| 1 | Supply and Erection of Double Pole (Bottom Portion Galvanised) 11 Mtr. long 410 SP-55 S.T. Pole support duly grouted, plinthed , plastered & painted in the same manner as already specified for respective supports suitable for pole mounted type substation with different types of M.S. channels and angle iron duly fabricated for Disc fittings TPMO, D.O. fuse, outside dropper & bracings including cost of material, labour and T&P required for proper completion of work as per drawing and direction of E/I. Only Manufacturers Whose GTP Approved in MVVNL. |
| 2 | Supply & Erection of 11 KV TPMO set complete with all material, labour, T&P etc. required for proper completion of the work. |
| 3 | Supply & Erection of 11 KV D.O. fuse set complete with all material, labour, T&P etc. required for proper completion of work. |
| 4 | Supply, Installation, Testing and Commissioning of 63 KVA, 11/.433 KV (EE Level-1)Transformerincluding Loading, unloading, local carriage with all material, labour, T&P required for proper completion of the work. Make MODERN/TRANSTRON/ELECON or Whoe Latest GTP Approved in MVVNL Having Valid CPRI/ERDA Type Test Report |
| 5 | Supply & Fixing of H.T/L.T jumpering and connection on double pole/four pole. lightening arrestors & T/F including cost of all material, labour T & P etc. required for proper completion of work. |
| 6 | Supply & Fixing of lightening arrestor set (3 Nos.) suitable for mounting on steel supports complete with all materials, labour and T & P required of proper completion of work as per direction of E/I. |
| 7 | Supply & Fixing of following SizeGIpipe \"B\" class for cable duly clamped with supports by 3 nos. with clamps of 20x3mm M.S. flat bolts nuts & washers required for proper completion of work. Make:- TATA/SAIL/JINDAL/as per direction of E/I. |
| 8 | 100 mm Dia (10.20 kg/Mtr.) |
| 9 | Supply and Burring of Safe Earthing Electrode T-39 Cu Copper Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 S.No. 727 (D) |
| 10 | Supply & Laying of 3 Core Standered Aluminium Conductor XLPE (Cross Linked Polyethylene) insulated PVC Bedded, Galvanised Flat Steel Strip armoured Cables Confirming to IS 7098 (Part-II with latest Ammendments) 11 KV Grade at a depth of 900 mm below Ground Level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps.Make:-Polycab/Gloster/KEI/Havells/Finolex/Universal/as per direction of E/I. |
| 11 | 3 Core 70 sqmm PWD SOR 2018 S.No. 506 (d) |
| 12 | Supply and jointing of 70 Sqmm 3 Core Outdoor Type11 KVjointing kit (Heat Sink) per XLPE cable including cost of all material Labour and T & P forproper completion of work as per direction of E/I. Make:- Raychem/Densons/3M/as per direction of E/I. |
| 13 | Supply & Laying of following size Al. conductor PVC insulated armoured served sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side on top. On surface the cable run shall be fixed on M.S clamps of suitable size or as directed by the E/I, Complete in all respect. The Armouring of the cable shall be properly connected with the earth conductor by clamps etc. Make:- Polycab/Gloster/KEI/Havells/Finolex/ Universal/as per direction of E/I. |
| 14 | 70 sqmm 3.5 core PWD SOR 2018 S.No. 501(m) |
| 15 | Supply and fixing of palm or pin copper tin plated cable socket (lugs) to the cable leads insulating with tape and making connections etc. complete in all respects (as per PWD SOR 2018 SI No. 504). |
| 16 | 35 Sqmm |
| 17 | 70 Sqmm |
| 18 | Supply and fixingof danger board (L.T.) size 200x250mm at suitable height of pole as per direction of E/I |
| 19 | Supply and fixingof barbed wire (1.5kg) duly clamped with 20x3mm M.S. flats at both ends on steel poles at suitable height as per direction of E/I. |