| 1 | Supply, laying,jointing & testing of XLPE insulated GI wire/strip armoured electric power cable (Heavy duty) with stranded aluminium conductor 33000 volts Earth grade, cross sectional area 300 Sqmm 3 Core confirming to IS:7098 Part-II laid in trenches /poles/on wall complete all as specified and as directed by the Engineer in charge. Make : Polycab/Havells/GlosterNOTE: EXCAVATION & EARTH WORK SHALL BE MEASURED & PAID SEPARATELY UNDER RELEVANT ITEM OF THIS SCHEDULE. |
| 2 | Supply and Erecting Steel Tubular swaged pole 11 meter SP 55 in truly vertical position complete with cast iron base plate, finial, taper plug etc. including painting of poles with two coats of synthetic enamel paint in red and white strips upto 1.5 mtr height from coping over a coat of red oxide primer including numbering of poles complete as directed by Engineer in charge.Note: Earth work , PCC , iron clamp. shall be measured and paid separtely under relevant item of this schedule. |
| 3 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth; for trench of cable/foundation of pole and stay etc and getting out in hard/dense soilsoil complete all as specified and as directed by the Engineer in charge. |
| 4 | All as per Item No: 03 above but depth exceeding beyond 1.5mtr and not exc 3 metre all as specified and as directed by the Engineer in charge |
| 5 | Material and labour for cross arms, bracings, supports clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coat of aluminium paint over a coat of red oxide primer including preparing the surface complete all as all as specified and as directed. |
| 6 | Material and labour for PCC ( 1:3:6 )Type C-2 (Using 40 mm grade aggregate as in foundation of pole, stay and filling and mass concrete) including providing necessary form work complete all as specified and as directed by the Engineer in charge. |
| 7 | Material and labour for PCC (set in cement mortar 1:4) type B1 1:2:4 using 20 mm grade stone aggregate as in copping of electric poleat site including providing necessary form work complete all as specified and as directed by the Engineer in charge |
| 8 | Material and labour for sand cushioning for protection of underground cable consolidated and compacted with clean dry sand all as specified and as directed by the Engineer in charge.Note: Compacted thickness of sand shall only be measured and paid under this item. |
| 9 | Supply and laying of factory made unreinforced pre-cast concrete cover class HV, Type 1,flat,size 300mmx 180mm x 40mm laid in trenches for HT cable protection complete all as specified and directed. Note- HT PCC cable cover shall comply with IS 5820 (1970) |
| 10 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in Soft/loose soil complete all as specified and as directed by the Engineer in charge |
| 11 | Removing excavated material to a distance n.exc 50 mtr and depositing where directed at level n.exc 1.5 mtr above the starting point all as specified and as directed by the Engineer in charge. |
| 12 | S&F cable jointing kit for 33 KV(Earthed) grade cable for outdoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 300 Sqmm complete all as specified and as directed by the Engineer in charge.Make : 3M/Raychem/Denson |
| 13 | Material and labour for galvanized iron tubing 150 mm bore light grade with all fitting laid in trenches/wall/floor/ pole for protection of cable including providing fixing clamps, bolts and nuts of suitable size all as specified and as directed by the Engineer in charge.Note:Excavation ,earth workshall be measured and paid separately. |