| 1 | Taking down carefully point wiring (light, fan, socket, etc.) complete including battens and fittings such as switch, ceiling rose, light fittings, regulators, socket, etc. and making good to disturbed surface of wall/floors, etc. complete all as specified and as directed. |
| 2 | M&L for point wiring with 1.5 sq.mm FRLS grade PVC insulated and unsheathed stranded copper conductor cable,1100 volts grade as per IS-694 drawn through and including PVC cassing and capping (not less than 20mm wide) complete with all acessories including PVC board/box of suitable size for mounting of switches, sockets, regulators, etc. including 1.5 sq.mm stranded copper conductor cable FRLS grade PVC insulated and unsheathed as earth continuity conductor for one light or fan point controlled by one 5 Amps switch one way complete by maintaining the colour code complete all as specified and as directed. |
| 3 | All as per Serial item No. 2 here-in-before but for one 3 pin 5 Amps switch socket outlet on independent board. |
| 4 | All as per Serial item No.2 here-in-before but for one 3 pin 5 Amps socket outlet on same board with other switches. |
| 5 | All as per Serial item No. 2 here-in-before but for one bell point controlled by one switch 5 Amps bell push. |
| 6 | All as per Serial item No2 here-in-before but point wiring with 2.5 sq.mm single core multistranded copper conductor cable for 6 pin 15 amps switch socket combination outlet on independent board with 2.5 sq.mm PVC insulated and unsheathed copper conductor as earth and connected to earth dolly. |
| 7 | S&F as in repairs switch piano, flush type, single pole one way 5 Amps, 230 volts complete all as specified and as directed. |
| 8 | S&F as in repairs bell push flush type, 5 Amps, 240 volts complete all as specified and as directed. |
| 9 | S&F as in repairs socket outlet 3 pin, 2 in 1, 5 Amps, flush type complete all as specified and as directed. |
| 10 | S&F as in repairs switch socket combination outlet 5 pin, 2 in 1, 5 Amps, flush type complete all as specified and as directed. |
| 11 | S&F as in repairs switch socket combination multipurpose 6 pin, 2 in 1, 5 and 15 Amps, flush type complete all as specified and as directed. |
| 12 | S&F as in repairs ceiling rose surface backelite of size 65x50mm three terminals, PVC / polycarbonateinsulated body complete all as specified and as directed. |
| 13 | S&F as in repairs bell ding dong, electric 230 volt, single phase complete all as specified and as directed. |
| 14 | S&F as in repairs lamp holder insulated PVC / polycarbonate/bakelite body with back plate suitable for batten fittings or PVC round or square box complete all as specified and as directed. |
| 15 | S&F as in repairs stepped type electronic fan regulator, two module size, flush type complete all as specified and as directed. |
| 16 | S&F as in repairs modular fan regulator, 120 W-2 module complete all as specified and as directed. |
| 17 | S&F as in repairs modular switch 1 way, 6 Amps, 1 module complete all as specified and as directed. |
| 18 | S&F as in repairs modular switch 1 way, 16 Amps, 1 module complete all as specified and as directed. |
| 19 | S&F as in repairs modular socket, 6 Amps 2/3 pin combined 2 module complete all as specified and as directed. |
| 20 | S&F as in repairs modular socket, 16 Amps 2/3 pin combined 2 module complete all as specified and as directed. |
| 21 | M&L for sub main wiring with two runs of single core 4 sq.mm FRLS PVC insulated copper cable, 1100 volts grade multistrand, unsheathed conductor drawn into PVC casing and capping and all necessary fittings including 4 sq.mm multi strand FRLS PVC insulated copper wire for earth continuty conductor connected to common earth dolly complete including taking down old unserviceable sub main wiring of any size and making good disturbed surfaces complete all as specified and as directed.Note :Two runs of cable 4 Sq.mm and one run of 4 Sq.mm cable along with conduit all together shall be measured as one unit. |
| 22 | All as per Serial Item No. 21 here-in-before but two runs of 6.0 Sq.mm copper cable and 01 run of 6 Sq.mm for earth dolly. |
| 23 | All as per Serial Item No. 21 here-in-before but two runs of 10.0 Sq.mm copper cable and 01 run of 10.0 Sq.mm for earth dolly. |
| 24 | All as per Serial Item No. 21 here-in-before but two runs of 2.5 Sq.mm copper cable and 01 run of 2.5 Sq.mm for earth dolly. |
| 25 | S&F rigid non-metallic PVC conduit/casing capping of size 25mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe, hooks, etc. complete all as specified and as directed. |
| 26 | S&F as in repairs MCB DB of sheet metal enclosure, double door, SPN, 8 way with 200 Amps rated bus bar and grouted in wall with plain cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) complete all as specified and as directed. |
| 27 | S&F as in repairs MCB DB of sheet metal enclosure, double door, SPN, 4 way with 200 Amps rated bus bar and grouted in wall with plain cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) complete all as specified and as directed. |
| 28 | S&F as in repairs MCB DB of sheet metal enclosure, double door, VTPN, 4 way with 250 Amps rated bus bar in which MCCB as a incomer and MCB as out going and grouted in wall with plain cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) complete all as specified and as directed.Make : Legrand, Cat Part No. 5077 50 or equivalent model from makes as specified in Particular Specifications. |
| 29 | S&F as in repairs factory made sheet steel distribution boards, TPN, 4 way, double door, 415 volts with provision for FP MCB as incomer and SP MCBs as outgoing and grouted in wall with plain cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) complete all as specified and as directed.Make :- Legrand, Cat Part No. 5072 50 or equivalent model from make as specified in Particular Specifications. |
| 30 | S&F as in repairs 240 volts, 50 Hz, 10 KA, \"C\" curve miniature circuit breaker (MCB) of SP, 6 to 32 Amps in accordance with IS/IEC 60898-1 and current carrying capacity in the MCB DB with connection testing and commissioning complete all as specified and as directed. |
| 31 | S&F as in repairs 240 volts, 50 Hz, 10 KA, \"C\" curve miniature circuit breaker (MCB) of SPN, 32 Amps in accordance with IS/IEC 60898-1 and current carrying capacity in the MCB DB with connection testing and commissioning complete all as specified and as directed. |
| 32 | S&F as in repairs 415 volts, 50 Hz, 10 KA, \"C\" curve miniature circuit breaker (MCB) of TPN, 40 to 100 Amps in accordance with IS/IEC 60898-1 and current carrying capacity in the DB with connection testing and commissioning complete all as specified and as directed. |
| 33 | S&F as in repairs MCCB 100 Amps current carrying capacity in accordance with IS/IEC 60898-1, 415 volts, 50 Hz, 16 KA, 3 pole thermal magnetic type along with spreader terminals complete all as specified and as directed. |
| 34 | S&F as in repairs MCCB 125 Amps in accordance with IS/IEC 60898-1 current carrying capacity 415 volts, 50 Hz, 16 KA, 3 pole thermal magnetic type along with spreader terminals complete all as specified and as directed. |
| 35 | S&F as in repairs MCCB 160 Amps in accordance with IS/IEC 60898-1 current carrying capacity 415 volts, 50 Hz, 36 KA, 3 pole thermal magnetic type along with spreader terminals complete all as specified and as directed. |
| 36 | S&F as in repairs LED lights fitting 1x 20W, 220 volt, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.Make:- Crompton, Cat Part No. CCS-120-20-65-SL-DP-NWH or equivalent model from makes as specified in Particular Specifications. |
| 37 | S&F as in repairs LED lights fitting 1x 10W, 220 volt, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed. |
| 38 | S&F as in repairs LED light fitting 1x9W / 1x10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed. Make:- Crompton, Cat Part No. LBHP-10-CDL or equivalent model from make as specified in Particular Specifications. |
| 39 | S&F as in repairs LED luminaire 600mmx600mm, 35/36 watt, 220 volt, AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders with LED lamp, suitable for roof ceiling including connecting up with driver three core flexible copper conductor cable of suitable size complete all as specified and as directed. |
| 40 | S&F LED building security light fitting 30/35 watt 230 volt, AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed. |
| 41 | S&F 7W LED bulb B-22 type white/warm white in colour complete all as specified and as directed. |
| 42 | S&F as in repairs polycarbonate unbreakable white globe doom of 8 inch dia in existing garden light pole complete all as specified and as directed. |
| 43 | S&F for LED post of lamp 40 watt, made in cast aluminium spigot housing with decorative opal polycarbonate cover diffuser and IP-65 protection complete all as specified and as directed. Make -Bajaj, Cat No. BGCL 40W LED WH orequivalent model from makes as specified in Particular Specifications. |
| 44 | S&F as in repairs LED luminaire 1 feet x 4 feet, 40 watt, 220 volt, AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders and LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed. |
| 45 | S&F as in repairs sheet metal enclosure with socket plug top and MCB DP 20 Amps including taking down old existing unserviceable one complete all as specified and as directed. |
| 46 | S&F PVC plug top, 16 Amps, suitable for geyser complete all as specified and as directed |
| 47 | S&F as in repairs smart wall mount wireless call button (with 120cm flexible cord), bed unit complete set button complete all as specified and as directed |
| 48 | S&F as in repairs LED display, 999 calls, 1 group shows at a time, 10 stored in a row of wall mount wireless call button bed unit complete all as specified and as directed |
| 49 | M&L for earthing with galvanised steel earth plate electrode 600mmx600mmx6mm thick burried directly in ground vertically to a depth of not less than 2.25m below ground level, connected to galvanise iron wire 4mm dia or 8 SWG as earthing lead by means of nuts, bolts and earth plate electrode at one end and connected to main switch board / DBs, etc. at other, earth strip encashed (protected) in and including 15mm bore GI pipe, \"medium grade\" with all fittings from top of electrode to main switch board/DBs, etc. fixed with and including 25x6mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe with 20mm bore GI pipe, \"medium grade\" from bottom of earth pit to top of electrode complete with earth pit in PCC (1:2:4) type B-2 (using 20mm graded crushed stone aggregate), RCC cover, funnel, wire mesh including necessary excavation and earth work all as shown in Electrical Plate No. 3 of SSR Part-I and testing after completion including taking up old unserviceable one complete all as specified and as directed. |
| 50 | Excavating in trenches not exc. 1.50m wide and not exc. 1.50m in depth, over areas and getting out as in soft / loose soil complete all as specified and as directed. |
| 51 | Excavating in trenches not exc. 1.50m wide and depth beyond the first 1.5m, over areas and getting out in soft / loose soil complete all as specified and as directed. |
| 52 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 250mm in soft/loose soil complete all as specified and as directed. |
| 53 | Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.50m above the starting point complete all as specified and as directed. |
| 54 | S&F 40mm dia galvanised iron pipe with all fittings, medium grade, laid in trenches for mechanical protection of earth strip of chemical earthing, etc. including taking down old unserviceable steel tubing of any grade with connections including re-fixing or removal from site complete all as specified and as directed. |
| 55 | M&L for salt around the earthing plate in layer complete all as specified and as directed. |
| 56 | M&L for charcoal around the earthing plate in layers complete all as specified and as directed. |
| 57 | S&F 4mm dia galvanised iron or steel wire as earth continuity conductor or main earthing lead, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing, etc. complete all as specified and as directed. |
| 58 | M&L for earthing PCC pit in plain cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) and RCC Cover of size 450x450x50mm in RCC (1:2:4) (using 20mm graded stone aggregate), reinforced with and including 8.0mm dia TMT bars @ 100mm centre to centre both ways including demolation and removing broken RCC cover from existing site complete all as specified and as directed |
| 59 | S&F as in repairs galvanised iron plate 600x600x6mm after taking out old existing unserviceable GI plate and re-fixing the same at orginal position complete all as specified and as directed.Note:- Rate of exavation, returing filling, removing, etc. shall be measured and paid saperately. |
| 60 | M&L for earthing with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground vertically to a depth of not less than 2.25m below ground level, connected to galvanise iron strip of size 25x4mm as earthing lead by means of nuts, bolts and washers, made out of galvanised iron mild steel and 40mm dia GI pipe \"light grade\" for protection of earth lead and connected to test point or as directed including pit in PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) and RCC cover of size 450x450x50mm in RCC (1:2:4) type B-1 (20mm graded stone aggregate) reinforced with and including 8.0mm dia TMT bars @ 100mm centre to centre both ways, galvanised iron wire mesh, funnel, GI watering pipe 20mm bore, medium grade, all as shown in Electrical Plate No. 3 of MES Schedule Part-I including necessary excavation and earth workin soft/loose soil including filling in, spreading, levelling, well ramming and removal of surplus soil upto a distance of 50m and testing on completion including taking down old existing unserviceable earthing complete all as specified and as directed. |
| 61 | M&L for earthingwith copper plate electrode 600x600x3.15mm thick burried directly in ground vertically to a depth of not less than 2.25m below ground level, connected to copper strip of size 20x3mm as earthing lead for protection of earth lead and connected to test point or as directed including pit in PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) and RCC cover of size 450x450x50mm in RCC (1:2:4) type B-1 (20mm graded stone aggregate) reinforced with and including 8.0mm dia TMT bars @ 100mm centre to centre both ways, GI wire mesh, funnel, GI watering pipe of size 20mm bore, medium grade, all as shown in Electrical Plate No. 3 of MES Schedule Part-I including necessary excavation in soft/loose soil, returning, filling in and removal of surplus soil upto a distance of 50m and testing on completionincluding taking down old existing unserviceable earthing complete all as specified and as directed. |
| 62 | S&F aluminium strip of size 25mmx3mm as earth continuity conductor, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing, etc. complete all as specified and as directed. |
| 63 | M&L for air termination, single pointed, copper rod of size 12mm dia and 300mm long complete all as specified and as directed |
| 64 | M&L for test point terminal block, made of gun metal or phosphorus bronze of size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex head screw complete all as specified and as directed. |
| 65 | Supply and laying 40mm dia GI pipe \"medium grade\" including all fittings complete all as specified and as directed. |
| 66 | M&L for galvanised iron strip of size 32x6mm, buried in ground with saddles and fixing screws, etc. on porcelain insulator/spacer on roof/wall and for loop earthing complete all as specified and as directed. |
| 67 | S&F as in repair fountain outer ring pipe (dia 25mm) of dia 8 feet round shape of fountain containing 26 Nos. of suitable brass nozzle including all necessary fittings complete all as specified and as directed. |
| 68 | S&F as in repair fountain outer ring pipe (dia 25mm) of dia 12.50 feet round shape of fountain containing 32 Nos. of suitable brass nozzle including all necessary fittings complete all as specified and as directed. |
| 69 | S&F as in repair stainless steel ½ inch shape 3 stage adjustable water fountain nozzle including all necessary fittings complete all as specified and as directed. |
| 70 | S&F as in repair fountain LED light of different colour luminaries of 36 watt, made in cast aluminium spigot housing with decorative opal polycarbonatecover diffuser and IP 65 protection nozzle including all necessary fittings complete all as specified and as directed. |
| 71 | Taking down exhaust/wall/pedestal fan of size 250mm to 450mm sweep of any make and refixing on same location or other location carefully at site and transporting from any location in side units/area to MES STORE YARD OF AGE E/M (AF) JORHAT for stripping fan washing thoroughly bearing/bush by petrol, washing / cleaning fan blades body, etc. and provision of new greasing, replacement of worn out / defactive unserviceable parts (wherever necessary) and re-assembling the same including provision of twisted twin core wire flexible wire up to 0.7m long with size 24/0, 020 (ISI marked) and testing the fan on full load to entire satisfaction complete all as specified and as directed.Note : (i) Defective / unserviceable parts replaced shall be measured and paid separately.(ii) The cost of taking down unserviceable parts is deemed to be inclusive with the quoted rate. |
| 72 | Stripping of exhaust / wall / pedestal fans of 250mm to 450mm sweep, any make, washing thoroughly bearing / bush by petrol, washing / cleaning fan blades body, etc. thoroughly and provision of new greasing, replacement of worn out / defactive unserviceable parts (wherever necessary) and re-assembling the same and testing the fan on full load to entire satisfaction complete all as specified and as directed.Note : (i) Defective / unserviceable parts replaced shall be measured and paid separately.(ii) The cost of taking down unserviceable parts is deemed to be inclusive with the quoted rate. |
| 73 | S&F as in repairs ball bearing of suitable size for exhaust / wall / pedestal fans 250mm to 450mm sweep complete all as specified and as directed.Make : NBC/SKF/TATA/SBBI |
| 74 | S&F as in repairs ISI marked 230/240/250 volts AC fan capacitor 4 MFD suitable for exhaust / wall / pedestal fans including condenser spacer and soldering of condenser wire to fan wire and fixing complete all as specified and as directed. |
| 75 | S&F as in repairs ceiling fans with blades, down rods, electronic regulator and accessories, 230 V, 1400mm sweep. minimum air delivery 245 CFM with service value 6.00 BEE. Five star rated with brush less direct current motor (BLDC) complete all as specified and as directed. |
| 76 | S&F as in repairs heavy duty exhaust fan, steel body, AC single phase, 230 volt of size 300mm sweep with blades and frame and louvers including all civil works complete all as specified and as directed.Make : Crompton, Cat No. 300MM Transair (Double ball bearing) or equivalent model of makes as specified in Particular Specifications. |
| 77 | S&F as in repairs heavy duty exhaust fan, steel body, AC single phase, 230 volt of size 450mm sweep with blades and frame and louvers including all civil works complete all as specified and as directed.Make : Crompton, Cat No. EXHD450 or equivalent model of makes as specified in Particular Specifications. |
| 78 | S&F as in repairs exhaust fan made of sturdy engineering plastic complete with louvers shutter, AC single phase RPM 1200,copper winding230 volt of size 300mm sweep with blades and frame and including all civil works and taking down old unserviceable one complete all as specified and as directed.Make : Crompton, Cat No. EXHD450 or equivalent model of makes as specified in Particular Specifications. |
| 79 | Taking down ceiling fan 1400mm / 1200mm sweep and refixing on same location or other location of any type / make and size carefully from fan hook and transporting from any location in side air force area to MES STORE YARD OF AGE E/M (AF) Jorhat and back after repairing and painting with synthetic enamel paint by spraying including filling cavity complete all as specified and as directed. |
| 80 | S&F as in repairs fan bearing of size 6201/6202 as approved suitable for ceiling fan 1200mm/1400mmsweep and make complete all as specified and as directed. |
| 81 | S&F as in repairs fan capacitor 2.5 MFD suitable for1200 / 1400 mm sweep ceiling fan complete all as specified and as directed. |
| 82 | Supply only plastic canopy upper and lower of any size and make of ceiling fan, fixed with suitable size of screws complete all as specified and as directed. |
| 83 | Supply only rubber reels including shackle clamp, bolts, nuts, washers, split pins of appropriate size as required complete all as specified and as directed. NOTE:- The contract sum shall be derived by deducting the amount shown in Schedule of Credit attached to this tender from total amount of Schedule \"A\"/BOQ. |