| 1 | Redevelopment of existing bore of following size :- 100 / 150 /200 / 250 mm dia. |
| 2 | S.I.T.C of Hot Press moulded SMC panel/Canopy Box of size(OD) 920 mm x 460 mm x 260 mm & (ID) 900 mm x 450 mm x250 mm , anti – corrosive, dust proof, rust proof, shock proof , Self-extinguishing property , resistant to heat , Vermin proof, Ultra Violet stabilized, Pilfer resistant, Suitable for mounting 1 no. 3 phase Starter, 1 no. 63 Amp 4 pole isolator and 1 no. 3 phase Energy meter, Socket for outgoing connection with pilferage proof SMC door duly welded with S/S handle having danger logo on its outer surface and with 1 no Hot Dip galvanized iron stand for a base of size 40 mm x 40 mm x 5 mm and height of the stand is 600 mm including 300 mm height below the ground with side strip of size 25 x 5 mm. |
| 3 | Providing and laying cement concreat 1:2:4 mix for sanitary sealing of well at top of 450mmX 450mmX 500 mm deep fromtop comp as reqd. |
| 4 | .Supplying, lowering, testing and commissioning of vertical type, multistage, totally enclosed water filled deep well submersible pumping set complete i/c connection etc. as reqda. Single Phase 1.5 HP having discharge of 72 LPM Approx. at 49 M Head |
| 5 | c Three Phase 5.0 HP having discharge of 300 LPM Approx. at 39 M Head. |
| 6 | Supplying and fixing following sizes of insulated steel flexible safety rope for holding submersible pump set i/c clips etc complete as reqd. (a) 6 mm dia |
| 7 | P&F following sizes of PVC insulated & PVC sheathed copper conductor 3 core submersible cable confirming to IS.694/1990 etc. as reqd.(a) 3 X 2.5 sq.mm. |
| 8 | Supply, lowering and fixing following size of G.I.Pipe (M-Class)i/c cutting threading on both sides etc. ISI marked etcas reqd..a.40mm(Nominal Bore) |
| 9 | b. 32 mm dia ( Nominal bore) |
| 10 | S& F following sizes ofGI Elbow as reqd.a. 40mm dia |
| 11 | b.32 mm dia |
| 12 | S&F following sizes ofGI socket as reqd.a. 40mmdia |
| 13 | b. 32 mm dia |
| 14 | S&F following sizes ofG.I. union as reqd. a. 40mm |
| 15 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.a. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 16 | S&F MS clamp made up of flat iron of size 50mmx 6 mm with 4 nut bolt for holding theG.I.Pipe from 40 mm to 65 mm dia pipe etc as reqd. |
| 17 | Supply, Installation, testing and commissioning of cubical type control panel board for single phase & Three Phasesubmersible pumping set of following rating complete with contactor, relay , MCB ,condenser ,voltmeter, ammeter and indication lamp etc includingconnections etc as reqd. a. 1.5 HP (Single Phase) |
| 18 | c. 5 HP (Three Phase) |
| 19 | Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size25mmx75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh and grounding the protection system in suitable quality of CC etc as reqd. |
| 20 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 21 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 22 | Lifting of existing submersible pump setwith its all accessories from well and lowering the same along with all accessories for the depth upto 50 meter complete as reqd. |
| 23 | Rewinding of single / three phase AC motors of vertical type multi stage submersible pump sets of following ratings :- (a) Single Phase 1/1.5 HP. |
| 24 | Rewinding of single / three phase AC motors of vertical type multi stage submersible pump sets of following ratings :- (a) Three Phase 5 HP. |
| 25 | Repairing of pumping unit of 1/1.5/3 HP vertical type multi stage submersible pump setby replacement of following accessories / parts etc compelete as reqd. (a) Gun metal bush / bearing. |
| 26 | (b) Pump Shaft. |
| 27 | (c ) Impeller. |
| 28 | Replacement of following items for cubicle panel etc. as required. (a) Capacitor 36 mfd |
| 29 | (b) Capacitor 50 mfd |
| 30 | (c) Contactor & Relay of Single Phase Starter unit. |
| 31 | (d) Contactor & Relay of three Phase Starter unit. |