| 1 | Material and Labour for sub main wiring with 2 runs of 2.5 Sqmm single core PVC insulated unsheathed FRLS copper cable 1100 Volts grade multistrandeddrawn throughnon metallic rigid PVC conduit ISI marked 25 mm dia including conduit accessories concealed/surface type on walls, roof,floors etc including one run of 2.5 Sqmm PVC copper conductor as earth continuity wire includingtaking downunserviceable sub main wiring including conduitall as specified and directed. Note : 2 Runs of 2.5 sqmm cable 1 run of 2.5 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 2 | All as per srl item No. 1 here-in-before but with 2 runs 4 sqmmincluding 1 run of 4 sqmm PVC copper conductor FRLS cable as earth continuity wire in not less than 25mm dia ISI marked PVC conduit..Note : 2 Runs of 4 sqmm cable 1 run of 4 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 3 | All as per srl item No. 1 here-in-before but with 2 runs 6 sqmmincluding 1 run of 6 sqmm PVC copper conductor FRLS cable as earth continuity wire in not less than 25mm dia PVC conduit.Note : 2 Runs of 6 sqmm cable 1 run of 6 sqmm cable and 1 run of PVC conduit shall measured as one unit for the purpose of payment. |
| 4 | All as per srl item No. 1 here-in-before, but sub main wiring with 4runs of 4sqmm with 2 run of 4 sqmm copper conductor FRLS as earth continuity wire in not less than 25mm dia PVC conduit.Note : 4 Runs of 4 sqmm cable 2 run of 4 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 5 | All as per srl item No. 1 here-in-before, but sub main wiring with 4runs of 6 sqmm with 2 run of 6 sqmm copper conductor FRLS as earth continuity wire in not less than 25mm dia PVC conduit.Note : 4 Runs of 6 sqmm cable 2 run of 6 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment. |
| 6 | All as per srl item No. 1 here-in-before, but sub main wiring with 4runs of 10 sqmm with 2 run of 10 sqmm copper conductor FRLS as earth continuity wire in not less than 25mm dia PVC conduit.Note : 4 Runs of 10 sqmm cable 2 run of 10 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment.Make for Item No 1 to 6 :For Copper wire : Finolex/Nicco/Havells/Gloster/KEI or its equivalentFor PVC conduit : Sudhakar/Polyplast/Supreme/GM or its equivalentMake of Gang Boxes: GM/Havells/Legrand or its equivalent |
| 7 | Taking down old unserviceable point wiring (Light, Fan, Socket or power) complete including fixture and fittings such as switches, ceiling roses, regulators, sockets, light fittings etc andmaking good to the disturbed surfaces of walls, ceilings and floor etc complete all as directed |
| 8 | Material and labour for point wiring complete with ISI marked1.5 SqmmPVC insulated multistranded single core cable with copper conductor (FRLS) 1100 volts grade drawn through and including PVC rigid conduit 20 mm or higher dia ISI marked as required at site including conduit accessories such as Junction Boxes, Inspection Covers etc,concealed/surface type on stone/brick masonry walls, roofs, floors etc by means of saddles and clamps etcincluding PVC gang boxes as required at site for concealed/surface conduit wiring and modular plates & covers as required at site for housing switches sockets, regulators etc. including providing of 1.5 Sqmm PVC insulated multistranded unsheathed FRLS copper conductor as earth continuity conductor and connecting to common earth dolly all as specified for and connecting up complete for the following:-One light/ fan point controlled by one, one way switch |
| 9 | One light point controlled by one, two way switch |
| 10 | One 5 Amps socket point on independent board. |
| 11 | One 5 Amps socket point on same board with other switches |
| 12 | All as per item No. 8 here-in-before but wiring with 2.5 Sqmm FRLS for 15 Amps switch socket combination on independent board/two pin earth plug and socketincluding providing 4 Sqmm PVC insulated multi stranded FRLS copper earth continuity conductor and connected to common earth dolly. |
| 13 | All as per item No. 8 here-in-before but wiring with 4.00 Sqmm FRLS for 15 Amps switch socket combination on independent board/two pin earth plug and socketincluding providing 4 Sqmm PVC insulated multi stranded FRLS copper earth continuity conductor and connected to common earth dolly. |
| 14 | S&F in replacement for Modular socket 6A 2/3 Pin2 module. |
| 15 | S&F in replacement for Modular socket 16A 2/3 Pin2 Module. |
| 16 | S&F in replacement for modular switch 1 way 6A 1 module. |
| 17 | S&F in replacement for modular switch 1 way 16A 1 module. |
| 18 | S&F in replacement of modular fan regulator 120W,240V, 1 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 19 | S&F in replacement of modular fan regulator 120W,240V, 2 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 20 | S&F in replacement of piano type fan regulator 120W,240V, 1 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 21 | S&F in replacement of piano type fan regulator 120W,240V, 2 module, suitable for ceiling fan of 1200/1400mm sweep. |
| 22 | S&F in replacement for modular switch 2 way 6A 1 module. |
| 23 | S&Fin replacement of switch piano flush type 5 Amps SP one way all as specified. |
| 24 | S&Fin replacement of switch piano flush type 15 Amps SP one way all as specified. |
| 25 | S&F inreplacement ofsocket & switch combination 5 Amps flush mounted3/5 pin multi purpose all as specified. |
| 26 | S&F inreplacement ofsocket & switch combination 5/15 Amps flush mounted3/5 pin multi purpose all as specified. |
| 27 | S&F in replacement for ceiling rose, 3 terminals /PVC/Polycarbonate, isolated body. |
| 28 | S& F in replacement surface mounting Plastic gang boxes suitable for modular switches3 module. |
| 29 | All as per item no.23 above, but of size 4 Module all as specified |
| 30 | All as per item no.23 above, but of size 6 Module all as specified |
| 31 | All as per item no.23 above, but of size 8 Module all as specified |
| 32 | All as per item no.23 above, but of size 12 Module all as specified |
| 33 | S&F in replacementfor white cover plate with frame 3 module. |
| 34 | S&F in replacementfor white cover plate with frame 4 module. |
| 35 | S&F in replacementfor white cover plate with frame 6 module. |
| 36 | S&F in replacementfor white cover plate with frame 8 module. |
| 37 | S&F in replacementfor white cover plate with frame 12 module. |
| 38 | PVC / polycarbonate Angle/Batten type lamp holders retrofit type |
| 39 | S&F in replacement ofLED tube 20Watt, 6500K CCT,proffesional luminaries with luminous efficiency not less than 120Lm/watt, Single side connection with < 10% THD incluidng taking down of exisitng fixture all as specified and directed. |
| 40 | S&F in replacment indoor industrial type surface/wall mounted LED integral batten 20W (4 feet), 6500K CCT, aluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic drivercomplete fixing with all accessories prewired and includingconnectingup with three coreflexible copper conductorcablewith suitable size complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 41 | S&F in replacment indoor industrial type surface/wall mounted LED integral batten 10W (2 feet), 6500K CCT, aluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic drivercomplete fixing with all accessories prewired and includingconnectingup with three coreflexible copper conductorcablewith suitable size complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 42 | S&F in replacment LED PLL lamp Hercules 18Watt, proffesional luminaries single side connection with < 10% THD, complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 43 | S&F in replacment indoor industrial type recess mounted LED Surface mounted for POP/Grid ceiling round/square downlight with white powder coated polycarbonate housing and pressure die-cast heat sink having high efficiency.15W, 6500K CCT, integral elctronic driver complete fixing with all accessories prewired and includingconnectingup with three coreflexible copper conductor cable as required at sitewith suitable size complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 44 | Supply & Fix in replacement recess mounted LED luminaire 36W2\"x2\" , 5700K CCT, luminous efficacy of not less than 120lm/wattdesigned for metric false ceiling type or alongwith frame suitable for Grid/POP ceiling or similar mounting system with concealed or exposed \"T\" sections, Glare free light alongwithelectronic driver complete with all accessories prewired and connecting up with three core twister flexible copper conductor cable with suitable size including making good to the disturbed portion of ceiling complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 45 | Supply & Fix in replacement recess mounted LED luminaire 36W4\"x1\" of size 1195x295x70 mm, 5700K CCT, luminous efficacy of not less than 120lm/wattdesigned for metric false ceiling type or alongwith frame suitable for Armstrong/ US Gypsum or similar mounting system with concealed or exposed \"T\" sections, Glare free light alongwithelectronic driver complete with all accessories prewired and connecting up with three core twister flexible copper conductor cable with suitable size including making good to the disturbed portion of ceiling complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 46 | S&F in replacement recess mounted LED high bay light with IP-66 protection pressure die cast body with high power SMD LEDs as light source of luminous efficacy 150lm/watt 120W, 240V, 5000K CCT, aluminium heat sinkalongwith inbuilt elctronic driver, wide beam angle ,including hanging the fitting with required hook arrangement required at site, complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 47 | S&F in replacement recess mounted LED high bay light with IP-66 protection pressure die cast body with high power SMD LEDs as light source of luminous efficacy 150lm/watt 80W, 240V, 5000K CCT, aluminium heat sinkalongwith inbuilt elctronic driver, wide beam angle ,including hanging the fitting with required hook arrangement required at site, complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 48 | S&Fin replacement 25 W LED security light fiitting of luminous capacity 2500lumens,IP-66 protection, 5700K CCT, inbuilt electronic driver with <10%THD made up of die cast aluminium housing with high power LED as lighting source and lens embeded toughned glass cover, separate driver compartment complete fixing with GI bracket made out of 40mm bore GI pipe light grade 1.5Mtr long bend to shape and fixed to pole/wall with necessary MS clamp accessories,complete removingunserviceable wires/cables incluidng taking down of exisitng fixture all as specified and directed. |
| 49 | Taking down ceiling fan/exhaust fan/ wall mounted fan / Air circulator fan of any sweep for servicing / repairing / maintenance, opening up, identifying and replacing the defective parts, cleaning, greasing,etc, reassembling and hanging up/fixing back at its original position, connecting up and testing complete all as directed.Note :1. Cost of spares such as capacitors, bearings, Shaft etc will be measured and paid for separately under respective Item of sch A as supply only. |
| 50 | Supply only capacitor of 2.5 mfd for ceiling fan/exhaust fan. |
| 51 | Supply only capacitor of 4 mfd for air circulator/exhaust fan. |
| 52 | Supply only bearing No.6201/6202/6203/6204 or any other No matching to the existing size and suitable for ceiling fan/exhaust fan/wall mounted fan. |
| 53 | Supply only carbon steel shaft as suitable for ceiling fan/Exhuast fan/ Pedestal Fan/ Air Circulator fans matching to the existing size. |
| 54 | Disconnecting electric connectionand taking down carefullyfan of any type and size/sweep as described below, removing the burnt winding of fan motor and cleaning the stator completely removing the burnt sludges from the slots andrewinding with super enameled copper winding wire of suitable gauge or of matching size to the existing wires with same turns ratio including all insulating material such as insulation paper sleeve, tape, varnishing etc and reassembling, testing, transporting back to site and refixing to original position all as directed by Engineer-in-charge. |
| 55 | Celling fan of size 1200/1400mm sweep. |
| 56 | Air circulator fans size 600 mm sweep wall mounting Oscillating type |
| 57 | Wall mounted/Pedstal fans size 350/450 mm sweep Oscillating. |
| 58 | Exhaust fan of 300/350/450 mm sweep. |
| 59 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.3mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 mm dia of minimum 15m length by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR PART-I connected to earthing test point all as specified or indicated including provision of earthing lead protection pipe, PCC earth pit with cover, excavation & earth work, testing on completion etc all as specified and directed by Engr-in-Charge. |
| 60 | M&L for testing of old earthing using calibrated earth tester and submitting result to Engr-in-Charge. Earthing which showing much more result as specified as directed and disconneted should replaced with new earthing items are considered as below :-Note :- (i) Watering of earthing with 2 bucket 30 ltrs water mixed with salt (Total 5 Kg) shall be carried out one day before the testing and the cost of the same shall deemed to included inquoted rate. |
| 61 | S&F/lay GI earth wire 4 mm dia on walls/flooras earth continuity conductor connected to DBs/ panels etc. |
| 62 | Supply and Fix GI tubing 15mm dia light grade for protection of GI earth wire complete all as specified and directed. |
| 63 | Supply and fixing amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning. |
| 64 | SP 5 To 32 AMP |
| 65 | SPN 32 AMP |
| 66 | SPN 40 to 63 AMP |
| 67 | Supply and fixing 415V 10KA \"C\" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning. |
| 68 | TP 25 To 63 AMP |
| 69 | TPN 16 To 32 AMP |
| 70 | TPN 40 To 100 AMP |
| 71 | Supply and fixing 415V 16 KA \"C\" curve miniature circuit breaker (MCCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning. |
| 72 | TP 63 to 100 A |
| 73 | FP 63 to 100 A |
| 74 | TP 125 A |
| 75 | FP 125 A |
| 76 | TP 160 A |
| 77 | FP 160 A |
| 78 | Supplying and fixing 4 sqmm 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular |
| 79 | All as per item no above 57 but of size 6 sqmm all as specified and directed |
| 80 | Supply & Fix in replacement PVC insulated round cable 3 core stranded copper conductor 1.5 sqmm as in connection cord. |
| 81 | All as per item no above but of size 2.5 sqmm all as specified and directed |
| 82 | Supply and fix in replacement sheet metal enclosures single pole MCB 20 Amps with a two pin and earth plug and socket complete with all accessaries etc all as directed by Engr-in-charge. |
| 83 | S & F in replacement industrial interlocked switched sockets surface/wall mounting socket 63 Amp 3P+N+E4 pole with straight plug 63 Amp 3P+N+E, IP 66 protection and sockets enclosure DX3 cabinet IP 66 protection 5 module fixed on wall/surface with including removing existing old socket,all as specified and as directed. |
| 84 | S & F in replacement industrial interlocked switched sockets surface/wall mounting socket 32 Amp 3P+N+E4 pole with straight plug 32 Amp 3P+N+E, IP 66 protection and sockets enclosure DX3 cabinet IP 66 protection 5 module fixed on wall/surface with including incoming removing existing old socket, all as specified and as directed. |
| 85 | Supply and fix in replacement metal clad plug top 3 pin, 20 amps, ISI marked heavy duty for ACconnection cord. |
| 86 | Supplying and Fixingsheet metal enclosure (MCCB Box)suitable forMCCB-TP/TPN (63 to 200)Amps 415 Volts and removing the unserviceable item all as specified and directed. |
| 87 | Material and labour for fixingindustrial type sheet metal enclosures forsingle pole240 volts complete with all accessories etc all as directed. |
| 88 | Material and labour for fixingindustrial type sheet metal enclosures for Double pole and240 volts complete with all accessories etc all as directed. |
| 89 | Material and labour for fixingindustrial type sheet metal enclosures for Triple pole415 volts complete with all accessories etc all as directed. |
| 90 | Material and labour for fixingindustrial type sheet metal enclosures for Triple pole and neutral 415 volts complete with all accessories etc all as directed. |
| 91 | Supply and fix in replacement MCB DB 04 way SPN (double door)sheet metal enclosure factory made suitable for MCB DB\"s 240 voltswith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed . |
| 92 | Supply and fix in replacement MCB DB 08 way SPN (double door)sheet metal enclosure factory made suitable for MCB DB\"s 240 voltswith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed . |
| 93 | Supply and fix in replacement MCB DB 12 way SPN (double door)sheet metal enclosure factory made suitable for MCB DB\"s 240 voltswith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed. |
| 94 | Supply and fix in replacement MCB TPN DB 04 way(double door)sheet metal enclosure factory made suitable for MCB TPN incomer and MCBs as outgoingwith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed. |
| 95 | Supply and fix in replacement VTPN DB 04 way(double door)sheet metal enclosure factory made suitable for MCCB 415 volts incomer and MCBs as outgoingwith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed. |
| 96 | Supply and fix in replacement VTPN DB 08 way(double door)sheet metal enclosure factory made suitable for MCCB 415 volts incomer and MCBs as outgoingwith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed. |
| 97 | Supply and fix in replacement VTPN DB 12 way(double door)sheet metal enclosure factory made suitable for MCCB 415 volts incomer and MCBs as outgoingwith 200 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed. |
| 98 | Note: (i)The contractor\"s representative will report to concerned JE E/M at 0900hrs daily to collect the list of defects and will submit the completion report on following daybefore 0900hrs to the JE E/M.(ii) The contractor has to rectify the defects and make the light fittings functional within 24 hours from the time the list of defectivelights is handed over to him / his rep by the concerned JE E/M.In case the light fitting is not made functional for whatsoever reason within the specified time limit, an amount of Rs 50/- per such defective light fitting per day will be recovered from the amount due to him through RAR / Final Bill. The contractor shall engage separate team of technicians / repairer for DMRL, ATC, RCMA areas.(iii) The contractor shall maintain proper record of repair / maint in a binded register duly bringing out the details of spares replaced on each and every light fitting and get it authenticated from concerned JE E/M on daily basis. The contractor shall put up the maint record register to Engineer-in-charge for inspection every Monday or as and when asked for. (iv) The contractor shall maintain sufficient stock of spares / material required for repair / maint of light fittings with the concerned JE E/M against the supply only items here-in-below. (v) The contractor should submit the copy of qulaification,Experience as Electrician and police verification certificateswhile sigining the site orders.(vi) The contractor is fully responsible for providing the safety standards to be maintained by the electricians while attending the electrical defects. |