Tender For Supply, Installation, Testing & Commissioning Of Single Arm street Light Pole And Other Electrical Work From Nuh Toad To Narsingdas Ashram - 1 Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 2 10 mtr 3 Supply and Fixing of Pole OEM fabricated hot dipped galvanisedM.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25mm) over the existing poles. All as per pre approved by Engineer incharge. For additional technical parameters of products/ work ,refer Annexure A attached with this BSR . 4 Single Arm overhang 5 Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) 70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in 6 LED Street Light fixture with Minimum lumen output 15000 lm 7 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P -I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure A attached with this BSR 8 16 sq mm 4 Core 9 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure A attached with this BSR 10 10.0 sqm 11 4 core 12 Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. B class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in-charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 13 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR 14 6 swg tinned copper wire 15 Supply & Laying following size B class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in-charge. (Earth Excavation will be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annex ure A attached with this BSR 16 80 mm dia 17 Labour charges for Trimming of tree branches/plants and prepairing route approaches for electric proposed line complete with prior permission of local authority in writing , taking proper shutdown from discom office and inform to DISCOM after complete the work. 18 P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 19 90 mm 20 SITC of Cutting back up surface up to 2 Mtr. Depth by digging by Bogie including all layers of crust for laying pipe line etc. and making good to original condition (excluding cost bitumen) 21 Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR .A) Excavation of Pit for Foundation Size upto required depth from Ground levelB) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.C) Providing and laying in position cement concrete of M-10 grade of 75 mm thicknessD) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete.E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and PedestalF) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations.G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. 22 pole foundation for octogonal pole form 10 mtr to 12 mtr 23 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 24 Single pole MCB (With B/C curve tripping Characteristics) 16 amprating 25 Four pole MCB (With B/C curve tripping Characteristics) 26 Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 27 63 amp 28 Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure A attached with this BSR . 29 one day reserve analog type 30 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: