| 1 | Preventive maintenance & repair of Fire alarm system and fire fightingincluding control panels for detection systemby means of their cleaning, checking of circuits including recalibration and testing including replacement of defective parts to make them serviceable all as directed .the Preventive maintenance of following item is also included as mention below. (a)Fire Pump of Capacity 100HP- 01 No (b)Jockey Pump 12.5 HP-01 No(c)Diesel Engine 85.5 KVA -01 No(d)Terrace booster Pump of Capcity 7.5 HP - 11 No (e) Zone Panel consisting of Zone card and Power Card-11 No (f)Main controlpanel of 16zone with 500 W PA system -01 NoNote : (a) Panel shall be checked every month as per direction of Engr-in-Charge. (b) Spares shall be measured and paid separately under relavent item of schedule as supply only.(For Sl Item No 4 to 10) (c) If complaint not rectified with in 24 hrs then penality @ 500/per day will be recovered.(d) Monthly checking of fire fighting system should be done every month |
| 2 | Cleaning ofinternal surafces ofUnderground sump/ Reservoirs of3,75,000 Litre capacity,by using high pressure rotary jet machine and pumping out/ flushing outwater, mud, sludge, dirt etc by any means of industrial vaccum cleaner including brooming down or steel wire brushing; scrapping down, moulds, moss and efflorescent salts andwashing the inside surfaces including pipes, ladders etc. and treating the surfaces by spraying sodium hypochlorite(anti bacterial agent) in a concentration as directedby meansof high pressure rotary jet machine & UV radiation disinfactant, disposing off the spoils to a distance not exceeding 50 M in a safe mannerwhere directed by Engineer-in-Charge. complete all as specified and directed. Note: Date of cleaning of UG Sump/Reservoir shall be mentioned on exposed surface of with synthetic enamel paint as directed by Engineer in Charge. |
| 3 | All as per item No 2 above but tank capacity 2,00,000 Litre. |
| 4 | Supply only Bearingof centrifugal pump 100 HP existing sizeMake SKF/Tata/NBC |
| 5 | Supply only Bearingof Jockey pump 12.5 HP existing sizeMake SKF/Tata/NBC |
| 6 | Supply only Bearingof Jockey pump 7.5 HP existing sizeMake SKF/Tata/NBC |
| 7 | Supply only rubber bush for coupling. |
| 8 | Supply only Gland bush set complete. |
| 9 | Supply only of Mechanical Seal for 100 HP all as per directed by Engr-In-Charge. |
| 10 | Supply only of Mechanical Seal for 7.5 HP all as per directed by Engr-In-Charge. |
| 11 | M&L for dismantling and rewinding of motor 7.5 HP cap of same gauge super enemmaled copper winding wire including insulating papper & testing complete all as directed. |
| 12 | M&L for dismantling and rewinding of motor 12 HP cap of same gauge super enemmaled copper winding wire including insulating papper & testing complete all as directed. |
| 13 | M&L for taking down & overhouling of fire hose reel drums by changing of clip ,greasing to swing smothly and refixing the same all as directed . |
| 14 | S&F in replacement fire hose reeldrum ISI marked & confirming to relevent IS for 20 mm hose pipe offire hadder all as directed. |
| 15 | M&L for Zubli clip for 20 mm dia hose reel pipe all as directed |
| 16 | M&L for fastner /Nut bolt for fixing the hose reel as per existing size all as directed |
| 17 | M&L for making hanging arrangment made out of FI holding clamp as per existing size dullypainted for fire exingusher at each floor of building with suitable nut bolt & washers complete all as directed |
| 18 | M&L for Air release valve for fire hadder near fire pump installed at tarrace of building all as directed. |
| 19 | Dismantling and cleaning of smoke cum heat detector from ceilingand refixing the same and testing complete all as directed. |
| 20 | S & F in replacement of detector complying with and type multisensor certified to EN-45 type heat & smoke detector photo electric /optical with base with self intelligence as per IS :11360 multisensor with smoke & heat combination confirming to IS with base complete all as directed. |
| 21 | S & FSS landing valve single headed 80 mm dia, flanged inlet 63 mm dia instant type female outlet complete with gun metal & cap & chain twist release type lugISI marked & confirming to relevent IS complete all as directed. Make : Omex/ New Age / Life guard |
| 22 | S&F in replacement for fire brigade inlet connection 2 way typeISI marked & confirming to relevent IS all as directed. |
| 23 | S &F in replacement of 63 mm dia RRL hose pipe 15 Mtr long with male & female SS couplings bend riveted tohose pipe ISI marked & confirming to relevent IS complete all as directed. |
| 24 | S&F in replacement of 20 mm dia rubber hose pipe 30 Mtr long with fixing arrangement ISI marked & confirming to relevent IS complete all as directed. |
| 25 | S&F 20 mm dia steel nozzleISI marked & confirming to relevent IS complete all as directed. |
| 26 | S&F 63 mm steel nozzleISI marked & confirming to relevent IS complete all as directed. |
| 27 | S&F in replacement of manual call point with push button fired bride MS box duly painted sealed with glass including necessary electrical connection all as directed. |
| 28 | S&F in replacement of low intensity hooter of 10 watt for warning of fire connected with central control panel installed in each zoneall as directed. |
| 29 | S&Fin replacement ofhose& horn for CO2 cylinderany size as per site requirement all as directed. |
| 30 | S&Fin replacement of DCP (Dry chemical powder) cylinder of 4 Kg capacity as per site requirement all as directed. |
| 31 | S&F 4 mm thick glass for hose boxes any size as per site requirement all as directed. |
| 32 | S & F in replacement ofMicroprocessor based detection system control panel of 12 zone mounted on walloutside the room made of mild steel sheet confiming to IS 513-1986, minimum 1.6 mm thick . Colour of the panel shall be fire red (shade No 536 of IS 5-1978) with gas release facility including all the wiring , fitting and accessaries and time delay arrangement (with setting for 30-60 sec) for flooding of gas auto and manual mode includingbattery charger unit with boost & trickle charger, battery box, connections to building automation system and taking down of old panel complete all as specified and directed. :-Make Agani device / Honeywell / ASE |
| 33 | S&F and commissioning of Booster pump for 440V, 3 Phase 50 Hz confirming to IS-12469:1988 with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 440 V, 3 phase, 50Hz 36m head, 450 LPM discharge of capacity 7.5 HPcomplete all as specified and directed. |
| 34 | S&F fully automatic star delta starter for Booster pump set capacity 450LPM discharge and 36 Mtr head including connecting all incoming and outgoing copper wire all as directed. |
| 35 | Dismantling wrought iron or mild steel work of any description not otherwise provided for, all as specified and directed |
| 36 | M&L for framed work such as grills,gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors;ladders; framed balusters; walk ways; railings; framework of Ladder in Over Head Tankand similar work con-forming to Fe 290.Gde-E-165complete all as specified and directed.Note :- Necessary safty tools and measure should be the whole responsiblity of contractor andrate of all T & P included in quoted rates. |
| 37 | M&L for applying two coat of synthetic enamel paint over a coat of red oxide primer including preparation of newly steel surface of any description exc. 10 cm width or girth complete all as specified and directed |
| 38 | Supply and fixing fire hose box made of 18 guague MS sheet 800 mm x 600 mm x 250 mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard including the support for on wall.Note : Rate quoted by the contractor deemed to inclusive of support brick work as described above. Make Shall be : Newage/Safex/Cease fire |
| 39 | S&F in replacement of MS ERW, heavy grade, pipe 80 mm bore including cutting and welding , fittings for fire hydrant all as directed. |
| 40 | All as per item no 39 but pipe size 150 mm |
| 41 | All as per item no 39 but pipe size 200 mm |
| 42 | M&L for applying of APP membrane over MS pipe for protection complete all as specified and directed by Engr-in-charge |
| 43 | Supply & Fixin replacement PVC insulated, sheathed electric cable FRLS 1100V gradetwo core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area in non metallic rigid PVC concealedconduitall as specified and directed. |
| 44 | S&F in replacement of pressure switch confirming to IS , of approved make all as directed by Engineer in Charge. |
| 45 | M&L for painting of old steel and iron surfaces of any description exceeding 10cm width or girth such as rising/distribution lines /over head tank lines with two coat of synthetic enemelled red paint after preparation of old painted surfaces all as directed. |
| 46 | M&L for pressure gauge 4 \" dia(0-14 Kg) rating ISI marked all as directed. |
| 47 | M&L for butterfly valve 100 mm diaISI marked & confirming to relevent IS complete all as directed Make- Leader/Zoloto/Sant |
| 48 | All as per item No 47 above but size 150 mm bore |
| 49 | S&F Non return valve (NRV) in replacementof size 150 mm ISI marked & confirming to relevent IS for fire hadder including nut,bolt & washer complete all as directed. |
| 50 | S&F in replacement of Branch pipe gun metal 63 mm instantaneous inlet,made threaded outlet 15 mm bore nozzle short as specified and directed |
| 51 | S&F of SS landing valve coupling 63 mm dia allas specified and directed |
| 52 | S & F of Copper conductor PVC sheathed cable stranded 3- core of size 16 Sqmm multistarnd , connected with and including suitable copper lugs all as directed by Engineer in Charge. |
| 53 | M&L for XLPE insulated, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade 10 Sqmm 4 corelaid in duct/ trenches or passing through pipe including connecting with suitable lugs, nuts and bolts and testing complete all as specified and directed |
| 54 | M&L for PVC insulated XLPE armoured CU cable of size 1.5 Sqmm 2 core for complete all as specified and directed |
| 55 | Supply and fixing of Contactor Model No MNX-140 making proper connection with suitble lugs all as per directed by Engr-In-Charge. |
| 56 | S&F in replacement battery 180 AH , having minmum 48 month warrentee of approved make complete all as specified and directed.Make: Exide/ Amaron/ Amco /Tata. Note :- Model Number with Serial Number of Battery suported with warrentee card number shall be entered in MB andOld battery shall be deposited to MES store Yard |
| 57 | S&F in replacement automatic battery charger 12V for existing make complete all as specified and directed. Note :- Model Number with Serial Number of Battery charger suported with warrentee card number shall be entered in MB |
| 58 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out for taking out/laying pipes in soft/loose soil complete all as specified and directed. |
| 59 | Returning, filling, in and including spreading levelling watering and well ramming in layers not exceeding 25cm thick in solf/loose soil after pipes are laidcomplete all as specified and directed . |
| 60 | Removing of excavated material not exc 50 mtr distance and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 61 | M&L for cutting of PCC/Hard standing/WBM roadfor passing of GI/CI pipes all as specified and directed . Note : Making good with PCC (1:3:6) type C2 shall be measured and paid separetely under respective item. |
| 62 | M&L for cement concrete 1:2:4 Type B 1 using 20 mm graded stone aggregate asas directed by Engineer- in -Charge. |
| 63 | M&L for PCC 1:2:4 Type B2 using 40 mm graded stone aggregate as in foundation , filling and mass concrete complete all as specified and as directed by Engineer- in -Charge. |
| 64 | Demolition of brick work masonry, built in cement mortar including all quoins, arches, pillars, etc, complete all as specified and directed. |
| 65 | M & L Brick work with modular fly ash bricks, Straight or curved on plan exc. 6 m mean radius built in CM 1:6, complete all as specified and directed. |
| 66 | Taking down cement of cement lime plaster of any description on brick or stone walls or concrete surfaces, ceiling etc including ranking out joints hacking for key scrubbing down with water etc complete all as specified and directed. |
| 67 | M&L for rendering 15mm thick in cement mortar (1:6) on fair faces of brick work or concrete surfaces , finished even and smooth without using extra lime orcement complete all as specified and directed. |
| 68 | M&L for preparing the new plastered surfaces and applying two coats of Oil bound distemper over one coat of primer on walls complete all as specified and directed. |
| 69 | M&L for preparing the new plastered surfaces and applying two coats of white wash on ceiling complete all as specified and directed. |
| 70 | M & L for construction of valve chamber900 x 900 x 900 mm internal dimensions,6 mm thick MS sheet cover with 2 Nos MS hinges welded to angle iron frame of 40x40x6 mm thick with lifting hook and locking arrangement complete with necessary earth work, brick work in CM (1:6), 230 mm thick,PCC bed (1:4:8) type D2 150 mm thick, cement plastering, finishing 15 mm thick in CM (1:4) and applying a coat of black bituminous paint to the steel surfaces incl dismantling and removal of old unserviceble valve pit remains all as specified and directed. |
| 71 | M & L for construction of valve chamber600 x 600 x 600 mm internal dimensions,6 mm thick MS sheet cover with 2 Nos MS hinges welded to angle iron frame of 40x40x6 mm thick with lifting hook and locking arrangement complete with necessary earth work, brick work in CM (1:6), 230 mm thick,PCC bed (1:4:8) type D2 150 mm thick, cement plastering, finishing 15 mm thick in CM (1:4) and applying a coat of black bituminous paint to the steel surfaces incl dismantling and removal of old unserviceble valve pit remains all as specified and directed. |
| 72 | Supply & fixing in replacement of lead acid battery of 12 Volt, 7 AH complete all as directed.Make EXIDE /OKAYA/AMRON. Note :- Model Number with Serial Number of Battery suported with warrentee card number shall be entered in MB |
| 73 | S & F of UPS of capacity 2 KVA, along with inbuilt battry suitable for backup of upto 5 hours, complete with all connection all as specified and directed by Engr-in-charge (For Main Fire Panel). Note :- Model Number with Serial Number of UPS suported with warrentee card number shall be entered in MB |
| 74 | S & F response indicator complete all as specified and directed.Make:- honeywell /Safecontrols /RAVEL |
| 75 | M & Lsub main wiring, single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 1.5 sqmm drawn in new PVC conduitcomplete all fixing accessories such as couplers lock, nuts, sadles, pipe hooks etc fixed properly all as directed by Engineer in Charge.Note : (i) PVC Conduit shall be measured and paid separately under respective item. |
| 76 | S&F rigid non metallic medium white / ivory PVC conduit medium grade ISI markedof size not less than 20 mm dia concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed position incl cutting chasing & making good to disturbed surfaces & matching with the existing colour of wall/floor etc all as directed by Engineer-in-Charge. |
| 77 | S&F rigid non metallic medium white / ivory PVC casing caping medium grade ISI markedof size not less than 20 mm dia inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, fixed properly all as directed by Engineer-in-Charge. |
| 78 | S&F control globe valve/ball valve of size 25 mm ISI marked & confirming to relevent IS for 20 mm dia hose pipe of fire haddercomplete all as directed. |