Supply, Removing of existing filters & Installation of new filtersBox /flange type HEPA ( Convetional/mini pleat) filters having following size with efficiency - 99.99 % down to 0.3 micron, Tested according to BS EN:1822. H14 filter class .Initial pressure drop of 250 Pa. Final Pressure drop 500-600pa in dirty condition with test dust no. G2 as per IS:7613:1973. The filtering media shall be made of very fine high efficiency micro fibre glass paper media interspaced with hot melt pleating & inclosed in Aluminium extruded section of following sizes for OT-1 to OT-5
2
610 x 610 x 150 mm,
3
1220 x 610 x 150 mm,
4
915 x 610 x 150 mm,
5
762 x 610 x 150 mm,
6
Third party Validation test as per ISO guideline and NABH standard comprising Filter Integrity Test of HEPA (DOP/PAO), Non Viable partical count test, Air velocity & ACPH measurement, Differencial pressure balancing, Temp & RH measusrement, flow pattern test with videography etc. for Operation Theater having 350 to 550 sqft area.