with accessories for laying earth conductor/ strip/ cable in ground/ surface/ recess as required. |
| 1150 | 50 mm dia. |
| 1151 | SupplyinganddrawingPVCinsulated&sheathedsolid/stranded copperconductormulticorecontrolcableISImarked(IS:1554)of 1.1kVgradeofapprovedmakeasperchapterE11,inexisting surfaceorrecessedconduit/casingcappingincludingmaking connections etc. as required. |
| 1152 | 4 core, 1.5 sq. mm. armoured |
| 1153 | 8 core, 1.5 sq. mm. armoured |
| 1154 | 8 core, 2.5 sq. mm. armoured |
| 1155 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 1156 | 160KW |
| 1157 | 110KW |
| 1158 | 90KW |
| 1159 | 75KW |
| 1160 | 55KW |
| 1161 | 45KW |
| 1162 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kAbreakingcapacity(B/C/Dtrippingcharacteristic as per type of load and site requirement) 4 KVimpulsewithstandvoltage,ISI markedIS8828(1996)/conforming to IEC 60898-1 2002, IEC 60947-2, low wattlosses, trip free mechanisum, energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm, conductor line load reversibility, IP 20 contact protection andfitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL/CPRI/ ERDA accrediated labtypetestreports & All as per preapproved by Engineer in-charge. For additional technical parametersofproduct / work refer Annexure \"A\" attached with this BSR |
| 1163 | Triple pole MCB(With B/C curve trippingCharacteristics), 6 A to 32 A rating |
| 1164 | 50/63 A rating |
| 1165 | 125 A rating |
| 1166 | Four pole MCB (With B/C curve tripping Characteristics), 6 A to 32 A rating |
| 1167 | Double pole MCB(With B/C curve tripping Characteristics) , 6 A to 32 A rating |
| 1168 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/freestandingfloormounteddustandverminproof compartmentalisedcubicalpanelasspecificationsandOther parameters requiredas per point (a) ,(b), (c),(d, (e), (f), (g), (h) as below:-(a)ThicknessofCRCAsheetshallbe2.0mm,cablealley compartmentshavingconcealedhingedtypedoorswithkeytype lock with / withoutdetachable extension type structure. Removable 3mm.thicksheetsteelglandplateswithappropriatesizeof knockouts for cables shall be provided(b) completepanelshallundergoaprocessofdegreasing,Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panelhavingPEfoam/Neoprenerubbergasketofnotlessthan 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.[c)interconnectionbetweenbusbarandswitchgears/cableshall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried outwith1.5Sq.mm,Earthwirewith2.5Sq.mmandCTwith2.5 sq.mmflexiblecopperwireonly.Alljoints/interconnectionsof copper bus bar shall be dully tinned . Clearance between main bus barandrisers/metalpartsshallbeatleast10mmadditionalto widthofbusbarBusbarisinsulatedbyHeatShrinkablesleeves. Earth and Neutral bus bar shall be half of the size of phase bus bar. (CostofBusbar/FlexiblewireforInterconnectionbetweenMain connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f)FloormountedpanelshallbemountedonBaseframeofISMCchannel size 100 x 50 x 5 mm( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute)shallbemeasuredbetweenphases,betweenphaseand neutralandbetweenphaseandearth.bothbeforeandafterhigh voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to befabricatedonlyfromCPRIapprovedfabricatoronly(CPRITest certificates to be submitted)All as per preapproved byEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .busbar and Switchgearis to be Paid Extra ) (d)WiringbetweencomponentswithinswitchgearandIncoming/ outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted.Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads,studswithtwonutsandidentificationstripsandshallhave adequate continuous current rating. For tap-offs, adjacent terminals withshortingstripsshallbeused.10%Spareterminalblocksshall be provided. Wire identification on marking strip shall correspond to thedesignationofthewiringdiagrams.Allwireterminalsonthe equipmentshallalsobemarkedwithdesignationcorrespondingto those of the wiring diagram. (e)Allwiringshallbeenclosedinplasticchannelsandneatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee |
| 1169 | SupplyingandfixingofAluminium(IEC60105ISO209-1,2)/ Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwithstandardshortcircuitwithstandcapacity,hightensilenuts and bolts spring washers in existing panel including bending , cutting inrequiredshapeandsizeandcolourcodingwithheatshrinkable PVCsleeves.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1170 | Electrolytic grade Aluminium bus bar 6010 grade |
| 1171 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/Frequencymeter/KWHmeter/MultiFunctionMeter/ Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96mmincludingmakingconnectionbyPVCinsulatedcopper conductorwithPVCsleeves/channeletc.asrequired.Allasper preapprovedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 1172 | ThreephaseAMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
| 1173 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW +KVA+KVAR+KVARH+KWH+DUALENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 |
| 1174 | Providing & Fixing of BISapproved Current Transformerasper PWD specification for electrical Works, ISI marked as perIS 2705-1992/conformingtoIEC60044-1,withsecondary terminal ofCT shall be brought out suitable to aterminalblockwhichshallbe easieraccessiblefortesting and terminalconnection,withall necessarysupportinexistingpanelincludingconnectionetc.as requiredCurrenttransformerRingTypeTapeWound/ResinCast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified.ISF<=5,Cucrosssectionofsecondarywire1.5sqmm (minimum),includingallnecessarysupportinexistingpanel includingconnectionetc.asrequired.Allasperpreapprovedby Engineerin-charge.AllasperpreapprovedbyEngineerin-charge. Foradditionaltechnicalparametersofproducts/work,referAnnexure \"A\" attached with this BSR . |
| 1175 | C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA |
| 1176 | C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA |
| 1177 | C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA |
| 1178 | Providing & Fixing ofCam operated rotary (Auto/manual) switches onexistingpanelwith2wayandoffpositionusinghighgrade engineeringmaterialtointernationalstandardswithcamassemblyinsulationofglassfilledpolyamidewithhightrackingindex.For reliable and stable electrical and mechanical endurance double butt contactswithsilverbi-metaloncoppershouldprovidedcontact assemblyis of operating temp range-25 degree C to55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanicallyminimum50000operations@300cycles/hourand electrically10,000operationsat100%rateddutyfor100cycles/ hourincludingmakingconnectionetc.asrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1179 | 10 AMP |
| 1180 | 16AMP |
| 1181 | Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947withintegralcircuit,IP65abovepanel&IP20terminal block,Approx.bodydiaforpanelnot lessthen20mm,lengthmin. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required. All as per pre approved by Engineerin-charge. Foradditionaltechnical parameters of products/ work, refer Annexure \"A\"attached with this BSR. |
| 1182 | Red/yellow/Blue |
| 1183 | Red/Gree/ white Colour |
| 1184 | Red/Gree/ white Colour |
| 1185 | Red/Green |
| 1186 | Providing&FixingofflushheadpushbuttonactuatorsIEC60947withintegralcircuit,IP65abovepanel&IP20terminalblock, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze forLed,PCBcontactsshallbeofbrass(tinplated),impulsedielectrictestedfor2.5KV,includingconnectionetc.asrequired.AllasperpreapprovedbyEngineerin-charge.Foradditional technicalparametersofproducts/work,referAnnexure\"A\" attached with this BSR |
| 1187 | Non luminous type |
| 1188 | Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 withonesideantiskidabberationmarksandpastingthe matwithsyntheticrubberadhesiveasrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1189 | 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) |
| 1190 | Providing&FixingofselfhealingIP20MPPtypeshuntcapacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1&2inexistingpanelorparallelwithloadterminals,thecapacitor shallbefittedwithdischargeresistors,pressuresensitive disconnector(PSD)andshallhavedissipationfactorlessthan 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min overcurrentcapacity1.8timesratedcurrent&peakinrushcurrent min.300timesofratedcurrent,llifeexpectancygreaterthan 100000hrs(tempclass-25D)in440V/480VCapacitorandfor 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per preapprovedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/ work,refer Annexure \"A\"attachedwith this BSR . |
| 1191 | HeavydutyThreephase440V,50Hzcylindricaltypecapacitor (Bank) |
| 1192 | Providing& Fixing of IP54 microprocessor based 3CT’s for all 3 phasesensingcompensationpowerfactorcorrectionrelaySize 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having3CTsensing,sensitivityupto50milliamp secondarycurrent,selfanalysingautoc/ksettingaccordingto targeted power factor setting, the relay shall have digit displayunit fordisplayofrealpowerfactor,targetedpowerfactor,lag/lead capacitorswitchingstatus,alarmoutputforundercurrent,over current, insufficient compensation, communication interface with RS 485,indication of switching onunits, auto/manual status, and shall haveoverloadprotection,novoltrelease,havingmultiparameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay includingmakingcoonectionwith1.5Sq.mmcopperwireetc.as required.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 1193 | 6 to 8 stage |
| 1194 | 12 to 14 stage |
| 1195 | Providing&Fixingof440Volt3polecapacitor (AC6B)duty contactor with 3 no. early make and post break auxiliary contacts in serieswithquickdischargedampingresistors/reactorstolimitthe inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1:2000,insulationvoltage1000V,impulsewithstand voltage8KV,Dinrailmountingtypeincludingmakingconnections, testingetc.asrequired.suitableforfollowingcapacitycapacitor bank.All as per pre approved by Engineer in-charge. For additional technicalparametersofproducts/ work, refer Annexure \"A\" attached with this BSR. |
| 1196 | up to 6 KVAR |
| 1197 | 10 KVAR |
| 1198 | 15 KVAR |
| 1199 | 25 KVAR |
| 1200 | 50 KVAR |
| 1201 | SITCofDrawouttype3/4poledoorinterlockAirCircuitBreaker (ACB)asconformingtoIS/IEC60947P-2:2003inexistingLT panel suitable for LT installation 440 V, 50 Hz and having adjustable overloadshort-circuit,Instantaneous,earthfault(LSIG)withseparateLEDindicationforeachtypeoffaultshallconfirmtoEMI/ EMC test, LCD/LED display, last 10 trip history, provisionofZSI, Communication, Power metering module, Thermal memory , trip free mechanisum,suitableforambient50degreeandutilization catagaryB.Inbuiltelectrical&mechanicalantipumpingfeature, 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw(1 sec), Uimp-12KV,breaktimenotmorethen25ms. Provisionforelectrical&mechanicalinterlockbetweenACBs, Min.electricaloperation 10000upto2000Aratingand5,000for 2500Ato4000A.includingmakingconnections,testingetc.as required. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineerin-charge.Foradditionaltechnicalparametersofproduct/ work refer Annexure \"A\" attached with this BSR |
| 1202 | 1250 A Rating ,50 kA |
| 1203 | SupplyandfixingoffollowingaccessoriesforAircircuitbreaker (ACB)compatiblewithMAinACBOEMasperPWDspecification forelectricalWorks,conformingtoIS/IEC60947P-2:2003 includingmakingconnectionetccompleteinallrespect. OEMshall havesubmit NABL/ CPRI / ERDA accrediated lab type test certificate before execution. All as per preapproved by Engineer in-charge. For additional technical parametersofproducts/work, refer Annexure \"A\" attached with this BSR . |
| 1204 | Shunt Trip Release |
| 1205 | Under voltage Release |
| 1206 | Microswitch for Indication |
| 1207 | Operation Counter |
| 1208 | Door Interlock |
| 1209 | Auxiliary Contact 4 NO + 4 NC |
| 1210 | Breaker Control Switch (TNC) |
| 1211 | SITCof3/4polecurrentlimitingMouldedcasecircuitbreaker (MCCB)madeofflameretardent&heatresistantmaterialhaving followingcurrentrating,shortcircuitbreakingcapacityat440/415 V,50Hz;O/L&S/Csettings,conformingtoIS/IEC60947P-2 :2003withfrontfaceandcentralisedadjustable,tripfree mechanisum,truecontactpositionindicator,lineload interchangeability, designed for both horizontal&vertical mounting withoutanyadverseeffectonelectricalperformance,suitablefor operationupto55degreeandwithoutderatingupto40degree,pollution degree 3, having positive isolation capability, push(test) totrip,triptimelessthen10msunders/ccondition,Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock&rotaryhandle,includingmakingconnections etc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1212 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting |
| 1213 | 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting |
| 1214 | Extended Rotary Handle |
| 1215 | Mechanical Interlocking kit |
| 1216 | Auxiliary + Trip alarm contact |
| 1217 | Spreaders for 250A, 4 Pole MCCB |
| 1218 | Spreaders for 630A, 4 Pole MCCB |
| 1219 | Providing&LayingP.V.C./XLPEinsulated&P.V.C.sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1KV with H4- Grade electrolytic aluminiumconductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC /Hume/Stoneware/PVCpipe/openduct/cabletrench/Cable tray(withcabletie)includingtestingetc.asrequiredoffollowing size.OEMmusthaveit\"sowninhouseNABLaccrediated LaboratoryfortestingprocedureasperIS:10810.Foradditional technicalparametersofproduct/workreferAnnexure\"A\"attached with this BSR |
| 1220 | 400 SQMM,3.5 CORE |
| 1221 | 120 SQMM,3.5 CORE |
| 1222 | 150 SQMM, 3 CORE |
| 1223 | 120 SQMM, 3 CORE |
| 1224 | 95 SQMM, 3 CORE |
| 1225 | 70 SQMM, 3 CORE |
| 1226 | 50 SQMM, 3 CORE |
| 1227 | 6.0 SQMM, 4 CORE |
| 1228 | 4.0 SQMM, 3 CORE |
| 1229 | Supply, Fabricating & installing following sizes ofperforated Hot dipped Galvanized iron cable tray (Galvanized thicknessnot less then 50 microns) with perforation not more then 17.5% in convenient sectionincluding horizontal and vertical bends, reducers tees, cross membersand otheraccessoriesasrequiredanddulysuspended fromthe ceiling with GIsuspendersincludingGIbolts&nuts, fastners,supportsetc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1230 | 100mm x 50mm x 1.6mm |
| 1231 | 150mm x 50mm x 1.6mm |
| 1232 | 300mm x 50mm x 1.6mm |
| 1233 | Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4-GradeelectrolyticaluminiumconductorconfirmingtoIS:8130 class-2ofpurity>99.6%,InsulationScreening:Extruded SemiconductingCompoundfollowedbyhelicallywrappedCopper Tape,round/flatstriparmouringofcables,Inner/outersheath PVCtypeST-2confirmingtoIS:5831inexistingRCC/Hume/ Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it\"s own in houseNABLaccrediatedLaboratoryfortestingprocedureasper IS:10810AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1234 | 3 core 95.0 Sq.mm |
| 1235 | Providing&makingheatshrinkabletypeindoor/outdoor/ straight through terminations/ joint kitsuitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011which coveredallsequence fortable2forterminationkitandtable 3forstreightthroughjoint inclusive thermal & dynamic short circuittest, humiditytest, soil fog test.CrosslinkingshallbedoneoutsidefactorywithE-beam/ peroxidetechnology.ExtrusionprocessshallbeinhouseOEM withinsamevicinity. including testing etc. as requiredoffollowing sizes. All as per pre approved by Engineer in-charge. For additional technicalparametersofproducts/ work, refer Annexure \"A\" attached with this BSR . |
| 1236 | 3 core 50/70/95 Sq.mm |
| 1237 | 3 core 50/70/95 Sq.mm |
| 1238 | Supply&Layingfollowingsizeearthstripinhorizontalorvertical runinsurfacebymeansofEarthstripDMCInsulatorincluding riveting/soldering/welding,Jointingshallbedonebyoverlapping andwith2setofBrass(forCustrip)/GI(forGIStrip)nutbolt& springwasherspacedat50cmmakingconnectionetc.as required. AllasperpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1239 | 50mm x 6mm copper strip |
| 1240 | 25mm x 6mm G.I. ( Hot Dipped) Strip |
| 1241 | 32mm x6mm G.I. ( Hot Dipped) Strip |
| 1242 | 50mm x 6mm G.I. ( Hot Dipped) Strip |
| 1243 | SupplyanderectionofGalvanizedIronpolewith galvanizingdone insingledipping(AveragecoatingthicknessMinimum65Microns) continuouslytaperedpoleshavingOctagonal/Circularcross-sectionsdesignedtowithstandthemaximumwindspeedasperIS 875,Thepoleshaftshallbemadefromsheetsteel(HTSteel ConformingtogradeS355JO)andconfirmingtoBSEN10025and shall be continuously tapered with single longitudinal welding. There shallnotbeanycircumferentialwelding.The weldingofpole shaft shallbe done by SubmergedArcWelding(SAW)process.pole shaftsshallbeprovidedwiththerigidflangeplateofsuitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to thepoleshaftattwolocationsi.e.frominsideandoutside.The octagonalPolesshallhavelockabledoorofapproximate500mm length at the elevation of 500 mmfrom the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) insidethepoleatdooropeningforcableconnectionoffollowing lengthanddimensionaspertableP-01withbaseplateand foundationboltontheExistingcementconcretefoundation.Allas perpreapprovedbyEngineerin-charge. Foradditionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 1244 | 7 Mtr., Poles with Octagonal Cross Section |
| 1245 | SupplyandFixingofPoleOEMfabricatedhotdippedgalvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in-charge.Foradditionaltechnicalparametersofproducts/work, referAnnexure \"A\" attached with this BSR . |
| 1246 | Single arm overhang |
| 1247 | ProvidingandLayingRCCFoundationforOctagonal/Conical StreetLight poles, High mast Poles as per Drawingattach at TableP-4withFollowingProcedure&Allasperpreapprovedby Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .A)ExcavationofPitforFoundationSizeuptorequireddepthfrom Ground level B)DressingofPitandDrystonepitching200mmthickincluding supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D)ReinforcementforR.C.C.workwithTMTbarsincluding straightening,cutting,bending,placinginpositionandbindingall complete. E)Centringandshutteringincludingstrutting,proppingetc.and removal of form work for Footing and Pedestal F)Providing&Fixingof2no.RequiredSizePLBHDPEPipe& Foundation Bolt with template as per OEM Recommendations.G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. |
| 1248 | Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 1249 | Providing&FixingofIK08IP-66protectedhighpowerLEDflood lightsystemwithsinglepiecePressurediecastaluminiumhousing, toughenedglassdiffuserwithsuitablelensesonLEDtoachieve variousbeamangles,ofhighpowerLEDof3to5watteach. Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate.TheSystemlevelLuminaireefficacy>=125lm/wt.LED driverInputVoltageAC120to270VACwithHighvoltageCutoff @>=300VACandAutoresettingSafety.PowerFactor>0.95, THD(I)<10%,drivercurrent<=750mA.drivershouldbePhaseto phaseprotectionof440Vfor4Hrs.ElectricalConnector,Surge ProtectionMin>=4KVinternaland10KVexternalbutinsidedriver compartment, System life of 50000 Burning hours with 70% of Initial Lumensmaintained,CRI>70andCCT5700K±355K.ManufacturesWordMark/NameEngraved/Embossing/ Screen printing on die cast housing to allow traceability/authenticity. Fixture shallbeIS10322Complianced.OEMMusthaveitsowninhouse NABLlabsetupforalltestingfacilitiesforLEDfixtures.(LM79/LM80)Certificate/reportwithliablewarrantyof product/accessoriesfromOEMshallbesubmitted.Allasperpre approvedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,referAnnexure\"A\"attachedwith this BSR . |
| 1250 | High Power LED Flood Light Minimum lumen output 10000 lm |
| 1251 | Providing&FixingofIK08,IP66protectedLEDStreetLight Luminaireonexistingbracket/pole.Fixturemadeofpowdercoated singlepiecepressurediecastaluminummaterialwithheat dissipationfinsonhousingwithUVstabilizedPC(UVstablization reportsubmittedforUVcover)/ToughenedGlasscoverand secondarylensoneachLED&shouldbeSMDtypeof3to5watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with HighvoltageCutoff@>=300VACandAutoresettingSafety, Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. TheluminaireshallbeBIScertifiedandTrademarkcertified.Life ExpectancyEqualormorethan50000burninghrswithMinimum 70%lumenmaintened,CRI>70andCCT5700K+355K.Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside drivercompartment.drivershouldbePhasetophaseprotectionof 440Vfor4Hrs.ManufacturesWordMark/Name Engraved/Embossingondiecasthousingtoallow traceability/authenticity.FixtureshallbeASPERIS10322 Complianced.OEMMusthaveitsowninhouseNABLlabsetupfor alltestingfacilitiesforLEDfixtures. (LM79/LM80)Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.AllasperpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 1252 | LED Street Light fixture with Minimum lumen output 8700 lm |
| 1253 | Providing&FixingofStreetlightbracketmadeoutfromfollowing size of \" B \" class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. asrequired.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1254 | 32 mm Dia. |
| 1255 | Providing & Fixing of IP - 65 protectedimpact resistant polycarbonate / Polysterene enclosures with knockoutforcable entry/outincludingfixingwithnut,bolt,fatneretcasrequired complete in all respect of following sizes.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1256 | 180 x 180 x 91 mm |
| 1257 | Supply,installation,testing&CommissioningofCopperwound distribution Transformer offollowingrating and%Impedance, 11/0.433KVDelta-StarConnected,VectorGroupDyn11,ONAN Cooledlosses as per IS 1180 part I 2014 (Fourth Revision) Level-1, withboltlesscoredesignincludingstandard accessories like conservator with prismatic oil level gauge, silica gel breather, Bucholz relay,pressed steel radiator fins, Radiator Valve(above 800 Kva)SuitablesizeHTcablebox,LTcableboxwithBusbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ),temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device,Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS:335-1953,EpoxyprimerandPUbasedpaintasTopcoat, Unidirectionalrollersforratingupto800kva&bi-directionalabove 800Kvarollerswithlockingarrangementetc.asrequired.The Transformershallbesubjectedtoroutinefactorytests(asper IS:2026 and IS:1180) including Temperature rise test inOEM\"s ownlab shall be witnessed by Department engineer Physically.Transformer shall be tested from CTLof discombefore charging of transformer&completeinstallaionmustbecertifiedfromElectrical InspectorateofficeasperIndianElectricityrule,(CTLtesting chargesandElectricalInspectionchargesshallbereimbursedby the department to the contractor)Following tests shall be carried out oneachtransformeratsitebyOEMenginerinpresenceof departmentauthorisedrepresentative:-a)Ratiotestoneach tapping.b)Resistanceofwindingsatprincipalandalltapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per preapprovedbyEngineerin-charge.Foradditionaltechnical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 1258 | 800 KVA with % Impedance 5.0 |
| 1259 | SITCofstarratedAluminiumwounddistributionTransformerof followingrating11/0.433KVDelta-StarConnected,VectorGroup Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as per IS2026-1977&lossesasdefinedasper2014(FourthRevision) Level-1 . including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise inwinding/oil 35-40 degree C upto 200 KVA& 40-45 degree C forabove200KVA,ISImarkeddrainvalve,DialtypeTemperature gauge,firstfillingoftransformeroilasperIS:335-1953,Epoxy basedpaint,includingcarryingofpre-commissionTesting& Charging of Transformer complete in all respect . TheTransformershallbesubjectedtoroutinefactorytests(asper IS:2026 and IS:1180) including testing from CTLof discombefore charging of transformer & complete installaion must be certified from ElectricalInspectorateofficeasperIndianElectricityrule,(CTL testingchargesandElectricalInspectionchargesshallbe reimbursedbythedepartment to the contractor). Allasperpre approved by Engineer in-charge. For additional technical parametersofproducts/ work, refer Annexure \"A\" attachedwith this BSR . |
| 1260 | 160KVA |
| 1261 | 200KVA |
| 1262 | 400 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 1263 | Supply&InstallationofD.P.StructureWithAIRBREAKSWITCH having following specifications A, B, C, D, E. All as per pre approved byEngineerin-charge.Foradditionaltechnicalparametersof products/ work, refer Annexure \"A\" attached with this BSR. A)Doublepolestructureon2noISMB(Ibeam)of size150x75 mm, 10 mtrlengthusing7noMSchanneleachofsize100mmx 50mmx2500mmcompleteinallrespectwithnuts,springs washers, clamps as required. B)Offloadtypegangoperated3-poleverticalflutetypeswitch suitablefor11KV;400A,3-ø,centralpostrotatingdoublebreak isolator complete with MS hardware , copper moving & fixed contact ,assemblyof9nospininsulator,GIpipeofsuitablelengthfor operation. C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators D)3piecenonlinearresistortype.lightingarrestorofapproved makesuitablefor3wire,11kvOverheadlinewith ratedvoltageof 9kv rms & nominal discharge current rating of 5 ka & complete with galvanizedclampingarrangementGIbolts,nuts,washeretcas required. E)3no11kvACSRconductorsmountedonpintypeinsularorsas required.6.GENERAL:Thegoshallbeoperatedbyhandoperated liver properly earthed with provision for locking mounted at 3’ |
| 1264 | SITCof11kV630Amps21KAfor3Sec.SF6insulated,outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU)manually operated in combination ofVCB modules andLoad Break switchconsistingofCopperbusbarinSF6insulated304(Non-FerriteNon-MagneticGrade)stainlesssteelenclosureofthickness 2.5mmwithmanometer.TheHVswitchgearandcontrolgear shouldbeconfirmingtoIEC-62271-100,IEC-62271-200-2003& IEC-60694-1996.TheRMUshouldbeinternalarctestedfor21KA for1SecondwithIAC-AFLclassificationforgastank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feederofRMUshouldhavevoltagepresenceindicator and compringoffollowings:-1no.microprocessorbasedSelfpowered numericalrelaywithoverCurrent/earthfault&shortcircuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden2.5VA,ratio50/1A,ClassofAccuracyclass5P10forO/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1nos.FaultPassageindicator,-Rightanglebootsforallthefeeder ModulesAllthetypetestcertificatesasperIECfromThirdpartyNABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation/SteelStructuretobepaidExtra)Allasperpre approvedbyEngineerin-charge.Foradditionaltechnical parametersofproducts/work,referAnnexure\"A\"attachedwith this BSR |
| 1265 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 1266 | SITCofHTmeteringcubicalpanelasapprovedByDISCOMs fabricatedout of18SWG CRCAsheet steelintwocompartment& MSangleofsize60mmX6mmhavingprovisionforFollowing: (i) ProvisionforfixingTrivector/Import-ExportMeter(Tobe supplied by DISCOMs) (ii) Provision for fixing of combined CT PT Set withCopperstripforConnection(TobesuppliedbyDISCOMs), iii) Test terminal Block,(iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections,etc. as required.AllasperpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1267 | SITC of LocalPush ButtonStation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 1268 | Heavy Duty AL & CU Lugs,Double Compression Cable Gland with Nickel Plated, Cable Tie, Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners, Clamps, Clips, Screw, Washers, Electrical Taps, HT Tap, Danger Plates, Condut Pipe, 40mmuPVC Pipe, 4.5 Kg. CO2 type portable fire extinguisher for Panel Room , Fire buckets with floor / wall mounting stand etc. required hardware & accessories for various sizes as per site requirements. |
| 1269 | 11KV Switchyard Civil work for Transformers Foundations, DP Structure, Chain Link Fencying 1500mm Height, MS Gate , 40mm Gravels, boundary wall, Earthing Chambers, HT/LT cable Trench,coversetc. |
| 1270 | 433VAC LT Panel for DMA Remote locationsin cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3+1 Phase 433 voltages, 50Hz, neutrally grounded, IP 5X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The indoor Panel switchegears (MCB, CTs, Contactors, auxiliary contacts, Space heater and lighting, RDOL for electrically operated laves with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel. Outdoor Panels shall be self-fabricate type only with Canopy, PLC & SCADA Compitible, complete operation carried for max. nos RDOL, Size - 450*300*600mm (for Electrically Operated Valve sin Remote)as per technical specifications and as directed by Engineer in charge. ( Prices are excluding EOV & EMF/BFM & fittings/ 3 Phase Power Connections at Remote locations ) |
| 1271 | AUTOMATION & PLC-SCADA WORKS |
| 1272 | Providing, installation, testing and commissioning of Diaphragm type Pressure Switches Sensing Element: Bellows / Diaphragm, Material ofsensorandotherwettedparts:SStype316,Housing:Diecast aluminum,Switchtype:Microswitch,Repeatability:±1%ofspan, Switch Contacts: 2 NO + 2 NC |
| 1273 | Chlorine Analyser : Transmitter : Range: 0.05 to 20 ppm, Power Supply 230 VAC, Input: 2 Digital Sensors - one for chlorine and second for pH, Output: 4-20mA HART, IP66/67 Protection / Tx protection cover required / Sensor Range 0-14 pH , able to transmit digital signal to transmitter, calibration data can be transferred to Transmitter , process temp: 65 deg cen/ Sensor range:0.05 to 20 mg/l. |
| 1274 | Providing,Installation,TestingandCommissioningofPressure Transmitter : Range:0-10Bar / Power Supply:24 V DC / Output: 4-20mAwithHART/Diaphragm:SS316L/ProcessConnection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 |
| 1275 | Providing,installation,testingandcommissioningofDiaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass,Overrangeprotection:125%ofmaximumpressure,Material ofsensorandotherwettedparts:SStype316,Housingmaterial: Die cast aluminum |
| 1276 | Providing,installation,testingandcommissioningofLevelSwitch( Conductivity)ConductivityProbes,Probeinsulation:Teflon,Probe head protection class: IP 65 of IS 13947 Part I, Probe head housing material: Aluminum |
| 1277 | Rigid for lengths ofup to 3 Mtr. |
| 1278 | Providing,installation,testingandcommissioningofONLINEUPS SYSTEM,SinglePhase230V,50Hzwith2hourbackupSMF battery bank as per specification |
| 1279 | 1 KVA |
| 1280 | Design,Manufacture,Supply,Installation, TestingandCommissioningofIndoortypePLC Panelofsizeapprox.800mmX500mmX 2000mm(LBH),Fabricatedoutofmin.2mm thickCRCAsheetcompletewithlatest configuration,necessaryprogrammingsoftware forPLC&SCADAandcomprisingofall accessories not limited to the following: DI 30No. DO 26No. AI 6No. AO 2No. MCB 16A DP 2No. MCB 6A DP6No. SMPS 100-240VAC/ 4.5A / 24 VDC 1No.Selector Switch (Auto/Manual) & Local / Remote2No. Control Relays1Lot Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with1No.Electronic Hooter1No. Control Transformer 200VA1No. Emergency STOP Push Button1No. Panel Cooling Fan & Filter2No.Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC3No. Push Button3No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc1Lot PanelHardware,lugs,terminations,ferruls, name plate Ect.1Lot UTILITY SOCET 16A, 3 PIN 2No. HMI Display 10 Inch, Colour1No. Isolators Dual Output, 24VDC1Lot |
| 1281 | Design,Manufacture,Supply,Installation, TestingandCommissioningofIndoortypePLC Panelofsizeapprox.800mmX500mmX 2000mm(LBH),Fabricatedoutofmin.2mm thickCRCAsheetcompletewithlatest configuration,necessaryprogrammingsoftware forPLC&SCADAandcomprisingofall accessories not limited to the following: DI 62No. DO 58No. AI 14No. AO 6No. MCB 16A DP 2No.MCB 6A DP6No. SMPS 100-240VAC/ 4.5A / 24 VDC 1No. Selector Switch (Auto/Manual) & Local / Remote2No. Control Relays1Lot Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with1No. Electronic Hooter1No. Control Transformer 200VA1No.Emergency STOP Push Button1No. Panel Cooling Fan & Filter2No.Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC3No.Push Button3No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc 1 LotPanelHardware,lugs,terminations,ferruls, name plate Ect. 1 LotUTILITY SOCKET 16A, 3 PIN 2 No. HMI Display 10 Inch, Colour 1 No. Isolators Dual Output, 24VDC1Lot |
| 1282 | Modular RTU complete with DI, DO, AI and modbus communication portsandpowersupply24VDCorforvariablepowersupplyusing batteries,rechargeablebatteries,solaror10.8VDCto28.8VDC with integrated modem; connection to control center via Tele Control Basic,DNP3,IEC60870-5-104andCommuncatinprotocols,on-board I/Os min. (8 DI, 4 DQ, 2 AI), configuration and diagnostics per (GSM/UMTS),MiniSIMcard,withadapterMicroSIMcardalso, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3,OpenVPN-Client.PanelEnclosureforCompactRTULocation, wall/floormountedalongwithwiringandrelatedaccessoriesand arrangementofmountingofRTU,ModemhavingIP-5XProtection. Panels shall be self-fabricate type only with Canopy. |
| 1283 | SITCofIntelligentManageableEthernetSwitchesproviding24x 10/100/1000FastEthernetports-and2dualpurposeuplink (provisionforCopper/FibreGigaconnectivity)withLANbased Software.TheLANbasedS/Wsupportsenhancedintegrated security,includingNetworkAdmissionControl(NAC),advanced qualityofservice(QoS),availabilityandscalablemanagementto enable new converged applications |
| 1284 | ProvidingandlayingStranded/FlexibleAnnealedeBarecopper conductor,XLPE/PVCinsulatedsuitablylaiduptogetheroverall polystertapedAl(innersheatedGISteelwireMylar/Drainwire) alongwithATCdrainwire,round/steelarmouredoverallPVC sheathed (ST-1) overall screenedCore armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1285 | 24 CORE, 1.0 sq. mm. |
| 1286 | 4 CORE, 1.0 sq. mm. |
| 1287 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (2 Pair * 0.75SQMM) |
| 1288 | Quad-bandGPRS/IOT/VPN/GSM/CLOUD 3G/4G/5G modemwithEthernetbridge/router/ serial server (RS232/485) interface. |
| 1289 | The Cloud based Water management & Data Monitoring system for the real time data analysis of the field struments/pumps/valves/ actuators located in the CPS / IPS/ any other field remote locations. 16 pump houses & the system working, a dedicated Cloud Server Instance will be provided with Database to store historical data of up to 5 years. The PLC system available in each pump house will send the data through Sim-based Modem to the Cloud at a time interval of 15 seconds. A Dashboard with all mentioned Locations will be created with an Overview of each Pump house & further the status of Pumps, running hours, status of valves, Tank Water Level, Pressure and all-important values will be displayed & stored in database.In total 3 users will be provided with the Monitoring Access of the system & 1 user will be provided with the Operation Access. A Daily/Weekly/Monthly Report Generation & download option will be provided with a standard predefined format. |
| 1290 | Cloud based Water management & Data Monitoring systemDash Board (12 Months * 5 years) |
| 1291 | Cloud based Water management & Data Monitoring system setup 5-year infrastructure Design & Development |
| 1292 | Cloud based Water management & Data Monitoring systemmonthly Recurring Charges (12 Months * 5 years) |
| 1293 | Instrumentation |
| 1294 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU), Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC -50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1295 | EFM100 mm |
| 1296 | EFM 150 mm |
| 1297 | EFM 200 mm |
| 1298 | EFM 250 mm |
| 1299 | EFM 300 mm |
| 1300 | EFM 400 mm |
| 1301 | EFM 450 mm |
| 1302 | EFM 500 mm |
| 1303 | EFM 600 mm |
| 1304 | House Service Connection |
| 1305 | Providing Household Tap Connection as per technical specification and approved drawing as per relevant IS code (amended up to date) from uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using PP/MS saddle piece (Complete job).This job includes digging out suitable size of pits and trench for laying service line in all kinds of soil (excluding road); depositing and refilling of pit & jhiri with watering & ramming /compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting duly approved in accordance with specification for potable water including MS/PP saddle piece, gunmetal ferrule 4.0 mm , GM Full-way Valve (IS:778 Mark) or ball valve (min. weight 165 gm) and specials, below ground level 20 mm nominal dia MDPE pipe PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Three layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above ground level using 20 mm dia PPR-C pipe with standard PPR fittings/ 15 mm dia GI pipe with fittings in the premises for fixing a tap / meter box (excluding) , inc accessories with flushing, cleaning, disinfecting and testing of pipe line complete required for making of service connection complete in all respect including labour charges . The service line should be laid at least 45 cm below ground level.Note: Road cut and restoration is not part of this item and paid separately. |
| 1306 | For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr. |
| 1307 | Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be doneby using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge.. |
| 1308 | Supply, Installation of 15 mm size AMI LoRa WAN/RF based Water Meters, conforming to ISO 4064:2005/ISI standards with MID/ISI approvalincluding Collection & Verification of Consumer Data, Automated Meter Reading in the identified DMAs of MC Jaipur Greater. |
| 1309 | Civil Work |
| 1310 | Construction of Panel Room on CWR at Dev Nagar |
| 1311 | Providing and fixing precast cement concrete coping 1 : 2 : 4 mix 50 mm thick complete as perspecification : |
| 1312 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1cement: 3 coarse sand) and making good the joints and cost of plastizers ( if required) excluding the cost of centering, shuttering and reinforcement for Beams, suspended floors, roofs, griders having lopes up to 15º, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases etc. M20 grade Nominal Mix / Design Mix ( lintel doors , window and ventilation ) |
| 1313 | Half brick masonry in Superstructure , above plinth level upto floor V level using bricks of designation 75; 5.8.2 Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 1314 | Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades ceramic glazed vitrified tiles with water absortion less than or equal to 0.08% confirming to IS:13753 & IS : 15622 on walls, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar).Size 600mm x 1200mm |
| 1315 | Providing & fixing door, window, chowkhats and other frames, including antitermite treatment, M.S. flat, hold fasts of size 250 x 40 x 3mm fixed with M.S. bolt 5mm dia 50mm long duly embedded in cement concrete M-15 grade :Nigeria teak wood Grade - I. |
| 1316 | Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure \"A\" : 35 mm thick, commercial Veneer Both side. |
| 1317 | Extra for providing external lipping with 2ndclass teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured) ; for door leaf shutt |
| 1318 | Extra for providing other type of fittings as mention in annexure A ( as approved by EI) : Stainless steel fittings. (for door leaf shuter) |
| 1319 | Providing and fixing bright finished Mortice lock of approved make Godrej or equivalent with pair of CP handles for doors with necessary screws etc complete (Best make of approved quality) as per direction of Engineer-in-charge. |
| 1320 | Providing & Fixing mica of approved make for inner/outer side of shutters with fevicol & nails completeas per approved by engineer in charge.0.8mm thick mica |
| 1321 | Providing brass handles/peg stays and fittings in place of oxidized fitting Sqm. 5% |
| 1322 | 5mm thick plain glass instead of 4mm thick plain glass Sqm. 95.00 |
| 1323 | Grading roof water proofing treatment with water profing compound :Cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 1324 | Providing batta (gola) 75 mm x 75 mm in cement concrete (1 : 2 : 4) including finishing with cement mortar 1 : 3 as per standard design. |
| 1325 | Plaster on new surface on walls in cement sand mortar 1:4 including racking of joint etc. complete fine finish : 20 mm thick |
| 1326 | 6 mm cement plaster to ceiling of mix 1 : 3 (1 cement : 3 fine sand).; Celling plaster |
| 1327 | Making grooves as per design in plaster 10 mm to 20 mm wide.; (add; 20 % R.M.of plaster work.) |
| 1328 | Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth completeNew Plastered Surface (three or more coats) |
| 1329 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specifications including primer coat and protecting coat including scaffolding and safety provision. Trowel Finish av. thickness 2000 to 2500 microns. |
| 1330 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1331 | Short point (up to 3 mtr.) |
| 1332 | Medium point (up to 6 mtr.) |
| 1333 | Long point (up to 10 mtr.) |
| 1334 | 3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexiblecopper earth conductor 1.1 kV grade(IS:694) inrecessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket,Modular face plate with grid plate, screws, making connections, testingetc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E- 05 & E - 07 For additional technical p |
| 1335 | On board |
| 1336 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1337 | 20 mm |
| 1338 | 25 mm |
| 1339 | 4.2 Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor of alum. alloy braid in existing surface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1340 | Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 & confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair forIdentification etc. as required. For additional technical parameters ofproduct / work refer Annexure \"A\" attached with this BSR;4.3.4 4 pair |
| 1341 | P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ;5.1.1 1.2 mm thick M. S. Sheet boxes ; |
| 1342 | 100mm x 100mm x 60mm |
| 1343 | 200mm x 250mm x 75mm |
| 1344 | P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1345 | P & F 1.00mm thick M.S. Recessed concealed box, round of size 150 mm dia, depth 100 mm complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1346 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1347 | Single pole MCB (With B/C curve tripping Characteristics) |
| 1348 | 6 A to 32 A rating |
| 1349 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947- III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 35sq.mm. IP 20 contact protection and fitted in existing distribution board /sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR;6.2.3 Four pole Isolator; 63 A rating |
| 1350 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1351 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 1352 | 6 Way (6+2) |
| 1353 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial gradePolycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 1354 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1355 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1356 | 6/16 A shuttered socket |
| 1357 | 7.29 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR; 7.29.1 5 step fan regulator 2 Module 360 dgree rotating |
| 1358 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1359 | Modular MCB 6 A to 32 A SP |
| 1360 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1361 | 3 Module Each 86.0 |
| 1362 | 6 Module Each 114.0 |
| 1363 | 8 Module Each 155.0 |
| 1364 | 12 Module Each 214.0 |
| 1365 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1366 | 11.3 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1367 | 10.0 Sq. mm, 4 core4 core |
| 1368 | Providing & Fixing of 1200 mm sweep BLDC technology power saving ceiling fan which can withstand on votage fluctuations from 140 volts to 240 volts ,power factor not less then 0.9 , service value (CMM/W) minimun 6.85 , air delivery minimun 220 CMM, speed minimum 330 RPM ( tolerance as per IS:374 2019 ) THD less then 10% and complete with down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe up to 80 cm , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . 15.4.1 Without Remote |
| 1369 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 300 mm sweep(900/1400 RPM) |
| 1370 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1371 | 17.3.1 Recessed Mounting ;Minimum lumen output 650 lm |
| 1372 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required.Gr I |
| 1373 | 3x 1.5 sq.mm |
| 1374 | 2 x 2.5 sq. mm. + 1x1.5sqmm ( All light and power Ckt) |
| 1375 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (AC Ckt) |
| 1376 | 4 x 10 sq.mm (Sub main) |
| 1377 | 1 x 6 sq.mm (With sub main ) |
| 1378 | Construction of boundary wall of Brick/ stone masonry as per enclosed GA drawing, scope of work and technical specifications complete work in all respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonry in CM: 1:6 section of foundation above PCC, 600 mm (W)x 450 mm (D) and 450 mm (W) x 450 mm (D) 4. Superstructure work: Stone masonry in CM: 1:6, W-300, height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonry and cement mortar plaster 20 mm thick on brick masonry in CM 1:6.6. Expansion joint shall be on every 30 mtr.7. On top of wall there shall be CC Coping 75 mm thick (1:2:4) shall be provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 1379 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 1380 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1381 | For Class-AA loading |
| 1382 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m-for pipe size-up to 100 mm |
| 1383 | Sluice valve chamber of size 1.17m x 0.95m x1.47mfor pipe size-from 125-to-150mm |
| 1384 | Sluice valve chamber of size 1.26m x1.185m x1.88m for pipe size-from 200-to-300mm |
| 1385 | Sluice valve chamber of size 1.39m x1.43m x2.245mfor pipe size-from 350-to-450mm |
| 1386 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm |
| 1387 | For in-campus Valve Chambers |
| 1388 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm (Shall be made as per GA Drawing and field Requirement) |
| 1389 | Construction of RCC Air valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, Plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1390 | For Class-AA loading |
| 1391 | Air valve chamber of size0.9m x1m x1.695mfor air valve size-from 50 mm-to-80mm |
| 1392 | Air valve chamber of size1m x1.1m x1.945m for air valve size of 100mm |
| 1393 | Air valve chamber of size1.05m x1.4m x2.42mfor air valve size of 150mm |
| 1394 | Air valve chamber of size1.325m x1.7m x2.875m for air valve size of 200mm |
| 1395 | RTU Structure (33 nos) Repairing of OHSR (14 nos) and Pumping House (4 nos) |
| 1396 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed : All kinds of soil |
| 1397 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. |
| 1398 | M15 grade Nominal Mix 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20mm nominal size). |
| 1399 | M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 1400 | Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement.M20 grade Nominal Mix / Design Mix |
| 1401 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required ) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc.M20 grade Nominal Mix / Design Mix |
| 1402 | Providing M-35 grade concrete by using cement as per codal provision instead of M-20 grade design mix. |
| 1403 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc. |
| 1404 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : |
| 1405 | Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates, anchor blocks, sills, chhajjas, lintel, beam, plinth beam etc. |
| 1406 | Columns, pillars, posts and struts etc. |
| 1407 | Arches, domes, vaults etc exceeding 6 Mtr span |
| 1408 | Add extra for additional height in centring, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan are is to be measured) |
| 1409 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor five level. (\"Original producers\" who manufacture billet directly from iron ores and roll the bilets to produce steel conforming to IS:1786) |
| 1410 | Cold twisted deformed bars (IS : 1786). |
| 1411 | Thermo-mechanically Treated bars (Conforming of relevent IS code) |
| 1412 | 5.2 Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : 5.2.1 Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 1413 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : |
| 1414 | Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 1415 | Half Brick work with mechanised autoclaved flyash lime bricks conforming to IS: 12894 :2002 of class designation 100 in superstructure above plinth level upto floor V level in.Cement mortar 1 : 4 (1 cement : 4 coarse sand) Sqm 586.00 |
| 1416 | Random Rubble stone masonry with hard stone in superstructure aboveplinth level and upto five levelabove 30cm. thick walls in :Cement Mortar 1:4 ( 1-Cement : 4-Sand). |
| 1417 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting (height upto 10 m) , fixing in position and applying a priming coat of approved steel primer all complete: |
| 1418 | Supply and fixing in cement mortar welded hand railing made out of MS round or square bars, flats etc. for staircase or verandah as per design complete in all respect (wooden or PVC hand railing to be paid extra) with priming coat of red oxide. |
| 1419 | Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide |
| 1420 | Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance. |
| 1421 | Providing and fixing precast cement concrete M-20 grade (Using mechanical Concrete Mixer) kerb stone top and bottom width 115 and 165 mm respectively, 250 mm high on 150 mm thick PCC M-10 grade foundation as per design, including fixing at site as per clause 408 of MoRT&H Specification including all material, labour, machinery, lighting, guarding and maintenance of diversion. |
| 1422 | Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : |
| 1423 | 20mm thick |
| 1424 | Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade including all scaffolding:INTERIOR;Two or more coats on new work including prepartion of base with primer, putty, lippy etc complete in all respect. |
| 1425 | Painting exterior surface of Wall with 100% acrylic exterior paint of approved brand and manufacture to give an even shade with two or more coats including prepartion of base with sand papering, primer, putty, etc complete in all respect including scaffolding and safety provision |
| 1426 | New Work |
| 1427 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specificationsincluding primer coat and protecting coat including scaffolding and safety provisionRoller Finish av. thickness 400 to 500 microns.; / Pump house & CWR PAINT WORK |
| 1428 | Painting with syntheticenamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work.,Note:Pump & other railing works,door windows,including etc, |
| 1429 | Painting (two or more coats) on rain water soil, waste and vent pipes and fitting with black anticorrosive bitumastic paint of approved brand and manufacture over and including a priming coat of ready mixed zinc chromate yellow primer on new work : |
| 1430 | Lettering with black Japan paint of approved brand and manufacture. |
| 1431 | 9.19 Providing and fixing steel glazed doors windows and ventilator shutters of standard rolled steel section (IS 1038- 1983) joints mitred and welded with steel lugs 13x3mm, 10cm. long embedded in cement concrete block 15x10x10cm. of 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) or with wooden plugs and screws or rawl plugs and screws with fixing clips or with bolts and nuts as required including providing and fixing of plain glass panes 4mm thick with cooper glazing clips and special metal sash putty of approved make or metal beading with screws complete including priming coat of approval steel primer, excluding the cost of metal beading and other fitting except necessary hinges of pivots steel handles peg stay etc. as required |
| 1432 | Windows side hung /Ventilators top or centre hung (openable) |
| 1433 | Providing & Fixing Premium Quality white glazed vitreous china Sanitary Wares (IS:2556 Mark) of approved make as per direction of Engineer-in-charge including cutting and making good the wall and floor. Wall Mounting European type W.C. |
| 1434 | Providing & Fixing premium qulaity WVC Urinal with PVC waste pipe, dome couplings, concealed iron brackets or screws etc. complete.; Flat Back (large) or half stall size 590x375x390 mm. |
| 1435 | Carriage of Materials by mechanical transport including loading, unloading and stacking ::Cost of carriage including loading, unloading & stacking for first 50 m. |
| 1436 | 4.13 Earth filling with available surplus soil excavated from foundations and taken only from outside of building plinth in layers not exceeding 20cm in depth, consolidating each deposited layer including ramming and watering and consolidation with lead up to 50 m and lift upto 1.5 m. |
| 1437 | Providing and fixing of precast concrete interlocking tiles of desired shape of M 30 grade manufactured from fully computerized automatic stationery hydraulic vibrio pressed machine and fully computerized automatic batching plant of class A1/A2 as per BS 6717:2001. The CC interlocking paving blocks be laid on average 50mm. thick bed of coarse sand and the joint is to be filled with fine sand. Laying procedure on compacted sub-base as defined. Complete job is to be executed as per the instruction of Engineer incharge. The rates to be inclusive of all lead & Lifts etc. complete as per specifications. Tensile splitting strength, abrasion and braking load etc. as per BS 6717:2001, Grey cement |
| 1438 | 100mm thick |
| 1439 | Providing and fixing 28 mm thick door shutter made of solid PVC foam profile with homogenous fine cellular structure having smooth outer integral skin having 71mm width & 28mm thick as styles and rails. Joints are made using solvent adhesive and GI \"C\" sections (39mm x 19mm x 0.6mm thick) or M S pipe (40mm x 20mm ) stiffener frame insert & telescopic polymeric \"L\" corners .The panel shall be filled with 3mm thick high - pressure compact laminate as per manufacturer\"s specifications and direction of Engineer-in charge, cover moulding shall be provided for covering fixing screws and elegant look.( for W.C. and bathroom door shutter). |
| 1440 | HT Metering Room and Campus Development work of Jhalan Gram and Dev Nagar |
| 1441 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level. |
| 1442 | In all types soils/saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc. |
| 1443 | Providing and fixing of 60mm thick precast cement concrete interlocking paver block casted with rubber moulds in approved reflective colour and design having minimum compressive trength of 300 kg/ sq cm. The CC paving blocks be laid on average 50mm thick bed of coarse sand and the joint is to be filled with fine sand. Laying procedure on compacted sub-base as defined. Complete job is to be executed as per the nstruction of Engineer in charge. The rates to be inclusive of all lead & Lifts etc. complete as per specifications. |
| 1444 | In out side of Room |
| 1445 | Providing 1.20 metre high fencing with angle iron posts 50 mm x 50 mm x 6 mm at 3 metre center to center with 0.40 metre embedded in M15 grade cement concrete, corner, end and every 10th post to be strutted, provided with welded steel wire fabric of 75 mm x 50 mm mesh or 75 mm x 25 mm mesh and fixed to iron posts by flat iron 50 x 5 mm and bolts etc. complete in all respects including all material, labour |
| 1446 | Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering - All work upto plinth level : |
| 1447 | 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 1448 | 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size). |
| 1449 | 1:3:6 (1 Cement : 3 fine/ coarse sand : 6 graded stone aggregate 40 mm nominal size) |
| 1450 | 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 20 mm nominal size). |
| 1451 | 1:5:10 (1 cement : 5 fine/ coarse sand : 10 graded stone aggregate 40 mm nominal size) |
| 1452 | Providing and laying damp-proof course with cement concrete grade M-15 (1 : 2 : 4) mortar prepared with 1% solution of water-proof compound complete as per specification |
| 1453 | 75mm thick. |
| 1454 | Centring and shuttering with plywood or steel sheet upto two stories or height upto 7.5 metre above plinth level including strutting, propping etc. and removal of form for :. |
| 1455 | Suspended floors, roofs, landings, balconies and access platform. |
| 1456 | Reinforced cement concrete work in beams, suspended floors, roofs having slope upto 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases upto two stories excluding the cost of centring, shuttering, finishing and reinforcement: M-20 Grade Concrete (1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size) -As per design mix) |
| 1457 | Reinforcement for R.C.C. work at all levels including straightening, cutting, bending, placing in position and binding all complete. Cold twisted bars |
| 1458 | Quantity as per CC M-20 Item No. 7 @ 90Kg/cum |
| 1459 | Brick work with machine moulded perforated bricks of class designation 125 conforming to IS: 2222 -1991 in superstructure above plinth level upto two stories in cement mortar 1:6 (1 cement : 6 coarse sand) : |
| 1460 | With Modular bricks |
| 1461 | Random rubble masonry with hard stone in foundation and plinth |
| 1462 | Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 1463 | Cement mortar 1:3 (1 cement : 3 coarse sand) |
| 1464 | Extra for random rubble masonry with hard stone in superstructure above plinth level and upto two stories. |
| 1465 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 1466 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths interlocked together through their entire length and jointed together at the end by end locks mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete including the cost of providing and fixing necessary 27.5cm long wire springs grade No.2 and M.S. top cover of required thickness for rolling shutters. 80x1.25mm M.S. laths with 1.25 mm thick top cover. |
| 1467 | Providing and fixing factory made ISI marked steel glazed doors, windows and ventilators side /top /centre hung with beading and all members such as F7D, F4B, K11 B and K12 B etc. complete of standard rolled steel sections, joints mitred and flash butt welded and sash bars tenoned and rivetted with 15x3mm lugs, 10cm long, embedded in cement concrete blocks 15x10x10cm of 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) or with wooden plugs and screws or rawl plugs and screws or with fixing clips or with bolts and nuts as required, including providing and fixing of hinges, pivots, float glass panes with glazing clips and special metal sash putty of approved make and a priming coat of approved steel primer excluding the cost of metal beading and other fittings except necessary hinges or pivots complete as per approved design. |
| 1468 | Providing and fixing bright finished brass casement window fasteners or peg stays to windows/ ventilators with necessary welding and machine screws etc. complete. |
| 1469 | Kota stone slab flooring 25mm thick over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) Area of each slab 900 to 2000 sqcm |
| 1470 | Kota stone slabs 25 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, ncluding rubbing and polishing complete. |
| 1471 | Providing and fixing on wall face Unplasticised Rigid PVC Single socketed pipes rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion |
| 1472 | 110 mm diameter |
| 1473 | Providing and fixing on wall face Unplasticised - PVC moulded fittings/ accessories for nplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. |
| 1474 | 110 mm Bend 87.5° |
| 1475 | Providing and fixing Unplasticised -PVC pipe clips of approved design to Unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 1476 | 110 mm diameter |
| 1477 | Cement plastering including T&P, scaffolding, material and complete labour, including cost of water, curing, racking of joints etc. with 20 mm cement plaster of mix : |
| 1478 | 1:3 (1 cement : 3 fine/ coarse sand) |
| 1479 | 1:4 (1 cement : 4 fine/ coarse sand) |
| 1480 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade |
| 1481 | New work (two or more coats) over and including priming coat with cement primer. |
| 1482 | Finishing walls with water proofing cement paint of required shade |
| 1483 | New work (Two or more coats applied @ 3.84 kg/10 sqm). |
| 1484 | Finishing walls with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : |
| 1485 | Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/ 10 sqm of approved brand or manufacture |
| 1486 | Providing and fixing bright finished brass hard drawn hooks and eyes |
| 1487 | 300 mm |
| 1488 | Wiring of light point/ fan point/ exhaust fan point/ call bell point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694) and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) vergin material PVC conduit & it\"s all accessories( J.B. , Bends etc.) , round tiles,18 SWG G.I. box with earth terminal, 6 A switch , 3 pin ceiling rose/ Lamp holder / 3 point Connector, 3.0 mm thick ISI marked phenolic laminated sheet (IS : 2036 - 1995), Al. alloy/ cadmium plated iron screws 20 mm cup washers etc. all as per pre approved by Engineer in charge, making connections, testing etc. complete as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E-04, E-05 & E-07. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1489 | Short point (up to 3 mtr.) |
| 1490 | Medium point (up to 6 mtr.) |
| 1491 | Long point (up to 10 mtr..) |
| 1492 | Providing & Fixing of ISI marked (IS:1293) 6 amp unbreakable 3 pin plug top with lamp indicator as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1493 | short point |
| 1494 | Providing & Fixing of ISI marked (IS:1293) 16 amp unbreakable 3 pin plug top with lamp indicator as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/work , refer Annexure \"A\" attached with this BSR . |
| 1495 | short point |
| 1496 | Providing & Fixing of ISI marked (IS :3854) 6 amp. flush type non modular switch as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material, minimum width of switch toggle ( PUSH PART ) should not less then 16 mm, brass terminal & captive screws including cutting hole in tile and making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1497 | Providing & Fixing of ISI marked (IS :3854) 16 amp. flush type non modular switch as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material , minimum width of switch toggle ( PUSH PART ) should not less then 16 mm, brass terminal & captive screws including cutting hole in tile and making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1498 | Plate Earthing as per PWD specification for electrical Works as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1499 | Supply and erection of M S swaged tubular pole conforming to IS:2713-1980 (part I to II) with galvanised base plate in position including excavation of the pit and filling the same with C.C. of M-20 grade (1:1.5:3) from base plate to 50 cm above ground level, with the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50 cm beyond 114.3mm outer dia around the pole. Duly finished with cement plaster, earthing terminals, cable entry, GI cable sleeve complete as required. After eraction pole shall be painted with two coat of red oxide primer and two quote of enamel paint of silver colour as per the direction of Engineer incharge.The pole shall be fabricated by using ISI mark tube for structural purpose of following height & designation. ( See Table P - 02 for specs. ) complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 1500 | Painintg of existing structureSR and other building, minor repair etc within the campus At Jhalana Gram OHSR, Himmat Nagar OHSR and Mahaveer nagar |
| 1501 | Horticulture Work |
| 1502 | O&M |
| 1503 | Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency) as per Scope of Work & terms & conditions of contract foryears after defect liability period of one year DLP (except power feeder, IEC & miscellaneous provision) for Water Supply Project |
| 1504 | 1st year |
| 1505 | 2nd year |
| 1506 | 3rd year |
| 1507 | 4th year |
| 1508 | 5th year |
| 1509 | (C). SUB TOTAL OF DIVISION SOUTH S-3 |
| 1510 | (D). DIVISION SOUTH S-4 |
| 1511 | Pipeline |
| 1512 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended upto date), with internal cement mortar lining for potable water with rubber ring (EPDM/SBR) joints as per IS: 5382-1985 (excluding special accessories) complete including all material, labour, hydraulic testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 1513 | 100 mm |
| 1514 | 150 mm |
| 1515 | 200 mm |
| 1516 | 250 mm |
| 1517 | 300 mm |
| 1518 | 350 mm |
| 1519 | 400 mm |
| 1520 | 450 mm |
| 1521 | 500 mm |
| 1522 | Providing, lowering, laying, aligning, fixing in position at and jointing at all level/ depths ISI marked HDPE pipes of PE-100 grade & PN-6 for potable water as per IS 4984 (amended upto date) in trenches in complete including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 1523 | 110mm dia |
| 1524 | 125mm dia |
| 1525 | 140mm dia |
| 1526 | 160mm dia |
| 1527 | 180mm dia |
| 1528 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 1529 | Depth upto 1.5 m |
| 1530 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level. |
| 1531 | In all types soils/ saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc. Depth upto 1.5 m |
| 1532 | Dismantling of cement concrete pavement by mechanical means using pneumatic tools, cutting theperipheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposalof dismantled materials up to a lead of 1000 metres including allowances for any additional dismantling beyond the drawings (measurement for payment to be as per standard drawings), rehandling of material/earth to complete the task. |
| 1533 | Dismantling of flexible pavement for pipe line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re_x0002_handling of material/earth to complete the tasks per technical specification and scope of work. |
| 1534 | Bituminous courses |
| 1535 | Granular courses |
| 1536 | Barricading with Sal ballies as per design including tying with vertical post by coconut strings including digging out holes in all types of soil complete in all respect with two horizontal members height 1.2 m upto 1.5m above ground level and vertical supports upto 2.5 centre and upto 3 days period including removal and cleaning the site complete in all respect & including dressing of sides and providing retro reflective tapes for traffic safety as per direction of Engineer-in charge in all types of soil. |
| 1537 | Carriage of Materials by mechanical transport including loading,unloading and stacking ::Sand, bazri, ballast, kankar- Lead upto 5 Km |
| 1538 | VALVES |
| 1539 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as perdirection of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1540 | Manually operated class PN 1.0 |
| 1541 | 250 mm HW |
| 1542 | 300 mm HW |
| 1543 | 350 mm with Gear |
| 1544 | 400 mm with Gear |
| 1545 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1546 | Motorized Sluice Valves with Electric Actuator with integral starter of Class PN 1.0 |
| 1547 | Inlet Pipe at Bisalpur line |
| 1548 | 200 mm dia |
| 1549 | 250 mm dia |
| 1550 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Double Acting Kinetic Air Valve with isolating Sluice Valve of approved makes for following pressure rating & dia complete, confirming to IS: 14845-2000 (amended up to date) and of following specifications: Body , Cover and Cowl - Grey Cast Iron as per IS:210- FG 200 ,Float -Stainless Steel AISI 304 / IS: 3444 , Float Guide_x0002_HBT1.HP Orifice- HTB2/ SS,Body seat ring - Leaded tin bronze/ SS .Seal ring and face ring - PDM/NBR ,Ends flanged according to IS 6418,Fastners - CS, Epoxy paint inside outside of food grade safe for drinking water ,Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1551 | Class PN 1.0 |
| 1552 | 80 mm dia |
| 1553 | Providing, lowering, laying, aligning, fixing in position in pipe line, Resilient Seated D/F DI Sluice valves of approved make & design standard of following dia complete (including jointing & jointing material ) including all material, labour, testing and commissioning along with pipe line as per Technical Specification & as per direction of Engineer. (Calculation of Valve attached at Annex -E16(3) |
| 1554 | Manually operated class PN 1.6 |
| 1555 | 80 mm dia |
| 1556 | 100 mm dia |
| 1557 | 150 mm dia |
| 1558 | 200 mm dia |
| 1559 | 250 mm dia |
| 1560 | 300 mm dia |
| 1561 | 350mm dia |
| 1562 | 500 mm dia |
| 1563 | Electrically Operated & SCADA Compatible class PN 1.6 |
| 1564 | 150 mm dia |
| 1565 | 250 mm dia |
| 1566 | 300 mm dia |
| 1567 | 400 mm dia |
| 1568 | 500 mm dia |
| 1569 | 600 mm dia |
| 1570 | Providing, lowering, aligning, fixing in position in pipe line, DIdouble flanged resilient seated Dual plate check valve of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body and cover inside and outside .Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410 , Hinge SS AISI 316/304,SpringSS AISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick .Suitablesupport structure as per directions of EICincluding jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1571 | Class PN 1.6 |
| 1572 | 100 mm dia |
| 1573 | 150 mm dia |
| 1574 | 200 mm dia |
| 1575 | 250 mm dia |
| 1576 | 300 mm dia |
| 1577 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, DI Body Flanged End Tamper proofKinetic Air Valve of approved makes of following pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(amended up to date) Body, High pressure cover , Low pressure cover, Cowl andJoint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fasteners - CS/ Galvanised steel, Outlet of big orifice will have a screen to prevent Tamper of float,with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amendedup to date) PN 1.6 ratings Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1578 | Class PN 1.6 |
| 1579 | 50 mm dia |
| 1580 | 80 mm dia |
| 1581 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 410/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318-LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318-LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. Insertion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1582 | Inlet Pipe from Bisalpur |
| 1583 | Plunger Type Flow Control Valve |
| 1584 | 200mm dia |
| 1585 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 1586 | 80 mm dia PN-1.0 |
| 1587 | 100 mm dia PN-1.0 |
| 1588 | 150 mm dia PN-1.0 |
| 1589 | 200 mm dia PN-1.0 |
| 1590 | 250 mm dia PN-1.0 |
| 1591 | 300 mm dia PN-1.0 |
| 1592 | 350 mm dia PN-1.0 |
| 1593 | 400 mm dia PN-1.0 |
| 1594 | 500 mm dia PN-1.0 |
| 1595 | 600 mm dia PN-1.0 |
| 1596 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1597 | 150 mm dia. |
| 1598 | 150 mm dia. |
| 1599 | 200 mm dia. |
| 1600 | 250 mm dia. |
| 1601 | 300 mm dia. |
| 1602 | Clear Water Reservoir |
| 1603 | Construction of RCC (Dome type) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: - |
| 1604 | a) Topographic survey, preparation of site contour plan, conducting SBC testand its approval from departmentbefore construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction.b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour and material charges including providing and fixing of accessories such as SS ladder, SS manhole frame and covers, water level indicator (float type), SS ventilator with SS screen, float valve, puddle collars, G.I. pipe railing around walk way, Top Dome/Slab, Staircase.c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g) Providing and applying three coats of cement-based paint on the remaining external surface area of the structure. |
| 1605 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder from roof slab to bottom Slab, inside container. Providing and fixing water level indicator (Float type).i) Providing and fixing MS ladder from ground to top slab. j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k)Providing and fixing of 150mm wide water bar for the construction joints in the container.l) Providing and fixing CI/DI puddle collars the vertical wall for connecting inlet, outlet, overflow and washout pipes of the reservoir.m) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. |
| 1606 | Sector-11 ( Mansarovar) |
| 1607 | Construction of RCC (Flat Slab Rectangular) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: |
| 1608 | a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approvalfromdepartment beforeconstruction.Submissionandapprovalofconcretemix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour andmaterialchargesincludingprovidingandfixingofaccessoriessuchasSSladder,SS manhole frame and covers, water levelindicator (floattype), SSventilator withSSscreen, float valve, puddle collars, G.I. pipe railing around walk way, Flat/Slab, rectangular .Staircase c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g)Providingandapplyingthreecoatsofcement-basedpaintontheremainingexternal surface area of the structure. |
| 1609 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder fromroofslabtobottomSlab,insidecontainer.Providingandfixingwaterlevelindicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k) Providingandfixingof150mmwidewaterbarfortheconstructionjoints inthe container.l)ProvidingandfixingCI/DIpuddlecollarstheverticalwallforconnectinginlet,outlet, overflow and washout pipes of the reservoir.m)Inlet,outlet,overflow,washoutpipesandvalvesarenotincludedinthiswork, provision for the same shall be taken separately. |
| 1610 | Rates for RCC Partially Underground type clear water reservoir SBC 10 T/sqm, SEISMIC ZONE-2 & 3. |
| 1611 | Budh Vihar ( Pratap Nagar) |
| 1612 | Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 1613 | 200 mm |
| 1614 | 250 mm |
| 1615 | 400 mm |
| 1616 | PUMPING MACHINERY |
| 1617 | Providing, installation, testing and commissioningof Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, class \"F\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein all respect as perspecification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 1618 | 37 KW; Proposed Budhsingh Pura CWR to Budhsinghpura Pressure Supply Zone |
| 1619 | 18.5 KW; Proposed SFS CWR to Sector -11 |
| 1620 | Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at synchronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts, Cement concrete foundation etc. complete with all respect as per the specification and scope of work and direction of Engineer in Charge of following range of duty conditions.Note: Duty condition of required pump shall also be mentioned in BoQ. |
| 1621 | Pump HouseMansarovar Sector 7 |
| 1622 | Discharge 81 to 90 LPS and head 61 to 70 M |
| 1623 | Pump HouseMansarovar Sector 9 |
| 1624 | Discharge 31 t0 40 LPS and head 31 to 40 M |
| 1625 | Pump HouseMansarovar Sector10 |
| 1626 | Discharge 20 to 30 LPS and head 31 to 40 M |
| 1627 | Pump HouseMansarovar SFS |
| 1628 | Discharge 61 to 70 LPS and head 31 to 40 M |
| 1629 | Pump HouseMansarovar Sector 1 |
| 1630 | Discharge 51 to 60 LPS and head 31 to 40 M |
| 1631 | Pump HouseMansarovar Sector 3 & 6 |
| 1632 | Discharge 71 to 80 LPS and head 31 to 40 M |
| 1633 | Pump House Budh Singh Pura Pratap Nagar (For Budhsingh pura Zone-2 Nos) (For Gandhi Vihar Zone- 2Nos) |
| 1634 | Discharge 71-80 LPS and Head 31-40 M (Budhsinghpura & Gandhi Vihar) |
| 1635 | Pump House Sector 76 Pratap Nagar |
| 1636 | Discharge 20 to 30 LPS and Head 20-30 M (Sector 76) |
| 1637 | Pump House Sector 3 Pratap Nagar |
| 1638 | Discharge 81 to 90 LPS and Head 31-40 M (Sector 3) |
| 1639 | Discharge 31 to 40 LPS and Head 31-40 M (Sector 3) |
| 1640 | Pump House Pratap Nagar Sector 5, Sector 7, Sector 10, Sector 16, Sector 17 |
| 1641 | Discharge 101-120 LPS and Head 31-40 M (Sector 5-3, Sector 7-3, sector 10-2, Sector16-2, Sector 17-1) |
| 1642 | Pump House Pratap Nagar Sector 7 , Sector 10 |
| 1643 | Discharge 41 to 50 LPS and head 31 to 40 M( Sector 7-1, sector 10-2) |
| 1644 | Pump House Pratap Nagar,Sector 16 |
| 1645 | Discharge 51 to 60 LPS and head 31 to 40 M( Sector 16-2) |
| 1646 | Pump House Pratap Nagar, Sector 17 |
| 1647 | Discharge 101-120 LPS and Head 41-50 M (Sector 17-2) |
| 1648 | Discharge 20 to 30 LPS and head 31 to 40 M(Sector 17-2) |
| 1649 | Pump House Sanganer Stadium,Kohinoor Sanaganer |
| 1650 | Discharge 51 to 60 LPS and head 31 to 40 M ( Stadium Pump House-4, Kohinoor PH-2) |
| 1651 | Pump House PHED Campus Sanganer |
| 1652 | Discharge 41 to 50 LPS and head 31 to 40 M( PHED Campus Pump House) |
| 1653 | Pump House PILI Ki khana Sanganer |
| 1654 | Discharge 61 to 70 LPS and head 31 to 40 M |
| 1655 | Pump House Muhana Mode |
| 1656 | Discharge 71-80 LPS and Head 31-40 M |
| 1657 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rolled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 1658 | 2 MT Capacity |
| 1659 | Span 7 M and Lift 6 M |
| 1660 | MS/DI SPECIALS |
| 1661 | Providing and fixing of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 1662 | MS pipe upto 600mm dia (with minimum 5mm thickness sheet) |
| 1663 | Providing, lowering, laying, aligning, fixing in position and jointing at all level/ depths DI standard specials with rubber ring (EPDM)/ nut bolt and insertion sheet and jointing as per IS: 9523-2000 or as amended up to date, such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, taxes, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge (excluding earth work). |
| 1664 | Upto 300mm dia |
| 1665 | Above 300mm dia and upto 600mm dia |
| 1666 | Providing and making flanged joints to double flanged C.I./ D.I. pipes and specials such as tees, bends, tapers, caps etc. at all level/depths within trenches complete including all material i.e. rubber insertions, bolts & nuts etc, labour, testing of joint, commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 1667 | 200 mm dia |
| 1668 | ELECTRICAL WORKS |
| 1669 | Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1670 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1671 | 100mm x 50mm x 1.6mm |
| 1672 | P/Laying P.V.C/XLPE insulated & P.V.C sheathed cable of 1.1 KV grade with Copper conductor of IS: 1554 P-I/IS: 7098 P-I in ground as per IS: 1255 including excavation of 30cm x 75cm size trench, 25cm thick under layer of sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 1673 | 2.5 sqmm. Armored 4 core |
| 1674 | 1.5 Sq.mm Armoured 6 Core |
| 1675 | Providing, Installation, Testing and Commissioning of Pressure Transmitter : Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA with HART / Diaphragm: SS316L / Process Connection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 At Pumps |
| 1676 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer.0 to 10.0 kg/cm² |
| 1677 | Providing, Installation, Testing and Commissioning of Pressure Transmitter : Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA with HART / Diaphragm: SS316L / Process Connection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 At Pumps |
| 1678 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to Modbus. |
| 1679 | 37 KW |
| 1680 | 18.5 KW |
| 1681 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLC Panel of size approx. 800 mm X 500 mm X 2000mm (LBH) , Fabricated out of min. 2 mm thick CRCA sheet complete with latest configuration, necessary programming software for PLC & SCADA and comprising of all accessories not limited to the following: |
| 1682 | DI 62No., DO 58 No. AI 14 No. AO 6 No. MCB 16A DP 2 No. MCB 6A DP 6 No. SMPS 100-240 VAC/ 4.5A / 24 VDC 1 No. Selector Switch (Auto/Manual) & Local / Remote 2 No. Control Relays 1 Lot Annunciator with 24 Windows NO to NC Type Microprocessor Based, Window Size 75*42mm, 110VAC, with 1 No. Electronic Hooter 1 No.Control Transformer 200 VA 1 No. Emergency STOP Push Button 1 No. Panel Cooling Fan & Filter 2 No. Panel Light with Door Switch, 7W 1 No. Control Indication Lamp for 24V DC, 220V AC 3 No. Push Button 3 No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc 1 Lot Panel Hardware, lugs, terminations, ferruls, name plate Ect. 1 Lot UTILITY SOCKET 16A, 3 PIN 2 No. HMI Display 10 Inch, Colour 1 No. Isolators Dual Output, 24V DC 1 Lot At Ramnagar, Housing Board, Subhash Nagar, Chandmari, Banipark Headworks |
| 1683 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLCPanel of size approx. 1000 mm X 600 mm X2000mm (LBH) , Fabricated out of min. 2 mmthick CRCA sheet complete with latest configuration, necessary programming software for PLC & SCADA and comprising of allaccessories not limited to the following:-Programmable Logic Controller (PLC) with Dual Hot Redundant CPU, Power supply,Communication Module, IO & Processor rack (Standard DC), Back upinterface/Expansion Module, Rack (Backplane) 10 slots for IO andProcessor. SCADA software shall have facility VPN, OPC, Smart Client, Web Enabled, Automation Report Generation, Archiving, Treands, Data Logging, etc. |
| 1684 | DI118 No.DO114 No.AI24 No.AO12 No.MCB 16A DP2 No.MCB 6A DP 6 No. SMPS 100-240VAC/ 4.5A / 24 VDC1 No. Selector Switch (Auto/Manual) & Local / Remote 2 No. Control Relays 1 Lot Annunciator with 24 Windows NO to NC TypeMicroprocessor Based, Window Size 75*42mm,110VAC, with 1 No.Electronic Hooter 1 No. Control Transformer 200VA 1 No. Emergency STOP Push Button 1 No. Panel Cooling Fan & Filter 2 No. Panel Light with Door Switch, 7W 1 No. Control Indication Lamp for 24VDC, 220VAC 3 No. Push Button 3 No. Power Wiring+Control Wiring + Control TB/ Fuse2A,TB etc 1 Lot Panel Hardware, lugs, terminations, ferruls,name plate Ect. 1 Lot UTILITY SOCKET 16A, 3 PIN 2 No. HMI Display 15 Inch, Colour 1 No. Isolators Dual Output, 24VDC 1 Lot Ethernet Switch ( Managed) 2 No. Operator Station including, Core i5 processor, 8GB RAM, 1TB SSD, DVD RW Drive, RS232/485/RJ45Port, 1 Parallel Port, 4 nos. USBPort, 2x Ethernet Cards, Keyboard, Opticalmouse, 32\"\" LED monitor, Latest windowsprofessional, Anti Virous, etc. 2 No. EngineeringStation including, Core i7 processor, 8 GB RAM, 1TB SSD, DVD RWDrive, RS-232/485/RJ45 Port, 1 Parallel Port, 4nos. USB Port, 2x Ethernet Cards, Keyboard,Optical mouse, 32\"\" LED monitor, Latest windowsprofessional, Anti Virous, etc. 2 No. Run Time & Development Programming andTroubleshooting software for PLC, HMI, SCADA,VPN, Web Client - OWS 1 No. Black and white, A4 Size Lazer Printer , copier,Scan.Hi-Speed USB 2.0 port; built-in Fast Ethernet 2 No. 10/100Base-TX network port; built-in WiFi802.11b/g/n Online UPS 3 KVA with 60 min Backup time. 1 No.At Panipech Headworks |
| 1685 | Compact RTU complete with DI, DO, AI and modbus communication ports and power supply. // Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and Communcation protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communications antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card also, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. Panel Enclosure for Compact RTU Location, wall/floor mounted along with wiring and related accessories and arrangement of mounting of RTU, Modem and having IP-5X Protection. Panels shall be self-fabricate type only with Canopy. |
| 1686 | Supply Installation, Testing & Commissioning of Intel i7 4th Generation processor 3Ghz or latest, 4GB RAM with 2TB hard disk, DVD-RW/keyboard/optical mouse/LAN card/24” LED monitor. Minimum 6 USB ports. With pre-loaded licensed Windows 10 or latest software PC |
| 1687 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 608311& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs(temp class - 25 D)in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1688 | Heavy duty Three phase 480 V , 50 Hz capacitor (Bank) |
| 1689 | Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phasesensing compensationpower factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 610006-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, overcurrent, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .12 to 14 stage |
| 1690 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1691 | 3 Core |
| 1692 | 25.0 Sq. mm |
| 1693 | 35.0 Sq. mm |
| 1694 | 50.0 Sq. mm |
| 1695 | 35.0 Sq. mm |
| 1696 | Supply , Installation, Testing and Comissioning of wall mounted remote ON/OFF Push Button station for AHU/Air washers made out from powder quoted CRCA sheet of 16 SWG , illuminated ON/OFF push button including making connections etc as equired complete in all respect.All as per pre approved by Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1697 | Supply, Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . For SCADA / PLC room. |
| 1698 | 1.5 TR ISEER not less then 4.6 |
| 1699 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1700 | Unarmour |
| 1701 | 4 core x 2.5 Sq.mm |
| 1702 | Supply, installation, testing and comissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified \"Class O\" in Fire Propagation as per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1703 | 38 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 1704 | 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 1705 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1706 | 20 mm |
| 1707 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1708 | 3 KVA |
| 1709 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 1710 | 50 mm dia per running inch length |
| 1711 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1712 | INSTRUMENTATION WORKS |
| 1713 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU), Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC -50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1714 | EMF150 for DN 150 mm |
| 1715 | EMF200 for DN 200 mm |
| 1716 | EMF250 for DN 250 mm |
| 1717 | EMF300 for DN 300 mm |
| 1718 | EFM 400 mm |
| 1719 | EFM 500 mm |
| 1720 | EFM 600 mm |
| 1721 | Household Tap connection |
| 1722 | Providing Household Tap Connection as per technical specification and approved drawing as per relevant IS code (amended up to date) from uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using PP/MS saddle piece (Complete job).This job includes digging out suitable size of pits and trench for laying service line in all kinds of soil (excluding road); depositing and refilling of pit & jhiri with watering & ramming /compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting duly approved in accordance with specification for potable water including MS/PP saddle piece, gunmetal ferrule 4.0 mm , GM Full-way Valve (IS:778 Mark) or ball valve (min. weight 165 gm) and specials, below ground level 20 mm nominal dia MDPE pipe PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Three layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above ground level using 20 mm dia PPR-C pipe with standard PPR fittings/ 15 mm dia GI pipe with fittings in the premises for fixing a tap / meter box (excluding) , inc accessories with flushing, cleaning, disinfecting and testing of pipe line complete required for making of service connection complete in all respect including labour charges. The service line should be laid at least 45 cm below ground level.Note: Road cut and restoration is not part of this item and paid separately. |
| 1723 | For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr. |
| 1724 | Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be doneby using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge. |
| 1725 | Supply, Installation of 15 mm size AMI LoRa WAN/RF based Water Meters, conforming to ISO 4064:2005/ISI standards with MID/ISI approvalincluding Collection & Verification of Consumer Data, Automated Meter Reading in the identified DMAs of MC Jaipur Greater. |
| 1726 | CIVIL WORKS |
| 1727 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1728 | For Class-A loading |
| 1729 | Sluice valve chamber of size1.39m x1.43m x2.185m for pipe size-from 350-to-450mm |
| 1730 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1731 | For Class-AA loading |
| 1732 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m- for pipe size-up to 100 mm |
| 1733 | Sluice valve chamber of size 1.17m x 0.95m x1.47m for pipe size-from 125-to-150mm |
| 1734 | Sluice valve chamber of size 1.26m x1.185m x1.88mfor pipe size-from 200-to-300mm |
| 1735 | Sluice valve chamber of size 1.39m x1.43m x2.245m for pipe size-from 350-to-450mm |
| 1736 | Sluice valve chamber of size 1.61m x1.75m x2.85m for pipe size-from 500-to-700mm |
| 1737 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1738 | For in-campus Valve Chambers |
| 1739 | Sluice valve chamber of size 1.61m x1.75m x2.85m for pipe size-from 500-to-700mm (Shall be made as per GA Drawing and field Requirement) |
| 1740 | Panel Room on CWR |
| 1741 | Construction of RCC Air valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, Plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1742 | For Class-A loading |
| 1743 | Air valve chamber of size0.9m x1m x1.71m for air valve size-from 50 mm-to-80mm |
| 1744 | OPERATION & MEINTINANCE |
| 1745 | Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency) as per Scope of Work & terms & conditions of contract for 5 year after defect liability period of one year DLP (except power feeder, IEC & miscellaneous provision) for Water Supply Project. |
| 1746 | 1st Year |
| 1747 | 2nd Year |
| 1748 | 3rd Year |
| 1749 | 4th Year |
| 1750 | 5th Year |
| 1751 | (D). SUB TOTAL OF DIVISION SOUTH S-4 |
| 1752 | ( E ) Division North-4 |
| 1753 | Pipeline |
| 1754 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended upto date), with internal cement mortar lining for potable water with rubber ring (EPDM/SBR) joints as per IS: 5382-1985 (excluding special accessories) complete including all material, labour, hydraulic testing and commissioning as per Technical Specifications and as per direction of Engineer. Note : E/w to be measured and paid separately. |
| 1755 | 100 mm |
| 1756 | 150 mm |
| 1757 | 200 mm |
| 1758 | 250 mm |
| 1759 | 300 mm |
| 1760 | 350 mm |
| 1761 | 400 mm |
| 1762 | 450 mm |
| 1763 | 500 mm |
| 1764 | 600 mm |
| 1765 | Providing, lowering, laying, aligning, fixing in position at and jointing at all level/ depths ISI marked HDPE pipes of PE-100 grade & PN-6 for potable water as per IS 4984 (amended upto date) in trenches in complete including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. |
| 1766 | 110mm dia |
| 1767 | 125mm dia |
| 1768 | 140mm dia |
| 1769 | 160mm dia |
| 1770 | 180mm dia |
| 1771 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level. |
| 1772 | In all types soils/ saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc. |
| 1773 | Depth upto 1.5 m |
| 1774 | Add extra for over all depth of excavation above 1.5 m and upto 3.0 m over item no 4.1 |
| 1775 | Dismantling of cement concrete pavement by mechanical means using pneumatic tools, cutting theperipheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposalof dismantled materials up to a lead of 1000 metres including allowances for any additional dismantling beyond the drawings (measurement for payment to be as per standard drawings), rehandling of material/earth to complete the task. |
| 1776 | DI K-7 Pipe |
| 1777 | Dismantling of flexible pavement for pipe line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, rehandling of material/earth to complete the tasks per technical specification andscope of work. |
| 1778 | Bituminous courses |
| 1779 | Granular courses |
| 1780 | Barricading with Sal ballies as per design including tying with vertical post by coconut strings including digging out holes in all types of soil complete in all respect with two horizontal members height 1.2 m upto 1.5m above ground level and vertical supports upto 2.5 centre and upto 3 days period including removal and cleaning the site complete in all respect & including dressing of sides and providing retro reflective tapes for traffic safety as per direction of Engineer-in charge in all types of soil. |
| 1781 | Valves |
| 1782 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as perdirection of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1783 | Motorised Sluice valve with electric actuator with integral starter of class PN.1.0 |
| 1784 | 200 mm dia |
| 1785 | Providing, lowering, laying, aligning, fixing inposition CI D/F short body pattern type butterfly valves having body, disc and end cover in graded cast irongenerally conforming to (IS13095/1991amendedup to date), synthetic rubber faced ring secured on disc by retaining ring with SS steel screw stub shaft of SS riding in Teflon bearing including C.C. foundation/ structural steel support, material,labour,testingalongwith pipe line andcommissioning asperTechnical Specifications andasper direction of Engineer in charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work |
| 1786 | Manually Operated Butterfly Valve PN-1.0 |
| 1787 | 200 mm dia (With Gear Operated) |
| 1788 | 300 mm dia (With Gear Operated) |
| 1789 | 250 mm dia(With Gear Operated) |
| 1790 | 450 mm with Gear |
| 1791 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Double Acting Kinetic Air Valve with isolating Sluice Valve of approved makes for following pressure rating & dia complete, confirming to IS: 14845-2000 (amended up to date) and of following specifications: Body , Cover and Cowl - Grey Cast Iron as per IS:210- FG 200 ,Float -Stainless Steel AISI 304 / IS: 3444 , Float Guide_x 005fHBT1.HP Orifice- HTB2/ SS,Body seat ring - Leaded tin bronze/ SS .Seal ring and face ring - PDM/NBR ,Ends flanged according to IS 6418,Fastners - CS, Epoxy paint inside outside of food grade safe for drinking water ,Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1792 | Class PN 1.0 |
| 1793 | 80 mm dia |
| 1794 | Providing, lowering, laying, aligning, fixing in position in pipe line, Resilient Seated D/F DI Sluice valves of approved make & design standard of following dia complete (including jointing & jointing material ) including all material, labour, testing and commissioning along with pipe line as per Technical Specification & as per direction of Engineer. |
| 1795 | Manually operated class PN 1.6 |
| 1796 | 100 mm dia |
| 1797 | 150 mm dia |
| 1798 | 200 mm dia |
| 1799 | 250 mm dia |
| 1800 | 300 mm dia |
| 1801 | 350mm dia |
| 1802 | 400 mm dia |
| 1803 | 450 mm dia |
| 1804 | 500 mm dia |
| 1805 | Electrically Operated & SCADA Compatible class PN 1.6 |
| 1806 | 150 mm dia |
| 1807 | 250 mm dia |
| 1808 | 300 mm dia |
| 1809 | 400 mm dia |
| 1810 | 500 mm dia |
| 1811 | 600 mm dia |
| 1812 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short body pattern type double eccentric Butterfly valves of approved make of following class & dia complete confirming to BS EN 593/ BS 5155/ IS 13095/1991 amendedup to date and of following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Face to face dimensions as per DIN 3202 F4/ IS 13095Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1813 | Class PN 1.6, Manually Operated with Gear |
| 1814 | 150 mm dia |
| 1815 | Class PN 1.6, Motorised Operated |
| 1816 | 200 mm dia |
| 1817 | 250 mm dia |
| 1818 | 300 mm dia |
| 1819 | Providing, lowering, aligning, fixing in position in pipe line, DIdouble flanged resilient seated Dual plate check valve of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body and cover inside and outside .Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410 , Hinge SS AISI 316/304,SpringSS AISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick .Suitablesupport structure as per directions of EICincluding jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1820 | Class PN 1.6 |
| 1821 | 150 mm dia |
| 1822 | 200 mm dia |
| 1823 | 250 mm dia |
| 1824 | 300 mm dia |
| 1825 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, DI Body Flanged End Tamper proofKinetic Air Valve of approved makes of following pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(amended up to date) Body, High pressure cover , Low pressure cover, Cowl andJoint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fasteners - CS/ Galvanised steel, Outlet of big orifice will have a screen to prevent Tamper of float,with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amendedup to date) PN 1.6 ratings Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1826 | Class PN 1.6 |
| 1827 | 40 mm dia |
| 1828 | 50 mm dia |
| 1829 | 80 mm dia |
| 1830 | 100 mm dia |
| 1831 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 410/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318-LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318-LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. Insertion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1832 | Plunger Type Flow Control Valve |
| 1833 | 200mm dia |
| 1834 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 1835 | 80 mm dia PN-1.0 |
| 1836 | 100 mm dia PN-1.0 |
| 1837 | 125 mm dia PN-1.0 |
| 1838 | 150 mm dia PN-1.0 |
| 1839 | 200 mm dia PN-1.0 |
| 1840 | 250 mm dia PN-1.0 |
| 1841 | 300 mm dia PN-1.0 |
| 1842 | 350 mm dia PN-1.0 |
| 1843 | 400 mm dia PN-1.0 |
| 1844 | 450 mm dia. PN-1.0 |
| 1845 | 500 mm dia PN-1.0 |
| 1846 | 600 mm dia PN-1.0 |
| 1847 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1848 | 150 mm dia. |
| 1849 | 200 mm dia. |
| 1850 | 250 mm dia. |
| 1851 | 300 mm dia. |
| 1852 | Providing and making flanged joints to double flanged C.I./ D.I. pipes and specials such as tees, bends, tapers, caps etc. at all level/depths within trenches complete including all material i.e. rubber insertions, bolts & nuts etc, labour, testing of joint, commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 1853 | 200 mm dia |
| 1854 | Over Head Service Reservoir |
| 1855 | Construction and commissioning of RCC INTZE type Over Head Service Reservoir of following capacity and staging as per the Scope of work and Technical specifications, consisting of the following main activities: - |
| 1856 | a) Topographic survey, preparation of site contour plan, conducting SBC testand its approval from departmentbefore construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc.c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR.The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.d) Providing and applying two coats of food grade epoxy paint on the inside surface on the top dome, edge beam and 600 mm height of the vertical wall.e)Conducting successfully hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the top surface of the Top Dome.g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc..h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top dome/Slab to bottom dome/Slab inside container. i) Providing and fixing of MS section ladder from the last landing to balcony having railing all around it and MS ladder with safety cage from balcony to top dome/slab.j) Providing and fixing water level indicator (float type). |
| 1857 | k) Providing and fixing of hand railing all around the balcony, top dome and staircase consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle iron vertical post at a maximum spacing of 1500mm centres.l) All MS parts to be painted with two coats of the enamel paint over the primer coat of red oxide.m) Providing and fixing of 150mm wide PVC water bar for the construction joints in the container (vertical wall & cone wall).n) Providing one Aluminium portable ladder of appropriate length to access first landing (3.5 to 4.5m above GL) from ground.o) Lighting arrestor consisting of providing and fixing of 2 Nos.of chemical earthing and connecting it to the conical cover of SS ventilator with two separate GI strips of 50mmX3mm.p) CI/DI puddle collar shall be fixed in the bottom dome/ slab for connecting inlet, outlet, overflow and washout pipe of the reservoir.q) Painting the name of the scheme and other details on the reservoir, and any other work related to structure as per the directions of Engineer-in- Charge, Technical Specification and Scope of Work.r) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. |
| 1858 | Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-II & STAGING 20 M |
| 1859 | 1500 KL capacity (In Jothawara RIICO AEN Office) |
| 1860 | 1500 KL capacity (At Naya Kheda N-4 Division Office campus) |
| 1861 | Rates for RCC OHSR,SBC 10 T/sqm, SEISMICZONE-II & STAGING 22 M |
| 1862 | 1750 KL capacity |
| 1863 | Forstagingabove22Mtr(onlyinexceptionalcondition where hydraulics not permit) add 2% per Mtr above 22 Mtr. |
| 1864 | 1750 KL capacity 24 m staging |
| 1865 | Providing and fixing double flanged ISI marked DIClass K-9 pipes as per IS:8329-2000 (amended up to date), asvertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr,jointing materials such as nuts, bolt, rubber packing, hydraulic testingetc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 1866 | 200 mm (Inlet) |
| 1867 | 250 mm(Overflow,Drain) |
| 1868 | 300 mm (Outlet) |
| 1869 | 400mm |
| 1870 | 450 mm |
| 1871 | Clear Water Reservoir |
| 1872 | Construction of RCC (Flat Slab Rectangular) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: |
| 1873 | a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approvalfromdepartment beforeconstruction.Submissionandapprovalofconcretemix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour andmaterialchargesincludingprovidingandfixingofaccessoriessuchasSSladder,SS manhole frame and covers, water levelindicator (floattype), SSventilator withSSscreen, float valve, puddle collars, G.I. pipe railing around walk way, Flat/Slab, rectangular .Staircase c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g)Providingandapplyingthreecoatsofcement-basedpaintontheremainingexternal surface area of the structure. |
| 1874 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder fromroofslabtobottomSlab,insidecontainer.Providingandfixingwaterlevelindicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k) Providingandfixingof150mmwidewaterbarfortheconstructionjoints inthe container.l)ProvidingandfixingCI/DIpuddlecollarstheverticalwallforconnectinginlet,outlet, overflow and washout pipes of the reservoir.m)Inlet,outlet,overflow,washoutpipesandvalvesarenotincludedinthiswork, provision for the same shall be taken separately. |
| 1875 | Rates for RCC Partially Underground type clear water reservoir SBC 10 T/sqm, SEISMIC ZONE-2 & 3. |
| 1876 | Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 1877 | 200 mm |
| 1878 | 250 mm |
| 1879 | 400 mm |
| 1880 | PUMPS & PUMPING MACHINERY |
| 1881 | Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at synchronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts, Cement concrete foundation etc. complete with all respect as per the specification and scope of work and direction of Engineer in Charge of following range of duty conditions. Note: Duty condition of required pump shall also be mentioned in BoQ. |
| 1882 | Naya Khera Pump House |
| 1883 | Discharge 121-140 LPS and Head 31-40 M |
| 1884 | Discharge 101-120 LPS and Head 31-40 M |
| 1885 | Discharge 31-40 LPS and Head 31-40 M |
| 1886 | Ambabari Pump House |
| 1887 | Discharge 161-180 LPS and head 31 to 40 M |
| 1888 | Discharge 121-140 LPS and head 31 to 40 M |
| 1889 | Discharge 61-70 LPS and head 20-30 M |
| 1890 | Discharge 181-200 LPS and head 31-40 M |
| 1891 | RIICO Pump House |
| 1892 | Discharge 41 to 50 LPS and head 41 to 50 M |
| 1893 | Sita Vihar Pump House |
| 1894 | Discharge 51 to 60 LPS and head 41 to 50 M |
| 1895 | Ganesh Colony Pump House |
| 1896 | Discharge 161 to 180 LPS and head 71 to 80 M |
| 1897 | Discharge 101 to 120 LPS and head 61 to 70 M |
| 1898 | 13 No. Pump House |
| 1899 | Discharge 121-140 LPS and head 31 to 40 M |
| 1900 | 9 No. Pump House |
| 1901 | Discharge 121-140 LPS and head 31 to 40 M |
| 1902 | 5 No. Pump House |
| 1903 | Discharge 51 to 60 LPS and head 31 to 40 M |
| 1904 | Sanjay Nagar Pump House |
| 1905 | Discharge 51 to 60 LPS and head 71 to 80 M |
| 1906 | Murlipura pump House |
| 1907 | Discharge 181 to 200 LPS and head 31 to 40 M (For Dadhich Nagar OHSR) |
| 1908 | Discharge 71-80 LPS and Head 20-30 M ( For Nanu Nagar OHSR) |
| 1909 | Discharge 141 to 160 LPS and head 31 to 40 M( For MurlipuraOHSR) |
| 1910 | Discharge 181 to 200 LPS and head 31 to 40 M ( For Murlipura OHSR) |
| 1911 | Providing, installation, testing and commissioningof Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, class \"F\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein all respect as perspecification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 1912 | 75 KW; Proposed Murlipura CWR to Murlipura Pressure Supply Zone |
| 1913 | 30 KW; For Harmada Pump house to Ambedkar Colony |
| 1914 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rolled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 1915 | 2 MT Capacity |
| 1916 | Span 7 M and Lift 6 M |
| 1917 | MS Specials |
| 1918 | Providing and fixing of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 1919 | MS pipe upto 600mm dia (with minimum 5mm thickness sheet) |
| 1920 | Providing, lowering, laying, aligning, fixing in position and jointing at all level/ depths DI standard specials with rubber ring (EPDM)/ nut bolt and insertion sheet and jointing as per IS: 9523-2000 or as amended up to date, such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, taxes, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge (excluding earth work). |
| 1921 | Upto 300mm dia |
| 1922 | Above 300mm dia and upto 600mm dia |
| 1923 | Electrical |
| 1924 | Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1925 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1926 | 100mm x 50mm x 1.6mm |
| 1927 | P/Laying P.V.C/XLPE insulated & P.V.C sheathed cable of 1.1 KV grade with Copper conductor of IS: 1554 P-I/IS: 7098 P-I in ground as per IS: 1255 including excavation of 30cm x 75cm size trench, 25cm thick under layer of sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 1928 | 2.5 sqmm. Armored 4 core |
| 1929 | 1.5 Sq.mm Armoured 6 Core |
| 1930 | Providing, Installation, Testing and Commissioning of Pressure Transmitter : Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA with HART / Diaphragm: SS316L / Process Connection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 At Pumps |
| 1931 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer.0 to 10.0 kg/cm² |
| 1932 | Providing, installation, testing and commissioning of Diaphragm type Pressure Switches Sensing Element: Bellows / Diaphragm, Material of sensor and other wetted parts: SS type 316, Housing: Die cast aluminum, Switch type: Microswitch, Repeatability: ± 1% of span, Switch Contacts: 2 NO + 2 NC |
| 1933 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to Modbus. |
| 1934 | 75 KW |
| 1935 | 30 KW |
| 1936 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 608311& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs(temp class - 25 D)in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1937 | Heavy duty Three phase 480 V , 50 Hz capacitor (Bank) |
| 1938 | Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phasesensing compensationpower factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 610006-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, overcurrent, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .12 to 14 stage |
| 1939 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 1940 | 3 Core |
| 1941 | 25.0 Sq. mm |
| 1942 | 35.0 Sq. mm |
| 1943 | 50.0 Sq. mm |
| 1944 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1945 | Unarmour |
| 1946 | 4 core x 2.5 Sq.mm |
| 1947 | Supply, installation, testing and comissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified \"Class O\" in Fire Propagation as per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1948 | 38 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 1949 | 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 1950 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1951 | 20 mm |
| 1952 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1953 | 3 KVA |
| 1954 | Household Tap Connection |
| 1955 | Providing Household Tap Connection as per technical specification and approved drawing as per relevant IS code (amended up to date) from uPVC/DI/AC/MS/GI pipe line up to consumer meter/premises by using PP/MS saddle piece (Complete job).This job includes digging out suitable size of pits and trench for laying service line in all kinds of soil (excluding road); depositing and refilling of pit & jhiri with watering & ramming /compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting duly approved in accordance with specification for potable water including MS/PP saddle piece, gunmetal ferrule 4.0 mm , GM Full-way Valve (IS:778 Mark) or ball valve (min. weight 165 gm) and specials, below ground level 20 mm nominal dia MDPE pipe PE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Three layered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and above ground level using 20 mm dia PPR-C pipe with standard PPR fittings/ 15 mm dia GI pipe with fittings in the premises for fixing a tap / meter box (excluding) , inc accessories with flushing, cleaning, disinfecting and testing of pipe line complete required for making of service connection complete in all respect including labour charges . The service line should be laid at least 45 cm below ground level.Note: Road cut and restoration is not part of this item and paid separately. |
| 1956 | For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr. |
| 1957 | Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be doneby using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge.. |
| 1958 | Supply, Installation of 15 mm size AMI LoRa WAN/RF based based Water Meters, conforming to ISO 4064:2005/ISI standards with MID/ISI approvalincluding Collection & Verification of Consumer Data, Automated Meter Reading in the identified DMAs of MC Jaipur Greater. |
| 1959 | AUTOMATION & PLC-SCADA Works and INSTRUMENTATION |
| 1960 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU), Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC -50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1961 | EMF150 for DN 150 mm |
| 1962 | EMF200 for DN 200 mm |
| 1963 | EMF250 for DN 250 mm |
| 1964 | EMF300 for DN 300 mm |
| 1965 | EFM 400 mm |
| 1966 | EFM 500 mm |
| 1967 | EFM 600 mm |
| 1968 | SITC of Ultrasonic Level Transmitter suitable for measuring water level in reservoir, Normal Powered 24VDC, Type of Transmitter: Two Wire ( 4-20 mA), Cable Entry:1/2\" NPT (F), Sensor Material: PP, slip-on Flange: 2 ½” Flange, Material of Construction for Slip-on flange: PP, output 4~20mA, HART compatible, accuracy +/_ 0.2 % as per detailed Technical specification, scope of work and direction of Engineer in charge. |
| 1969 | Measuring range 0.0 to 6.0 mtr |
| 1970 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLC Panel of size approx. 800 mm X 500 mm X 2000mm (LBH) , Fabricated out of min. 2 mm thick CRCA sheet complete with latest configuration, necessary programming software for PLC & SCADA and comprising of all accessories not limited to the following: |
| 1971 | DI62No. , DO 58No. AI 14No. AO 6No. MCB 16A DP2No.MCB 6A DP6No.SMPS 100-240VAC/ 4.5A / 24 VDC1No.Selector Switch (Auto/Manual) & Local / Remote2No.Control Relays1LotAnnunciator with 24 Windows NO to NC Type Microprocessor Based, Window Size 75*42mm, 110VAC, with1No.Electronic Hooter1No.Control Transformer 200VA1No.Emergency STOP Push Button1No.Panel Cooling Fan & Filter2No.Panel Light with Door Switch, 7W1No.Control Indication Lamp for 24VDC, 220VAC3No.Push Button3No.Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc1LotPanel Hardware, lugs, terminations, ferruls, name plate Ect.1LotUTILITY SOCKET 16A, 3 PIN2No.HMI Display 10 Inch, Colour1No.Isolators Dual Output, 24VDC 1 Lot At Ramnagar, Housing Board, Subhash Nagar, Chandmari, Banipark Headworks |
| 1972 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLC Panel of size approx. 1000 mm X 600 mm X2000mm (LBH) , Fabricated out of min. 2 mmthick CRCA sheet complete with latest configuration, necessary programming software for PLC & SCADA and comprising of allaccessories not limited to the following:-Programmable Logic Controller (PLC) with DualHot Redundant CPU, Power supply,Communication Module, IO & Processor rack(Standard DC), Back upinterface/ExpansionModule, Rack (Backplane) 10 slots for IO andProcessor. SCADA software shall have facilityVPN, OPC, Smart Client, Web Enabled, Automation Report Generation, Archiving, Treands, Data Logging, etc. |
| 1973 | DI118 No.DO114 No.AI24 No.AO12 No.MCB 16A DP2 No.MCB 6A DP 6 No. SMPS 100-240VAC/ 4.5A / 24 VDC1 No. Selector Switch (Auto/Manual) & Local / Remote 2 No. Control Relays 1 Lot Annunciator with 24 Windows NO to NC TypeMicroprocessor Based, Window Size 75*42mm,110VAC, with 1 No.Electronic Hooter 1 No. Control Transformer 200VA 1 No. Emergency STOP Push Button 1 No. Panel Cooling Fan & Filter 2 No. Panel Light with Door Switch, 7W 1 No. Control Indication Lamp for 24VDC, 220VAC 3 No. Push Button 3 No. Power Wiring+Control Wiring + Control TB/ Fuse2A,TB etc 1 Lot Panel Hardware, lugs, terminations, ferruls,name plate Ect. 1 Lot UTILITY SOCKET 16A, 3 PIN 2 No. HMI Display 15 Inch, Colour 1 No. Isolators Dual Output, 24VDC 1 Lot Ethernet Switch ( Managed) 2 No. Operator Station including, Core i5 processor, 8GB RAM, 1TB SSD, DVD RW Drive, RS232/485/RJ45Port, 1 Parallel Port, 4 nos. USBPort, 2x Ethernet Cards, Keyboard, Opticalmouse, 32\"\" LED monitor, Latest windowsprofessional, Anti Virous, etc. 2 No. EngineeringStation including, Core i7 processor, 8 GB RAM, 1TB SSD, DVD RWDrive, RS-232/485/RJ45 Port, 1 Parallel Port, 4nos. USB Port, 2x Ethernet Cards, Keyboard,Optical mouse, 32\"\" LED monitor, Latest windowsprofessional, Anti Virous, etc. 2 No. Run Time & Development Programming andTroubleshooting software for PLC, HMI, SCADA,VPN, Web Client - OWS 1 No. Black and white, A4 Size Lazer Printer , copier,Scan.Hi-Speed USB 2.0 port; built-in Fast Ethernet 2 No. 10/100Base-TX network port; built-in WiFi802.11b/g/n Online UPS 3 KVA with 60 min Backup time. 1 No.At Panipech Headworks |
| 1974 | Compact RTU complete with DI, DO, AI and modbus communication ports and power supply. // Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and Communcation protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communications antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card also, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. Panel Enclosure for Compact RTU Location, wall/floor mounted along with wiring and related accessories and arrangement of mounting of RTU, Modem and having IP-5X Protection. Panels shall be self-fabricate type only with Canopy. |
| 1975 | Supply Installation, Testing & Commissioning of Intel i7 4th Generation processor 3Ghz or latest, 4GB RAM with 2TB hard disk, DVD-RW/keyboard/optical mouse/LAN card/24” LED monitor. Minimum 6 USB ports. With pre-loaded licensed Windows 10 or latest software PC |
| 1976 | Supply , Installation, Testing and Comissioning of wall mounted remote ON/OFF Push Button station for AHU/Air washers made out from powder quoted CRCA sheet of 16 SWG , illuminated ON/OFF push button including making connections etc as equired complete in all respect.All as per pre approved by Engineer in-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 1977 | Supply, Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . For SCADA / PLC room. |
| 1978 | 1.5 TR ISEER not less then 4.6 |
| 1979 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 1980 | Civil Works |
| 1981 | Carriage of Materials by mechanical transport including loading,unloading and stacking :: Sand, bazri, ballast, kankar- Lead upto 5 Km |
| 1982 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1983 | For Class-AA loading |
| 1984 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m-for pipe size-up to 100 mm |
| 1985 | Sluice valve chamber of size 1.17m x 0.95m x1.47mfor pipe size-from 125-to-150mm |
| 1986 | Sluice valve chamber of size 1.26m x1.185m x1.88m for pipe size-from 200-to-300mm |
| 1987 | Sluice valve chamber of size 1.39m x1.43m x2.245mfor pipe size-from 350-to-450mm |
| 1988 | Sluice valve chamber of size 1.61m x1.75m x2.85mfor pipe size-from 500-to-700mm |
| 1989 | For Class-A loading |
| 1990 | Sluice valve chamber of size1.26m x1.185m x1.82mfor pipe size-from 200-to-300mm |
| 1991 | Sluice valve chamber of size1.39m x1.43m x2.185m for pipe size-from 350-to-450mm |
| 1992 | Construction of RCC Air valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, Plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 1993 | For Class-A loading |
| 1994 | Air valve chamber of size0.9m x1m x1.71m for air valve size-from 50 mm-to-80mm |
| 1995 | Sluice valve chamber of size 1.61m x1.75m x2.85m for pipe size-from 500-to-700mm (Shall be made as per GA Drawing and field Requirement) |
| 1996 | Panel Room on CWR |
| 1997 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 1998 | 50 mm dia per running inch length |
| 1999 | O&M |
| 2000 | Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency) as per Scope of Work & terms & conditions of contract for 5 year after defect liability period of one year DLP (except power feeder, IEC & miscellaneous provision) for Water Supply Project |
| 2001 | 1st Year |
| 2002 | 2nd Year |
| 2003 | 3rd Year |
| 2004 | 4th Year |
| 2005 | 5th Year |
| 2006 | (E). SUB TOTAL OF DIVISION North-4 |
| 2007 | (F) BOQ OF PROJECT DIVISION- I |
| 2008 | Pipeline |
| 2009 | Manufacturing, supplying ,lowering, laying and jointing in position tocorrect line spirally welded SAW/Fabricated MS Pipe having bevelled end plates / coils, confirming to IS 3589-2001 or its latest revision/amendments, for following thickness and inside diameter, including all taxes (Central and local), transportation and freight charges,inspection charges, loading/ unloading charges, including cost of labour and material, specials (Tee, bend etc.), field joints, satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge; (excluding earthwork, internal lining and outer coating).Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item andshall not be paid separately. |
| 2010 | Replacement of 300 mm outlet CI pipe from Amanishah 13.5 ML CWR |
| 2011 | Inner dia 300 mm and Outer dia of pipe 323.9 mm and thickness |
| 2012 | 4.5 mm |
| 2013 | Inner dia 350 mm and Outer dia of pipe 355.6 mm and thickness (Individual Delivery main from pumps) |
| 2014 | 8 mm |
| 2015 | Inner dia 400 mm and Outer dia of pipe 406.4 mm and thickness (Individual Delivery main from pumps and replacement of 2 nos 400 mm outlet CI pipe from Amanishah 13.5 ML CWR) |
| 2016 | 8.8 mm |
| 2017 | Outer dia of pipe 610 mm and thickness (For delivery Feeder Govind Nagar/Shashtri Nagar) |
| 2018 | 6.3 mm |
| 2019 | Outer dia of pipe 813 mm and thickness (For delivery Feeder VKI and Inlet Pipe from Bisalpur pipeline and Inlet pipe from Amanishah 13.5 ML CWR) |
| 2020 | 8 mm |
| 2021 | Outer dia of pipe 1016 mm and thickness |
| 2022 | 10 mm |
| 2023 | Providing and applying Spray applied, 100% Solids (Solvent free) Two Component PU ( Polyurethane) coating as per AWWA C222 Standard on external surface of M.S. Pipe including preparation of pipe outer surface by solvent cleaning, abrasive blasting to a finish of Grade 2.5 to DIN EN ISO 8501-1 and surface profile of 50 to 75 microns as per DIN EN ISO 8503-2 including field joints coating at site complete as per technical specification and direction of Engineer in In charge. Minimum dry film thickness of coating shall be 1000 micron |
| 2024 | Providing and making inner cement mortar lining to M.S. Pipes with mechanical devices in cement mortar 1:1 proportion , including cost of all materials, labour, special sand required, machinery, power generation, all equipments, including carrying out \"C\" value performance test of pipeline, including field joints at site complete as per technical specification and direction of Engineer in In charge. |
| 2025 | 9 mm thick for pipes up to 700 mm dia |
| 2026 | 12 mm thick for pipes above 700 mm dia |
| 2027 | Earth work in excavation by mechanical means (Hydraulic Excavator) / manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and thenreturning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.: All kinds of soil |
| 2028 | Add extra for over all depth of excavation above 1.5 m and upto 3.0 m |
| 2029 | Dismantling of cement concrete pavement for pipe line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. |
| 2030 | Dismantling of flexible pavement for pipe line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re_x0002_handling of material/earth to complete the tasks per technical specification and scope of work. |
| 2031 | Bituminous courses |
| 2032 | Granular courses |
| 2033 | Barricading with Sal ballies as per design including tying with vertical post by coconut strings including digging out holes in all types of soil complete in all respect with two horizontal members height 1.2 m upto 1.5m above ground level and vertical supports upto 2.5 centre and upto 3 days period including removal and cleaning the site complete in all respect & including dressing of sides and providing retro reflective tapes for traffic safety as per direction of Engineer-in charge in all types of soil. |
| 2034 | Making interconnection with existing Bisalpur Transmission pipe line, this includes making arrangement for taking shut down of supply in Bisalpur feeder, Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line upto depth of 3.0 mtr,deployment of all required skilled/ unskilled manpower, machinaries (Crain, JCB, drill machine, welding machine, Dewatering pumps, tractor etc) and completing the interconnection within the limited time lines. Note: Above item is including MS pipe specials. |
| 2035 | Near Panipech Tiraha |
| 2036 | Clear Water Reservoir |
| 2037 | Construction of RCC (Flat Slab Rectangular) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: |
| 2038 | a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approvalfromdepartment beforeconstruction.Submissionandapprovalofconcretemix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour andmaterialchargesincludingprovidingandfixingofaccessoriessuchasSSladder,SS manhole frame and covers, water levelindicator (floattype), SSventilator withSSscreen, float valve, puddle collars, G.I. pipe railing around walk way, Flat/Slab, rectangular .Staircase c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g)Providingandapplyingthreecoatsofcement-basedpaintontheremainingexternal surface area of the structure. |
| 2039 | h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder fromroofslabtobottomSlab,insidecontainer.Providingandfixingwaterlevelindicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide.k) Providingandfixingof150mmwidewaterbarfortheconstructionjoints inthe container.l)ProvidingandfixingCI/DIpuddlecollarstheverticalwallforconnectinginlet,outlet, overflow and washout pipes of the reservoir.m)Inlet,outlet,overflow,washoutpipesandvalvesarenotincludedinthiswork, provision for the same shall be taken separately. |
| 2040 | 15000 KL capacity for Amanishah Campus |
| 2041 | Valves |
| 2042 | Providing, lowering, aligning, fixing in position in pipe line, CI double flanged Dual plate check valve of approved make of following Pressure rating & dia complete, as per API: 594/ API: 598 and of following specifications: Body & Cover of Grey cast iron of IS:210/ FG200 , Disc / plates - Cast steel ,Disc seal ring of EPDM/ NBR (food grade quality) ,Body seat of SS ,Face to face dimensions as per API: 594 ,Flanges Drilled as per IS:1538. Epoxy (Non-Toxic & suitable for drinking water) applied on body & cover inside and outside . Shaft/Stop Pin of SS- AISI- 304/410 ,Hinge SS AISI 316/304 / CS ,Spring SS AISI 316/304 , Bonnet Gasket EPDM ,Bush-Brass with EPDM/NBR \"O \"ring seal.Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel), Insertion rubber of black EPDM 6mm thick . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 2043 | Class PN 1.0 |
| 2044 | 350 mm dia |
| 2045 | 400 mm dia |
| 2046 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick .Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 2047 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 2048 | 350 mm dia |
| 2049 | 400 mm dia |
| 2050 | 600 mm dia |
| 2051 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short body pattern type double eccentric Butterfly valves of approved make of following class & dia complete confirming to BS EN 593/ BS 5155/ IS 13095/1991 amended up to date and of following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Face to face dimensions as per DIN 3202 F4/ IS 13095 Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SSAISI-410/316 & shaft bearings- bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal, Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-incharge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 2052 | Class PN 1.6, Motorised Operated |
| 2053 | Delivery Pipe from Pump |
| 2054 | 350 mm dia |
| 2055 | 400 mm dia |
| 2056 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 410/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318-LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318-LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. Insertion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 2057 | On Inlet Pipe from Bisalpur |
| 2058 | Plunger Type Flow Control Valve |
| 2059 | 800mm dia |
| 2060 | 1000mm dia |
| 2061 | On Outlet Pipe from old Amanishah 13.5 ML CWR |
| 2062 | 300 mm dia |
| 2063 | 400mm dia |
| 2064 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 2065 | 350 mm dia. |
| 2066 | 400 mm dia. |
| 2067 | 600 mm dia. |
| 2068 | 800 mm dia. |
| 2069 | 1000 mm dia. |
| 2070 | Removing of existing CI/ DI Double flange sluice valves, non return valves, butter fly valves etc. in existing Distribution/ Rising Main/ Transmission Main pipe line of following sizes, works include de-jointing of valve, dewatering, taking it out of the pit with adequate safety arrangement at site and then refill the pit from excavated sand by ramming it at sides of pipe & up to ground level. Work shall be done as per specification, scope of work and direction of Engineer-in-charge. All old material shall be removed safely & all old material shall be deposited in Divisional Store.Note: Rates are exclusive of earth work and road cutting. |
| 2071 | 300 mm dia. |
| 2072 | 350 mm dia. |
| 2073 | 400 mm dia. |
| 2074 | 450 mm dia. |
| 2075 | 500 mm dia. |
| 2076 | 600 mm dia. |
| 2077 | Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer\"s specifications including appropriate priming coat, preparation of surface, etc. complete. |
| 2078 | On steel work (Pump installation) |
| 2079 | Pumping Machinery |
| 2080 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover. |
| 2081 | Providing, installation, testing and commissioning of Submerged Centrifugal Pump sets with motor 4 pole synchronised speed of 1500 rpm ( water immersed, dry air filled, lass \"F\" insulated TEWC motor integrally mounted on volute casing pump sets for drinking water ) 3 phase, 415 volt +/- 10%, along with suitable foundation/installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 2082 | 200 KW |
| 2083 | Providing, installation, testing and commissioning of submersible dewatering pump set conforming to relevant IS codes and as per scope of work and Technical Specifications, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft, impeller, pump and motor body. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply, with cable guard. The pump set shall be suitable for direct coupling, with suitable suction strainer etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 2084 | 2.2 KW (3.0 HP) |
| 2085 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to Modbus. |
| 2086 | 200 KW |
| 2087 | MS Specials |
| 2088 | Providing and fixing of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. |
| 2089 | MS pipe upto 600mm dia (with minimum 5mm thickness sheet) |
| 2090 | MS pipe Avove 600mm dia (with minimum 6.3 mm thickness sheet) |
| 2091 | Electrical Works |
| 2092 | Providing and fixing in position lightening arrester set complete with 600mmx600mmx6mmthickG.I. earthingplate embeddedbelow groundinearthlingpitat3.5metrdepth,G.I.stripofsize 25mmx5mm thick from earthing plate to top of Over head tank, G.I. FinialmadeofGIbar25mmdiaand2mlongfixedontopofOH tankandconnectedtoGIstrip.Theearthlingsetshallcomplyof IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 2093 | Pipe Ear thing as per IS: 3043 with perforated 3.0 Mtr. Long, 40 mm dia. ‘B’classG.I.Pipeincludingallaccessorieslikenut, bolts, reducer, nipple, wire meshed funnel, and C.C finishedchamber coveredwithhingedtypewithlockingarrangementC.I. Cover, C.I. Frame of size 300mm x 300 mm and embodying the pipe complete withalternatelayerssaltandcoke/charcoal,testingofearth resistance as required. |
| 2094 | S & Laying following size ‘B’ Class G.I.Pipe confirming to IS: 1239 P-1 (1990) with accessories for laying earth conductor/ strip/ cable in ground/ surface/ recess as required. |
| 2095 | 50 mm dia. |
| 2096 | SupplyinganddrawingPVCinsulated&sheathedsolid/stranded copperconductormulticorecontrolcableISImarked(IS:1554)of 1.1kVgradeofapprovedmakeasperchapterE11,inexisting surfaceorrecessedconduit/casingcappingincludingmaking connections etc. as required. |
| 2097 | 4 core, 1.5 sq. mm. armoured |
| 2098 | 8 core, 1.5 sq. mm. armoured |
| 2099 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 2100 | 200KW |
| 2101 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kAbreakingcapacity(B/C/Dtrippingcharacteristicaspertypeof loadandsiterequirement)4KVimpulsewithstandvoltage,ISI markedIS8828(1996)/conformingtoIEC60898-12002,IEC 60947-2,lowwattlosses,tripfreemechanisum,energylimitingofclass3asperIEC, minimumphaseterminationcapacityof 35sq.mm. , conductor line load reversibility , IP 20 contact protection andfittedinexistingdistributionboard/sheets,minimumelectrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A&aboveratingincludingmakingconnections,testingetc.as required. OEM shall have submitNABL / CPRI / ERDA accrediated labtypetestreports&AllasperpreapprovedbyEngineerin-charge.Foradditionaltechnicalparametersofproduct/workrefer Annexure \"A\" attached with this BSR |
| 2102 | Double pole MCB(With B/C curve tripping Characteristics) , 6 A to 32 A rating |
| 2103 | Triple pole MCB(With B/C curve trippingCharacteristics),50/63 A rating |
| 2104 | Four pole MCB (With B/C curve tripping Characteristics), 6 A to 32 A rating |
| 2105 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/freestandingfloormounteddustandverminproof compartmentalisedcubicalpanelasspecificationsandOther parameters requiredas per point (a), (b), (c), (d), (e), (f), (g), (h) as below:-(a) ThicknessofCRCAsheetshallbe2.0mm,cablealley compartmentshaving concealedhingedtypedoorswithkey type lock with /without detachable extension type structure. Removable 3mm.thicksheetsteelglandplateswithappropriatesizeof knockouts for cables shall be provided (b) completepanelshallundergoaprocessofdegreasing,Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panelhavingPEfoam/Neoprenerubbergasketofnotlessthan 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.[c) interconnectionbetweenbusbarandswitchgears/cableshall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried outwith1.5Sq.mm,Earthwirewith2.5Sq.mmandCTwith2.5 sq.mmflexiblecopperwireonly. Alljoints / interconnectionsof copper bus bar shall be dully tinned . Clearance between main bus barandrisers/metalpartsshallbeatleast10mmadditionalto widthofbusbarBusbarisinsulatedbyHeatShrinkablesleeves. Earth and Neutral bus bar shall be half of the size of phase bus bar. (CostofBusbar / FlexiblewireforInterconnectionbetweenMain connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. (d) WiringbetweencomponentswithinswitchgearandIncoming/ outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted.Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads,studswithtwonutsandidentificationstripsandshallhave adequate continuous current rating. For tap-offs, adjacent terminals withshortingstripsshallbeused.10%Spareterminalblocksshall be provided. Wire identification on marking strip shall correspond to thedesignationofthewiringdiagrams.Allwireterminalsonthe equipmentshallalsobemarkedwithdesignationcorrespondingto those of the wiring diagram. (e) Allwiringshallbeenclosedinplasticchannelsandneatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee busbar and Switchgearis to be Paid Extra )(f) FloormountedpanelshallbemountedonBaseframeofISMC channel size 100 x 50 x 5 mm( to be paid Extra ) (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute)shallbemeasuredbetweenphases,betweenphaseand neutralandbetweenphaseandearth.bothbeforeandafterhigh voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to befabricatedonlyfromCPRIapprovedfabricatoronly(CPRITest certificates to be submitted)All as per preapproved byEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2106 | SupplyingandfixingofAluminium(IEC60105ISO209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwithstandardshortcircuitwithstandcapacity, hightensilenuts and bolts spring washers in existing panel including bending , cutting inrequiredshapeandsizeandcolourcodingwithheatshrinkable PVC sleeves. AllasperpreapprovedbyEngineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2107 | Electrolytic grade Aluminium bus bar 6010 grade |
| 2108 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/Frequencymeter/KWHmeter/MultiFunctionMeter/ Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96mmincludingmakingconnectionbyPVCinsulatedcopper conductorwithPVCsleeves / channel etc. asrequired. All as per pre approvedbyEngineerin-charge. For additionaltechnical parametersofproducts/work,refer Annexure \"A\" attachedwith this BSR . |
| 2109 | ThreephaseAMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
| 2110 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW +KVA+KVAR+KVARH+KWH+DUALENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 |
| 2111 | Providing&FixingofBISapprovedCurrentTransformerasper PWD specification for electrical Works ,ISI marked as perIS 2705-1992/conformingtoIEC60044-1,withsecondaryterminalofCT shallbebroughtoutsuitabletoaterminalblockwhichshallbe easieraccessiblefortestingandterminalconnection,withall necessarysupportinexistingpanelincludingconnectionetc.as requiredCurrenttransformerRingTypeTapeWound/ResinCast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified.ISF<=5,Cucrosssectionofsecondarywire1.5sqmm (minimum), includingallnecessarysupportinexistingpanel includingconnectionetc. asrequired. Allasperpreapprovedby Engineerin-charge. AllasperpreapprovedbyEngineerin-charge. Foradditionaltechnicalparametersofproducts/work,refer Annexure \"A\" attached with this BSR . |
| 2112 | C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA |
| 2113 | Providing & Fixing of Cam operated rotary (Auto/manual) switches onexistingpanelwith 2 wayandoffpositionusinghighgrade engineeringmaterial to internationalstandardswithcamassemblyinsulationofglassfilledpolyamidewithhightrackingindex.For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on coppershould provided contact assembly is of operating temp range-25 degree C to55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanicallyminimum50000operations @300cycles/ hour and electrically 10,000 operationsat100%rateddutyfor 100 cycles/ hourincludingmakingconnectionetc. asrequired. Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2114 | 10 AMP |
| 2115 | 16AMP |
| 2116 | Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947 withintegralcircuit,IP65abovepanel&IP 20 terminal block, Approx. bodydiaforpanelnot lessthen20mm,lengthmin. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineerin-charge. For additionaltechnical parametersofproducts/ work, refer Annexure \"A\" attachedwith this BSR . |
| 2117 | Red/yellow/Blue |
| 2118 | Red/Gree/ white Colour |
| 2119 | Red/Gree/ white Colour |
| 2120 | Red/Green |
| 2121 | Providing&FixingofflushheadpushbuttonactuatorsIEC60947withintegralcircuit,IP65abovepanel&IP20terminalblock, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze forLed,PCBcontactsshallbeofbrass(tinplated),impulsedielectrictestedfor2.5KV, includingconnectionetc.asrequired.Allasperpreapprovedby Engineerin-charge.Foradditional technicalparametersofproducts/ work,refer Annexure\"A\" attached with this BSR |
| 2122 | Non luminous type |
| 2123 | Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skidabberationmarksand pasting the mat withsynthetic rubber adhesive asrequired.Allasperpre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2124 | 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) |
| 2125 | Providing&FixingofselfhealingIP20MPPtypeshuntcapacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1&2inexistingpanelorparallelwithloadterminals,thecapacitor shallbefittedwithdischargeresistors,pressuresensitive disconnector(PSD)andshallhavedissipationfactorlessthan 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min overcurrentcapacity1.8 times rated current & peak inrush current min.300 timesofratedcurrent,llifeexpectancygreaterthan 100000 hrs(temp class - 25 D) in440 V/480 V Capacitorandfor 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per preapprovedbyEngineerin-charge. For additionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 2126 | HeavydutyThreephase440V,50Hzcylindricaltypecapacitor (Bank) |
| 2127 | Providing& Fixing of IP54 microprocessor based 3CT’s for all 3 phasesensingcompensationpowerfactorcorrectionrelaySize 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having3CTsensing,sensitivityupto50milliamp secondarycurrent,selfanalysingautoc/ksettingaccordingto targeted power factor setting, the relay shall have digit displayunit fordisplayofrealpowerfactor,targetedpowerfactor,lag/lead capacitorswitchingstatus,alarmoutputforundercurrent,over current, insufficient compensation, communication interface with RS 485,indication of switching onunits, auto/manual status, and shall haveoverloadprotection,novoltrelease,havingmultiparameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay includingmakingcoonectionwith1.5Sq.mmcopperwireetc.as required. All as per pre approved by Engineerin-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2128 | 12 to 14 stage |
| 2129 | Providing&Fixingof440Volt3polecapacitor(AC6B)duty contactor with 3 no. early make and post break auxiliary contacts in serieswithquickdischargedampingresistors/reactorstolimitthe inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1:2000,insulationvoltage1000V,impulsewithstand voltage8KV,Dinrailmountingtypeincludingmakingconnections, testingetc.asrequired.suitableforfollowingcapacitycapacitor bank.All as per pre approved by Engineer in-charge. For additional technicalparameters ofproducts/ work,refer Annexure\"A\" attached with this BSR . |
| 2130 | 25 KVAR |
| 2131 | 50 KVAR |
| 2132 | SITCofDrawouttype3/4poledoorinterlockAirCircuitBreaker (ACB)asconformingtoIS/IEC60947P-2:2003inexistingLT panel suitable for LT installation 440 V, 50 Hz and having adjustable overloadshort-circuit,Instantaneous, earth fault (LSIG) with separate LEDindicationfor each type of fault shall confirm to EMI/EMC test, LCD/LED display, last 10 trip history, provisionofZSI, Communication, Power metering module, Thermal memory, trip free Mechanisum, suitableforambient50degreeandutilization catagaryB. Inbuiltelectrical&mechanicalantipumpingfeature, 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw(1 sec), U imp - 12 KV, breaktimenotmorethen25ms. Provisionforelectrical&mechanicalinterlockbetweenACBs, Min.electricaloperation 10000 upto 2000 A rating and5,000 for 2500 A to 4000 A. includingmaking connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineerin-charge. For additionaltechnicalparameters ofproductwork refer Annexure \"A\" attached with this BSR |
| 2133 | 2500 A Rating ,50 kA |
| 2134 | 1600 A Rating ,50 kA |
| 2135 | SupplyandfixingoffollowingaccessoriesforAircircuitbreaker (ACB)compatiblewithMAinACBOEMasperPWDspecification forelectricalWorks,conformingtoIS/IEC 60947 P- 2 :2003 including makingconnectionetccompleteinallrespect. OEM shall have submit NABL/CPRI/ ERDA accrediated lab type test certificate beforeexecution.Allas per pre approved by Engineer in-charge. For additionaltechnicalparameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2136 | Shunt Trip Release |
| 2137 | Under voltage Release |
| 2138 | Microswitch for Indication |
| 2139 | Operation Counter |
| 2140 | Door Interlock |
| 2141 | Auxiliary Contact 4 NO + 4 NC |
| 2142 | Breaker Control Switch (TNC) |
| 2143 | 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 2144 | Providing&LayingP.V.C./XLPEinsulated&P.V.C.sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - Iof1.1KVwithH4-Gradeelectrolyticaluminiumconductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC /Hume/Stoneware/PVCpipe/openduct/cabletrench/Cable tray(withcabletie)includingtestingetc.asrequiredoffollowing size.OEMmusthaveit\"sowninhouseNABLaccrediated LaboratoryfortestingprocedureasperIS:10810.Foradditional technicalparametersofproduct/workreferAnnexure\"A\"attached with this BSR |
| 2145 | 400 SQMM,3.5 CORE |
| 2146 | 240 SQMM, 3 CORE |
| 2147 | 4.0 SQMM, 3 CORE |
| 2148 | Supply,Fabricating&installingfollowingsizesofperforatedHot dippedGalvanizedironcabletray(Galvanizedthicknessnotless then 50 microns) with perforation not more then 17.5% in convenient sectionincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended fromtheceilingwithGIsuspendersincludingGIbolts&nuts, fastners,supportsetc.asrequired.Allasperpreapprovedby Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2149 | 100mm x 50mm x 1.6mm |
| 2150 | 150mm x 50mm x 1.6mm |
| 2151 | 300mm x 50mm x 1.6mm |
| 2152 | Supply&Layingfollowingsizeearthstripinhorizontalorvertical runinsurfacebymeansofEarthstripDMCInsulatorincluding riveting/soldering/welding,Jointingshallbedonebyoverlapping andwith2setofBrass(forCustrip)/GI(forGIStrip)nutbolt& springwasherspacedat50cmmakingconnectionetc.as required.AllasperpreapprovedbyEngineerin-charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2153 | 50mm x 6mm G.I. ( Hot Dipped) Strip |
| 2154 | Providing&FixingofIK08IP-66protectedhighpowerLEDflood lightsystemwithsinglepiecePressurediecastaluminiumhousing, toughenedglassdiffuserwithsuitablelenses on LED to achieve variousbeamangles, ofhighpowerLED of 3 to 5 watteach. Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate.TheSystemlevelLuminaireefficacy>=125lm/wt.LED driverInputVoltageAC120to270VACwithHighvoltageCutoff @>=300VACandAutoresettingSafety.PowerFactor>0.95, THD(I)<10%,drivercurrent<=750mA.drivershouldbePhaseto phaseprotectionof440Vfor4Hrs.ElectricalConnector,Surge ProtectionMin>=4KVinternaland10KVexternalbutinsidedriver compartment, System life of 50000 Burning hours with 70% of Initial Lumensmaintained, CRI>70 and CCT 5700K ±355K. ManufacturesWord Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shallbeIS10322Complianced.OEMMusthaveitsowninhouse NABLlabsetupforalltestingfacilitiesforLEDfixtures.(LM79/LM80)Certificate/reportwithliablewarrantyof product/accessoriesfromOEMshallbesubmitted.Allasperpre approvedbyEngineerin-charge. Foradditionaltechnical parametersofproducts/work,refer Annexure\"A\"attachedwith this BSR . |
| 2155 | High Power LED Flood Light Minimum lumen output 10000 lm |
| 2156 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 2157 | Heavy Duty AL & CU Lugs,Double Compression Cable Gland with Nickel Plated, Cable Tie, Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners, Clamps, Clips, Screw, Washers, Electrical Taps, HT Tap, Danger Plates, Condut Pipe, 40mmuPVC Pipe, 4.5 Kg. CO2 type portable fire extinguisher for Panel Room, Fire buckets with floor / wall mounting stand ect. required hardware & accessories for various sizes as per site requirements. |
| 2158 | AUTOMATION & PLC-SCADA Works |
| 2159 | Chlorine Analyser : Transmitter : Range: 0.05 to 20 ppm, Power Supply 230 VAC, Input: 2 Digital Sensors - one for chlorine and second for pH, Output: 4-20mA HART, IP66/67 Protection / Tx protection cover required / Sensor Range 0-14 pH , able to transmit digital signal to transmitter, calibration data can be transferred to Transmitter , process temp: 65 deg cen/ Sensor range:0.05 to 20 mg/l. |
| 2160 | Providing,Installation,TestingandCommissioningofPressure Transmitter : Range:0-10Bar / Power Supply:24 V DC / Output: 4-20mAwithHART/Diaphragm:SS316L/ProcessConnection: 1/2 \"NPT (M) / Accuracy: 0.15% Protection: IP67 |
| 2161 | Providing,installation,testingandcommissioningofDiaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass,Overrangeprotection:125%ofmaximumpressure,Material ofsensorandotherwettedparts:SStype316,Housingmaterial: Die cast aluminum |
| 2162 | Providing, installation, testing and commissioning of Diaphragm type Pressure Switches Sensing Element: Bellows / Diaphragm, Material ofsensorandotherwettedparts:SStype316,Housing:Diecast aluminum,Switchtype:Microswitch,Repeatability:±1%ofspan, Switch Contacts: 2 NO + 2 NC |
| 2163 | Providing,installation,testingandcommissioningofLevelSwitch( Conductivity)ConductivityProbes,Probeinsulation:Teflon,Probe head protection class: IP 65 of IS 13947 Part I, Probe head housing material: Aluminum |
| 2164 | Rigid for lengths from 3 - 10 Mtr. |
| 2165 | Providing,installation,testingandcommissioningofONLINEUPS SYSTEM,SinglePhase230V,50Hzwith2hourbackupSMF battery bank as per specification |
| 2166 | 2 KVA |
| 2167 | Design,Manufacture,Supply,Installation, TestingandCommissioningofIndoortypePLC Panelofsizeapprox.800mmX500mmX 2000mm(LBH),Fabricatedoutofmin.2mm thickCRCAsheetcompletewithlatest configuration,necessaryprogrammingsoftware forPLC&SCADAandcomprisingofall accessories not limited to the following:DI102No. DO 98No. AI 22No. AO 16No.MCB 16A DP 2No.MCB 6A DP6No. SMPS 100-240VAC/ 4.5A / 24 VDC 1No. Selector Switch (uto/Manual) & Local / Remote2No. Control Relays1LotAnnunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with1No.Electronic Hooter1No. Control Transformer 200VA1No. Emergency STOP Push Button1 No. Panel Cooling Fan & Filter2No. Panel Light with Door Switch, 7W1No. Control Indication Lamp for 24VDC, 220VAC3No. Push Button3No. Power Wiring+Control Wiring + Control TB/ Fuse 2A,TB etc 1 LotPanelHardware,lugs,terminations,ferruls, name plate Ect. 1 Lot UTILITY SOCKET 16A, 3 PIN2No. HMI Display 12 Inch, Colour1No. Isolators Dual Output, 24VDC1Lot |
| 2168 | SITCofIntelligentManageableEthernetSwitchesproviding24x 10/100/1000FastEthernetports-and2dualpurposeuplink (provisionforCopper/FibreGigaconnectivity)withLANbased Software.TheLANbasedS/Wsupportsenhancedintegrated security,includingNetworkAdmissionControl(NAC),advanced qualityofservice(QoS),availabilityandscalablemanagementto enable new converged applications |
| 2169 | ProvidingandlayingStranded/FlexibleAnnealedeBarecopper conductor,XLPE/PVCinsulatedsuitablylaiduptogetheroverall polystertapedAl(innersheatedGISteelwireMylar/Drainwire) alongwithATCdrainwire,round/steelarmouredoverallPVC sheathed (ST-1) overall screenedCore armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 2170 | 24 CORE, 1.0 sq. mm. |
| 2171 | 4 CORE, 1.0 sq. mm. |
| 2172 | Providing and laying Stranded/ Flexible Annealed Bare copper conductor, XLPE/PVC insulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wire overall PVC sheathed (ST-1) overall screenedPair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (2 Pair * 0.75SQMM) |
| 2173 | Quad-bandGPRS/IOT/VPN/GSM/CLOUD 3G/4G/5G modemwithEthernetbridge/router/ serial server (RS232/485) interface. |
| 2174 | Instrumentation Work |
| 2175 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) ,Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC -50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 2176 | Inlet Pipe to 15 ML CWR from Bisalpur main and Outlet pipe towards VKI and GN Feeder |
| 2177 | EFM 600 mm |
| 2178 | Providing, Installation, Testing and Commissioning of Ultrasonic Flow Meter Insertion Type: Principle: Time of Flight / Type: Insertion / Protection : IP68 / Power Supply: 230 V AC / Output : 4-20 mA with HART / Accuracy: 2 - 3% 1000 -4000 mm |
| 2179 | 1000-4000 mm (On 1200 mm Inlet pipe from Ram Niwas Bagh near pani peech tiraha) |
| 2180 | Civil work |
| 2181 | RCC Channel, EOT Crane and Valve Chambers |
| 2182 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed :All kinds of soil |
| 2183 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. |
| 2184 | M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 2185 | Providing and laying in position Ready mix concrete manufactured in fullyautomatic Batching Plant andtransported to site intransit mixer for having continous agitated mixer, manufactured as per approved mix design of specified grade of RCC work including pumping of R.M.C. from transit mixer to site of laying , exculding the cost of centering, shuttering and reinforcement with all lead and lift including cost of admixtures in recommended portion as per IS 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer in charge. All works upto floor V floor M20 grade Design Mix by using cementas per codal provision.RATE 6089/cum ;ADD-Providing M-30 grade concreteby usingcement as per codal provision instead ofM-20 grade design mix.194/cum. |
| 2186 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft, bases of columns etc. |
| 2187 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 2188 | Steel work in built up tubular trusses including cutting, hoisting ( height upto 10 m)fixing in position and applying a priming coat of approved steel primer, welded and bolted including special shaped washers etc. complete. For Roofing |
| 2189 | Hot finished welded type tubes. |
| 2190 | Providing & fixing UV stabilised fiberglass reinforced plastic sheet roofing upto any pitch including fixing with polymer coated „J‟ or „L‟ hooks, bolts & nuts 8mm dia. G.I plain/bitumen washers complete but excluding the cost of purlins, rafters, trusses etc. The sheets shall be manufactured out of 2400 TEX panel rovigs incorporating minimum 0.3% Ultra-voilet stabiliser in resin system under approximately 2400 psi and hot cured. They shall be of uniform pigmentation and thickness without air pockets and shall confoim to IS 10192 and IS 12866.The sheets shall be opaque or translucent, clear or pigmented, textured or smooth as specified |
| 2191 | 5.0mm thick (Wt. 8.4 Kg./Mtr. Sq.) |
| 2192 | Construction of Pump house of RCC framed structure with pump pit in RCC walls as per scope of work and technical specification complete work in all respect including electrical works for indoorand outdoor lighting and fans, rain water drainage, sanitary, plumbing, monorail/ EOT crane etc. complete as per direction of Engineer-in-charge. The GA, structure, electrical, sanitary, P&ID, SLD to be prepared by the contractor and submitted to department for approval for earth quake zone II. |
| 2193 | Pump House with Monorail arrangement(8.431 m x 12 m) (As per GA Drawing) |
| 2194 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. |
| 2195 | For in-campus Valve Chambers |
| 2196 | Sluice valve chamber of size 1.61m x1.75m x2.85m for pipe size-from 500-to-700mm (Shall be made as per GA Drawing and field Requirement) |
| 2197 | For Class-AA loading |
| 2198 | Sluice valve chamber of size 2.3 m x 2.4 m x 3.8 m for pipe size-from 1000-to-1500 mm |
| 2199 | Providing and fixing of reinforced Ferro-Cement drain covers designed for \"A\" class loading duly marked on cover with adequate steel reinforcement having thickness 75mm to 150mm anti corrosive bitumen painted M.S. plate , Rim and M.S. lifting hooks, Admixtures like plasticizer, bond improving compound, shrinkage, resistance compound, abrasion resistant complete as per approved design etc |
| 2200 | Standard Size 2100 x 500mm (150mm thick) for span 1201 to 1500mm |
| 2201 | Driven cast-in-place true vertical R.C.C. piles excluding reinforcement complete as per drawing and technical specification as per clause 1100, 1600 & 1700 of MoRT&H Specification including all material, labour and machinery. |
| 2202 | 450 mm dia pile |
| 2203 | RCC Grade M -20 (Design mix) (111 nos. piles to be driven at 10 mtr depth) |
| 2204 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rolled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 2205 | 2 MT Capacity |
| 2206 | Span 7 M and Lift 6 M |
| 2207 | Construction of Panel Room on CWR at Amanishah HW |
| 2208 | Providing and fixing precast cement concrete coping 1 : 2 : 4 mix 50 mm thick complete as perspecification : |
| 2209 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required ) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. M20 grade Nominal Mix / Design Mix |
| 2210 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement for Beams, suspended floors, roofs, griders having lopes up to 15º, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases etc. M20 grade Nominal Mix / Design Mix |
| 2211 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel propsand removal Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc.of formwork for upto floor five level for :Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc. |
| 2212 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel propsand removal Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc.of formwork for upto floor five level for_Columns, pillars, posts and struts etc. |
| 2213 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level.(Original producers who manufactura billet directly from iron ores and roll the billets to produce steel conforming to IS:786)Thermo-mechanically Treated bars (Tata, SAIL) |
| 2214 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 2215 | Half brick masonry in Superstructure , above plinth level upto floor V level using bricks of designation 75; 5.8.2 Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 2216 | Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades ceramic glazed vitrified tiles with water absortion less than or equal to 0.08% confirming to IS:13753 & IS : 15622 on walls, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar).Size 600mm x 1200mm |
| 2217 | Providing & fixing door, window, chowkhats and other frames, including antitermite treatment, M.S. flat, hold fasts of size 250 x 40 x 3mm fixed with M.S. bolt 5mm dia 50mm long duly embedded in cement concrete M-15 grade :Nigeria teak wood Grade - I. |
| 2218 | Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure \"A\" : 35 mm thick, commercial Veneer Both side. |
| 2219 | Extra for providing external lipping with 2ndclass teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured); for door leaf shutt |
| 2220 | Extra for providing other type of fittings as mention in annexure A ( as approved by EI) : Stainless steel fittings. (for door leaf shuter) |
| 2221 | Providing and fixing bright finished Mortice lock of approved make Godrej or equivalent with pair of CP handles for doors with necessary screws etc complete (Best make of approved quality) as per direction of Engineer-in-charge. |
| 2222 | Providing & Fixing mica of approved make for inner/outer side of shutters with fevicol & nails completeas per approved by engineer in charge.0.8mm thick mica |
| 2223 | 9.19 Providing and fixing steel glazed doors windows and ventilator shutters of standard rolled steel section (IS 1038- 1983) joints mitred and welded with steel lugs 13x3mm, 10cm. long embedded in cement concrete block 15x10x10cm. of 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) or with wooden plugs and screws or rawl plugs and screws with fixing clips or with bolts and nuts as required including providing and fixing of plain glass panes 4mm thick with cooper glazing clips and special metal sash putty of approved make or metal beading with screws complete including priming coat of approval steel primer, excluding the cost of metal beading and other fitting except necessary hinges of pivots steel handles peg stay etc. as required |
| 2224 | Windows side hung /Ventilators top or centre hung (openable) |
| 2225 | Providing brass handles/peg stays and fittings in place of oxidized fitting Sqm. 5% |
| 2226 | 5mm thick plain glass instead of 4mm thick plain glass Sqm. 95.00 |
| 2227 | Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance. Sqm. 617.00 |
| 2228 | Grading roof water proofing treatment with water profing compound :Cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 2229 | Providing batta (gola) 75 mm x 75 mm in cement concrete (1 : 2 : 4) including finishing with cement mortar 1 : 3 as per standard design. |
| 2230 | Plaster on new surface on walls in cement sand mortar 1:4 including racking of joint etc. complete fine finish : 20 mm thick |
| 2231 | 6 mm cement plaster to ceiling of mix 1 : 3 (1 cement : 3 fine sand).; Celling plaster |
| 2232 | Making grooves as per design in plaster 10 mm to 20 mm wide.; (add; 20 % R.M.of plaster work.) |
| 2233 | Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth completeNew Plastered Surface (three or more coats) |
| 2234 | Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade including all scaffolding:Two or more coats on new work including prepartion of base with primer, putty, lippy etc complete in all respect. |
| 2235 | Finishing walls with textured exterior paint of required shade as per approved colour complete as per manufacturers specifications including primer coat and protecting coat including scaffolding and safety provision. Trowel Finish av. thickness 2000 to 2500 microns. |
| 2236 | 1.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2237 | Short point (up to 3 mtr.) |
| 2238 | Medium point (up to 6 mtr.) |
| 2239 | Long point (up to 10 mtr.) |
| 2240 | 3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexiblecopper earth conductor 1.1 kV grade(IS:694) inrecessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thickwith earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket,Modular face plate with grid plate, screws, making connections, testingetc. as required. For specification of copper Conductor, PhenolicLaminated sheet\"s & Electrical/ Wiring accessories refer Chapter E - 04, E- 05 & E - 07 For additional technical p |
| 2241 | On board |
| 2242 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2243 | 20 mm |
| 2244 | 25 mm |
| 2245 | 4.2 Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor of alum. alloy braid in existing surface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2246 | Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TECspecification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair forIdentification etc. as required. For additional technical parameters ofproduct / work refer Annexure \"A\" attached with this BSR;4.3.4 4 pair |
| 2247 | P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ;5.1.1 1.2 mm thick M. S. Sheet boxes ; |
| 2248 | 100mm x 100mm x 60mm |
| 2249 | 200mm x 250mm x 75mm |
| 2250 | P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2251 | P & F 1.00mm thick M.S. Recessed concealed box, round of size 150 mm dia, depth 100 mm complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2252 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2253 | Single pole MCB (With B/C curve tripping Characteristics) |
| 2254 | 6 A to 32 A rating |
| 2255 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947- III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 35sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR;6.2.3 Four pole Isolator; 63 A rating |
| 2256 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2257 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 2258 | 6 Way (6+2) |
| 2259 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial gradePolycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 2260 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2261 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2262 | 6/16 A shuttered socket |
| 2263 | 7.29 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captivescrews & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ; 7.29.1 5 step fan regulator 2 Module 360 dgree rotating |
| 2264 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2265 | Modular MCB 6 A to 32 A SP |
| 2266 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2267 | 3 Module Each 86.0 |
| 2268 | 6 Module Each 114.0 |
| 2269 | 8 Module Each 155.0 |
| 2270 | 12 Module Each 214.0 |
| 2271 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2272 | 11.3 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2273 | 10.0 Sq. mm, 4 core4 core |
| 2274 | Providing & Fixing of 1200 mm sweep BLDC technology power saving ceiling fan which can withstand on votage fluctuations from 140 volts to 240 volts ,power factor not less then 0.9 , service value (CMM/W) minimun 6.85 , air delivery minimun 220 CMM, speed minimum 330 RPM ( tolerance as per IS:374 2019 ) THD less then 10% and complete with down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe up to 80 cm , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 15.4.1 Without Remote |
| 2275 | 15.12 Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 300 mm sweep(900/1400 RPM) |
| 2276 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2277 | 17.3.1 Recessed Mounting ;Minimum lumen output 650 lm |
| 2278 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required.Gr I |
| 2279 | 3x 1.5 sq.mm |
| 2280 | 2 x 2.5 sq. mm. + 1x1.5sqmm ( All light and power Ckt) |
| 2281 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (AC Ckt) |
| 2282 | 4 x 10 sq.mm (Sub main) |
| 2283 | 1 x 6 sq.mm (With sub main ) |
| 2284 | Construction of new office building |
| 2285 | Earth work in excavation by mechanical means (Hydraulic Excavator)/manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter. All kinds of soils |
| 2286 | Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidating each deposited layer by ramming and watering including lead up to 50 meter and with all lift. |
| 2287 | Supplying and Filling in plinth with blown sand under floors including watering ramming consolidating and dressing complete including cost of sand. |
| 2288 | Surface dressing of the ground including removing vegetation and inequalities not exceeding 15cm deep and disposal of rubbish lead up to 50 Mtr. and lift up to 1.5 Mtr. : All kinds of soil. |
| 2289 | Supplying chemical emulsionin sealed containers including delivery as specified. Chlorpyriphos/Lindane emulsifiable concentrate of 20% |
| 2290 | Diluting and injection Chloropyrifos Emulsifiable concentrate 20% with 1% concentration for PRE-CONSTRUCTIONAL Anti termite treatment as per IS 6313 part III as amended from time to time and creating a continuous chemical barrier under and around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor along the external perimeter of building expansion joints, over the top surface of consolidated earth of which aproch is to be laid surrounding of pipes and conduits etc. complete as per specification (Plinth floor area only shall be measured for payment and excluding the cost of chemical emulsion). |
| 2291 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level.M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size). |
| 2292 | Construction of embankment with approved material obtained from borrow pits with all lifts and leads, transporting tosite,spreading,gradingtorequired slope and compacting by vibratory roller 8-10 Tonne to meet requirement of Table300-2includingcostof compensation for earth taken from private land with ALL lead As per MoRTH specification Clause No. 305. |
| 2293 | Carriage of Materials by mechanical transport including loading,unloading and stacking ::Sand, bazri, ballast, kankar- Lead upto 5 Km |
| 2294 | Carriage charges for Earth, Sand, Lime, Morrum manure or sludge upto 10 KM lead |
| 2295 | Carriage charges for Building Rubbish Stone metal (Grit and ballast etc.)upto 10 KM lead |
| 2296 | Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement. M20 grade Nominal Mix / Design Mix |
| 2297 | Providing M-25 grade concrete by using cement as per codal provision instead of M-20 grade design mix. |
| 2298 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc. |
| 2299 | Providing and fixing aluminum work for doors ,windows, ventilators and partition with extruded built up standard tubular / appropriate Z sections and other sections of approved make conforming to IS :733 and IS :1285, fixed with rawl plugs and screws or with fixing clips ,or with expansion hold fasteners including necessary filling up of gap. at junctions , at top ,bottom and sides with required PVC/neoprene felt etc. Aluminium section shall be smooth ,rust free, straight ,mitered and jointed mechanically wherever required including cleat angle Aluminium snap beading for glazing /paneling , C.P. brass/ stainless steel screws Al. Tower bolt & Al. handle & Al. Aldrop etc.,all complete as per architectural drawings and the directions of Engineer- in – charge .(Glazing and paneling to be paid for separately). Polyester Powder coating aluminum (minimum thickness of powder coating 50 micron) |
| 2300 | Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: Cement Mortar 1:6 (1-Cement : 6-Sand). |
| 2301 | Supplying and fixing in walls machine cut and polished stone shelves, tands and in CM 1:3 with machine cut edges : Sand or other approved stone 25mm thick. |
| 2302 | Supplying and fixing machine cut fine dressed Red/Pink sand stone dasa or coping, with full moulding if required laid on cement mortar 1:4 including pointing with admixture of pigment matching with the stone shade. 25 mm thick |
| 2303 | Providing and fixing Marble stone flooring table rubbed, 15-18 mm thick over 20mm (Av.) thick base of CM 1:4 (1 cement : 4 coarse sand) jointing with white cement mortar 1:2 (1 white cement : 2 marble dust) with pigment to match the shade of the marble slab including grinding, rubbing and polishing complete. OR Providing and fixing stone slabs table rubbed, 15-18 mm thick in Walls, Steps, Pillars, Counters, Jambs, Shelves, Sills etc. laid on 12mm (Av.) thick base of CM 1:3 (1 cement : 3 coarse sand) jointing with white cement mortar 1:2 (1white cement : 2 marble dust) with pigment to match the shade of the marble slab including grinding, rubbing and polishing complete. Makrana Adanga. 1501 Cm2 to 3600 Cm2 Tiles |
| 2304 | Providing and fixing Granite stone slab mirror polished and machine edge cut in walls, pillars, steps, Shelves, Sills Counters, Floors etc. laid on 12mm (Av.) thick base of cement mortar 1:3 (1 cement : 3 coarse sand) jointing with white cement mortar 1:2 (1white cement : 2 marble dust) with pigment to match the shade of the marble slab including grinding, rubbing and polishing complete. Jhunjhunu / Jalore Red/Choclate/Black/Pink Colour). 1501 Cm2 to 3600 Cm2 Tiles |
| 2305 | Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades glazed tiles confirming to IS : 13753 & IS :15622 of size 200mm x 300mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar). |
| 2306 | Providing and fixing 1st quality MAT finished ceremic tile size 300x300mm confirmingto IS : 13755 and IS : 15622 colour such as white, grey, ivory, fume red brown, light green, light blue and other light shades in floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (including the cost of cement mortar bed 1:4). |
| 2307 | P & F 1st qualityVitrified Porcelain Polished tiles on floor, skirting and steps etc.in different sizes (thickness to be specified by manufactuer) with water absorption less than 0.08% and conforming to IS 15622 of approved make in all colour and shade,laid with 20 mm thick CM 1 : 4 including grounting the joints with white cement and matching pigment etc complete. size 600 mm X 600 mm |
| 2308 | Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure \"A\" : 30 mm thick . Decorative teak veneer both side |
| 2309 | Extra for providing external lipping with 2nd class teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured) Over item no. 8.13. |
| 2310 | Providing and fixing curtain rods of 1.25 mm thick chromium plated brass plate, with two chromium plated brass brackets fixed with C.P. brass screws and wooden plugs, etc., wherever necessary complete: 20 mm |
| 2311 | Providing and fixing pressed steel door frames confirming to IS 4351 manufactured from commercial mild steel sheet of 1.25 mm thickness including hinges jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25mm, or base ties of 1.25mm pressed mild steel welded or rigidly fixed together by mechanical means, adjustable lugs with split end tail to each jamb including steel butt hinges 2.5mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface including filling with CC 1:2:4(M15 grade) complete as directed by Engineer-incharge. Profile E |
| 2312 | Providing and fixing in position collapsible steel shutters with vertical M.S. Channels 20 x 10 x 2mm and bracket with flat iron diagonals 20 x 5mm. size with top and bottom rail of Tiron 40 x 40 x 6mm. with 40mm dia steel pulleys/ball bearing complete with bolts, nuts locking arrangements inside and outside stoppers, handles etc. as per specification including applying a priming coat of approved steel primer. (To be measured and paid as per outer dimension). |
| 2313 | Providing and fixing Square bars or other flat welded to window, ventilatiors etc. |
| 2314 | Crazy marble stone flooring 20mm thick marble stone with black or of specified colour topping including filling the gaps with cement marble chips mix in proportion of 4 : 7 (4cement : 7 white black or white or black marble chips) size from 1mm to 4mm by volume and under layer of 25mm thick cement concrete [1:2:4, graded stone aggregate 12.5mm nominal size] rubbing and polishing and cement slurry etc. complete : In ordinary cement. |
| 2315 | Kota stone slab flooring 25 mm thick over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand). For area of each slab from 2001 to 5000 Sq.Cm |
| 2316 | Random rubble dry stone Kharanja under floor. |
| 2317 | Filling of sunk portion of roof with earthen pots of required height including filling voids with 1:3:6 light concrete, using brick bats complete levelling and dressing the surface by 50mm thick cement concrete 1:2:4 as per specification. |
| 2318 | Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finish : 20mm thick. |
| 2319 | Making of drip course (Tapka) in cement sand mortar 1:6 width upto 40 mm and 10 mm thick as per approved design. |
| 2320 | Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding: New work (Two or more coats applied @ 3.84 kg/10 sqm). |
| 2321 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 2322 | Removing mortar from stones and cleaning stones and concrete articles including stacking (net quantity of stacks of cleaned materials will be measured): In cement mortar |
| 2323 | Dismantling doors, windows and clearstory windows steel or wood shutter including chowkhats and holdfasts etc. complete and stacking within 50 meters lead: Of area 3 square meter and below. |
| 2324 | Taking out doors, windows and clearstory windows shutters (steel or wood) including stacking within 50 meters lead: Of area 3 square meter and below |
| 2325 | Dismantling stone slab/ terrazo chip flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 meters lead. |
| 2326 | Providing and fixing glazing in aluminium door, window ,ventilator shutters and partitions etc. with PVS / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge.(Cost of aluminium snap beading shall be paid in basic item.) With float glass panes of 5.0 mm thickness ( weight not less than 13.50 kg/sqm) |
| 2327 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture IS : 6315 marked, for doors including cost of cutting floors as required, embedding in floors and cover plates with brass pivot and single piece M.S. With stainless steel cover plate |
| 2328 | 30mm thick factory made solid both side Pre laminated panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles and 15x15mm top & bottom rails. M.S .frame shall have a coat of steel primers of approved make and manufacture M.S. frame covered with 5mm thick heat moulded PVC „C channel of size 30mm thickness, 70mm width out of which 50mm shall be flat and 20mm shall be tapered in 45 degree angle on either side forming tiles; and 5mm thick, 95mm wide PVC sheet out of which 75mm shall be flat and 20mm shall be tapered on the inner side to form top and bottom rail and 115mm wide PVC sheet out of which 75 mm shall be flat and 20mm shall be tapered on both sides to form lock rail. Top bottom and lock rails shall be provided either side of the panel. 10mm (5mm x 2) thick, 20mm wide cross PVC sheet shall be provided as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded/ sealed to the stiles & rails with 7mm (5mm +2mm) thick x 15mm wide PVC sheet bending on inner side, and joined together with solvent cement adhesive. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the „C Channel using PVC solvent adhesive etc. complete as per direction of Engineer-in-charge, manufacture‟s specification & drawing.(For W.C.and bathroom door shutter). |
| 2329 | Providing and fixing stainless steel railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). Grade 304 |
| 2330 | SANITARY WORK |
| 2331 | P & F Indian type white glazed vitreous china 1st quality W.C. orissa pan (IS :2556 Mark) with 100 mm vitreous china P or S trap including cutting and making good the wall and floor: Size 580x440mm. |
| 2332 | P & F White Vitreous China Double Syphonic European W.C. (I.S:2556Mark) with mounted W.V.C. flushing cistern of (IS : 2556 Mark) of 10 litre capacity complete with all necessary internal fittings including cutting and making good the wall and floor. |
| 2333 | Providing & Fixing premium qulaity WVC Urinal with PVC waste pipe, dome couplings, concealed iron brackets or screws etc. complete. Flat Back (small) size 440x265x315 mm. |
| 2334 | P&F Marble Urinal Partition slab both sides polished of approved design cut from marble size 900x600mm. Makrana II quality marble having light spots |
| 2335 | P & F Low level Flushing Cistern of 10 litres capacity (IS : 2556 mark) of approved make with complete fittings C.I. brackets duly painted, brass ball cock with ball (IS: 1703 mark) complete including cutting and making good the wall: WVC for symphonic EWC. |
| 2336 | P & F WVC Wash basin (Ist quality IS:2556 Mark) of approved make with C.I. brackets duly painted 1 No. 15 mm C.P. Pillar cock (IS:8934 Mark) & 32 mm C.P. brass waste coupling of approved make, P.V.C Waste pipe with PVC nut 32 mm complete including cutting & making good the wall : Size 580 mm x 450 mm |
| 2337 | P & F Looking Mirrors with P.V.C. frame of approved make as per direction of Engineer-in-charge 1.45.1 Size 500x400mm |
| 2338 | P & F Grating of approved quality/make:Stainless Steel Sheet size 125mm dia. Heavy Quality of approved make |
| 2339 | P & F Acrylic Toilet accessories set consisting of Towel rail, shelf, towel ring, soap dish, paste & brush holder & twin peg of approved quality/make. |
| 2340 | P & F Jet spray for water closet with C.P. Copper Tube flange of approved make. |
| 2341 | P & F Premium quality water closet Seat Covers with brass hinges complete Solid PVC (ISI marked) grade-I White for EWC. |
| 2342 | Providing and fixing Polyethylene - Aluminium -Polyethylene (PE-AL-PE) Composite Pressure Pipes as per 15450 : 2004 U.V. stablised with carbon black having thermal stabillity for hot and cold water supply, capable to withstand temperature upto 80ºC including all special fittings of composite material (engineering plastic blend and brass inserts wherever required) e.g. elbows, tees, reducers, couplers connectors etc.with clamps at 1.00 metre pacing.This include the cost of cutting chases and including testing of joints complete as per direction of Engineer In charge Concealed installation including cutting chases and making good the walls etc. complete. |
| 2343 | (i) 1620 (20mm OD) pipe |
| 2344 | P & F Bib Cock (IS : 8931 Mark), Superior quality ofapproved make: Brass 400 gm,15mm nominal bore. |
| 2345 | P & F Stop Cock (IS :8931 Mark), superior quality & of approved make: Brass 400 gm. 15mm nominal bore. |
| 2346 | P & F Full-way Valve (IS:778 Mark) or wheel valve ofapproved make :Gun-metal 25mm nominal bore. |
| 2347 | P & F PVC Storage Tank ISI Marked (IS : 12701) indicating theBIS license No),of approved make with cover, 25mm dia 1M long G.I. over-flow pipe & 25 Cm. long wash out pipe with plug & socket, including making connection etc., complete of approved design:1000 litres capacity. |
| 2348 | P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2 .) approved quality /make including joining the pipe with solvent cement rubber ring and lubricant.110 mm dia |
| 2349 | Providing & Laying C.C. 1:3:6 (Stone Agreegate 20mm nominal size) all around PVC Pipe including 7.5 cm thick bed concerte [Width & Height = Dia of Pipe in CM+15CM] excluding cost of Pipe & Excavation of trenches etc. PVC pipe 110 mm dia |
| 2350 | P&F rigid PVC pipe fittings (IS: 4985 mark) of approved quality /make including joining the pipe with solvent cement rubber ring and lubricant: |
| 2351 | Coupler (socket) 110mm dia. |
| 2352 | Plain Tee 110 mm dia. |
| 2353 | Door Tee 110 mm dia. |
| 2354 | Door \"Y\" 110 mm dia. |
| 2355 | Bend 45 |
| 2356 | Vent Cowel 110 mm dia |
| 2357 | Door Cap 110 mm dia |
| 2358 | Pipe Clip 110 mm dia |
| 2359 | W.C. connector with lipring 110 mm dia. |
| 2360 | Construction of manhole in all type of soil inner size 90 X 60 Cm. 300 mm thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5:10 in foundation, 20 mm thick inside plaster in CM 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring, making channels, 80mm thick stone slab covering with 40mm thick M-15 grade C.C. flooring, Cement cover with frame of 450mm dia, earthwork etc. complete as per design including disposal of surplus earth within 50 mtr. lead. Depth up to 0.5 M |
| 2361 | Construction of chamber in all type of soil with 300 mm thick masonry in CM 1:6 m,10 cm thick C.C. 1:5:10 in foundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring , earthwork etc. complete as per design including disposal of surplus earth within a lead of 50 mtr. Inside size 300 X 300 mm depth upto 0.5 M Cement cover with frame. |
| 2362 | Construction of soakage well in all type of soil with 300 mm thick dry masonry, top and bottom 300 mm course in CM 1:6, 80mm thick stone slab, jointing of slab in CM 1 : 3, Ralthal, Kharanja, 40 mm thick M-15 grade C.C flooring , earthwork complete as per approved drawing including disposal of earth within a lead of 50 mtr. Size 300 Cm. dia outside & 300 Cm. depth . |
| 2363 | Construction of septic Tank in all types of soil with 40 Cm .thick masonry in CM 1:6, 15 Cm thick C.C bed of 1:5:10, M-15 grade C.C floor & RCC slab covering with M15 grade c.c. floor, 50 mm thick stone slab partition walls, 20 mm thick plaster in CM 1:6 finished with neat floating cement, 4 Nos stone foot rests of approved design ,two No. 450 mm dia each Ferro cement cover with frame, earth work etc. complete as per approved drawing including disposal of surplus earth within a lead of 50 mtr:- Size 230 x110 x150 cm.(for 20 users) with 115 mm thick RCC (M-20) slab with Tor steel reinforcement 10mm ϕ @15 cm c/c bothways including shuttering complete in all respect. |
| 2364 | APPROACH ROAD |
| 2365 | Construction of embankment with approved material obtained from borrow pits with all lifts and leads, transporting to site, spreading, gradingtorequired slopeand compactingby vibratory roller 8-10 TonnetomeetrequirementofTable300-2includingcostof compensation for earth taken fromprivate landwith ALLlead As per MoRTH specification Clause No. 305. |
| 2366 | Providingandlayinggranularsub-basematerialhaving P.I.notmorethan6,includingspreadinginlayersnot exceeding 150 mm compacted thicknessand consolidation by 8-10 tonne power rollerto required camber and grade including cost of water and hire charges ofmachinery,includingT&Pwithalllead(Compacted thicknesstobemeasured).asperMORTHspecification table 400-1, 400-2.For grading-III with CBR value not less than 20 to attain 100% proctor density. |
| 2367 | Providing, laying, spreadingand compactingstone aggregate of specfic as per table 400-7 to Water Bound Macadam specification including spreading in uniform thickness,handpackingroll-ingwithvibratoryroller in stages to proper grade and camber, applying and brooming requisite type of screening and binding materials to fill-up the interstices of coarse aggregates watering (with water browser) and rolling making necessary earthen bund to protect edegs, lighting, guarding, barricading and maintenance of diversion etc. [MoRTH specfication : Clause 404] ( By manual means).Grading III , 53 mm to 22.4 mm@ 0.91 cum per 10 Sqm for compacted thickness of 75 mm.(Crusher broken).Stone screening type \"B\" |
| 2368 | Providing and laying controlled cement concrete for cement concrete pavements including mixing and vibrations concrete with necessary needle vibrators and surface with screed board vibrating complete in all respect with 20/25mm stone aggregate (crusherbroken) including anti-skid textured finish to required camber/superelevation and grade including framework,vaccume process, dewatering, seperation membrane of 125micron thickness as anti fraction layer,cutting of tranverses and longitudinal joints,4to6mm width with joint filling by sealent, 25mm wideExpansion jointsusing 25mm impregated bitumen board including dowel bars in prescribed intervel with curing etc. as per specification. with cement concrete M-30 grade |
| 2369 | Providinganderectingdirectionandplaceidentification retro-reflectorisedsignasperIRC:67madeofhigh intensitygradesheetingexclusiveoflettering,border& signs fixed over aluminium sheeting, 2 mm thick fixed on a mildsteelangleironframe50mmx50mmx6mm supported on mild steel angle iron post 75 x 75 x 6 mm upto the top of sign board, length of post from bottom of sign boardis 2.85m.uptofoundationlevelpostdulypaintedinblack andwhitesyntheticenamel alternateship30cm.wide fixed to the ground by means properly designed foundation with M-15 grade cement concrete 45cm x 45cm x 60 Cm , 60 Cm below ground level as per approved drawing & as per MORTH specifications clause 801. Double angle post.120 cm. X 90 cm. |
| 2370 | Electrical Items for Building Work |
| 2371 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it\"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter-53, 54 & 56 for additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2372 | Short point (up to 3 mtr.) |
| 2373 | Medium point (up to 6 mtr.) |
| 2374 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it\"s ISI marked(IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copperConductor, Phenolic Laminated sheet\"s & Electrical/ Wiring accessories refer Chapter-53, 54 & 56. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2375 | On board |
| 2376 | Short point (up to 3 mtr.) |
| 2377 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2378 | 20 mm |
| 2379 | 25 mm |
| 2380 | 32mm |
| 2381 | 40mm |
| 2382 | Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor of alum. alloy braid in existing surface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2383 | Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TECspecification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair forIdentification etc. as required. For additional technical parameters ofproduct / work refer Annexure \"A\" attached with this BSR;4.3.4 4 pair |
| 2384 | P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR ;5.1.1 1.2 mm thick M. S. Sheet boxes ; |
| 2385 | 100mm x 100mm x 60mm |
| 2386 | 225mm x 100mm x 60mm |
| 2387 | 200mm x 250mm x 75mm |
| 2388 | 300mm x 375mm x 75mm |
| 2389 | P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2390 | P & F 1.00mm thick M.S. Recessed concealed box, round of size 150 mm dia, depth 100 mm complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2391 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2392 | 6 A to 32 A rating |
| 2393 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947- III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 35sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR;6.2.3 Four pole Isolator; 63 A rating |
| 2394 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar, masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2395 | 6 Way (6+2) |
| 2396 | 8 Way |
| 2397 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial gradePolycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 2398 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2399 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2400 | 6/16 A shuttered socket |
| 2401 | Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work referAnnexure \"A\" attached with this BSR ;7.29.1 5 step fan regulator 2 Module 360 dgree rotating |
| 2402 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2403 | Modular MCB 6 A to 32 A SP |
| 2404 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2405 | 3 Module |
| 2406 | 6 Module |
| 2407 | 8 Module |
| 2408 | 12 Module |
| 2409 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2410 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed UnArrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 2411 | 10.0 Sq. mm, 4 core |
| 2412 | Providing & Fixing of 1200 mm sweep BLDC technology power saving ceiling fan which can withstand on votage fluctuations from 140 volts to 240 volts ,power factor not less then 0.9 , service value (CMM/W) minimun 6.85, air delivery minimun 220 CMM, speed minimum 330 RPM (tolerance as per IS:374 2019 ) THD less then 10% and complete with down rod of 15 mm dia . ERW (Electrical resistance welded) of 1.6mm nominal thick medium duty steel pipe up to 80 cm, cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR. Without Remote |
| 2413 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 300 mm sweep(900/1400 RPM) |
| 2414 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2415 | Recessed Mounting ;Minimum lumen output 650 lm |
| 2416 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with HDPE, Category 6A/Class Ea, U/FTP (Unscreened/Foiled Twisted Pair), 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 C.2 & ISO/IEC 11801 2nd Ed, The copper conductors should be balanced twisted in pairs, Unscreened and Aluminum Foil Sheilding of Individual pairs protected by a Low Smoke Zero Halogen (LSZH)(IEC 60332-1) Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 500 Mhz. Should meet IEEE 802.3af & IEEE 802.3at for POE applications. Cable Should support Ethernet 10GBASE-T according to the standards. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR |
| 2417 | Supply, Installation, & Testing of 19\" 1U Rack Mounted/ surface mounted aluminum/ CRCA 1.2mm powder coated, multimode glass Fiber Optic Cable Patch panel/LIU loaded with flangless/screwable adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws, nuts to install the panel for rack/wallmount applications as per requirement complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2418 | Multi Mode LIU 12 Ports Each 8691.00 |
| 2419 | Supply , Installation, Testing and Comissioning of Unmanaged Switch Plug-and-play - easy setup with no configuration or no software needed, following Port fast ethernet - 8 port 10/100 MBPS auto-negotiation RJ45 ports, IEEE 802.3x flow control ,supports autoMDI/MDIX, eliminating the need for crossover cables including making connection etc as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . 24 Port |
| 2420 | Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent 10/100 Ethernet Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports / with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software including making connections etc as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2421 | Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2422 | 1.5 TR ISEER not less then 4.6 |
| 2423 | O&M |
| 2424 | Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency) as per Scope of Work & terms & conditions of contract for 5 years after defect liability period of one year DLP (except power feeder, IEC & miscellaneous provision) for Water Supply Project |
| 2425 | 1st year |
| 2426 | 2nd year |
| 2427 | 3rd year |
| 2428 | 4th year |
| 2429 | 5th year |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy